Plan Review Details - Permit 05082001
Plan Review Stops For Permit 05082001
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-22 Cont ID  
Sent By shill Date 2005-11-22 Time 11:42 Rev Time 1.00
Received By shill Date 2005-11-22 Time 07:17 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-14 Cont ID  
Sent By shill Date 2005-10-14 Time 09:10 Rev Time 1.00
Received By shill Date 2005-10-14 Time 09:10 Sent To PC
Notes
2005-10-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 ***PLAN REVIEW ONLY***
  
 1.)PLEASE NOTE THAT GOVERNING CODE
 CHANGED TO FBC2004 EFFECTIVE OCTOBER 1,
 2005.
  
 2.)ENERGY CALCS TO BE PREPARED USING
 FORMS FROM CURRENT CODE.THE ENERGY
 CALCS SUBMITTED REFER TO THE 01 VERSION
 OF FBC.
  
 3.)ON THE PLAN, PLEASE DECLARE
 GOVERNING CODE, MINIMUM EXISTING
 BUILDING TYPE AND OCCUPANCY.
  
 4.)THIS IS A PLAN REVIEW ONLY.PERMIT
 APPLICATION REQUIRED FOR PERMIT
 ISSUANCE.
  
 5.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-06 Cont ID  
Sent By shill Date 2005-09-06 Time 07:55 Rev Time 1.00
Received By shill Date 2005-09-06 Time 07:48 Sent To  
Notes
2005-09-06 00:00:00****CORRECTIONS****
 ****PLAN CHECK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, FBC103.1.2.
  
 3.)PLEASE READ FAC61G1-16.003, 004.
 THE SEAL IS TO BE DATED.
  
 4.)THE STAFF LOUNGE SINK IS TO COMPLY
 WITH ALL REQUIREMENTS OF FBC11-4.24.
 PROVIDE A DETAIL.NOTE THAT THE DOOR
 SWINGS INTO THE CLEAR FLOOR SPACE.
  
 5.)SHEET A2 WEST PORTION SHOWS A NEW
 LOBBY, IS THIS A PART OF THIS PERMIT?
  
 6.)PROVIDE A DETAIL FOR THE 1 HOUR
 INFILL WALL, EITHER A LISTED ASSEMBLY OR
 CALCULATED FIRE RESISTANCE FBC709.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-17 Cont ID  
Sent By dpalmer Date 2005-11-17 Time 18:35 Rev Time 0.30
Received By dpalmer Date 2005-11-17 Time 18:32 Sent To  
Notes
2005-11-17 00:00:00***** NOTE*****
  
 PLEASE SEE PLANS ARE STAMPED FOR
 ELECTRICAL.
  
 ** PLEASE SEE A NEW PERMIT NUMBER WILL
 BE REQUIRED TO BE GENERATED AND PLANS
 ARE JUST NOW BEING SUBMITTED FOR PERMIT
 AS OF NOV 10, 2005.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-10-08 Cont ID  
Sent By dpalmer Date 2005-10-08 Time 17:27 Rev Time 0.33
Received By dpalmer Date 2005-10-08 Time 17:14 Sent To  
Notes
2005-10-08 00:00:00*********** UNSAT *************
  
  
 **************************************
 PLEASE SEE PREVIOUS NOTES WHICH
 MENTIONED PLANS WERE ONLY SUBMITTED FOR
 "PLAN REWVIEW" AND WERE NOT SUBMITTED
 FOR PERMIT.
 PLEASE SEE PLANS WERE SUBMITTED ONCE
 AGAIN FOR "PLAN REVIEW" ONLY AND NOT FOR
 PERMIT.
  
 PLEASE KNOW, AS OF OCT 1ST, 2005, THE
 CODE HAS CHANGED TO THE NEW FBC 2004.
 THIS WILL AFFECT ANY AND ALL REFERENCES
 TO 2001 FBC ON PLANS.
 PLEASE SEE THAT PLANS AND A NEW PERMIT
 APPLICATION MUST BE SUBMITTED UNDER 2004
 FBC.
 PLEASE KNOW THAT THE "PLAN REVIEW"
 NUMBER OF 05082001 WILL BE REQUIRED TO
 BE CHANGED WHEN SUBMITTING FOR PERMIT.
  
  
 ELECTRICAL PLANS STAMPED , AS NEC 2005
 DOES NOT CHANGE UNTIL JULY 06.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-02 Cont ID  
Sent By dpalmer Date 2005-09-02 Time 12:55 Rev Time 1.00
Received By dpalmer Date 2005-09-02 Time 12:54 Sent To  
Notes
2005-09-02 00:00:00*********** UNSAT *************
  
 PLEASE SEE PLANS ARE SUBMITTED FOR "PLAN
 REVEW" ONLY AND HAVE NOT BEEN SUBMITTED
 FORPERMIT.
  
  
  
 1)NOTE: PLEASE SEE SEE PANEL "A" WHICH
 INDICATES FEEDERS AS 4 # 13'S.
 THIS APPEARS TO BE A MISPRINT.
 PLEASE ADJUST AND CORRELATE WITH FEEDERS
 INDICATED ON RISER.
  
 2)NOTE: PLEASE SEE PANEL "B" INDICATES
 LOAD FOR PANEL"A" AS BEING 10A'S?
 PLEASE SEE PANEL "A" LOAD IS SHOWN MUCH
 HIGHER.
  
 3)NOTE: PLEASE CLARIFY IF NEW OR EXSITNG
 RECEPT IS AVAILABLE FOR ROOFTOP A/C
 UNIT.
 210.63,210.8
  
 4)NOTE: PLEASE BE SURE THE TITLE BLOCK
 FOR ARCHITECT/FIRM CONTAINS THE PRINTED
 NAME AND LICENSE # OF ARCHITECT. FAC
 61G1-16.004,
 PLEASE SEE THIS IR REQUIRED OF ALL
 TRADES AND FOR ALL SHEETS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLU INSERT NEW REVISED SHEETS INTO
 COMPLETER SETS FOR REVIEW AND STAMPING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-10-11 Cont ID  
Sent By mwennerg Date 2005-10-11 Time 09:47 Rev Time 0.00
Received By mwennerg Date 2005-10-11 Time 09:47 Sent To  
Notes
2005-10-11 00:00:00******PLAN REVIEW ONLY******

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-06 Cont ID  
Sent By mwennerg Date 2005-09-06 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2005-09-06 Time 11:06 Sent To  
Notes
2005-09-06 00:00:00******DENIED******
  
 1) 2A- 10B,C RATED FIRE EXTINGUISHER(S)
 ARE REQUIRED. PLEASE SHOW THE LOCATION
 THAT MUST SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION OF WALLS AND CEILINGS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-16 Cont ID  
Sent By adarroug Date 2006-05-16 Time 14:48 Rev Time 0.00
Received By adarroug Date 2006-05-16 Time 14:48 Sent To  
Notes
2006-05-17 00:00:00TO "BOB"#1
2006-05-16 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-16 Cont ID  
Sent By adarroug Date 2005-11-16 Time 15:34 Rev Time 0.00
Received By adarroug Date 2005-11-16 Time 15:34 Sent To  
Notes
2005-11-16 00:00:00TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-07 Cont ID  
Sent By adarroug Date 2005-10-07 Time 10:38 Rev Time 0.00
Received By adarroug Date 2005-10-07 Time 10:38 Sent To  
Notes
2005-10-07 00:00:00TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-31 Cont ID  
Sent By adarroug Date 2005-08-31 Time 17:24 Rev Time 0.00
Received By adarroug Date 2005-08-31 Time 17:24 Sent To  
Notes
2005-08-31 00:00:00TO "BOB"#6

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-05-19 Cont ID  
Sent By tgordon Date 2006-05-19 Time 09:12 Rev Time 0.30
Received By tgordon Date 2006-05-19 Time 09:12 Sent To P
Notes
2006-05-19 00:00:00REVISION TO MACH PLANS PAGE M1.01 .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-10-14 Cont ID  
Sent By pkrauss Date 2005-10-14 Time 07:09 Rev Time 0.00
Received By pkrauss Date 2005-10-14 Time 07:09 Sent To  
Notes
2005-10-14 00:00:00APPROVED 9-7-05

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-09-07 Cont ID  
Sent By pkrauss Date 2005-09-07 Time 13:55 Rev Time 0.35
Received By pkrauss Date 2005-09-07 Time 09:14 Sent To  
Notes
2005-09-07 00:00:00PLAN CHECK ONLY

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-05-30 Cont ID  
Sent By jleech Date 2006-05-30 Time 14:09 Rev Time 0.00
Received By jleech Date 2006-05-30 Time 14:09 Sent To  
Notes
2006-05-30 00:00:00REVISION DENIED;
 1. FLOOR DRAINS FOR DENTAL CHAIRS TO BE
 A MINIMUM OF 2" SEE FBC-2004 PLUMBING
 TABLE 709.1.
 2.SHUTOFF VALVES FOR COMP. AIR REQUIRED
 PER NFPA 99C SEC.5.3.4.1(C).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-10-13 Cont ID  
Sent By jleech Date 2005-10-13 Time 07:27 Rev Time 0.75
Received By jleech Date 2005-10-13 Time 07:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-09-14 Cont ID  
Sent By jleech Date 2005-09-14 Time 10:05 Rev Time 2.50
Received By jleech Date 2005-09-14 Time 10:04 Sent To  
Notes
2005-09-14 00:00:00DENIED;
 1. STAFF LOUNGE SINK TO COMPLY WITH FBC
 2001 CHAPTER 11 SEC. 11-4.24.1 THRU
 11-4.24.7. SHOW DETAIL.
 2.FBC 2001 PLUMBING TABLE 403.1 MINIMUM
 FACILITIES REQUIRES A DRINKING FOUNTAIN.
 3.PLEASE SUBMIT MANUFACTOR'S INFORMATION
 FOR, AIR COMPRESSOR, VACUUM PUMP, AND
 MODEL TRIMMER ASSEMBLY.
 MED-GAS
 1.VACUUM PIPING TO COMPLY WITH NFPA 99C
 SEC. 4-5.2.2.1 CLEANOUT FACILITIES
 REQUIRED. SHOW ON DRAWING.
 2.VACUUM PUMP EXHAUST IS REQUIRED TO GO
 TO THE OUTSIDE. PLEASE SHOW LOCATION AND
 SIZE OF PIPE.
 3.(ADD TO NOTES) PLUMBING CONTRACTOR
 REQUIRED TO BE LICENSED TO INSTALL
 MEDICAL GAS. SEPARATE PERMIT REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  
  
  
  
  
  