Plan Review Details - Permit 05081926
Plan Review Stops For Permit 05081926
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-27 Cont ID  
Sent By alange Date 2005-09-27 Time 07:27 Rev Time 2.00
Received By alange Date 2005-09-27 Time 07:27 Sent To  
Notes
2005-09-27 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SUBMIT TWO COPIES OF ORIGONAL SIGNED
 AND SEALED SURVEY SHOWING ADDITION TO BE
 DONE.FS 472.025
  
 3.SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING:ROOFING, EXTERIOR DOORS AND
 STRAPS AND TIEDOWNS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL INFORMATION ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 ANY QUESTIONS CALL ME,
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 11:55 Rev Time 0.00
Received By dpalmer Date 2005-09-10 Time 11:48 Sent To P
Notes
2005-09-10 00:00:00****** UNSAT ******
  
 ** PLEASE SEE PLANS ARE COMING BACK FOR
 ZONING COMMENTS, PLEASE MAKE THE BELOW
 MINOR CORRECTIONS AT THIS TIME.
  
  
 1)NOTE: PLEASE INDICATE NEW FOOTER STEEL
 AND COLD WATER BOND AT NEW PANEL AT THE
 DETACHED GARAGE. 250.50,250.32.
 GRND IS NOTED.
  
 2)NOTE: PLEASE SEE PANEL "A" SCHEDULE
 OCP SHOWN FOR NEW PANEL "B" SUB PANEL.
 PLEASE CORRELATE SIZE WITH 240.6 AND
 100A SUB PANEL. (APPEARS TO BE A
 MISPRINT).
  
 3)NOTE: PLEASE SEE 210.8A2, WHICH
 REQUIRES ALL RECEPT IN GARAGE TO BE
 GFI/GFI PROTECTED.
 PLEASE SEE EXISTING AREA WITH NEW BRNACH
 CIRCUITS FOR UTILITY RM.
 PLEASE ALSO SEE LAUNDRY RM, GEN PURPOSE
 RECEPT ALSO WITIN 6' OF L. TUB.
  
 4)NOTE: PLEASEPLANS MENTION EXISTING
 PANEL TO BE REMOVED, HOWEVER NOTES
 MENTIONS, PANEL TO REMAIN AS J-BOX.
  
 THESE WERE ITEMS REDLINED, HOWEVER PLANS
 NEED COMMENTS FROM OTHER REVIEWER(S) TO
 BE ADDRESSED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 11:01 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 11:01 Sent To E
Notes
2005-09-07 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-27 Cont ID  
Sent By alange Date 2005-09-27 Time 07:31 Rev Time 0.00
Received By alange Date 2005-08-30 Time 10:19 Sent To  
Notes
2005-08-30 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-13 Cont ID  
Sent By tgordon Date 2005-09-13 Time 11:43 Rev Time 0.30
Received By tgordon Date 2005-09-13 Time 11:43 Sent To B
Notes
2005-09-13 00:00:00*** DENIED ***
 1) CAN NOT HAVE A CASED OPENING BETWEEN
 GARAGE AND AIR CONDITIONED UTILITY ROOM,
 FBC R-309.1 .
 2) RETURN AIR DUCT MUST BE ATTACHED TO
 AHU, NO OPEN AIR PLENUM. OR INSTALL A 20
 MIN. FIRE RATED DOOR TO MECH. ROOM, FBC
 R-309.1
 3) RETURN AIR DUCT NEEDS TO BE 10",
 FBC/M 601.4 .
 4) PLEASE NOTE YOU WILL NEED A GAS
 PERMIT WHEN YOU RUN YOUR GAS LINES.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-09-13 Cont ID  
Sent By jleech Date 2005-09-13 Time 10:01 Rev Time 0.75
Received By jleech Date 2005-09-13 Time 10:00 Sent To M
Notes
2005-09-13 00:00:00DENIED;
 1.CLEANOUT REQUIRED ON W/M STACK 4'
 ABOVE FINISH FLOOR.
 2.SHOW CLEANOUT AT JUNCTURE OF BUILDING
 DRAIN AND BUILDING SEWER. SEC 708.3.5.
  
 GAS RISER DIAGRAM; THE FOLLOWING
 INFORMATION IS REQUIRED.
 1. TYPE OF GAS, (LP OR NATURAL)
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). EXISTING GAS
 PIPING, LOAD AND LENGHT MUST BE KNOWN TO
 PROPERY SIZE SYSTEM.
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2 (POINT
 OF USE HEATERS) CHECK CLEARANCE BETWEEN
 HEATER AND LAUNDRY ROOM WINDOW.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-06 Cont ID  
Sent By mmclean Date 2005-09-06 Time 17:28 Rev Time 0.00
Received By mmclean Date 2005-09-06 Time 17:28 Sent To I
Notes
2005-09-06 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF CURRENT
 SURVEY WITH SETBACKS OF THE EXISTING
 STRUCTURE.
 2. NEED TO SHOW THE NEW ADDITION ON TWO
 COPY OF CURRENT SURVEY WITH SETBACKS.
 (SIDE & FRONT).
 3. SITEPLAN PROVIDED DOES NOT SHOW THE
 REQUIRED INFORMATION NEEDED TO COMPLETE
 A ZONING REVIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720