Plan Review Details - Permit 05081855
Plan Review Stops For Permit 05081855
Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-10-14 Cont ID  
Sent By dpalmer Date 2005-10-14 Time 10:20 Rev Time 1.25
Received By dpalmer Date 2005-10-14 Time 10:05 Sent To  
Notes
2005-10-14 00:00:00********** UNSAT2ND REVIEW *********
  
 PLEASE SEE MANY NOTES FROM PREVIOUS
 REVIEWWHICH STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE: NOTE #1, NO, PLEASE SEE BASED ON
 SCALE PROVIDED ON PLANS, ONE GFI IS
 STILL MISSING. SEE REDLINED PLANS.
  
 2)NOTE: NOTE #2, NO, PLEASE SEE LOCATION
 OF WASHER AND DRYER NOT SHOWN ON PLANS.
 PLEASE SEE PREVIOUS RISER DID NOT
 INDICATE A PANEL "C" FOR AN APT? PLEASE
 CLARIFY IF THIS PANEL IS EXISITNG OR
 NEW.
 PLEASE CALL IF NEW AS THERE MAY BE SOME
 CODE COMMENTS. IF EXIST , ONLY IDENTIFY
 AS EXIST. PLEASE HOWEVER SEE COMMENTS
 FOR LOAD CALCULATIONS.
  
 3)NOTE: NOTE#3 OK, AS PLANS MENTIONS ALL
 A/C AS EXISTING AND NOT PROPOSED WORK TO
 BE DONE.
  
 4)NOTE: NOTE #4 OK, PLEASE KNOW, EVEN IF
 SHLEVING IS NOT IN A CLOSET, THE CODE
 TAKES INTO ACCOUNTAMIN SHELVING
 DISTANCE FROM WALLS.
 PLEASE SEE A FLOURESCENE FIXTURE ABOVE
 DOOR IS OK PER 410.8
  
 5)NOTE: NOTE#5, NO, PLEASE SEE NOTE ON
 PLANS DOES NOT INCLUDE QLL REQUIRED PER
 210.12. PLEASE ALSO SEE NOTE NOW SHOWN
 FOR SD'S INDICATES BEING CONNECTED TO A
 GFI CIRCUIT?
 PLEASE SEE ARC FAULT AND GFI ARE TWO
 DIFFERENT PROTECTION METHODS.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 OK.
  
 8)NOTE: NOTE #8 NO,
 PLEASE SEE MIN AWG REQUIRED FOR OCP TO
 BE BASED ON 240.4,310.16.
 PLEASE SEE DRYER SHOWING 40A OCP ON #10
 AWG.
 PLEASE KNOW, NOW LOAD FOR WATER IS HSOWN
 AT 3.8 KW, HOWEVER 422.13 WHICH REQUIRES
 MIN OCP TO BE 125% AND 422.11E REQUIURES
 MAX OCP AT 150%. PLEASE KNOW AT 3.8 KW,
 40A OCP IS TOO HIGH.
  
 9)NOTE: NOTE #9, NO, PLEASE SEE 424.3B
 FOR MIN OCP FOR AHU. MIN 125%
  
 10)NOTE: NOTE #10 NO, PLEASE SEE 220.16
 FOR MIN OF 5KW TO BE SHOWN FOR DRYER.
 PLEASE SEE RESPONSEMENTIONS 5KW IS
 SHOWN, HOWEVER PANEL SCHEDULE/LOAD CALCS
 INDICATE 2.5KW.
  
 11)NOTE: NOTE #11 NO, SEE PREVIOUS NOTE
 #8 FOR WATER HEATER COMMENT.
  
 12)NOTE: NOTE #12 NO, PLEASE SEE 220 FOR
 MIN LOAD CALCULATIONS,
 PLEASE SEE CONDENSING UNIT LOAD IS NOW
 SHOWN AT 23 KVA/KW?? PLEASE VERIFY. "IF"
 A/C CU IS 23KW, THEN THE COOLING LOAD IS
 TO BE FIGURED ON LOAD CALCULATIONS AS
 THIS LOAD IS LARGER THAN HEAT. THIS
 APPEARS TO BE AMISPRINT OR INCORRECT
 ??
 PLEASE SEE LOAD FROM PANEL "C" DOES NOT
 INDICATE OF THERE IS ANY A/C LOADS?
 PLEASE SEE NEC 220 FOR MIN KW RATING FOR
 STOVE/RANGE/OVEN TO BE PER NAMEPLATE ,
 MIN 8KW.
 PLEASE SEE LOAD SHOWN FOR PANEL "B" IS
 BEING DE-RATED TWICE.
 LOAD SHALL BE FIGURED AND DE-RATED FOR
 LOAD ON PANEL "B", HOWEVER THE CONNECTED
 LOAD MUST BE SHOWN AND FIGURED WHEN
 CALCULATIONS FOR PANEL "A" ARE DONE.
  
  
 13)NOTE: NOTE #13 OK, AS PLANS NOW
 INDICATE MAIN SERVICE AS EXISTING.
  
 14)NOTE: NOTE #14 OK. ADDED.
  
 15)NOTE: NOTE #15 NO, SEE PREVIOUS NOTE
 WITH RESPECT TO CONNECTION OF SD'S.
  
 16)NOTE: NOTE #16 OK, EXISTING.
  
 17)NOTE: NOTE #17, NO, PLEASE SEE ONLY
 THE PRINTED NAME IS SHOWN ON PLANS.
 FBC 104.2.1
  
 18)NOTE: NOTE #18, NO, PLEASE KNOW,
 VALUE MUST BE BASED ON WHAT IS WOULD
 COST AT FAIR MARKET VALUE IF A
 CONTRACTOR WAS DOING THE WORK.
 104.6.5
  
 19)NOTE: PLEASE SEE FBC CHAPTER 34 WITH
 RESPECT TO REMODEL WORK FOR ELECTRICAL
 WIRING.
 PLEASE KNOW, EXSITING OTHER AREAS MAY BE
 REQUIRED TO BE BROUGHT UP TO MIN CODE,
 IF NOT ALREADY. PLANS/NOTES MENTIONS
 EXISTING AREAS HAVE ALREADY BEEN BROUGHT
 UP TO CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
 13)NOTE:

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-02 Cont ID  
Sent By dpalmer Date 2005-09-02 Time 07:05 Rev Time 0.80
Received By dpalmer Date 2005-09-01 Time 21:02 Sent To  
Notes
2005-09-02 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE 210.52C1 FOR SOME
 MISSING GFI RECEPTS ALONG KITCHEN
 COUNTERSPACE.
 PLEASE ALSO SEE AREA IN KITCHEN AT
 MICROWAVE LOCATION APPEARS TO BE
 COUNTERSPACE?
 PLEASE SEE 210.8A6 FOR ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI /GFI PROTECTED.
  
 2)NOTE: PLEASE SHOW LOCATION OF ALL
 SERVICE EQUIPMENT AS SHOWN ON RISER.
 PLEASE LABEL PANELS, A, B ETC.
 PLEASE SHOW LOCATIONS OF ALL APPLIANCES
 AS INDICATED ON PANEL SCHEDULES.
 WASHER, DRYER, AHU, CU ETC.
  
 3)NOTE: PLEASE SEE 440.11 FOR MISSING
 DISCONNECTS FOR A/C EQUIPMENT.
 PLEASE SEE 210.63 FOR MISSING GFI FOR
 CU.
  
 4)NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCE OF LT FIXTURE IN CLOSET.
  
 5)NOTE: PLEASE SEE PLANS INDICATE ARC
 FAULT PROTECTION FROM THE PREVIOUS CODE.
 PLEASE SEE 2002 NEC 210.12, WHICH
 REQUIRES ARC FAULT PROTECTION FOR ALL
 OUTLETS IN BEDRMS, LTS, FANS, SD'S
 RECEPTS ETC.
  
 6)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52
  
 7)NOTE; PLEASE SEE MISSING DEDICATED
 BATH CIRCUIT PER 210.52D,210.11C3 MUST
 BE 20A #12
  
 8)NOTE: PLEASE PROVIDE PANEL SCHEDULE(S)
 SHOWING ALL MINCIRCUITS AND CORRELATE
 WITH LOAD CALCULATIONS.
 PLEASE SHOW ALL MIN AWG PER NEC 310.16
 PLEASE SEE 3-SMALL APPL CIRCUITS SHOWN
 ON PANEL SCHEDULE, ONLY 2 SHOWN IN LOAD
 CALCS.
 PLEASE SEE CORRELATE ALL ITEMS ON PANEL
 SCHEDULE(S) WITH LOADS SHOWN IN LOAD
 CALCULATIONS.
 (DRYER, A/C SYSTEM,, ETC
  
 9)NOTE: PLEASE SEE MIN OCP FOR AHU HEAT,
 SHALL BE SIZED PER 424.3B
 MIN 125%.
  
 10)NOTE: PLEASE SEE 220.16, MIN OF 5KW
 SHALL BE FIGURED FOR DRYER. PLEASE SEE
 3.6 SHOWN.
 PLEASE ADJUST.
  
 11)NOTE: PLEASE VERIFY 2500W WATER
 HEATER. PLEASE BE SURE THIS IS THE TOTAL
 NAME PLATE RATING AND NOT ONLY ONE
 ELEMENT. THISSIZE UNIT SEEMS SMALL FOR
 A 1200 SQ FT HOUSE.
  
 12)NOTE: PLEASE SEE A/C HEAT LOAD MAY
 NOT BE DE-RATED AT 40%. PLEASE SEE
 220.31B FOR LOAD CALCULATIONS.
 PLEASE SEE MIN SERVICE SHOWN MENTIONS,
 100A'S, HOWEVER 200A SERVICE IS SHOWN ON
 RISER?
  
 13)NOTE: PLEASE INDICATE MIN GROUNDING
 ELECTRODE SYSTEM PER 250.50. COLD WATER
 PIPE AND MIN OF 2-GRNDS RODS.
  
 14)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO SUB
 PANEL.
 PLEASE SEE 250.110 AND 250.122 FOR
 SIZING.
  
 15)NOTE: PLEASE SEE SD'S ARE BEING SHOWN
 CONNECTED TO WHAT APPEARS TO BE LAUNDRY
 RM LT. IF THIS THE CASE, ARC FAULT
 PROTECTION WOULD ALSO BE REQUIRED FOR
 THIS CIRCUIT.
  
 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 17)NOTE: PLEASE SEE FBC 104.2.1 WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS .
  
 18)NOTE: PLEASE SEE 104.6.5, VALUATION
 FOR SCOPE OF WORK MUST BE BASED ON FAIR
 MARKET VALUE. (CONTRACTORS PRICE)
 INCLUDING ALL LABOR AND MATERIALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
2005-09-01 00:00:00IN ELEC FOR REVIEW.
 NOTES TO FOLLOW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 14:47 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 14:47 Sent To E
Notes
2005-10-11 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-29 Cont ID  
Sent By adarroug Date 2005-08-29 Time 13:00 Rev Time 0.00
Received By adarroug Date 2005-08-29 Time 13:00 Sent To E
Notes
2005-08-29 00:00:00TO "E" BOX