Plan Review Details - Permit 05081856
Plan Review Stops For Permit 05081856
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-10-20 Cont ID  
Sent By alange Date 2005-10-20 Time 07:53 Rev Time 0.50
Received By alange Date 2005-10-20 Time 07:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-10-18 Cont ID  
Sent By alange Date 2005-10-18 Time 14:22 Rev Time 0.33
Received By alange Date 2005-10-18 Time 14:19 Sent To  
Notes
2005-10-18 00:00:00****CORRECTIONS****
  
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 THIRD REVIEW:
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.SHOW SLAB DETAIL AND METHOD OF
 SLAB TIE DOWN.FOR EXAMPLE: SLAB
 THICKNESS, REINFORCEMENT USED, TYPE AND
 SIZE OF TIE-DOWNS USED.MACHINE BOLTS
 NOT RECCOMMENDED FOR CONCRETE.
  
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-06 Cont ID  
Sent By alange Date 2005-10-06 Time 08:46 Rev Time 0.33
Received By alange Date 2005-10-06 Time 08:44 Sent To  
Notes
2005-10-06 00:00:00****CORRECTIONS****
  
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 SECOND REVIEW:
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.SHOW SLAB DETAIL AND METHOD OF
 SLAB TIE DOWN.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.SUBMIT 2 COPIES OF ALL DOCUMENTS AND
 HAVE PERSON RESPOSIBLE FOR THE DESIGN
 SIGN ALL PAGES.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-19 Cont ID  
Sent By alange Date 2005-09-19 Time 15:06 Rev Time 0.33
Received By alange Date 2005-09-19 Time 15:01 Sent To P
Notes
2005-09-19 00:00:00****CORRECTIONS****
  
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.SHOW SLAB DETAIL AND METHOD OF
 SLAB TIE DOWN.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.SUBMIT 2 COPIES OF ALL DOCUMENTS AND
 HAVE PERSON RESPOSIBLE FOR THE DESIGN
 SIGN ALL PAGES.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2005-09-14 Cont ID  
Sent By btrobaug Date 2005-09-14 Time 11:34 Rev Time 0.33
Received By btrobaug Date 2005-09-14 Time 11:31 Sent To P
Notes
2005-09-14 00:00:00 
 ALL ELECTRICAL COMMENTS ADDRESSED ON
 GEN/ELEC APPLICATIONAND SUBMITTALS
 #05081413.
  
 WRT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-01 Cont ID  
Sent By dpalmer Date 2005-09-01 Time 07:45 Rev Time 0.40
Received By dpalmer Date 2005-09-01 Time 07:43 Sent To M
Notes
2005-09-01 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE MECH COMMENTS AND
 SHOW LOCATION DIMENTIONS FROM DWELLING.
 PLEASE SEE BLDG REVIEW COMMENTS FOR
 SLAB/TIE DOWNOR BOLT DOWN DETAIL
 REQUIRED.
  
  
 2)NOTE: PLEASE SUBMIT TWO COPIES OF
 MANUFACTURES SPECS/CUT SHEETS FOR
 GENERATOR AND ATS.
 PLEASE SEE OWNER MANUAL IS NOT REQUIRED
 , JUST THE BASIC CUT SHEETS FOR
 GENERATOR AND TRANSFER SWITCH.
  
  
 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM
 FOR ELECTRICAL SERVICE SHOWING
 INSTALLATION OF NEW EQUIPMENT. PLEASE
 SEE LINE AND LOAD CONDUCTORS CAN NOT BE
 LOCATED IN METER CAN.
 PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS ARE ONLY INSTALLED AFTER THE
 FIRST MENAS OF DISCONNECT.
 250.6,250.24 ETC
 GRND RODS ALSO REQUIRED AT
 SERVICE.250.50
  
  
 4)NOTE: PLEASE SEE 225.31 FOR MISSING
 MEANS OF DISCONNECT. PLEASE SEE 225.34
 FOR GROUPING OF THIS MEANS OF DISCONNECT
 WITH EXISTING MAIN.
 PLEASE SEE 225.36, THIS DISCONNECTING
 MEANS SHALL BE LISED AS "SERVICE
 EQUIPMENT".
  
 5)NOTE: PLEASE PROVIDE
 LOADS/CALCULATIONS FOR ITEMS INSTALLED
 ON NEW PANEL.
 PLEASE SEE CIRCUITS SHOWN DO NOT SEEM TO
 BE ALL CIRCUITS.
 PLEASE INDICATE OF ALL APPLIANCES ARE
 GAS? ETC
 GEN LT AND RECEPTS LOADS ARE THE ONLY
 LOADS THAT MAY BE DE-RATED.
 ALL APPLIANCE, MOTOR, CONNECTED LOADS
 INCLUDING HEAT LOAD FROM A/C SHALL BE
 FIGURED AT 100%.
 702.5
  
 6)NOTE: PLEASE INDICATE THE GEN PRIME
 MOVER, LP, NAT GAS?
 PLEASE SEE CALCS SUBMITTED INDICATE A
 40KA UNIT BEING INSTALLED, WHICH PER
 MANUAL WOULD INDICATE THIS AS AN LP
 SYSTEM. IS THIS CORRECT?
 MANUAL SUBMITTED IS LABLED AS 37KW FOR
 NATURAL GAS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 18:16 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 18:16 Sent To E
Notes
2005-10-11 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 14:55 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 14:55 Sent To B
Notes
2005-09-29 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-19 Cont ID  
Sent By alange Date 2005-09-19 Time 15:06 Rev Time 0.00
Received By alange Date 2005-08-29 Time 10:09 Sent To  
Notes
2005-08-29 00:00:00TO "GEN-RES" BOX "E"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-10-14 Cont ID  
Sent By pkrauss Date 2005-10-14 Time 14:58 Rev Time 0.00
Received By pkrauss Date 2005-10-14 Time 14:50 Sent To P
Notes
2005-10-17 00:00:00GIVEN TO ART LANGE 10/17/05, NO PLUMBING
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-06 Cont ID  
Sent By pkrauss Date 2005-09-06 Time 07:20 Rev Time 0.55
Received By pkrauss Date 2005-09-06 Time 07:20 Sent To P
Notes
2005-09-06 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.DISTANCES FROM BUILDING STRUCTURE &
 FRESH AIR INTAKES SUCH AS, WINDOWS,
 DOORS, VENTS IN ROOF SOFFITS.
  
 2.INFORMATION SUBMITTED INDICATES THIS
 GENERATOR'S FUEL WILL BE LP GAS.PLEASE
 PROVIDE LOCATION AND THE CAPACITY OF LP
 TANK.
  
 3.INDICATE DISTANCES FROM THE PROPERTY
 LINES & BUILDING STRUCTURE TO THE FUEL
 TANK.
  
 4.PROVIDE SIZING OF GAS LINE.SHOW
 COMPLIANCE WITH NFPA 58, SEE THE
 ATTACHED.
  
 ADDTIONAL PERMIT REQUIRED FOR THE LP
 GAS.CONTRACTOR TO BE A LPG SPECIALTY
 INSTALLER OR LP GAS DEALER PER FS 527

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-01 Cont ID  
Sent By mmclean Date 2005-09-01 Time 07:40 Rev Time 0.00
Received By MMCLEAN Date 2005-09-01 Time 07:43 Sent To  
Notes
2005-09-01 00:00:00PER MICHELLE M. UNDER 05081413