| 2005-11-10 00:00:00 | ****CORRECTIONS**** |
| | ****PLAN REVIEW ONLY*** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)FBC* 109.3.6.1SPECIAL INSPECTOR. |
| | A STRUCTURAL INSPECTION PLAN MUST BE |
| | SUBMITTED PRIOR TO THE ISSUANCE OF A |
| | BUILDING PERMIT FOR THE CONSTRUCTION OF |
| | A THRESHOLD BUILDING.A THRESHOLD |
| | BUILDING IS ANY BUILDING WHICH IS |
| | GREATER THAN THREE STORIES OR 50 FEET IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY |
| | OCCUPANCY WITH 5,000 SQFT AREA AND |
| | GREATER THAN 500 OCCUPANTS.THREE |
| | COPIES OF THE PLANS AND OTHER DOCUMENTS |
| | WILL BE REQUIRED FOR PERMITTING |
| | PURPOSES. |
| | |
| | PLEASE SUBMIT FOUR SIGNED AND SEALED |
| | INSPECTION PLANS.REGARDING THE SPECIAL |
| | INSPECTOR'S INSPECTION PLAN PREPARED BY |
| | WALTER P. MOORE, THE CERTIFICATE OF |
| | AUTHORIZATION FOR THE FIRM AND THE |
| | PRINTED NAME OF THE PERSON SEALING THE |
| | DOCUMENT IS TO BE ON THE PLAN, |
| | FAC61G15-23.002. |
| | |
| | PRIOR TO PERMIT ISSUANCE, PLEASE ARRANGE |
| | WITH HAROLD PISKURA (INSPECTION SERVICES |
| | MANAGER, 561-805-6711) A MEETING |
| | INVOLVING THE OWNER, THRESHOLD |
| | INSPECTOR, JOB INSPECTOR, CONTRACTOR AND |
| | ENGINEER. |
| | |
| | 3.)THE BUILDING OFFICIAL MAY, AT HIS |
| | DISCRETION, ISSUE A SPECIAL PERMIT FOR |
| | THE FOUNDATION ONLY, UPON WRITTEN |
| | REQUEST BY THE OWNER AND CONTRACTOR. THE |
| | HOLDER OF SUCH SPECIAL PERMIT IS |
| | PROCEEDING AT HIS/HER OWN RISK AND |
| | WITHOUT ASSURANCE THAT A PERMIT FOR THE |
| | REMAINDER OF THE WORK WILL BE GRANTED |
| | AND THAT CORRECTIONS WILL NOT BE |
| | REQUIRED IN ORDER TO MEET THE PROVISIONS |
| | OF THE TECHNICAL CODES. |
| | |
| | 4.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY PRIOR TO PERMIT ISSUANCE. |
| | THE PLANS MUST BE STAMPED AND THE |
| | RECEIPT ATTACHED TO THE APPLICATION. |
| | 561-233-5025 |
| | |
| | 5.) THE APPLICATION PROJECT DESCRIPTION |
| | STATES THAT IT IS TO INCLUDE UNDERGROUND |
| | MECHANICAL, ELECTRIC AND PLUMBING.NO |
| | PLANS FOR MEP WERE SUBMITTED.NO |
| | MECHANICAL OR PLUMBING REVIEW DONE. |
| | SLAB PERMIT CANNOT BE ISSUED UNTIL |
| | UNDERGROUND MEPS AND FIRE REVIEWS HAVE |
| | BEEN DETERMINED TO BE CODE COMPLIANT. |
| | |
| | 6.)S1.0, DESIGN CRITERIA, C.1.7, |
| | BALCONIES STATES 60.SEE FBC TABLE |
| | 1607.1; THAT IS FOR ONE AND TWO FAMILY |
| | DWELLINGS ONLY; SHOULD BE 100. |
| | |
| | 7.)S1.0, DESIGN CRITERIA, F.1 REFERS |
| | TO ASCE7-02.FBC35, REFERENCED STANDARD |
| | IS ASCE7-98. |
| | |
| | 8.)S1.0, DESIGN CRITERIA, C.1 NOTES 1, |
| | SHOW THAT THE LIVE LOAD REDUCTION IS IN |
| | COMPLIANCE WITH FBC1607.9. |
| | |
| | 9.)S1.0, DESIGN CRITERIA, F1.D, |
| | FBC1603.1.4, INCLUDE THE APPLICABLE |
| | ENCLOSURE CLASSIFICATION. |
| | |
| | 10.)S1.0, DESIGN CRITERIA, F, PROVIDE |
| | A PROPOSED BUILDING HEIGHT. |
| | |
| | 11.)S1.0, DESIGN CRITERIA, F.2.A, THE |
| | EDGE STRIP DIMENSION WAS LEFT |
| | BLANK. |
| | |
| | 12.) S1.0, DESIGN CRITERIA, K, SEE |
| | HANDRAIL AND GUARD DESIGN REQUIREMENTS |
| | FBC1607.7.1. |
| | |
| | 13.)S1.0, DESIGN CRITERIA, L, DESIGN |
| | FOR STAIR RAIL MAY BE REQUIRED TO COMPLY |
| | WITH ALL REQUIREMENTS OF FBC1607.7.1 AS |
| | STAIR RAILS ARE BOTH A GUARD AND A |
| | HANDRAIL. |
| | |
| | 14.)SUBMIT ORIGINAL SIGNED, SEALED AND |
| | DATED SOILS REPORT, FBC1802.2. |
| | |
| | 15.)PROVIDE A SURVEY OF THIS |
| | PROPERTY. |
| | |
| | 16.)THIS PROPERTY IS IN A FLOOD ZONE. |
| | FFE IS TO BE 6" ABOVE BFE, CITY OF WEST |
| | PALM BEACH MUNICIPAL CODE 94-546.ARE |
| | THE ELEVATIONS SHOWN ON S6.2 NGVD? |
| | |