Plan Review Details - Permit 05081943
Plan Review Stops For Permit 05081943
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-12 Cont ID  
Sent By shill Date 2005-12-12 Time 14:56 Rev Time 0.50
Received By shill Date 2005-12-12 Time 14:50 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-14 Cont ID  
Sent By shill Date 2005-10-14 Time 14:47 Rev Time 1.00
Received By shill Date 2005-10-14 Time 14:47 Sent To PC
Notes
2005-10-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)THE COPIER OUTSIDE OF OPEN OFFICE
 103 APPEARS TO OBSTRUCT THE ACCESSIBLE
 ROUTE.SHOW CLEARANCE ON THE PLAN,
 FBC11-4.3.
  
 3.)SUBMIT TWO SIGNED, SEALED AND DATED
 SETS OF PLANS.ONLY ONE SEALED SET
 SUBMITTED.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-09 Cont ID  
Sent By dpalmer Date 2006-02-09 Time 17:29 Rev Time 0.00
Received By dpalmer Date 2006-02-09 Time 17:29 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-07 Cont ID  
Sent By dpalmer Date 2005-12-07 Time 20:24 Rev Time 0.00
Received By dpalmer Date 2005-12-07 Time 20:15 Sent To  
Notes
2005-12-07 00:00:00ADDED PLUMB STOP FOR REVIEW. NEW SHEETS
 ADDED TO SETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 12:55 Rev Time 0.50
Received By dpalmer Date 2005-09-03 Time 12:51 Sent To  
Notes
2005-09-03 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS.
 PLEASE SEE 700.12E FOR CIRCUTING OF
 EM/EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE CORRELATE WITH A PANEL SCHEDULE
 TO BE SUBMITTED.
  
 2)NOTE: PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 PLEASE BE SURE TO SEE ANY COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-02-10 Cont ID  
Sent By mwennerg Date 2006-02-10 Time 14:31 Rev Time 0.00
Received By mwennerg Date 2006-02-10 Time 14:31 Sent To  
Notes
2006-02-10 00:00:00REVISION DATED 2/3/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-06 Cont ID  
Sent By mcarsill Date 2005-12-06 Time 13:57 Rev Time 0.00
Received By mcarsill Date 2005-12-06 Time 13:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-21 Cont ID  
Sent By mwennerg Date 2005-09-21 Time 14:46 Rev Time 0.00
Received By mwennerg Date 2005-09-21 Time 14:45 Sent To  
Notes
2005-09-21 00:00:00******DENIED******
  
 1) ONLY ONE SET OF PLANS HAVE BEEN
 SIGNED, DATED AND SEALED.
  
 2) EXIT SIGNS SHALL BE LOCATED IN A
 MANNER THAT MAKES THEM VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS.
  
 3) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/ WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-09 Cont ID  
Sent By adarroug Date 2006-02-09 Time 11:30 Rev Time 0.00
Received By adarroug Date 2006-02-09 Time 11:30 Sent To E
Notes
2006-02-09 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-01 Cont ID  
Sent By adarroug Date 2006-02-01 Time 13:05 Rev Time 0.00
Received By adarroug Date 2006-02-01 Time 13:05 Sent To M
Notes
2006-02-01 00:00:00TO "TGORDON" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-16 Cont ID  
Sent By adarroug Date 2005-11-16 Time 14:42 Rev Time 0.00
Received By adarroug Date 2005-11-16 Time 14:42 Sent To  
Notes
2005-12-02 00:00:00TO "COMM" BD#25
2005-11-16 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-14 Cont ID  
Sent By shill Date 2005-10-14 Time 14:48 Rev Time 0.00
Received By shill Date 2005-08-30 Time 10:15 Sent To  
Notes
2005-08-30 00:00:00TO "COMM" BD#22

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-02-01 Cont ID  
Sent By tgordon Date 2006-02-01 Time 15:51 Rev Time 0.20
Received By tgordon Date 2006-02-01 Time 15:51 Sent To  
Notes
2006-02-01 00:00:00REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-07 Cont ID  
Sent By rregueir Date 2005-12-07 Time 17:22 Rev Time 0.00
Received By rregueir Date 2005-12-07 Time 17:22 Sent To  
Notes
2005-12-07 00:00:00----------------PROVISO-----------------
  
 ABOVE CEILING AREA IS BEING USED AS A
 PLENUM. VERIFY THAT THERE ARE NO
 COMBUSTIBLE MATERIALS ABOVE THE CEILING.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-12 Cont ID  
Sent By pkrauss Date 2005-10-12 Time 06:36 Rev Time 0.35
Received By pkrauss Date 2005-10-12 Time 06:34 Sent To  
Notes
2005-10-12 00:00:00DENIED:
 ONLY ONE SET OF PLANS ARE SIGNED, SEALED
 AND DATED AS REQUIRED BY FS 481.221 &
 471.025.
  
 PROVISO:
 1.PLEASE VERIFY EXISTING FIRE DAMPERS.
  
 2.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-02-10 Cont ID  
Sent By kstevens Date 2006-02-10 Time 07:30 Rev Time  
Received By kstevens Date 2006-02-10 Time 07:30 Sent To  
Notes
2006-02-10 00:00:00REVISION OK WITH PROVISOS
  
 MANUF SPECIFICATION/INSTALLATION SHEETS
 REQUIRED FOR INSTA-HOT WATER HEATERS AT
 TIME OF PLUMBING FINAL INSPECTION.
  
 BALL VALVE TO BE NEAR CHECK VALVE WITH
 UNION FOR SERVICING VALVE.
  
 VENT TO EXISTING VENT LINE. NO AAV'S

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-12-13 Cont ID  
Sent By pschmitz Date 2005-12-13 Time 06:21 Rev Time 0.00
Received By pschmitz Date 2005-12-13 Time 06:21 Sent To B
Notes
2005-12-13 00:00:00RE-STAMP PLANS
2005-12-07 00:00:00NEW SHEETS.
 NO STAMPS FROM PREVIOUS REVIEW.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-10-03 Cont ID  
Sent By pschmitz Date 2005-10-03 Time 14:05 Rev Time 0.00
Received By pschmitz Date 2005-10-03 Time 14:05 Sent To  
Notes
***NONE***