Plan Review Details - Permit 05081409
Plan Review Stops For Permit 05081409
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2006-10-30 Cont ID  
Sent By alange Date 2006-10-30 Time 11:02 Rev Time 0.00
Received By alange Date 2006-10-30 Time 11:02 Sent To  
Notes
2006-10-30 11:03:16BUILDING REVIEW DONE BY ELECTRICAL REVIEWER

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-03 Cont ID  
Sent By alange Date 2006-10-03 Time 09:14 Rev Time 0.33
Received By alange Date 2006-10-03 Time 09:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-10-03 Cont ID  
Sent By alange Date 2005-10-03 Time 10:55 Rev Time 0.33
Received By alange Date 2005-10-03 Time 10:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-19 Cont ID  
Sent By alange Date 2005-09-19 Time 14:14 Rev Time 0.33
Received By alange Date 2005-09-19 Time 14:14 Sent To  
Notes
2005-09-19 00:00:00DENIED
  
 PROPERTY IS IN FLOOD ZONE "A" .PLEASE
 SHOW ON PLANS HOW THE FINISHED SLAB
 HEIGHT WILL BE AT 6" ABOVE THE BASE
 FLOOD ELEVATION OF 7FT.
  
 ANY QUESTIONS CALL ME,
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2006-10-28 Cont ID  
Sent By dpalmer Date 2006-10-28 Time 14:42 Rev Time 0.00
Received By dpalmer Date 2006-10-28 Time 14:29 Sent To P
Notes
2006-10-28 14:42:22****** RED-LINED PLANS ****
  
  
 SHEET(S) "A", RED-LINED AS THIS IS A PORTABLE UNIT
 ONLY, AND ZONING COMMENT DOES NOT APPLY.
  
 REDLINED SLAB DETAIL STILL BEING SHOWN ON "E" SHEETS AS
 NIC.SLAB IS NOTAPPLICABLE AS UNIT WILL BE ON
 WHEELS, AND WILL PUG IN DURING EMERGENCIES ONLY. TWIST
 LOCK WP DEVICES SHOWN.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-09-13 Cont ID  
Sent By dpalmer Date 2006-09-13 Time 21:04 Rev Time 0.00
Received By dpalmer Date 2006-09-13 Time 20:59 Sent To P
Notes
2006-09-13 00:00:00***** UNSAT ****
  
 1) NOTE: PLEASE REVISE PLANS FOR THE NEW
 PROPOSED PORTABLE GENERATOR. RISER STILL
 SHOWS A PERMANANT UNIT. PLEASE SEE THE
 SPECS SUBMITTED ALSO STILL INDICATE THIS
 BEING A PERMANANT INSTALLED UNIT.
 IF THIS IS GOING TO BE A "PORTABLE
 UNIT", HOW IS THE ATS GOING TO BE AN
 ATS? ONCE THIS ATS SENSES THE LOSS OF
 POWER THIS WILL TRANSFER OVER TO ??
 PLEASE SHOW HOW THIS NEW SCENERIO WILL
 BE CONNECTED AND WIRED INTO THE ATS ETC.
 RISER FOR REVIEW OF CODE COMPLIANCE IS
 NOT COMPLETE OR REVISED AT THIS TIME.
  
 FBC 106.1.2, ADMIN SECT.
 2002 NEC
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-07-03 Cont ID  
Sent By dpalmer Date 2006-07-03 Time 07:14 Rev Time 0.00
Received By dpalmer Date 2006-07-03 Time 07:07 Sent To PC
Notes
2006-07-03 00:00:00REV PANEL SCHEDULE.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-06-25 Cont ID  
Sent By dpalmer Date 2006-06-25 Time 15:23 Rev Time 0.00
Received By dpalmer Date 2006-06-25 Time 15:23 Sent To PC
Notes
2006-06-25 00:00:00****** UNSAT *******
  
 1) NOTE: PLEASE SEE PANEL STP IS SHOWING
 WRONG CONDUCTOR SIZES. THE OCP AND AWG
 WAS REDLINED ON THREE SETS OF PREVIOUS
 PLANS AND MUST BE CORRECTED.
 PLEASE ALSO SEE CU LOAD IS SHOWN AS
 10.4KW, YET THE OCP IS ONLY 30A'S??
 PLEASE REVISE AND ADJUST.
 240.4,310.16, 424.3B, ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-12-30 Cont ID  
Sent By dpalmer Date 2005-12-30 Time 07:01 Rev Time 0.00
Received By dpalmer Date 2005-12-29 Time 15:09 Sent To  
Notes
2005-12-30 00:00:00INCREASED GEN TO 25KW OK.
 REVISED OPC AND AWG FOR AHU.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-12-19 Cont ID  
Sent By dpalmer Date 2005-12-19 Time 06:22 Rev Time 0.00
Received By dpalmer Date 2005-12-19 Time 06:17 Sent To  
Notes
2005-12-19 00:00:00********** UNSAT **********
  
  
 1)NOTE: PLEASE SEE 424.3B WHICH REQUIRES
 THE MIN OCP FOR AHU TO BE 125%, (60A)
 FOR A 10KW UNIT.
  
 2)NOTE: PLEASE SEE INCREASE IN GENERATOR
 TO 25KW WITH 125A OCP AT GENERATOR,
 HOWEVER FEEDERS ARE ONLY RATED AT 100A'S
 AND SHOWS 125A OCP.
 PLEASE ADJUST.
 PLEASE SEE EITHER 310.15B6 OR 310.16 FOR
 SIZING.
  
 3)NOTE: PLEASE PROVIDE THE MANUFACTURES
 CUT SHEET WHICH INDICATES THE KW RATING
 FOR THIS UNIT @ NG AND LP.
 NOTE: 25KW IS TYPICALLY THE RATING ON
 LP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-29 Cont ID  
Sent By dpalmer Date 2005-09-29 Time 18:02 Rev Time 0.00
Received By dpalmer Date 2005-09-29 Time 17:21 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-09 Cont ID  
Sent By alange Date 2005-09-19 Time 14:18 Rev Time 0.00
Received By dpalmer Date 2005-09-09 Time 15:02 Sent To M
Notes
2005-09-09 00:00:00****UNSAT ****
  
 1)NOTE: PLEASE SEE SPECS/MANUFACTURE
 SHEETS SUBMITTED CONTAIN TWO DIFFERENT
 ATS SWITCHES, PANELS.
 PLEASE SEE 225.31 WHICH REQUIRES A MEANS
 OF DISCONNECT ON THE LOAD SIDE OF
 TRANSFER SWITCH.
 IT IS NOTEDTHAT PANEL SHOWN ON RISER
 INDICATES A MCB, HOWEVER SPECS SUBMITTED
 DOES NOT CORRELATE WITH THIS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-10-30 Cont ID  
Sent By mperson Date 2006-10-30 Time 08:19 Rev Time 0.33
Received By mperson Date 2006-10-30 Time 08:19 Sent To B
Notes
2006-10-30 08:54:14REVISION: GENERATOR CHANGED FROM STATIONARY TO
 PORTABLE.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-10-02 Cont ID  
Sent By mperson Date 2006-10-02 Time 11:37 Rev Time 0.33
Received By mperson Date 2006-10-02 Time 11:37 Sent To B
Notes
2006-10-02 00:00:00******REVISION DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW:
  
 1. PER FBC-2004 FUEL GAS, SECTION
 411.1.4 OUTDOOR APPLIANCE CONNECTORS:
 PLEASE SHOW THAT THE QUICK-DISCONNECT
 COUPLINGS SUBMITTED COMPLY WITH
 ANSI Z21.69, CONNECTORS FOR MOVABLE GAS
 APPLIANCES.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-10-25 Cont ID  
Sent By adarroug Date 2006-10-25 Time 09:15 Rev Time 0.00
Received By adarroug Date 2006-10-25 Time 09:15 Sent To E
Notes
2006-10-25 09:15:58TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-09-11 Cont ID  
Sent By adarroug Date 2006-09-11 Time 13:50 Rev Time 0.00
Received By adarroug Date 2006-09-11 Time 13:50 Sent To E
Notes
2006-09-11 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 10:59 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 10:59 Sent To Z
Notes
2006-09-05 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-30 Cont ID  
Sent By adarroug Date 2006-06-30 Time 10:19 Rev Time 0.00
Received By adarroug Date 2006-06-30 Time 10:19 Sent To E
Notes
2006-06-30 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-06-23 Time 16:36 Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 16:36 Sent To E
Notes
2006-06-23 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-12-28 Cont ID  
Sent By adarroug Date 2005-12-28 Time 09:19 Rev Time 0.00
Received By adarroug Date 2005-12-28 Time 09:19 Sent To E
Notes
2005-12-28 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-12 Cont ID  
Sent By adarroug Date 2005-12-12 Time 14:07 Rev Time 0.00
Received By adarroug Date 2005-12-12 Time 14:07 Sent To E
Notes
2005-12-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 19:02 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 19:02 Sent To E
Notes
2005-09-23 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-19 Cont ID  
Sent By adarroug Date 2005-09-06 Time 08:44 Rev Time 0.00
Received By alange Date 2005-09-06 Time 08:43 Sent To E
Notes
2005-09-06 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 17:26 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 17:26 Sent To Z
Notes
2005-08-23 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-16 Cont ID  
Sent By tgordon Date 2005-09-16 Time 11:38 Rev Time 0.20
Received By tgordon Date 2005-09-16 Time 11:38 Sent To B
Notes
2005-09-16 00:00:00*** PROVISO ***
 1) GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENINGS. 2001 FBC/M 804.3.3 .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-09-06 Cont ID  
Sent By jleech Date 2005-09-06 Time 09:59 Rev Time 0.25
Received By jleech Date 2005-09-06 Time 09:59 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-08 Cont ID  
Sent By mmclean Date 2006-09-08 Time 16:32 Rev Time 0.00
Received By mmclean Date 2006-09-08 Time 16:32 Sent To I
Notes
2006-09-08 00:00:00NOTE: THE PROPOSED GENERATOR SHALL NOT
 BE CLOSER THAN 8.6 FROM SIDE PROPERTY
 LINE.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-02 Cont ID  
Sent By mmclean Date 2005-09-02 Time 17:33 Rev Time 0.00
Received By mmclean Date 2005-09-02 Time 17:33 Sent To I
Notes
***NONE***