| Plan Review Stops For Permit 05081307 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-08-29 |
Time |
12:53 |
Rev Time |
1.50 |
| Received By |
mjacobs |
Date |
2005-08-29 |
Time |
11:58 |
Sent To |
PC |
|
| Notes |
| 2005-08-29 00:00:00 | 1) PLEASE PROVIDE A FLOOR PLAN SHOWING | | | WHERE THE STORM PANELS WILL BE | | | INSTALLED. | | | | | | 2) PLEASE SHOW HOW THE PANELS WILL BE | | | INSTALLED FROM THE INSIDE OF THE | | | RESIDENCE. IF ACCORDIAN SHUTTERS WILL BE | | | USED, PROVIDE TWO COPIES OF PRODUCT | | | APPROVALS FOR PLAN REVIEW. | | | | | | 3) DESIGN PRESSURES FOR BUILDINGS OVER | | | 60FEET ARE REQUIRED TO DESIGNED USING | | | ASCE7, FBC 1606.1.1. DOCUMENTS PREPARED | | | BY AN ENGINEER AND SUBMITTED FOR PUBLIC | | | RECORD ARE TO BE SIGNED,SEALED AND | | | DATED,ALONG WITH THE PRINTED NAME AND | | | NUMBER OF THE ENGINEER.FAC61G15-23.002. | | | | | | 4) IF STORM PANELS ARE INSTALLED, SHOW | | | HOW YOU WILL ENTER THE RESIDENCE AFTER | | | THE STORM PANELS ARE ALL INSTALLED. | | | | | | BUILDING PLAN REVIEW | | | MYRON JACOBS. | | | TEL: (561)805-6726 | | | FAX: (561)659-8026 | | | [email protected]. | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-19 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-19 |
Time |
16:28 |
Sent To |
B |
|
| Notes |
| 2005-08-19 00:00:00 | TO "MISC" BOX#1 |
|
|
|