Plan Review Details - Permit 05081420
Plan Review Stops For Permit 05081420
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-11-29 Cont ID  
Sent By alange Date 2005-11-29 Time 08:30 Rev Time 1.66
Received By alange Date 2005-11-29 Time 07:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-26 Cont ID  
Sent By alange Date 2005-09-26 Time 13:08 Rev Time 3.25
Received By alange Date 2005-09-23 Time 16:23 Sent To  
Notes
2005-09-26 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS.FS 472.025
  
 4.SHOW MINIMUM FOOTING DEPTH AT 12"
 BELOW GRADE.FBC 1804.1.3
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-06-27 Cont ID  
Sent By dpalmer Date 2006-06-27 Time 18:46 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 18:40 Sent To PC
Notes
2006-06-27 00:00:00REV FOR ALL CORRECTIONS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-06-20 Cont ID  
Sent By dpalmer Date 2006-06-20 Time 20:59 Rev Time 0.00
Received By dpalmer Date 2006-06-20 Time 20:39 Sent To PC
Notes
2006-06-20 00:00:00******** UNSAT ***********
  
 1) NOTE: PLEASE SEE RISER AND PLANS HAVE
 BEEN REVISED AND NO MAINS ARE SHOWN, IN
 FACT PANELS ARE BOTH SHOWN AS MLO??
 PLEASE SEE 230.70,240.4 ETC
 215.5
  
 2) NOTE: PLEASE SEE MIN LOAD FOR
 WASHER/LAUNDRY SHALL BE 1.5KW. (SHOWS
 1.2).
 215.5,220.16,210.11C
  
 3) NOTE: PLEASE SEE SD IN MASTER BEDRM
 SHALL BE LOCATED WITH IN 12" OF THE
 HIGHEST POINT ON THE FLAT CEILING.
 NFPA-72 2002 11.5.1.1,11.8.3
  
 4) NOTE: PLEASE SEE 408.4, THE
 CIRCUITING SHOWN ONPANEL SCHEDULES
 SHALL INDICATE THE SPECIFIC ROOMS AND
 AREAS IN WHICH THEY FEED. PLEASE SEE
 NUMEROUS CIRUITS ONLY REFERENCE "GEN
 LTS",ETC.
 IE: MASTER BDRM LTS, HALL LTS, BATH #3
 LTS ETC.
 PLEASE BE SURE ALL ROOM AND AREA
 DESIGNATIONS ARE ON PLANS AS SHOWN ON
 PREVIOUS PLANS SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-17 Cont ID  
Sent By dpalmer Date 2005-11-17 Time 20:57 Rev Time 0.33
Received By dpalmer Date 2005-11-17 Time 20:48 Sent To P
Notes
2005-11-17 00:00:00ELECTRICAL PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-02 Cont ID  
Sent By dpalmer Date 2005-09-02 Time 14:31 Rev Time 0.75
Received By dpalmer Date 2005-09-02 Time 14:31 Sent To M
Notes
2005-09-02 00:00:00******** UNSAT**********
  
 1)NOTE: PLEASE SEE SOME MISSING RECEPTS
 PER 210.52C1 ALONG KITCHEN COUNTERSPACE.
  
 2)NOTE: PLEASE SEE 210.52 FOR A COUPLE
 MISSING RECEPTS.
  
 3)NOTE: PLEASE INDICATE THE # OF FEEDERS
 FOR SUB PANEL "B".
 PLEASE SEE RISER SHOWS #4?
 215.5
  
 4)NOTE: PLEASE SHOW LOCATIONS AND
 IDENTIFY ALL SERVICE EQUIPMENT ON PLANS.
 PLEASE LABEL PANELS, DISC'S ETC.
 215.5, PANLE "B", METER/MAIN COMBO.
  
 5)NOTE: PLEASE CORRELATE PLANS AND PANEL
 SCHEDULE FOR THE # OF FRIG'S. PLEASE SEE
 PLANS INDICATE 3 AND PANEL SCHEDULE
 SHOWS 2.
  
 6)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAIN PANEL TO
 SUB PANEL "B".
 250.110,250.122
  
 7)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.;
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-25 Cont ID  
Sent By adarroug Date 2006-06-25 Time 17:10 Rev Time 0.00
Received By adarroug Date 2006-06-25 Time 17:10 Sent To E
Notes
2006-06-25 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 13:29 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 13:29 Sent To E
Notes
2006-06-20 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-12 Cont ID  
Sent By adarroug Date 2005-12-12 Time 13:35 Rev Time 0.00
Received By adarroug Date 2005-12-12 Time 13:35 Sent To P
Notes
2005-12-12 00:00:00TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 11:45 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 11:45 Sent To E
Notes
2005-11-15 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 10:59 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 10:59 Sent To E
Notes
2005-09-02 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-26 Cont ID  
Sent By alange Date 2005-09-26 Time 13:11 Rev Time 0.00
Received By alange Date 2005-08-24 Time 17:31 Sent To  
Notes
2005-08-24 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-09-07 Cont ID  
Sent By prafter Date 2005-09-07 Time 10:31 Rev Time 1.00
Received By prafter Date 2005-09-07 Time 10:31 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-01-18 Cont ID  
Sent By jleech Date 2006-01-18 Time 07:53 Rev Time 0.33
Received By jleech Date 2006-01-18 Time 07:53 Sent To  
Notes
2006-01-18 00:00:00REVISED SANITARY RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-11-22 Cont ID  
Sent By jleech Date 2005-11-22 Time 15:32 Rev Time 0.33
Received By jleech Date 2005-11-22 Time 15:32 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-09-08 Cont ID  
Sent By jleech Date 2005-09-08 Time 10:10 Rev Time 0.50
Received By jleech Date 2005-09-08 Time 10:10 Sent To B
Notes
2005-09-08 00:00:00DENIED;
 1.RISER DIAGRAM DOESNOT MATCH FLOOR
 PLAN.
 2.W/M AND L/T ARE NOT ON THE SAME WALL.
 SEPARATE STACK REQUIRED FOR L/T.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-01 Cont ID  
Sent By mmclean Date 2005-09-01 Time 17:28 Rev Time 0.00
Received By mmclean Date 2005-09-01 Time 17:28 Sent To I
Notes
***NONE***