Plan Review Details - Permit 05081988
Plan Review Stops For Permit 05081988
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-01-13 Cont ID  
Sent By alange Date 2006-01-13 Time 15:17 Rev Time 1.00
Received By alange Date 2006-01-13 Time 14:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-12-30 Cont ID  
Sent By alange Date 2005-12-30 Time 08:36 Rev Time 0.50
Received By alange Date 2005-12-30 Time 08:25 Sent To Z
Notes
2005-12-30 00:00:00DENIED
 THIRD REVIEW:
  
 1. A. LAWSON SINGLE HUNG WINDOW PRODUCT
 APPROVALS OK.
 B. LAWSON EXTERIOR DOOR MISSING SECOND
 COPY OF STATE PRODUCT APPROVAL AND
 MISSING 2 COPIES OF MIAMI-DADE PRODUCT
 APPROVAL.
 C.LAWSON MULLIONS MISSING TWO COPIES
 OF CORRESPONDING MIAMI-DADE PRODUCT
 APPROVAL.
 2.ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING STATE PRODUCT APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-29 Cont ID  
Sent By alange Date 2005-11-29 Time 16:37 Rev Time 1.00
Received By alange Date 2005-11-29 Time 16:06 Sent To Z
Notes
2005-11-29 00:00:00DENIED
 SECOND REVIEW:
  
 1.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR IMPACT PROTECTION, WINDOW
 MULLIONS AND STRAPS AND HANGERS.
  
 2.ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING STATE PRODUCT APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.BUILDING PERMIT VALUATION IS TOO
 LOW.ADJUST PERMIT VALUATION TO INCLUDE
 ALL MATERIAL AND LABOR OR I WILL ADJUST
 IT ACCORING TO MARSHALL AND SWIFT
 EXTIMATING GUIDE.ADDITIONAL PERMIT
 FEES ARE DUE.
  
 5. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 8.CLEARLY SHOW ON PLANS EXISTING AREAS
 AND AREAS OF NEW WORK.
  
 9. INCLUDE A WINDOW AND DOOR SCHEDULE.
  
 10.SHOW EXTERIOR WALL DETAIL.IS IT
 MASONARY OR WOOD FRAMED?SUBMIT DETAILS
 FOR NEW OPENINGS.
  
 11.PLANS SHOULD BE DESIGNED TO THE
 2001 FBC SEE LETTER ATTACHED BY
 ARCHITECT.
  
 NEW NOTES:
 A.SHOW FOOTING DETAILS INCLUDING
 METHOD OF REINFORCMENT.
 B.DESIGNER OF RECORD SHALL SIGN ALL
 PAGES.FBC 104.2.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-23 Cont ID  
Sent By alange Date 2005-09-23 Time 14:05 Rev Time 1.50
Received By alange Date 2005-09-23 Time 14:05 Sent To  
Notes
2005-09-23 00:00:00DENIED
  
 1.SUBMIT PRODUCT APPROVALS FOR
 WINDOWS, EXTERIOR DOORS AND IMPACT
 PTOTECTION.
  
 2.ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING STATE PRODUCT APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.SUBMIT A DETAIL FOR THE STAIR CASE
 TO BE REPLACED.
  
 4.BUILDING PERMIT VALUATION IS TOO
 LOW.ADJUST PERMIT VALUATION TO INCLUDE
 ALL MATERIAL AND LABOR OR I WILL ADJUST
 IT ACCORING TO MARSHALL AND SWIFT
 EXTIMATING GUIDE.ADDITIONAL PERMIT
 FEES ARE DUE.
  
 5. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 6.NEW WINDOWS OVER TUB SHOWER AREA
 SHALL HAVE SAFTEY GLAZING. FBC 2405.2.1
  
 7.SHOW SIZE TYPE AND LOCATION OF
 BEDROOM WINDOWS SO THAT EMERGENCY ESCAPE
 RESCUE OPENINGS CAN BE VERIFIES. FBC
 1005.4.
  
 8.CLEARLY SHOW ON PLANS EXISTING AREAS
 AND AREAS OF NEW WORK.
  
 9. INCLUDE A WINDOW AND DOOR SCHEDULE.
  
 10.SHOW EXTERIOR WALL DETAIL.IS IT
 MASONARY OR WOOD FRAMED?SUBMIT DETAILS
 FOR NEW OPENINGS.
  
 11.SHOW PRESSURES AT NEW DOOR AND
 WINDOW LOCATIONS PER FBC CH. 16
  
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2005-12-19 Cont ID  
Sent By btrobaug Date 2005-12-19 Time 13:25 Rev Time 0.50
Received By btrobaug Date 2005-12-19 Time 12:55 Sent To B
Notes
2005-12-19 00:00:00 
 PLEASE SEE CARPENTER ELEC HAS AN
 APPLICATION PENDING FOR THE ELECTRICAL
 WORK ON THIS PROJECT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2005-09-07 Cont ID  
Sent By jleahy Date 2005-09-07 Time 10:32 Rev Time 0.15
Received By jleahy Date 2005-09-07 Time 10:32 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-15 Cont ID  
Sent By adarroug Date 2005-12-15 Time 09:25 Rev Time 0.00
Received By adarroug Date 2005-12-15 Time 09:25 Sent To Z
Notes
2005-12-15 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-22 Cont ID  
Sent By adarroug Date 2005-11-22 Time 10:47 Rev Time 0.00
Received By adarroug Date 2005-11-22 Time 10:47 Sent To B
Notes
2005-11-22 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-23 Cont ID  
Sent By alange Date 2005-09-23 Time 14:08 Rev Time 0.00
Received By alange Date 2005-09-01 Time 13:43 Sent To  
Notes
2005-09-01 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-07 Cont ID  
Sent By tgordon Date 2005-09-07 Time 11:45 Rev Time 0.15
Received By tgordon Date 2005-09-07 Time 11:45 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-09-14 Cont ID  
Sent By jleech Date 2005-09-14 Time 12:55 Rev Time 0.00
Received By jleech Date 2005-09-14 Time 12:55 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-01-05 Cont ID  
Sent By mmclean Date 2006-01-05 Time 10:57 Rev Time 0.00
Received By mmclean Date 2006-01-05 Time 10:57 Sent To  
Notes
2006-01-05 00:00:00OK TO APPROVE PER ANGELLA JONES-VANN.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-12-05 Cont ID  
Sent By mmclean Date 2005-12-05 Time 17:38 Rev Time 0.00
Received By mmclean Date 2005-12-05 Time 17:38 Sent To I
Notes
2005-12-05 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF SURVEY WITH
 SETBACKS.
 2. MUST SHOW THE LOCATION OF STAIR.
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720