Plan Review Details - Permit 05081388
Plan Review Stops For Permit 05081388
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-09-12 Cont ID  
Sent By jwitmer Date 2005-09-12 Time 07:55 Rev Time 0.22
Received By jwitmer Date 2005-09-12 Time 07:47 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-05 Cont ID  
Sent By dpalmer Date 2005-12-05 Time 10:09 Rev Time 0.00
Received By dpalmer Date 2005-12-05 Time 10:09 Sent To M
Notes
2005-12-05 00:00:00REDLINED MISSING EQUIPMENT GROUNDING
 CONDUCTORS.
  
  
 REDLINED, MAINS GROUPED AS SHOWN ON
 RISER. SITE PLANS/SLAB DETAIL DOES NOT
 SHOW THIS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-04 Cont ID  
Sent By dpalmer Date 2005-09-04 Time 16:54 Rev Time 0.60
Received By dpalmer Date 2005-09-04 Time 16:46 Sent To M
Notes
2005-09-04 00:00:00******** UNSAT ***********
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 SUBMITTED STATED INSTALLATION OF A NEW
 70KW HOME GENERATOR, HOWEVER SPECS ETC
 SUBMITTED INDICATE 80KW?
 PLEASE CORRELATE.
  
 2)NOTE: PLEASE SEE OVERVIEW OF
 EQUIPMENT, GEN ETC SHOWN ON SLAB DETAIL
 PAGE DOES NOT INCLUDE LOCATION OF NEW
 ATS.
 PLEASE SEE 230.70, A MAIN DISCWITH
 OVERCURRENT PROTECTION OUTSIDE ON THE
 LINE SIDE OF NEW ATS WILL BE REQUIRED AS
 NO MORE THAN 8' OF UNPROTECTED
 CONDUCTORS IS PERMITTED INSIDE DWELLING.
  
 3)NOTE: PLEASE SEE ATS IS REQUIRED TO BE
 RATED AS SERVICE EQUIPMENT. THIS
 NOTATION COULD NOT BE LOCATED ON SPECS
 SUBMITTED.
 225.36, 230.66
  
 4)NOTE: PLEASE SEE THE DISCONNECTING
 MEANS FROM GENERATOR SHALL BE GROUPED OR
 IMMEDIATELY ADJACENT/CLOSE PROXIMITY.
 225.34
  
 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 PERTAINING TO SURVEY SUBMITTED.
 PLEASE SEE FAC 61G17-7.002, FS 472.025
 WHICH REQUIRES THE SURVEYOR TO SIGN
 SURVEY'S WITH AN ORIGINAL SIGNATURE.
 PLEASE SEE SURVEY SUBMITTED CONTAINS A
 RAISED SEAL OVER A PHOTOCOPIED
 SIGNATURE.PLEASE CALL FOR OPTIONS OF
 SURVEY.
  
 7)NOTE: PLEASE SEE VALUATION SHALL
 INCLUDE GENERATOR, TRANSFER SW (NEMA-1
 OR 3?) AND ALL LABOR AND MATERIALS.
 FBC 104.6.5ADMINISTRATIVE AMENDMENTS.
 PLEASE ADJUST.
  
 8)NOTE: PLEASE SEE AN "EQUIPMENT
 GROUDING CONDUCTOR IS BEING SHOWN FROM
 METER TO THE LINE SIDE OF ATS SHOWN.
 PLEASE SEE 250.6, 250.24 "EQUIPMENT
 GROUNDING CONDUCTORS' ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-23 Cont ID  
Sent By adarroug Date 2005-11-23 Time 13:42 Rev Time 0.00
Received By adarroug Date 2005-11-23 Time 13:42 Sent To E
Notes
2005-11-23 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 09:26 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 09:26 Sent To E
Notes
2005-09-02 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 18:49 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 18:48 Sent To Z
Notes
2005-08-23 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-05 Cont ID  
Sent By tgordon Date 2005-12-05 Time 10:30 Rev Time 0.20
Received By tgordon Date 2005-12-05 Time 10:30 Sent To  
Notes
2005-12-05 00:00:00*** PROVISO ***
 1) GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF/EAVE VENTS),
 AND TEN FEET AWAY FROM ADJACENT
 BUILDING OPENINGS. 2001 FBC/M 804.3.3
 2) NATURAL GAS PIPING WILL REQUIRE A
 GAS PERMIT APPLICATION BY A LICENSE
 PLUMBING CONTRACTOR.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-08 Cont ID  
Sent By tgordon Date 2005-09-08 Time 14:01 Rev Time 0.20
Received By tgordon Date 2005-09-08 Time 14:01 Sent To P
Notes
2005-09-08 00:00:00*** DENIED ***
 1) GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF/EAVE VENTS),
 AND TEN FEET AWAY FROM ADJACENT
 BUILDING OPENINGS. 2001 FBC/M 804.3.3
 2) NATURAL GAS PIPING WILL REQUIRE A
 GAS PERMIT APPLICATION BY A LICENSE
 PLUMBING CONTRACTOR.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-09-09 Cont ID  
Sent By jleech Date 2005-09-09 Time 08:19 Rev Time 0.33
Received By jleech Date 2005-09-09 Time 08:19 Sent To B
Notes
2005-09-09 00:00:00GAS PERMIT REQUIRED. PLUMBING CONTRACTOR
 TO MAKE APPLICATION WITH PLANS

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-01 Cont ID  
Sent By mmclean Date 2005-09-01 Time 14:56 Rev Time 0.00
Received By mmclean Date 2005-09-01 Time 14:56 Sent To I
Notes
***NONE***