| 2006-04-25 00:00:00 | ********** UNSAT 4TH TIME ********* |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM ALL |
| | PREVIOUS REVIEWS WHICH STILL NEED TO BE |
| | ADDRESSED. |
| | PLEASE ALSO SEE NEW COMMENTS DUE TO |
| | CHANGES MADE TO PLANS. |
| | |
| | 1)NOTE: PLEASE SUBMIT COMPLETE LOAD |
| | CALCUALTIONS PER SECTION 220.31B OF THE |
| | NEC>. 2002 |
| | |
| | 2)NOTE: PLEASE SEE PLANS ARE NOW COMING |
| | BACK WITH RISER CHNAGED AND RISER/PLANS |
| | DO NOT INDICATE THE OCP AT MAIN SERVICE |
| | WHICH FEEDS THE NEW SUB-PANEL. |
| | 215.5 |
| | |
| | 3) NOTE: PLEASE SEEMISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN HOUSE |
| | PANEL TO POOL HOUSE PANEL. |
| | 250.32. |
| | PLEASE ALSO SEE 250.66 FOR THE MIN |
| | GROUNDING ELECTRODE CONDUCTOR AT THE |
| | DETACHED BLDG. |
| | PLEASE SEE RISER SHOW A #10. THIS IS TOO |
| | SMALL. |
| | |
| | 4) NOTE: PLEASE SEE WALL UNIT A/C IS |
| | SHOWN A 3KW, ON WHAT IS SHOWN ON PLANS |
| | AS A SINGLE PHASE FEED. PLEASE SEE MAX |
| | VA FOR 115/120V BRANCH CIRCUIT IS 1440 |
| | FOR 15A OR 1920 FOR 20. |
| | 240.4,310.16 ETC. |
| | |
| | 5) NOTE: PLEASE SEE THERE IS NOW NO |
| | PANEL SCHEDULE SUBMITTED TO VERIFY THE |
| | OCP, AWG FOR BRANCH CIRCUITS OF THIS NEW |
| | PANEL. WHERE DID THE PANEL SCHEDULE FROM |
| | PREVIOUS PLANS GO.?? |
| | PLEASE SUBMIT AND PLEASE SEE NEC 2002 |
| | FOR ALL MIN SIZES AS REQUIRED. |
| | |
| | 6) NOTE: PLEASE SEE ALL BRANCH CIRCUITS |
| | IN THIS NEW POOL HOUSE SHALL BE ARC |
| | FAULT.210.12 |
| | PLEASE NOTE, AS ONLY AFCI PROTECTION IS |
| | NOTED FOR RECEPTS IN BEDRM FOR A/C AND |
| | GEN PURPOSE RECEPTS. |
| | |
| | 7) NOTE: PLEASE REVIEW REQUESTED ALL |
| | OLD/VOIDED SHEETS TO BE REMOVED FROM |
| | SETS AND ONLY TO INSERT NEW SHEETS, THIS |
| | WAS DONE, HOWEVER PREVIOUS NOTES |
| | REQUESTED TO SUBMIT ANY OLD/VOIDED |
| | REMOVED SHEETS AND SUBMIT SEPARATELY. |
| | PLEASE SEE NO REMOVED SHEETS WERE |
| | SUBMITTED FOR REFERENCE. |
| | PLEASE DO SO. |
| | |
| | 8) NOTE: PLEASE SEE PLANS ARE NOW COMING |
| | BACK WITH THE TITLE BLOCK FROM THE |
| | ORIGINAL ENGINEER OF RECORD BEING |
| | REMOVED FROM ELECTRICLA SHEETS?? |
| | PLEASE SEE FBC ADMINISTRATIVE SECTION |
| | 104.2.1. PLANS WHICH ARE NOT REQUIRED TO |
| | BE DONE BY ARCHITECT OR ENGINEER, STILL |
| | MUST CONTAIN THE PRINTED NAME AND THE |
| | SIGNATURE OF THE DESIGN PROFESSIONAL AND |
| | PERSON RESPONSIBLE FOR PLANS AND DESIGN. |
| | PLEASE SEE PLANS DO NOT CONTAIN EITHER. |
| | |
| | |
| | 9) NOTE: PLEASE SEE A NOTICE WAS GIVEN |
| | ON PERVIOUS REVIEW WHICH STATED |
| | 553.80(2)(B) WHICH RESPECT TO PLANS |
| | COMING BACK WITH ANY OF THE SAME CODE |
| | COMLIANCE COMMENTS NOT ADDRESS, A 4X FEE |
| | FOR THE PLAN REVIEW PORTION OF THE |
| | PERMIT FEE SHALL BE ACCESSED. |
| | PLEASE KNOW, THIS IS NOW DONE AND THE |
| | FEE OF $720 MUST BE PAID BEFORE |
| | RESUBMITTING PLANS FOR NEXT RESUB. |
| | IT IS STRONGLY RECOMMENDED A MEETING BE |
| | HELD TO GO OVER PLANS. THIS MEETING |
| | SHOULD INCLUDE THE DESIGN PROFESSIONAL |
| | FOR PROJECT INCLUDING THE ENGINEER,AND |
| | CONTRACTOR AT A MIN. |
| | ONE SET OF PLANS ARE BEING RETAINED. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |