Plan Review Details - Permit 05081995
Plan Review Stops For Permit 05081995
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-09-11 Cont ID  
Sent By shill Date 2007-09-11 Time 15:27 Rev Time 0.00
Received By shill Date 2007-09-11 Time 15:27 Sent To  
Notes
2007-09-11 15:28:03REVISION 8/28/07

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-07-06 Cont ID  
Sent By shill Date 2006-07-06 Time 09:21 Rev Time 0.00
Received By shill Date 2006-07-06 Time 09:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-06-16 Cont ID  
Sent By shill Date 2006-06-16 Time 14:46 Rev Time 0.00
Received By shill Date 2006-06-16 Time 14:46 Sent To  
Notes
2006-06-16 00:00:00ENGINEER REDLINED IN MEETING 6/16

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-07 Cont ID  
Sent By shill Date 2006-06-07 Time 17:50 Rev Time 0.00
Received By shill Date 2006-06-07 Time 17:50 Sent To  
Notes
2006-06-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS REVIEW, NUMBERING
 REMAINING THE SAME FOR CONSISTENCY
  
 1.)N/A
  
 2.)ADDRESSED.
  
 3.)THE TOTAL RISER HEIGHT IS 9.25 IN,
 EXCEEDS THE 9IN MAXIMUM HEIGHT
 FBC1009.3(7).
  
 THE RISER HEIGHT WAS NOT CHANGED.THE
 ENGINEER CALLED AND STATED THAT THE
 RISER HEIGHT IS 7 3/4" ON THE PLAN.AS
 I DID NOT HAVE THE PLAN IN FRONT OF ME,
 I TOLD HIM THAT IS ACCEPTABLE.HOWEVER,
 THE RISER HEIGHT IS NOT 7 3/4".THAT
 DIMENSION ON THE PLAN SHOWN FROM GRADE
 TO THE BOTTOM OF THE FIRST TREAD.
 WHEN YOU ADD THE TREAD HEIGHT, 1 1/2",
 THE TOTAL IS 9.25 IN.SEE ATTACHED
 COMMENTARY IN REGARDS TO CORRECT WAY TO
 MEASURE RISER HEIGHT.
  
 4.)A HANDRAIL EXTENSION AT THE BOTTOM
 OF THE STAIR IS REQUIRED, FBC1009.11.5.
  
 NO DIMENSIONS SHOWN.THE EXTENSION IS
 NOT COMPLIANT, PLEASE READ REFERENCED
 CODE SECTION.EXTENSION REQUIRED AT THE
 TOP OF THE FLIGHT ALSO.SEE
 FBC1009.11.5 AND SHOW COMPLIANCE WITH
 ALL DIMENSIONS ON THE PLAN.THE PLAN
 VIEW IS TO MATCH THE ELEVATIONS. NOTE
 THAT THE EXTENSION AS SHOWN GRAPHICALLY
 IS NOT CORRECT BUT ALSO DOES NOT SHOW
 ANY DIMENSIONS.SEE ATTACHED
 COMMENTARY.
  
 5.)N/A
  
 NEW COMMENTS:
  
 6.)LANDING REQUIRED FOR THE STAIR,
 FBC1009.4.
  
 7.)THE TREADS ON AN OPEN TREAD
 STAIRWAY IS TO COMPLY WITH FBC1009.3.2
 EXCEPTION 1 (4" SPHERE).COMMENTARY
 ATTACHED.
  
 8.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS ARE NOT PROPERLY ADDRESSED A
 THIRD TIME.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-14 Cont ID  
Sent By shill Date 2006-03-14 Time 08:23 Rev Time 0.00
Received By shill Date 2006-03-14 Time 08:10 Sent To  
Notes
2006-03-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PREVIOUS REVIEW WAS DONE ON
 FBC2001.THE NEW ENGINEERING DECLARES
 FBC2004.CONFIRM THAT OTHER SHEETS
 DECLARE FBC2004, IF APPLICABLE.
  
 3.)THE TOTAL RISER HEIGHT IS 9.25 IN,
 EXCEEDS THE 9IN MAXIMUM HEIGHT
 FBC1009.3(7).
  
 4.)A HANDRAIL EXTENSION AT THE BOTTOM
 OF THE STAIR IS REQUIRED, FBC1009.11.5.
  
 5.)THE PLANS STATE THAT THIS WAS
 DESIGNED UNDER ASCE7-98, CORRECT
 STANDARD IS ASCE7-02, FBC35.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-14 Cont ID  
Sent By shill Date 2005-10-14 Time 15:46 Rev Time 0.50
Received By shill Date 2005-10-14 Time 15:46 Sent To  
Notes
2005-10-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-07-07 Cont ID  
Sent By dpalmer Date 2006-07-07 Time 19:10 Rev Time 0.00
Received By dpalmer Date 2006-07-07 Time 18:27 Sent To  
Notes
2006-07-07 00:00:00*** NOTE ***
  
 PLEASE SEE PLANS REDLINED ON RISER FOR
 SIGNAGE LOCATIONS AND TO VERIFY LOCATION
 OF DISCONNECT PER E-2 AND WHAT IS NOTED
 ON RISER NOTES.
  
 STAMPED GEN SUBMITTIALS
 STAMPED ATS SUBMITTIALS.
 STAMPED ELECTRICAL SHEETS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-06-07 Cont ID  
Sent By dpalmer Date 2006-06-07 Time 07:43 Rev Time 0.00
Received By dpalmer Date 2006-06-07 Time 06:58 Sent To  
Notes
2006-06-07 00:00:00******* UNSAT 3RD REVIEW *******
  
 ** PLEASE SEE NOTES FROM PREVIOUS
 REVIEW(S) WHICH STILL REMAIN.
  
 1) NOTE: PLEASE SEE NOTES ADDED TO RISER
 THAT MENTIONS THE NEW SERVICE ENTRANCE
 RATED MAIN/ATS SWITCHES TO MEET 230.76,
 230.79, ETC HOWEVER PLEASE SEE THE SPECS
 SUBMITTED DO NOT INDICATE THIS.?
 PLEASE KNOW THE FIRST MEANS OF
 DISCONNECT FOR THE SERVICE ARE NOW THESE
 NEW PEICES OF EQUIPMENT SHOWN AND FFROM
 THE INFORMATION SUBMITTED, THIS CAN BE
 NOT VERIFIED
 PLEASE SEE 225.31 REQUIRES A MEANS OF
 DISCONNECT FOR THE FEEDERS COMING FROM
 THE GENERATOR UP AND INTO THE BUILDING
 AT THE NEAREST POINT OF ENTRANCE. PLEASE
 SEE THESE APPEAR TO BE ROUTED INSIDE THE
 BUILDING? ONLY MENTIONS "HIGH ON THE
 WALL". IS THIS OUTSIDE OR INSIDE?PLEASE
 SEE 230.6.
  
 2) NOTE: PLEASE SEE THE RISER DIAGRAM
 DOES NOT CORRELATE FOR THE NEW SERVICE
 ENTRANCE RATED ATS/MAIN(S). PLEASE SEE
 NOTE #3 ON RISER MENTIONS THE ATS/MAIN
 BEING 4-POLE AS NEEDED AND REQUIRED ,
 HOWEVER PLEASE SEE THE RISER IS STILL
 SHOWING THESE AS 3-POLE?
 PLEASE SEE THE COVER SHEETS ON THE
 GENERATOR/ ATS SUBMITTIALS EVEN MENTIONS
 FROM THE DESIGN FIRM THAT THE ATS
 SUMMARY IS NOT CORRECT. PLEASE SEE THE
 ATS SUMMARY INDICATES A 3-POLE ATS.
 PLEASE KNOW, ALL SPECS, RISER AND NOTES
 SHALL CORRELATE.
  
 3) NOTE: PLEASE SEE RISER STILL
 INDICATES "GFI" PROTECTION FOR THESE
 ATS/ MAINS. PLEASE SEE 230.95,240.13
 ETC. THIS CLASS OF PROTECTION IS NOT
 GFI. PLEASE KNOW THERE IS A SUBSTANTIAL
 DIFFERENCE BETWEEN GFI AND GF
 PROTECTION. PLEASE ADJUST RISER IN ALL
 LOCATION.
  
 4) NOTE: PLEASE SEE A NOTICE ATTACHED
 PER FS 553.80(2)(B) IS NOW GIVEN WITH
 RESPECT TO PLANS AND REPEAT COMMENTS.
 THIS IS ONLY A NOTICE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS OR
 COMMENTS , PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE SO THAT THESE
 ITEMS CAN BE GONE OVER. PLEASE KNOW,
 CONTACT TO MYSELFHAS NOT BEEN DONE AS
 OF TODAY'S DATE AND THIS REVIEW.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-23 Cont ID  
Sent By dpalmer Date 2006-02-23 Time 17:25 Rev Time 0.00
Received By dpalmer Date 2006-02-23 Time 16:06 Sent To  
Notes
2006-02-23 00:00:00**** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE SOME NEW COMMENTS AS
 INFORMATION FOR EQUIPMENT IS NOW BEING
 SUBMITTED FOR REVIEW.
  
 1)NOTE:
  
 2)NOTE: PLEASE SEE A NOTE ON PLANS
 MENTIONS ATS'S ARE TO HAVE A MANUAL
 MEANS OF DISCONNECT AND THAT MEANS OF
 DISCONNECT IS GOING TO BE ON THE OUTSIDE
 OF THE EQUIPMENT AND RATED FOR THE LOAD
 SERVED, (230.76,230.79 ETC), HOWEVER THE
 SPECS SUBMITTED DO NOT CONFIRM AND
 CORRELATE WITH THIS??
  
  
 3)NOTE: PLEASE SEE THE ATS'S ARE ALSO
 BEING SHOWN AS 3-POLE? PLEASE SEE SYSTEM
 IS SHOWING GFI, THIS SHOULD BE GF
 PROTECTED AS GFI IS FOR PERSONNEL
 PROTECTION.
 PLEASE SEE 230.95,240.13,700.7D,700.26
 AND NFPA-110 6.2.15
 PLEASE ALSO SEE THIS FOLLOWING TEXT
 TAKEN DIRECTLY FROM PAGE #5 FROM ASCO.
  
 "WHERE GROUND FAULTPROTECTION IS
 TRIGGERED BY THE CODE AND AN ALTERNATE
 POWER SUPPLY IS INCLUDED,SWITCHING OF
 THE NEUTRAL BECOMES NECESSARY. THE
 CIRCUIT SHOWN ABOVE ILLUSTRATESSUCH A
 CIRCUMSTANCE. THE SERVICE IS LARGER THAN
 1,000 AMPS. CONSEQUENTLY, GROUNDFAULT
 PROTECTION IS REQUIRED AT THE MAIN
 SERVICE DISCONNECT AT A MINIMUM. IF IT
 IS INSTALLED THERE AND THE GENERATOR
 NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL,
 A GROUND FAULT WHEN THE GENERATOR IS
 FEEDING THE LOAD WILL CAUSE THE MAIN
 SERVICE DISCONNECT TO OPEN. THIS WILL
 NOTDISCONNECT THE ARCING FAULT FROM
 THE GENERATOR. COORDINATION IS THUS
 LOST."
 PLEASE SEE AS IT IS REVIEWED BY THIS
 OFFICE AND OTHER CONSULTATIONS, A 4-POLE
 ATS WOULD BE REQUIRED, THIS WOULD ALSO
 CREATE THE SEPARATELY DERIVED SYSTEM,
 AND PLEASE ADJUST THE GROUNDING
 ELECTRODE SYSTEM AT THE GEN ACCORDINGLY.
  
 4)NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FS
 471.025 TO BE CLEAR AND VISABLE WIHT ALL
 SAID INFORMATION ON RIASED SEAL. PELASE
 SEE ONLY ONE SHEET FROM EACH SET IS
 VISABLE WITH THIS INFORMATION AND RAISED
 SEAL.
 PLEASE ALSO SEE 61G15-23.001 WHICH
 REQUIRES THE SEAL TO CONTAIN THE WORDING
 OF "LICENSE" AND NOT "CERTIFICATE"
 PLEASE KNOW, THIS WAS PASSED FEB 04 AND
 AND EXTENSION WAS GRANTED TO THE DATE OF
 DEC 31ST, 2005 ONLY. PLEASE BE SURE
 CORRECTED SEAL IS PRESENT WHEN SIGNING
 AND SEALING PLANS.
  
 **PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONLY ONE COPY OF
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ?

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 19:29 Rev Time 0.90
Received By dpalmer Date 2005-09-10 Time 19:07 Sent To  
Notes
2005-09-10 00:00:00*************** UNSAT ***********
  
  
 1)NOTE: PLEASE SUBMIT ALL SPECS/CUT
 SHEETS/ MANUFACTURES SHEETS FOR NEW
 GENERATOR, ATS, AND SUB-BASE FUEL TANK.
 PLEASE SEE REVIEW OF SOME CODE
 COMPLIANCE COMMENTS CAN NOT VERIFIED AT
 THIS TIME.
  
 2)NOTE: PLEASE SEE NEW SERVICE ENTRANCE
 RATED ATS/ MAINS SHALL CLEARLY INDICATE
 THE MANUAL MEANS OF DISCONNECT LOCATED
 ON ON THE OUTSIDE OF EQUIPMENT.
 230.76,230.79.
  
 3)NOTE: PLEASE SEE 110.26, 110.26A1
 CONDITION 2 FOR CLEARENCES ABOUT
 ELECTRICAL EQUIPMENT.
 PLEASE SEE PLANS AS SHOWN FOR LAYOUT
 DOES NOT MEET THE MIN OF 3 1/2 FT.
 PLEASE ALSO SEE RISER DIAGRAM APPEARS TO
 SHOW A NEW GUTTER BEING INSTALLED
 DIRECTLY IN-FRONT OF NEW MAINS/ATS.
 PLEASE SEE 110.26 WHICH REQUIRES CLEAR
 SPACE. IS THIS THE NEW GUTTER BEHINF ATS
 MAIN? PLEASE SEE THIS GUTTER IF BEHIND
 ATS/ MAINS WILL HAVE LESS THAN 1' FOR
 ACCESS??
  
 4)NOTE: PLEASE SEE FIRE REVIEW COMMENTS.
 PLEASE SEE THAT NEW GENERATOR
 ANNUNCIATOR PANEL SHALL BE LOCATED IN
 CLOSE PROXIMITY TO ANY EXSITING FACP.
 NFPA-101.
  
 5)NOTE: PLEASE SEE COLOR CODING OF
 FEEDERS FOR 277/480 SHALL BE AS FOLLOWS.
 A-BROWN, B-PURPLE AND C- YELLOW.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND AND
 STAMPING.
 ONE COPY OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMERWPB.ORG
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-07-13 Cont ID  
Sent By mwennerg Date 2006-07-13 Time 14:16 Rev Time 0.00
Received By mwennerg Date 2006-07-13 Time 14:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-06-15 Cont ID  
Sent By mwennerg Date 2006-06-15 Time 13:08 Rev Time 0.00
Received By mwennerg Date 2006-06-15 Time 13:08 Sent To  
Notes
2006-06-15 00:00:00***DENIED***
  
 1) PLEASE PROVIDE COMPLIANCE USING
 ADOPTED EDITIONS AND SHOW ON PLANS.
  
 2) HANDRAILS TO COMPLY WITH FBC AND NFPA
 101, SEC. 7.2.2.4.4.
  
 3) PLEASE SEE COMMENT REGARDING FUEL
 TANK PERMITTING REQUIREMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-03-14 Cont ID  
Sent By mwennerg Date 2006-03-14 Time 15:10 Rev Time 0.00
Received By mwennerg Date 2006-03-14 Time 15:10 Sent To  
Notes
2006-03-14 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO P.E. SEAL REQUIREMENTS.
  
 2) WORK SHALL APPLY WITH ALL APPLICABLE
 CODES AND NFPA 110.
  
 3) PLEASE PROVIDE APPROPRIATE PROTECTION
 FOR ALL EQUIPMENT IF SUBJECT TO
 MECHANICAL DAMAGE.
  
 4) WORK TO COMPLY WITH NFPA 1, 2003
 EDITION SECTION 11.7.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-14 Cont ID  
Sent By mwennerg Date 2005-09-14 Time 14:57 Rev Time 0.00
Received By mwennerg Date 2005-09-14 Time 14:57 Sent To  
Notes
2005-09-14 00:00:00******DENIED******
  
 1) IS THERE AN EXISTING FIRE ALARM
 SYSTEM IN THE BUILDING? IF SO, PLEASE
 ILLUSTRATE THE LOCATION OF THE CONTROL
 PANEL.
  
 2) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR GENERATOR AND FUEL TANK.
  
 3) WORK TO COMPLY WITH NFPA 110 AND ALL
 APPLICABLE CODES.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-09-06 Cont ID  
Sent By rbrown Date 2007-09-06 Time 19:09 Rev Time 0.00
Received By rbrown Date 2007-09-06 Time 19:09 Sent To  
Notes
2007-09-06 19:10:33REVISED SITE PLAN SENT TO LINDA MIA FRANCO FOR ZONING
 REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-12-07 Cont ID  
Sent By adarroug Date 2006-12-07 Time 16:48 Rev Time 0.00
Received By adarroug Date 2006-12-07 Time 16:48 Sent To  
Notes
2006-12-21 09:10:19TO "COMM" BD#21
2006-12-07 16:49:17WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-06 Cont ID  
Sent By adarroug Date 2006-07-06 Time 08:31 Rev Time 0.00
Received By adarroug Date 2006-07-06 Time 08:31 Sent To  
Notes
2006-07-06 00:00:00TO "COMM" BD#44-NEW SHEETS FOR "BLDG"
 SUBMITTED--EXPEDITED PERMIT--

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 09:07 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 09:07 Sent To  
Notes
2006-06-06 00:00:00TO "COMM" BD#1--EXPEDITED PLANS--
2006-05-26 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-26 Cont ID  
Sent By adarroug Date 2006-01-26 Time 16:41 Rev Time 0.00
Received By adarroug Date 2006-01-26 Time 16:41 Sent To  
Notes
2006-02-21 00:00:00TO "COMM" BD#11
2006-01-26 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 10:57 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 10:57 Sent To  
Notes
2005-09-07 00:00:00TO "COMM" BD#64

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-10-14 Time 14:24 Rev Time 0.00
Received By shill Date 2005-09-01 Time 14:24 Sent To Z
Notes
2005-09-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-01-03 Cont ID  
Sent By pkrauss Date 2007-01-03 Time 10:41 Rev Time 0.00
Received By pkrauss Date 2007-01-03 Time 09:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-07-12 Cont ID  
Sent By pkrauss Date 2006-07-12 Time 15:21 Rev Time 0.00
Received By pkrauss Date 2006-07-12 Time 14:49 Sent To  
Notes
2006-07-07 00:00:00NEEDS MECH REVIEW AS NEW DIESEL FUEL
 PLANS ARE REVISED AND SUBMITTED.
 PREVIOUS REVIEW SHOULD HAVE BEEN A "F"
 STATUS INSTEAD OF "N".

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2006-06-13 Cont ID  
Sent By pkrauss Date 2006-06-13 Time 17:33 Rev Time 0.00
Received By pkrauss Date 2006-06-13 Time 17:32 Sent To  
Notes
2006-06-13 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS INDICATING
 THE FOLLOWING:
  
 - PIPE MATERIAL, SIZE, AND LAYOUT.
 - INDICATE SUPPLY, RETURN, & VENT
 - INDICATE PIPE SUPPORT.
 - INDICATE SUPPORT ANCHORING
 - INDICATE ALL VALVES
  
 SHOW COMPLIANCE WITH 2004 FMC CHAPTER
 13, NFPA 110, NFPA 30, NFPA 37, NFPA 70.
  
 ADDITIONAL PERMIT REQUIRED FOR FUEL TANK
 & PIPING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-03-02 Cont ID  
Sent By pkrauss Date 2006-03-02 Time 08:57 Rev Time 0.00
Received By pkrauss Date 2006-03-02 Time 06:46 Sent To  
Notes
2006-03-02 00:00:00DENIED:
 1. ENGINEERED PLANS ARE REQURIED TO HAVE
 A RAISED SEAL FS471.025 & FAC
 61G15-23.002.PLAN SHEET E-1 & E-2 ARE
 NOT SEALED.SEE ALSO COMMETN #4 BY
 DEWEY PALMER, ELECTRICAL PLANS EXAMINER.
  
 PER 2004 FMC 303.4, EQUIPMENT SHALL NOT
 BE INSTALLED IN A LOCATION WHERE SUBJECT
 TO MECHANICAL DAMAGE UNLESS PROTECTED BY
 APPROVED BARRIERS.
  
 ADDITIONAL PERMIT REQUIRED FOR FUEL OIL
 PIPING SHOW COMPLIANCE WITH 2001 NFPA 31
 WITH FUEL PIPING.PROVIDE PIPE SIZING,
 MATERIAL, LAYOUT AND SUPPORT.PLEASE
 PROVIDE PLANS WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-14 Cont ID  
Sent By pkrauss Date 2005-09-14 Time 16:57 Rev Time 0.40
Received By pkrauss Date 2005-09-14 Time 16:57 Sent To  
Notes
2005-09-14 00:00:00ADDTIONAL PERMIT REQUIRED FOR FUEL TANK.
 PLEASE SUBMIT ALL PERTINANT INFORMATION
 WITH FUEL TANK PERMIT APPLICATION.
  
 PLEASE NOTE, PERMIT APPLICATION
 INDICATES FUEL TANK.PLEASE CLARIFY
 LOCATION OF FUEL TANK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 5 Status P Date 2007-09-07 Cont ID  
Sent By lfranco Date 2007-09-07 Time 10:23 Rev Time 0.00
Received By lfranco Date 2007-09-07 Time 10:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2006-07-07 Cont ID  
Sent By lfranco Date 2006-07-07 Time 12:31 Rev Time 0.00
Received By lfranco Date 2006-07-07 Time 12:31 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2006-06-06 Cont ID  
Sent By rbrown Date 2006-04-25 Time 11:14 Rev Time 0.00
Received By rbrown Date 2006-04-25 Time 11:13 Sent To  
Notes
2006-06-19 00:00:00PLANNING DEPARTMENT RESUBMITTAL
 NADINE BIGBY, PLANNER
 RE-SUBMITTAL 6/29/06 2ND NOTATION
  
 RE-SUBMITTAL FOR PALM TRAN PERMIT NO.
 05081995 AT 3201 ELECTRONICS WAY.
 PER OUR MEETING ON FRIDAY, JUNE 16, 2006
 PLEASE FIND A BRIEF EXPLANATION OF THE
 REQUIREMENTS STILL PENDING FOR APPROVAL.
 THE FOLLOWING ITEMS SHALL BE ADDRESSED:
  
 1.PROVIDE A BETTER DETAIL OF THE AREA,
 NOT AN ENLARGEMENT.THIS CAN BE
 ACCOMPLISHED BY PROVIDING A DIGITAL COPY
 AND/OR A REDUCE COPY OF THE SURVEY.THE
 SURVEY SHALL INCLUDE THE FOLLOWING:
  
 A. SCREENING AND ELEVATION OF WALL/
 HEDGES AROUND GENERATOR/ FUEL TANK, AND
 SETBACK DISTANCE.
  
 B. PURSUANT TO SECTION 94-443(B)(1)
 BUFFERING:
 LANDSCAPE BUFFERING FOR INDUSTRIAL USES,
 THE BUFFER STRIP SHALL BE TEN FEET WIDE
 ALONG THE EDGE OF PROPERTY WHEN ADJACENT
 TO A PUBLIC THOROUGHFARE AND AT LEAST 5
 FEET WIDE ALONG THE EDGE OF PROPERTY
 WHEN ADJACENT TO NONRESIDENTIAL ZONING
 DISTRICTS.
  
 2.PURSUANT TO SECTION 94-444(B) OPEN
 SPACE STANDARDS:
 (B) FUEL OR OIL OR PROPANE TANKS,
 GENERATORS SHALL NOT BE PERMITTED UNLESS
 APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK,
 DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND
 STEEL.WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT
 INTERVALS.A FOUR-SIDED ENCLOSURE WITH
 AN OBSCURING GATE MAY BE REQUIRED AS A
 CONDITION FOR SITE PLAN APPROVAL.
  
 THE SCREENING SHALL ENCLOSE BOTH FUEL
 TANK INCLUDING ROOFTOP EXHAUST (TANK)
 AND GENERATOR.
  
 3. PURSUANT TO SECTION 94-305(B)(4)
 SETBACKS
 (B)(4) SETBACK ENCROACHMENT: MECHANICAL
 EQUIPMENT SHALL NOT PROJECT MORE THAN 4
 FEET INTO A SETBACK.
  
 IF YOU NEED MORE INFORMATION, I CAN BE
 REACHED AT 822-1435.
  
 THANK YOU
2006-06-13 00:00:00PLANNING AND ZONING: FAILED
  
 RESUBMITTAL
 THE FOLLOWING ITEMS WERE NOT ADDRESSED:
  
 1.PROVIDE A BETTER DETAIL OF THE AREA,
 NOT AN ENLARGEMENT.
  
 2.PURSUANT TO SECTION 94-444(B)FUEL OIL
 OR PROPANE TANKS, GENERATORS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE
 SCREENING IS PROVIDED.
  
 3. PURSUANT TO SECTION 94-305(B)(4)
 MECHANICAL EQUIPMENT MAY NOT PROJECT
 MORE THAN FOUR FEET INTO SETBACK.
  
 REVIEWED BY: NADINE BIGBY, PLANNER
  
 IF YOU NEED MORE INFORMATION, I CAN BE
 REACHED AT 822-1435.
2006-06-06 00:00:00THE FOLLOWING COMMENTS WERE ORIGINALLY
 ENTERED BY NADINE BIGBY UNDER THE
 GEN-ELEC (ELECTRICAL) PERMIT FOR THE
 GENERATOR:
  
  
 PLANNING AND ZONING DEPARTMENT: FAILED
  
 THE FOLLOWING ITEMS SHALL BE ADDRESSED:
  
 1. PROVIDE A BETTER DETAIL OF THE AREA
 ON THE SITE PLAN.
  
 2. SCREENING IS REQUIRED AROUND FUEL
 TANK AND GENERATOR.
  
 REVIEWED BY NADINE BIGBY, PLANNER
  
 IF YOU NEED MORE INFORMATION, I CAN BE
 REACHED AT (561)822-1435.

Review Stop Z ZONING
Rev No 2 Status N Date 2006-06-06 Cont ID  
Sent By adarroug Date 2006-04-25 Time 12:23 Rev Time 0.00
Received By adarroug Date 2006-04-25 Time 10:00 Sent To  
Notes
2006-04-28 00:00:004/25/06-COMMENTS FOR THE ZONING REVIEW
 UNDER PERMIT#05081998ADARROUGH

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-06 Cont ID  
Sent By mmclean Date 2005-09-06 Time 18:47 Rev Time 0.00
Received By mmclean Date 2005-09-06 Time 18:47 Sent To I
Notes
2005-09-06 00:00:00DENIED,
 1. MUST PROVIDE A COMPLETE SITEPLAN WITH
 DIMENSION OF LOT & SETBACK OF STRUCTURE
 FROM PROPERTY LINE.
 2. NEED THE DIMENSION OF GENERATOR AND
 SETBACK FROM STRUCTURE & PROPERTY LINE.
  
 NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720