Plan Review Details - Permit 05081390
Plan Review Stops For Permit 05081390
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-22 Cont ID  
Sent By alange Date 2006-03-21 Time 14:12 Rev Time 2.00
Received By alange Date 2006-03-21 Time 14:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-29 Cont ID  
Sent By alange Date 2005-12-29 Time 07:36 Rev Time 1.25
Received By alange Date 2005-12-29 Time 07:33 Sent To  
Notes
2005-12-29 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 6."R" VALUES DO NOT MATCH PLANS FROM
 ENERGY CALCS.
  
 7.ON BITUMEN ROOF PRODUCT APPROVAL,
 PAGES 1 - 6 ARE OK AND THEN SELECT WHAT
 TYPE OF ASSEMBLY WILL BE USED FROM THE
 REST OF THE PAGES SINCE NOT ALL SYSTEMS
 ARE APPROVED.
  
 8.SUBMIT TWO ORIGONAL SURVEYS SHOWING
 ROOM ADDITION.
  
 9.BASED ON SBCCI BUILDING VALUATION
 DATA, THE PERMIT VALUE HAS BEEN REVISED
 TO $16,760.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-22 Cont ID  
Sent By alange Date 2005-09-22 Time 07:23 Rev Time 2.00
Received By alange Date 2005-09-22 Time 07:10 Sent To Z
Notes
2005-09-22 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR STRAPS AND TIE-DOWNS.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.IS NEW ADDITION TO BE
 AIRCONDITIONED?PLANS DO NOT SHOW ANY
 NEW A/C SQUARE FOOTAGE.
  
 5.SHOW SIZE AND TYPE OF EXISTING
 BEDROOM WINDOW SO THAT EGRESS SIZES CAN
 BE VERIFIED.FBC 1005.4
  
 6.SUBMIT TWO COPIES OF ENERGY CALCS
 PER FBC CHAPTER 13.
  
 7.ON BITUMEN ROOF PRODUCT APPROVAL,
 PAGES 1 - 6 ARE OK AND THEN SELECT WHAT
 TYPE OF ASSEMBLY WILL BE USED FROM THE
 REST OF THE PAGES SINCE NOT ALL SYSTEMS
 ARE APPROVED.
  
 8.SUBMIT TWO ORIGONAL SURVEYS SHOWING
 ROOM ADDITION.
  
 9.BASED ON SBCCI BUILDING VALUATION
 DATA, THE PERMIT VALUE HAS BEEN REVISED
 TO $16,760.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-22 Cont ID  
Sent By btrobaug Date 2006-03-22 Time 09:14 Rev Time 0.50
Received By btrobaug Date 2006-03-22 Time 09:14 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-03-15 Cont ID  
Sent By jleahy Date 2006-03-15 Time 10:04 Rev Time 0.45
Received By jleahy Date 2006-03-15 Time 10:04 Sent To  
Notes
2006-03-15 00:00:00WHERE DOES THE FEED COME FOR PANEL "B"
 IT IS NOT SHOWN ON PANEL "A" SCHEDULE.
  
 GROUND ROD TO SMALL FOR PANEL "B"
 250.66, 250.53E
  
 GROUNDING ELECTRODES SHALL BE COMMON
 ELECTRODES TO BE BONDED TO EACH OTHER.
  
 NEUTRAL SHALL NOT BE BONDED AT PANEL "B"
 250.24A5

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-08-28 Cont ID  
Sent By jleahy Date 2005-08-28 Time 21:21 Rev Time 0.45
Received By jleahy Date 2005-08-28 Time 21:21 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-13 Cont ID  
Sent By adarroug Date 2006-03-13 Time 11:06 Rev Time 0.00
Received By adarroug Date 2006-03-13 Time 11:06 Sent To E
Notes
2006-03-13 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 12:24 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 12:24 Sent To Z
Notes
2006-03-02 00:00:00TO "Z" BOX/RESUB--NEW SHEETS ADDED FOR
 "ELECT" AND "PLUMB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 09:24 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 09:24 Sent To B
Notes
2005-12-27 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-13 Cont ID  
Sent By adarroug Date 2005-12-13 Time 19:17 Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 19:17 Sent To Z
Notes
2005-12-13 00:00:00TO 'Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-22 Cont ID  
Sent By alange Date 2005-09-22 Time 07:24 Rev Time 0.00
Received By alange Date 2005-08-24 Time 09:13 Sent To  
Notes
2005-08-24 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-30 Cont ID  
Sent By tgordon Date 2005-08-30 Time 11:55 Rev Time 0.15
Received By tgordon Date 2005-08-30 Time 11:55 Sent To P
Notes
2005-08-30 00:00:00NOT NEEDED AT THIS TIME.
 NO MECH. CONTRACTOR OR MECH. PLANS
 SUBMITED AT THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-03-16 Cont ID  
Sent By jleech Date 2006-03-16 Time 10:25 Rev Time 0.00
Received By jleech Date 2006-03-16 Time 10:25 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-09-08 Cont ID  
Sent By jleech Date 2005-09-08 Time 12:44 Rev Time 0.25
Received By jleech Date 2005-09-08 Time 12:44 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-03-10 Cont ID  
Sent By mmclean Date 2006-03-10 Time 14:34 Rev Time 0.00
Received By mmclean Date 2006-03-10 Time 14:34 Sent To I
Notes
2006-03-10 00:00:00NOTE: THE PROPOSED ADDITION MUST BE A
 MINIMUM 6FT FROM EXISTING SHED.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-12-23 Cont ID  
Sent By mmclean Date 2005-12-23 Time 17:30 Rev Time 0.00
Received By mmclean Date 2005-12-23 Time 17:29 Sent To I
Notes
2005-12-23 00:00:00DENIED,
 1. THE METAL SHED MUST BE 5FT FROM THE
 PROPERTY LINE.
 2. THE OLD SURVEY SHOWS THE SHED BEING
 MOVED CLOSER TO THE PROPERTY LINE.
 3. THE METAL SHED SHOULD BE RELOCATED TO
 MEET THE SIDE SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-23 Cont ID  
Sent By mmclean Date 2005-09-23 Time 15:33 Rev Time 0.00
Received By mmclean Date 2005-09-23 Time 15:33 Sent To  
Notes
2005-09-23 00:00:00DENIED,
 1. NEW ADDITION MUST BE 6FT FROM THE
 METAL BLDG.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720