Plan Review Details - Permit 05081992
Plan Review Stops For Permit 05081992
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-02-15 Cont ID  
Sent By alange Date 2006-02-15 Time 16:03 Rev Time 1.50
Received By alange Date 2006-02-15 Time 14:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-05 Cont ID  
Sent By alange Date 2006-01-05 Time 08:07 Rev Time 1.25
Received By alange Date 2006-01-05 Time 07:41 Sent To  
Notes
2006-01-05 00:00:00DENIED
  
 1."R" VALUES ON ENERGY CALCS DO NOT
 MATCH PLANS.
  
 2.PRODUCT APPROVALS SUBMITTED ARE
 INCOMPLETE.
 A. ALL AMERICAN SHUTTERS ARE MISSING
 ATATE PRODUCT APPROVAL.
 B.PGT SH ONLY ONE COPY OF NOA AND NO
 STATE PRODUCT APPROVAL.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-26 Cont ID  
Sent By alange Date 2005-09-26 Time 12:05 Rev Time 1.66
Received By alange Date 2005-09-26 Time 11:51 Sent To  
Notes
2005-09-26 00:00:00DENIED
  
 1.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 2.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.SUBMIT ORIGONAL SIGNED AND SEALED
 SURVEYS.FS 472.025.
  
 4.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5.SHOW FINISH FLOOR HEIGHT.MINIMUM
 FINISH FLOOR SLAB HEIGHT SHALL BE 4"
 ABOVE GRADE.WPB AMMENDMENT TO THE FBC
 1804.1.7
  
 6.SHOW HOW BOTTOM PLAT WILL ATTACH TO
 SLAB.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-04-25 Cont ID  
Sent By dpalmer Date 2006-04-25 Time 18:02 Rev Time 0.00
Received By dpalmer Date 2006-04-25 Time 16:51 Sent To P
Notes
2006-04-25 00:00:00********** UNSAT 4TH TIME *********
  
 ** PLEASE SEE SOME COMMENTS FROM ALL
 PREVIOUS REVIEWS WHICH STILL NEED TO BE
 ADDRESSED.
 PLEASE ALSO SEE NEW COMMENTS DUE TO
 CHANGES MADE TO PLANS.
  
 1)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCUALTIONS PER SECTION 220.31B OF THE
 NEC>. 2002
  
 2)NOTE: PLEASE SEE PLANS ARE NOW COMING
 BACK WITH RISER CHNAGED AND RISER/PLANS
 DO NOT INDICATE THE OCP AT MAIN SERVICE
 WHICH FEEDS THE NEW SUB-PANEL.
 215.5
  
 3) NOTE: PLEASE SEEMISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN HOUSE
 PANEL TO POOL HOUSE PANEL.
 250.32.
 PLEASE ALSO SEE 250.66 FOR THE MIN
 GROUNDING ELECTRODE CONDUCTOR AT THE
 DETACHED BLDG.
 PLEASE SEE RISER SHOW A #10. THIS IS TOO
 SMALL.
  
 4) NOTE: PLEASE SEE WALL UNIT A/C IS
 SHOWN A 3KW, ON WHAT IS SHOWN ON PLANS
 AS A SINGLE PHASE FEED. PLEASE SEE MAX
 VA FOR 115/120V BRANCH CIRCUIT IS 1440
 FOR 15A OR 1920 FOR 20.
 240.4,310.16 ETC.
  
 5) NOTE: PLEASE SEE THERE IS NOW NO
 PANEL SCHEDULE SUBMITTED TO VERIFY THE
 OCP, AWG FOR BRANCH CIRCUITS OF THIS NEW
 PANEL. WHERE DID THE PANEL SCHEDULE FROM
 PREVIOUS PLANS GO.??
 PLEASE SUBMIT AND PLEASE SEE NEC 2002
 FOR ALL MIN SIZES AS REQUIRED.
  
 6) NOTE: PLEASE SEE ALL BRANCH CIRCUITS
 IN THIS NEW POOL HOUSE SHALL BE ARC
 FAULT.210.12
 PLEASE NOTE, AS ONLY AFCI PROTECTION IS
 NOTED FOR RECEPTS IN BEDRM FOR A/C AND
 GEN PURPOSE RECEPTS.
  
 7) NOTE: PLEASE REVIEW REQUESTED ALL
 OLD/VOIDED SHEETS TO BE REMOVED FROM
 SETS AND ONLY TO INSERT NEW SHEETS, THIS
 WAS DONE, HOWEVER PREVIOUS NOTES
 REQUESTED TO SUBMIT ANY OLD/VOIDED
 REMOVED SHEETS AND SUBMIT SEPARATELY.
 PLEASE SEE NO REMOVED SHEETS WERE
 SUBMITTED FOR REFERENCE.
 PLEASE DO SO.
  
 8) NOTE: PLEASE SEE PLANS ARE NOW COMING
 BACK WITH THE TITLE BLOCK FROM THE
 ORIGINAL ENGINEER OF RECORD BEING
 REMOVED FROM ELECTRICLA SHEETS??
 PLEASE SEE FBC ADMINISTRATIVE SECTION
 104.2.1. PLANS WHICH ARE NOT REQUIRED TO
 BE DONE BY ARCHITECT OR ENGINEER, STILL
 MUST CONTAIN THE PRINTED NAME AND THE
 SIGNATURE OF THE DESIGN PROFESSIONAL AND
 PERSON RESPONSIBLE FOR PLANS AND DESIGN.
 PLEASE SEE PLANS DO NOT CONTAIN EITHER.
  
  
 9) NOTE: PLEASE SEE A NOTICE WAS GIVEN
 ON PERVIOUS REVIEW WHICH STATED
 553.80(2)(B) WHICH RESPECT TO PLANS
 COMING BACK WITH ANY OF THE SAME CODE
 COMLIANCE COMMENTS NOT ADDRESS, A 4X FEE
 FOR THE PLAN REVIEW PORTION OF THE
 PERMIT FEE SHALL BE ACCESSED.
 PLEASE KNOW, THIS IS NOW DONE AND THE
 FEE OF $720 MUST BE PAID BEFORE
 RESUBMITTING PLANS FOR NEXT RESUB.
 IT IS STRONGLY RECOMMENDED A MEETING BE
 HELD TO GO OVER PLANS. THIS MEETING
 SHOULD INCLUDE THE DESIGN PROFESSIONAL
 FOR PROJECT INCLUDING THE ENGINEER,AND
 CONTRACTOR AT A MIN.
 ONE SET OF PLANS ARE BEING RETAINED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-02-06 Cont ID  
Sent By dpalmer Date 2006-02-06 Time 17:35 Rev Time 0.00
Received By dpalmer Date 2006-02-06 Time 17:04 Sent To M
Notes
2006-02-06 00:00:00******** UNSAT 3RD REVIEW *********
  
 ** PLEASE SEE NOTES FROM PREVIOUS
 REVIEW(S) WHICH STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE: PLEASE SEE A MEANS OF DISCONNECT
 IS REQUIRED AT THE DETACHED VLDG PER
 225.31
 RISER SHOWS THIS AT MAIN HOUSE?
  
 2)NOTE: PLEASE SEE LOAD CALCULATIONS FOR
 BOTH THE MAIN EXIST PANEL AND NEW SUB
 PANEL SHALL BE DONE PER NEC 220,220.31B
 ETC.
 PLEASE SEE THE LOADS ON NEW SUB PANEL
 SHALL CORRELATE WITH THE NEW LOAD ADDED
 TO MAIN PANELS. THIS MAY NOT BE DE-RATED
 TWICE.
 PLEASE SEE THERE IS NO LOCATION IN THE
 CODE THAT PERMIT THE FIRST 10 KW AT
 65%?? ETC.
  
 3)NOTE: PLEASE SEE SD ADDED TO PLANS,
 HOWEVER THIS SD WAS ADDED AND SHOWN
 WITHIN 3' OF BATHRM DOOR. PLEASE KNOW,
 THIS MUST BE LOCATED MORE THAN 3' FROM
 BATH DOOR AS REQUIRED PER NFPA-101
 11.8.3.5
  
 4)NOTE: PLEASE SEE PREVIOUS PLANS WERE
 REDLINED WITH A MISSING RECEPT FOR 2' OF
 WALL SPACE. PLEASE SEE THIS WAS ADDED,
 HOWEVER THIS HAS BEEN HAND-WRITTEN ON
 PLANS WHICH ARE SIGNED, AND SEALED BY AN
 ENGINEER.
 FS 471.025
  
 5)NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO THE DESIGN PROFESSIONAL AND
 REPEAT CODE COMPLIANCE COMMENTS.
 PLEAS KNOW, IF PLANS COME BACK WITH ANY
 OF THE SAME COMMENT NOT ADDRESSED A 4X
 FEE SHALL BE ACCESSED AS REQUIRED PER
 STATUE ABOVE AND PLANS SHALL BE RETAINED
 FOR POSSIBLE REVIEW BY THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS.
 PLEASE ADDRESS ALL COMMENTS.
  
  
 6)NOTE: PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WHICH REQUESTED ALL
 OLD/VOIDED SHEETS TO BE "REMOVED" FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO SETS FOR REVIEW AND STAMPING.
 PLEASE ONLY SUBMIT ONE SET OF OLD SHEETS
 FOR REFERENCE.
 THIS WAS NOT DONE AND ALL OLD/VOIDED
 SHEETS REMAIN IN SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-12-30 Cont ID  
Sent By dpalmer Date 2005-12-30 Time 08:16 Rev Time 0.00
Received By dpalmer Date 2005-12-30 Time 07:38 Sent To P
Notes
2005-12-30 00:00:00***********UNSAT ************
  
 1)NOTE: PLEASE SEE 225.31 FOR MEANS OF
 DISCONNECT REQUIRED AT THE DETACHED
 GARAGE. THE RISER SHOWS A DISCONNECT
 ,HOWEVR THIS IS NOT CLEAR WHERE IT IS
 LOCATED.
  
 2)NOTE: PLEASE PROVIDE THE LOAD
 CALCUALTIONS FOR EXISTING DWELLING
 ADDING NEW LOAD OF 34 A'S. PLEASE SEE
 220.31B FOR MIN LOAD CALCS.
 PLEASE PROVIDE THE OCP AT EXISTING HOUSE
 PANEL TO FEED TO SUB PANEL.
  
 3)NOTE: SE REDLINED PLANS FOR MISSING
 RECEPT PER 210.52
  
 4)NOTE: PLEASE SEE NFPA-72 11.5.1.1,
 WHICH WILL REQUIRE A SD INSIDE THIS
 ADAPTABLE SLEEPING AREA. MUST BE 20'
 AWAY FROM COOKING APPLIANCES, OR OF A
 PHOTO-ELECTRIC EYE/RE-SETTING TYPE.
  
 ** PLEASE KNOW, THE RECORDED NOCHAS
 NOW EXPIRED AS PER FS 713.13(2). WORK
 HAS NOTCOMMENCED WITHIN 90 DAYS OF
 RECORDING, THE NOC SHALL BECOME VOID.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-14 Cont ID  
Sent By jleahy Date 2005-09-14 Time 15:10 Rev Time 0.45
Received By jleahy Date 2005-09-14 Time 15:10 Sent To M
Notes
2005-09-14 00:00:00WINDOW UNITS IN BEDROOM SHALL BE
 PROTECTED BY ARC FAULT CIRCUIT BREAKER.
 210.12
  
 OUTLETS REQUIRED OUTSIDE PER 210.52.E
  
 PLAN SHOWS 50AMP PANEL ON RISER AND
 100AMP ON FLOOR PLAN?????

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2005-08-30 Cont ID  
Sent By dalvarez Date 2005-08-30 Time 12:20 Rev Time 0.15
Received By dalvarez Date 2005-08-30 Time 12:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 11:42 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 11:42 Sent To E
Notes
2006-04-21 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-30 Cont ID  
Sent By adarroug Date 2006-01-30 Time 09:26 Rev Time 0.00
Received By adarroug Date 2006-01-30 Time 09:26 Sent To E
Notes
2006-01-30 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-28 Cont ID  
Sent By adarroug Date 2005-12-28 Time 16:42 Rev Time 0.00
Received By adarroug Date 2005-12-28 Time 16:42 Sent To E
Notes
2005-12-28 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 11:57 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 11:57 Sent To E
Notes
2005-09-08 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-26 Cont ID  
Sent By alange Date 2005-09-26 Time 12:05 Rev Time 0.00
Received By alange Date 2005-09-01 Time 11:03 Sent To  
Notes
2005-09-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-02-07 Cont ID  
Sent By tgordon Date 2006-02-07 Time 09:14 Rev Time 0.20
Received By tgordon Date 2006-02-07 Time 09:14 Sent To P
Notes
2006-02-07 00:00:00WALL UNIT AND BATHROOM EXHAUST FAN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-09-15 Cont ID  
Sent By tgordon Date 2005-09-15 Time 08:44 Rev Time 0.15
Received By tgordon Date 2005-09-15 Time 08:44 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-04-29 Cont ID  
Sent By jleech Date 2006-04-29 Time 09:57 Rev Time 0.00
Received By jleech Date 2006-04-29 Time 09:57 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-02-15 Cont ID  
Sent By jleech Date 2006-02-15 Time 07:11 Rev Time 0.00
Received By jleech Date 2006-02-15 Time 07:11 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-01-03 Cont ID  
Sent By jleech Date 2006-01-03 Time 08:30 Rev Time 0.00
Received By jleech Date 2006-01-03 Time 08:30 Sent To B
Notes
2005-12-30 00:00:00NEW PLUMB RISER

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-09-17 Cont ID  
Sent By jleech Date 2005-09-17 Time 06:17 Rev Time 0.25
Received By jleech Date 2005-09-17 Time 06:17 Sent To B
Notes
2005-09-17 00:00:00NOT ENOUGH INFORMATION TO DO A PLUMBING
 PLAN REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-07 Cont ID  
Sent By mmclean Date 2005-09-07 Time 18:40 Rev Time 0.00
Received By mmclean Date 2005-09-07 Time 18:40 Sent To I
Notes
***NONE***