| Plan Review Stops For Permit 05081999 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-04-19 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-04-19 |
Time |
10:56 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2006-04-19 |
Time |
10:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-03-07 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-03-07 |
Time |
14:26 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2006-03-07 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2006-03-07 00:00:00 | DENIED | | | | | | | | | 3.MIAMI-DADE PRODUCT APPROVAL FOR | | | SUTTERS IS ALUMINUM WORLD INC. AND THE | | | STATE PRODUCT APPROVAL SUBMITTED IS FOR | | | ALL AMERICAN SHUTTERS.SUBMIT PRODUCT | | | APPROVALS THAT MATCH EACH OTHER. | | | | | | 4.INCLUDE CERTIFICATE OF AUTHORIZATION | | | NUMBER ON "A" SHEETS.FS 471.023 | | | 61G15-23.002.THIS IS REQUIRED TO BE ON | | | PLANS FOR THE ENGINNER. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-09-29 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-09-29 |
Time |
08:10 |
Rev Time |
1.88 |
| Received By |
alange |
Date |
2005-09-29 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2005-09-29 00:00:00 | DENIED | | | | | | 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 2.PLEASE SIGN OWNER AGENT ON ENERGY | | | CALCS. | | | | | | 3.SUBMIT TWO COPIES OF PRODUCT | | | APPROVALS FOR LINTELS AND IMPACT | | | PROTECTION. | | | | | | 4.INCLUDE CERTIFICATE OF AUTHORIZATION | | | NUMBER ON "A" SHEETS.FS 471.023 | | | 61G15-23.002. | | | | | | 5.SHOW HOW EXISTING BUILDING WILL | | | COMPLY WITH FBC 3401.7.1.2.1 | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-03-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-01 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-01 |
Time |
13:14 |
Sent To |
P |
|
| Notes |
| 2006-03-01 00:00:00 | ***** PLEASE SEE CERTIFICATE OF | | | AUTHORIZATION NUMBER IS STILL MISSING ON | | | TITLE BLOCKS FOR ENGINEERING FIMR. THIS | | | WAS NOTED ON PREVIOUS REVIEW AND NOTE | | | MENTIOSN THIS DID NOT APPLY TO THE | | | ELECTRICAL SHEETS AS THE ENGINEERING | | | FIRM DID NOT HAVE TITLE BLOCK ON | | | ELECTRICAL SHEETS. | | | PREVIOUS COMMENT WAS NOT FOR ARCHITECT | | | FIRM. | | | | | | PLEASE SEE FORTHCOMING BLDG REVIEW | | | COMMENTS AS THIS STILL APPLIES. | | | FAC 61G15-23.002, FS 471.023 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-09-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-10 |
Time |
12:34 |
Rev Time |
0.44 |
| Received By |
dpalmer |
Date |
2005-09-10 |
Time |
12:24 |
Sent To |
P |
|
| Notes |
| 2005-09-10 00:00:00 | ********* UNSAT ********** | | | | | | | | | 1)NOTE: PLEASE SEE MISSING REQUIRED NEW | | | FOOTER STEEL TO ALSO BE PART OF THE NEW | | | GROUNDING ELECTRODE SYSTEM FOR NEW | | | SERVICE. | | | PLEASE SEE RISER SHOWS ONLY COLD WATER | | | PIPE? NO GRND ROD(S) ETC. 250.50. | | | | | | 2)NOTE: PLEASE SEE PLANS SHOWS A NEW | | | STACKABLE WASHER/DRYER, HOWEVER THIS IS | | | NOT LISTED ON PANEL SCHEDULE OR LOAD | | | CALCULATIONS. | | | 215.5,220.31 | | | PLEASE SHOW OCP, AWG AND KW RATING. | | | 240.4,310.16 | | | | | | 3)NOTE: PLEASE SEE 2002 NEC 210.12 WHICH | | | REQUIRES ARC FAULT PROTECTION FOR ALL | | | OUTLETS IN BEDRMS. SD, LTS, FANS, | | | RECEPTS, ETC. | | | | | | 4)NOTE: PLEASE SEE FBC CHAPTER | | | 34,3401.7.1.2.1 FOR ADDITIONS TO EXSITNG | | | DWELLING IN R-3 OCCUPANCIES. | | | PLEASE SEE ADDTIONS OVER 25% TO EXISTING | | | DWELLING. | | | PLEASE SHOW EITHER EXISTING OR NEW SMOKE | | | DETECTORS WHICH MEET NFPA-72 11.5.1.1 . | | | THESE SHALL BE WIRED IN-LINE WITH NEW | | | ADDTION SD'S. | | | PLEASE ALSO SHOW ALL NEW OR EXSITNG | | | RECEPTS IN LOCATIONS WHICH ARE REQUIRED | | | TO BE GFI/GFI PROTECTED. (KITCHENS, | | | BATHS, OUTSIDE, ETC. 210.8A1-7). | | | | | | 5)NOTE: PLEASE INCLUDE NEW SERVICE | | | ENTRANCE CONDUCTORS AND RISER SIZE AND | | | TYPE.; PLANS NOTES THIS BY FPL, HOWEVER | | | FPL ONLY IS RESPONSIBLE FOR THE SERVICE | | | DROP UP TO THE WEATHER-HEAD. | | | 310.15B6,240.4 | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | 1)NOTE: PLEASE SEE MISSING CERTIFICATE | | | OF AUTHORIZATION NUMBER ON A- SHEETS. | | | THIS IS NOT FOR ELECTRICAL SHEETS. | | | 61G15-23.002, FS 471.023 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-04-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-11 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-11 |
Time |
09:17 |
Sent To |
P |
|
| Notes |
| 2006-04-11 00:00:00 | TO "P" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-02-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-22 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-22 |
Time |
16:13 |
Sent To |
E |
|
| Notes |
| 2006-02-22 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-09-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-07 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-07 |
Time |
10:09 |
Sent To |
E |
|
| Notes |
| 2005-09-07 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-09-29 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-09-29 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2005-08-31 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2005-08-31 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-09-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-09-19 |
Time |
08:07 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2005-09-19 |
Time |
08:07 |
Sent To |
B |
|
| Notes |
| 2005-09-19 00:00:00 | MECHANICAL PERMIT NOT APPLYED FOR AT | | | THIS TIME, NO MECH. CONTRACTOR LISTFD | | | AND NO MECH. PLANS SUBMITTED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2006-04-12 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-04-12 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-04-12 |
Time |
12:56 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-03-06 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-03-06 |
Time |
13:52 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2006-03-06 |
Time |
13:52 |
Sent To |
B |
|
| Notes |
| 2006-03-06 00:00:00 | DENIED; | | | SHOW AUTOMATIC CLOTHES WASHER ON RISER | | | DIAGRAM. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2005-09-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-09-17 |
Time |
06:42 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2005-09-17 |
Time |
06:41 |
Sent To |
M |
|
| Notes |
| 2005-09-17 00:00:00 | NOT ENOUGH INFORMATION TO DO A PLUMBING | | | PLAN REVIEW. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-09-06 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-09-06 |
Time |
19:57 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-09-06 |
Time |
19:57 |
Sent To |
I |
|
| Notes |
| 2005-09-06 00:00:00 | NEW ADDITION MUST MEET THE 25FT IN FRONT | | | SETBACK (DOUBLE FRONTAGE). |
|
|