Plan Review Details - Permit 05081893
Plan Review Stops For Permit 05081893
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-05-19 Cont ID  
Sent By alange Date 2006-05-19 Time 08:32 Rev Time 1.50
Received By alange Date 2006-05-19 Time 08:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-04-28 Cont ID  
Sent By alange Date 2006-04-28 Time 15:00 Rev Time 1.00
Received By alange Date 2006-04-28 Time 15:00 Sent To  
Notes
2006-04-28 00:00:00DENIED
 FIFTH REVIEW:
  
 3.POMA SHUTTER IS WITH A STORM DEPOT
 STATE PRODUCT APPROVAL.
 TRACO SINGLE HUNG WINDOW HAS A FIXED
 WINDOW STATE PRODUCT APPROVAL.
 MATCH THE MIAMI-DADE PRODUCT APPROVAL
 WITH THE APPROPRIATE STATE PRODUCT
 APPROVAL.
 ALL MIAMI-DADE PRODUCT APPROVALS
 SHALL HAVE THE FOLLOWONG STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SURVEYS SHALL CONTAIN ORIGIONAL
 SEALS AND SIGNATURES.FS 472.025
  
  
 A.SUBMIT PRODUCT APPROVALS FOR STRAPS
 AND TIE-DOWNS USED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-04-11 Cont ID  
Sent By alange Date 2006-04-11 Time 09:08 Rev Time 0.00
Received By alange Date 2006-04-11 Time 09:04 Sent To  
Notes
2006-04-11 00:00:00DENIED
 FOURTH REVIEW:
  
 3.POMA SHUTTER IR WITH A STORM DEPOT
 STATE PRODUCT APPROVAL.
 TRACO SINGLE HUNG WINDOW HAS A FIXED
 WINDOW STATE PRODUCT APPROVAL.
 MATCH THE MIAMI-DADE PRODUCT APPROVAL
 WITH THE APPROPRIATE STATE PRODUCT
 APPROVAL.
 ALL MIAMI-DADE PRODUCT APPROVALS
 SHALL HAVE THE FOLLOWONG STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SURVEYS SHALL CONTAIN ORIGIONAL
 SEALS AND SIGNATURES.FS 472.025
  
  
 A.SUBMIT PRODUCT APPROVALS FOR STRAPS
 AND TIE-DOWNS USED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-27 Cont ID  
Sent By alange Date 2006-02-27 Time 07:53 Rev Time 1.00
Received By alange Date 2006-02-27 Time 07:51 Sent To  
Notes
2006-02-27 00:00:00DENIED
 SECOND REVIEW:
  
 3.ALL MIAMI-DADE PRODUCT APPROVALS
 SHALL HAVE THE FOLLOWONG STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.BASED ON SBCCI BUILDING VALUATION
 TABLES THE MINIMUM PERMITTED VALUE SHALL
 BE NO LESS THAN $13,861.00ADDITIONAL
 PERMIT FEES ARE DUE.
  
 6.SURVEYS SHALL CONTAIN ORIGIONAL
 SEALS AND SIGNATURES.FS 472.025
  
 7.SUBMIT A WALL FRAMING DETAIL.
  
  
 A.SUBMIT PRODUCT APPROVALS FOR STRAPS
 AND TIE-DOWNS USED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-09 Cont ID  
Sent By alange Date 2005-12-09 Time 15:10 Rev Time 1.00
Received By alange Date 2005-12-09 Time 15:00 Sent To  
Notes
2005-12-09 00:00:00DENIED
 SECOND REVIEW:
  
 2.FOOTING SHALL EXTEND A MIN. OF 12"
 BELOW GRADE AND TOP OF SLAB SHALL BE A
 MIN ON 4" ABOVE GRADE.PLEASE SHOW ON
 PLANS. FBC 1804.1.3 AND FBC 1804.1.7 WPB
 AMMENDMENTS.
  
 3.ALL MIAMI-DADE PRODUCT APPROVALS
 SHALL HAVE THE FOLLOWONG STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.BASED ON SBCCI BUILDING VALUATION
 TABLES THE MINIMUM PERMITTED VALUE SHALL
 BE NO LESS THAN $13,861.00ADDITIONAL
 PERMIT FEES ARE DUE.
  
 6.SURVEYS SHALL CONTAIN ORIGIONAL
 SEALS AND SIGNATURES.FS 472.025
  
 7.SUBMIT A WALL FRAMING DETAIL.
 SIGN AND SEAL NEW PAGES SUBMITTED.
  
 8.VERIFY FLOOR PLAN SCALE. INCORRECT
 SCALE ON PLANS.
  
 NEW COMMENTS:
 A.SUBMIT PRODUCT APPROVALS FOR STRAPS
 AND TIE-DOWNS USED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-23 Cont ID  
Sent By alange Date 2005-09-23 Time 07:34 Rev Time 1.75
Received By alange Date 2005-09-23 Time 07:12 Sent To  
Notes
2005-09-23 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.FOOTING SHALL EXTEND A MIN. OF 12"
 BELOW GRADE AND TOP OF SLAB SHALL BE A
 MIN ON 4" ABOVE GRADE.PLEASE SHOW ON
 PLANS. FBC 1804.1.3 AND FBC 1804.1.7 WPB
 AMMENDMENTS.
  
 3.ALL MIAMI-DADE PRODUCT APPROVALS
 SHALL HAVE THE FOLLOWONG STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.IMPACT PROTECTION REQUIRED FOR NEW
 WINDOWS.SUBMIT PRODUCT APPROVALS FOR
 SHUTTERS OR A SEPERATE PERMIT WILL BE
 REQUIRED.
  
 5.BASED ON SBCCI BUILDING VALUATION
 TABLES THE MINIMUM PERMITTED VALUE SHALL
 BE NO LESS THAN $13,861.00ADDITIONAL
 PERMIT FEES ARE DUE.
  
 6.SURVEYS SHALL CONTAIN ORIGIONAL
 SEALS AND SIGNATURES.FS 472.025
  
 7.SUBMIT A WALL FRAMING DETAIL.
  
 8.VERIFY FLOOR PLAN SCALE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-11 Cont ID  
Sent By jleahy Date 2006-02-18 Time 18:09 Rev Time 0.45
Received By jleahy Date 2006-02-18 Time 18:08 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-13 Cont ID  
Sent By jleahy Date 2005-11-30 Time 09:17 Rev Time 0.30
Received By jleahy Date 2005-11-30 Time 09:17 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-31 Cont ID  
Sent By jleahy Date 2005-08-31 Time 22:21 Rev Time 0.30
Received By jleahy Date 2005-08-31 Time 22:21 Sent To M
Notes
2005-08-31 00:00:00SCREEN PORCH REQUIRES OUTLETS EVERY 12'
  
 PLAN SHOWS NO LIGHTS OR SWITCHES FOR
 OUTSIDE.
  
 JAKE644-7291

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-05-17 Cont ID  
Sent By adarroug Date 2006-05-17 Time 14:17 Rev Time 0.00
Received By adarroug Date 2006-05-17 Time 14:17 Sent To B
Notes
2006-05-17 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-04-27 Cont ID  
Sent By adarroug Date 2006-04-21 Time 12:03 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 12:04 Sent To  
Notes
2006-04-27 00:00:00TO "ALANGE" DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-05 Time 14:14 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 14:14 Sent To B
Notes
2006-04-05 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 17:02 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 17:02 Sent To E
Notes
2006-02-15 00:00:00TO "JLEAHY" DESK/RESUB-NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-07 Cont ID  
Sent By adarroug Date 2005-12-07 Time 09:29 Rev Time 0.00
Received By adarroug Date 2005-12-07 Time 09:29 Sent To E
Notes
2005-12-07 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-29 Cont ID  
Sent By adarroug Date 2005-11-29 Time 09:00 Rev Time 0.00
Received By adarroug Date 2005-11-29 Time 09:00 Sent To E
Notes
2005-11-29 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 13:42 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 13:42 Sent To E
Notes
2005-08-30 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-23 Cont ID  
Sent By alange Date 2005-09-23 Time 07:34 Rev Time 0.00
Received By alange Date 2005-08-30 Time 10:12 Sent To  
Notes
2005-08-30 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-01 Cont ID  
Sent By tgordon Date 2005-09-01 Time 11:56 Rev Time 0.15
Received By tgordon Date 2005-09-01 Time 11:56 Sent To P
Notes
2005-09-01 00:00:00** PROVISO **
 PLEASE PROVIED MECH. PLANS WHEN APPLYING
 FOR YOUR MECH. PERMIT.
 BATHROOMS WITHOUT A WINDOW HAVING 3 SQ.
 FT. OF OPEN SPACE REQUIRE A MECH.
 EXHAUST UNIT,PER. F.B.C./M. 402.3.1 TG

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-02-21 Cont ID  
Sent By jleech Date 2006-02-21 Time 13:44 Rev Time 0.00
Received By jleech Date 2006-02-21 Time 13:43 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-09-13 Cont ID  
Sent By jleech Date 2005-09-13 Time 15:09 Rev Time 0.25
Received By jleech Date 2005-09-13 Time 15:09 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-12-06 Cont ID  
Sent By jleahy Date 2005-12-13 Time 12:23 Rev Time 0.00
Received By mmclean Date 2005-12-06 Time 13:56 Sent To I
Notes
2005-12-06 00:00:00THE PROPOSED BEDROOM, MEETS THE SETBACKS
 (REAR & SIDE) MM

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-30 Cont ID  
Sent By mmclean Date 2005-08-30 Time 10:23 Rev Time 0.00
Received By mmclean Date 2005-08-30 Time 10:23 Sent To I
Notes
2005-08-30 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF THE
 SHOWING THE ADDITION WITH SETBACKS (SIDE
 & REAR).
 2. SITEPLAN PROVIDED DOES NOT PROVIDE
 ALL INFO NEEDED FOR COMPLETE REVIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720