Plan Review Details - Permit 05081866
Plan Review Stops For Permit 05081866
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-28 Cont ID  
Sent By alange Date 2005-09-28 Time 07:35 Rev Time 1.33
Received By alange Date 2005-09-28 Time 07:35 Sent To  
Notes
2005-09-28 00:00:00DENIED
  
 1.SUBMIT PRODUCT APPROVALS FOR
 ROOFING.ALL PRODUCT APPROVALS
 SUBMITTED SHALL HAVE THE FOLLOWING STATE
 PRODUCT APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.FOOTING DEPTH SHALL BE A MINIMUM OF
 12" BELOW GRADE.PLAEASE SHOW ON
 DETAIL.FBC 1804.1.3
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER FBC CH. 13.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-09 Cont ID  
Sent By dpalmer Date 2005-09-09 Time 20:34 Rev Time 0.30
Received By dpalmer Date 2005-09-09 Time 20:34 Sent To P
Notes
2005-09-09 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE LIST THE ARC FAULT
 PROTECTED CIRCUITS PER 2002 NEC 210.12.
  
 2)NOTE: PLEASE CLARIFY IF THE NEW WATER
 HEATER ANDSHOWN IS BEING RELOCATED.
 215.5
  
 3)NOTE: PLEASE SEE 210.52D MISSING GFI
 RECEPT FOR NEW BATH.
  
 4)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPT.
  
 5)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS TO EXSITING BLDG'S.
 PLEASE SEE ADDITIONS MORE THAN 25%
 REQUIRESSMOKE DETECTORS INSIDE AND
 OUTSIDE ALL BEDRMS PER NFPA-72
 11.5.1.1
 PLEASE ALSO SHOW ALL EXISTING LOCATIONS
 WHICH ARE REQUIRED TO BE GFI PROTECTED
 PER 210.8. KITCHENS, BATHS , OUTSIDE ,,,
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICLA
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 10:20 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 10:20 Sent To E
Notes
2005-09-07 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-08-29 Time 11:37 Sent To  
Notes
2005-08-29 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-13 Cont ID  
Sent By tgordon Date 2005-09-13 Time 10:07 Rev Time 0.15
Received By tgordon Date 2005-09-13 Time 10:07 Sent To B
Notes
2005-09-13 00:00:00NOT APPLYING FOR MECMANICAL PERMIT AT
 THIS TIME NO MECHANICAL CONTRACTOR OR
 MECH. PLANS SUBMITTED.
 NOTE: NEED ENERGH CALCULATIONS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-09-13 Cont ID  
Sent By jleech Date 2005-09-13 Time 09:09 Rev Time 0.25
Received By jleech Date 2005-09-13 Time 09:09 Sent To M
Notes
2005-09-13 00:00:00NO RISER DIAGRAM. NOT ENOUGH INFORMATION
 TO DO A PLUMBING PLAN REVIEW.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-06 Cont ID  
Sent By mmclean Date 2005-09-06 Time 15:13 Rev Time 0.00
Received By mmclean Date 2005-09-06 Time 15:13 Sent To I
Notes
2005-09-06 00:00:00DENIED,
 1. NEW ADDITION MUST MEET THE SIDE
 SETBACK OF 5FT MINIMUM, 15FT TOTAL.
 2. MUST PROVIDE TWO COPY OF UPDATED
 SURVEY SHOWING THE SIDE SETBACKS OF THE
 NEW ADDITION.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720