Plan Review Details - Permit 05081999
Plan Review Stops For Permit 05081999
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-19 Cont ID  
Sent By alange Date 2006-04-19 Time 10:56 Rev Time 1.00
Received By alange Date 2006-04-19 Time 10:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-07 Cont ID  
Sent By alange Date 2006-03-07 Time 14:26 Rev Time 1.00
Received By alange Date 2006-03-07 Time 14:26 Sent To  
Notes
2006-03-07 00:00:00DENIED
  
  
 3.MIAMI-DADE PRODUCT APPROVAL FOR
 SUTTERS IS ALUMINUM WORLD INC. AND THE
 STATE PRODUCT APPROVAL SUBMITTED IS FOR
 ALL AMERICAN SHUTTERS.SUBMIT PRODUCT
 APPROVALS THAT MATCH EACH OTHER.
  
 4.INCLUDE CERTIFICATE OF AUTHORIZATION
 NUMBER ON "A" SHEETS.FS 471.023
 61G15-23.002.THIS IS REQUIRED TO BE ON
 PLANS FOR THE ENGINNER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-29 Cont ID  
Sent By alange Date 2005-09-29 Time 08:10 Rev Time 1.88
Received By alange Date 2005-09-29 Time 08:00 Sent To  
Notes
2005-09-29 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.PLEASE SIGN OWNER AGENT ON ENERGY
 CALCS.
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR LINTELS AND IMPACT
 PROTECTION.
  
 4.INCLUDE CERTIFICATE OF AUTHORIZATION
 NUMBER ON "A" SHEETS.FS 471.023
 61G15-23.002.
  
 5.SHOW HOW EXISTING BUILDING WILL
 COMPLY WITH FBC 3401.7.1.2.1
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-01 Cont ID  
Sent By dpalmer Date 2006-03-01 Time 13:29 Rev Time 0.00
Received By dpalmer Date 2006-03-01 Time 13:14 Sent To P
Notes
2006-03-01 00:00:00***** PLEASE SEE CERTIFICATE OF
 AUTHORIZATION NUMBER IS STILL MISSING ON
 TITLE BLOCKS FOR ENGINEERING FIMR. THIS
 WAS NOTED ON PREVIOUS REVIEW AND NOTE
 MENTIOSN THIS DID NOT APPLY TO THE
 ELECTRICAL SHEETS AS THE ENGINEERING
 FIRM DID NOT HAVE TITLE BLOCK ON
 ELECTRICAL SHEETS.
 PREVIOUS COMMENT WAS NOT FOR ARCHITECT
 FIRM.
  
 PLEASE SEE FORTHCOMING BLDG REVIEW
 COMMENTS AS THIS STILL APPLIES.
 FAC 61G15-23.002, FS 471.023
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 12:34 Rev Time 0.44
Received By dpalmer Date 2005-09-10 Time 12:24 Sent To P
Notes
2005-09-10 00:00:00********* UNSAT **********
  
  
 1)NOTE: PLEASE SEE MISSING REQUIRED NEW
 FOOTER STEEL TO ALSO BE PART OF THE NEW
 GROUNDING ELECTRODE SYSTEM FOR NEW
 SERVICE.
 PLEASE SEE RISER SHOWS ONLY COLD WATER
 PIPE? NO GRND ROD(S) ETC. 250.50.
  
 2)NOTE: PLEASE SEE PLANS SHOWS A NEW
 STACKABLE WASHER/DRYER, HOWEVER THIS IS
 NOT LISTED ON PANEL SCHEDULE OR LOAD
 CALCULATIONS.
 215.5,220.31
 PLEASE SHOW OCP, AWG AND KW RATING.
 240.4,310.16
  
 3)NOTE: PLEASE SEE 2002 NEC 210.12 WHICH
 REQUIRES ARC FAULT PROTECTION FOR ALL
 OUTLETS IN BEDRMS. SD, LTS, FANS,
 RECEPTS, ETC.
  
 4)NOTE: PLEASE SEE FBC CHAPTER
 34,3401.7.1.2.1 FOR ADDITIONS TO EXSITNG
 DWELLING IN R-3 OCCUPANCIES.
 PLEASE SEE ADDTIONS OVER 25% TO EXISTING
 DWELLING.
 PLEASE SHOW EITHER EXISTING OR NEW SMOKE
 DETECTORS WHICH MEET NFPA-72 11.5.1.1 .
 THESE SHALL BE WIRED IN-LINE WITH NEW
 ADDTION SD'S.
 PLEASE ALSO SHOW ALL NEW OR EXSITNG
 RECEPTS IN LOCATIONS WHICH ARE REQUIRED
 TO BE GFI/GFI PROTECTED. (KITCHENS,
 BATHS, OUTSIDE, ETC. 210.8A1-7).
  
 5)NOTE: PLEASE INCLUDE NEW SERVICE
 ENTRANCE CONDUCTORS AND RISER SIZE AND
 TYPE.; PLANS NOTES THIS BY FPL, HOWEVER
 FPL ONLY IS RESPONSIBLE FOR THE SERVICE
 DROP UP TO THE WEATHER-HEAD.
 310.15B6,240.4
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 1)NOTE: PLEASE SEE MISSING CERTIFICATE
 OF AUTHORIZATION NUMBER ON A- SHEETS.
 THIS IS NOT FOR ELECTRICAL SHEETS.
 61G15-23.002, FS 471.023
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-11 Cont ID  
Sent By adarroug Date 2006-04-11 Time 09:17 Rev Time 0.00
Received By adarroug Date 2006-04-11 Time 09:17 Sent To P
Notes
2006-04-11 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-22 Cont ID  
Sent By adarroug Date 2006-02-22 Time 16:13 Rev Time 0.00
Received By adarroug Date 2006-02-22 Time 16:13 Sent To E
Notes
2006-02-22 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 10:09 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 10:09 Sent To E
Notes
2005-09-07 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-29 Cont ID  
Sent By alange Date 2005-09-29 Time 08:16 Rev Time 0.00
Received By alange Date 2005-08-31 Time 15:57 Sent To  
Notes
2005-08-31 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-19 Cont ID  
Sent By tgordon Date 2005-09-19 Time 08:07 Rev Time 0.20
Received By tgordon Date 2005-09-19 Time 08:07 Sent To B
Notes
2005-09-19 00:00:00MECHANICAL PERMIT NOT APPLYED FOR AT
 THIS TIME, NO MECH. CONTRACTOR LISTFD
 AND NO MECH. PLANS SUBMITTED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-04-12 Cont ID  
Sent By jleech Date 2006-04-12 Time 12:56 Rev Time 0.00
Received By jleech Date 2006-04-12 Time 12:56 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-03-06 Cont ID  
Sent By jleech Date 2006-03-06 Time 13:52 Rev Time 0.33
Received By jleech Date 2006-03-06 Time 13:52 Sent To B
Notes
2006-03-06 00:00:00DENIED;
 SHOW AUTOMATIC CLOTHES WASHER ON RISER
 DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-09-17 Cont ID  
Sent By jleech Date 2005-09-17 Time 06:42 Rev Time 0.25
Received By jleech Date 2005-09-17 Time 06:41 Sent To M
Notes
2005-09-17 00:00:00NOT ENOUGH INFORMATION TO DO A PLUMBING
 PLAN REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-06 Cont ID  
Sent By mmclean Date 2005-09-06 Time 19:57 Rev Time 0.00
Received By mmclean Date 2005-09-06 Time 19:57 Sent To I
Notes
2005-09-06 00:00:00NEW ADDITION MUST MEET THE 25FT IN FRONT
 SETBACK (DOUBLE FRONTAGE).