Plan Review Details - Permit 05081294
Plan Review Stops For Permit 05081294
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-06-02 Cont ID  
Sent By rmcdouga Date 2006-06-02 Time 09:45 Rev Time 0.00
Received By rmcdouga Date 2006-06-02 Time 09:45 Sent To  
Notes
2006-06-02 00:00:00PROVISO
  
 1) THE NOTICE OF COMMENCEMENT HAS
 EXPIRED. THE NOC MUST BE RE-RECORDED
 BEFORE THE PERMIT CAN BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-05-22 Cont ID  
Sent By rmcdouga Date 2006-05-22 Time 10:00 Rev Time 0.00
Received By rmcdouga Date 2006-05-22 Time 10:00 Sent To  
Notes
2006-05-22 00:00:00DENIED BY BUILDING
 SAME COMMENTS FROM PREVIOUS REVIEW.
  
 1) THE ATTIC INSULATION SPECIFIED ON THE
 WALL SECTION OF SHEET 2 OF THE PLANS IS
 R-19. THE ENERGY CALCULATION FORM
 SPECIFIES R-30 ATTIC INSULATION. PLEASE
 CORRECT.
  
 2) ADDRESS COMMENTS FROM OTHER TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-05-15 Cont ID  
Sent By rmcdouga Date 2006-05-15 Time 15:04 Rev Time 0.00
Received By rmcdouga Date 2006-05-15 Time 15:04 Sent To  
Notes
2006-05-15 00:00:00DENIED BY BUILDING
  
 1) THE ATTIC INSULATION SPECIFIED ON THE
 WALL SECTION OF SHEET 2 OF THE PLANS IS
 R-19. THE ENERGY CALCULATION FORM
 SPECIFIES R-30 ATTIC INSULATION. PLEASE
 CORRECT.
  
 2) ADDRESS COMMENTS FROM OTHER TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-08 Cont ID  
Sent By rmcdouga Date 2006-02-08 Time 07:53 Rev Time 0.00
Received By rmcdouga Date 2006-02-08 Time 07:53 Sent To M
Notes
2006-02-08 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) COMMENTS OF OTHER TRADES MUST BE
 ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-15 Cont ID  
Sent By rmcdouga Date 2005-12-15 Time 13:23 Rev Time 0.00
Received By rmcdouga Date 2005-12-15 Time 13:23 Sent To  
Notes
2005-12-15 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE INTERNAL PRESSURE COEIFFICIENT IS
 MISSING THE PLUS AND MINUS SIGNS
 INDICATING POSITIVE AND NEGATIVE
 PRESSURES. SEE ASCE 7-98.
  
 4) AN EGRESS DOOR WITH A MINIMUM 32"
 WIDE CLEAR OPENING IS REQUIRED. IF USING
 A DOUBLE DOOR ONE OF THE LEAFS MUST
 COMPLY. SEE 2001 FBC 1003.2.3, 1012.1.7
 AND 1012.1.8.
  
 5) PROVIDE A SITE PLAN SPECIFING THE
 ASSUMED PROPERTY LINE BETWEEN THE THE
 TWO STRUCTURES LOCATED ON THE SAME LOT.
 PROVIDE CALCULATIONS OF THE PERCENT OF
 WALL AREA ALLOWED AS OPENINGS BY FBC
 TABLE 600 FOR THE EXISTING AND THE NEW
 STRUCTURES. SEE 2001 FBC 504 AND TABLE
 600. (THIS HAS NOTHING TO DO WITH
 OPENING PROTECTIVES REQUIRED BY FBC 705
 WHICH DOES NOT APPLY TO R3 OCCUPANCIES.)
  
  
 6) ADDRESS COMMENTS OF OTHER REVIEWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-23 Cont ID  
Sent By rmcdouga Date 2005-09-23 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2005-09-23 Time 07:02 Sent To  
Notes
2005-09-23 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE INTERNAL PRESSURE COEIFFICIENT IS
 MISSING THE PLUS AND MINUS SIGNS
 INDICATING POSITIVE AND NEGATIVE
 PRESSURES. SEE ASCE 7-98.
  
 4) AN EGRESS DOOR WITH A MINIMUM 32"
 WIDE CLEAR OPENING IS REQUIRED. IF USING
 A DOUBLE DOOR ONE OF THE LEAFS MUST
 COMPLY. SEE 2001 FBC 1003.2.3, 1012.1.7
 AND 1012.1.8.
  
 5) THE BEDROOM WINDOW MUST COMPLY WITH
 THE EMERGENCY EGRESS REQUIREMENTS OF
 1005.4.
  
 6) PROVIDE AN EXTERIOR WALL SECTION ON
 THE PLANS. FBC 104.2
  
 7) 1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE.
  
 8) SPECIFY A 1.5 INCH RECESS IN THE
 CONCRETE FLOOR SURFACE WHERE THE
 EXTERIOR WALL MASONRY UNITS BEAR. CITY
 AMENDMENTS TO FBC 2111.1.9.
  
 9) CITY AMENDMENTS TO FBC 1804.1.7
 REQUIRE THE FLOOR ELEVATION AT THE
 PERIMETER OF A MONOLITHIC FOUNDATION AT
 HABITABLE AREAS TO BE A MINIMUM OF 4
 INCHES ABOVE THE EXTERIOR FINISH GRADE.
  
 10)FL BLD CODE 2309.6 ATTIC ACCESS,
 PROVIDE ATTIC ACCESS 20"X36" MINIMUM.
  
 11) SPECIFY ATTIC VENTILATION AS
 REQUIRED BY FBC 2309.7.
  
 12) SPECIFY THE LOCATION OF THE 40 GAL.
 ELECTRIC WATER HEATER. FBC 104.2
  
 13) PROVIDE A SITE PLAN SPECIFING THE
 ASSUMED PROPERTY LINE BETWEEN THE THE
 TWO STRUCTURES LOCATED ON THE SAME LOT.
 PROVIDE CALCULATIONS OF THE PERCENT OF
 WALL AREA ALLOWED AS OPENINGS BY FBC
 TABLE 600 FOR THE EXISTING AND THE NEW
 STRUCTURES. FBC 504 AND TABLE 600.
  
 14) SPECIFY THE CONNECTION TYPE AND THE
 ANCHOR TYPE THAT WILL BE USED FOR THE
 STORM PANELS. SEE SHEET 4 OF THE PRODUCT
 APPROVAL. THE STORM PANEL INSTALLATION
 SCHEDULE LISTS WING NUTS AS THE ANCHOR
 TYPE. THIS IS NOT ONE OF THE ANCHORS
 LISTED ON THE PRODUCT APPROVAL. THE
 SCHEDULE ALSO INDICATES THAT THE PANELS
 ARE BOLTED. THIS REFERS TO PANELS WITH
 LONG SPANS THAT ARE REQUIRED TO BE
 BOLTED TOGETHER IN THE MIDDLE OF THE
 SPAN. THIS IS NOT NECESSARY FOR YOUR
 PROJECT.
  
 15) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT A
 COVER SHEET FOR THE ROOF SHINGLES.
  
 16) THE FL COVER SHEET FOR THE STANLEY
 DOOR SYSTEM DOES NOT MATCH THE MIAMI
 DADE NOA.
  
 17) THE MIAMI DADE NOA FOR THE SINGLE
 HUNG WINDOWS IS NOT THE ONE LISTED ON
 THE STATE WEBSITE FOR THE FL #
 SUBMITTED. THE CORRECT ONE IS NOA #
 02-1203.02.
  
 18) THE DRAWINGS ATTACHED TO THE STANLEY
 DOOR NOA DO NOT BELONG WITH THE NOA.
 THEY HAVE DIFFERENT APPROVAL NUMBERS.
  
 19) SUBMIT PRODUCT APPROVALS FOR THE
 SINGLE INSWING EXTERIOR DOOR AND THE
 DOUBLE OUTSWING EXTERIOR DOOR.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 8 Status N Date 2006-06-02 Cont ID  
Sent By dpalmer Date 2006-06-02 Time 10:06 Rev Time 0.00
Received By dpalmer Date 2006-06-02 Time 10:06 Sent To  
Notes
2006-06-02 00:00:00ELECTRICAL PLANS TO BE SUBMITTED UNDER
 SEPARATE PERMIT. PLANS SUBMITTED UNDER
 BUILDING PERMIT ARE NOT COMPLIANT AND
 ALL ELECTRICAL SHOWN HAS BEEN CROSSED
 OUT PER REQUEST OF CONTRACTOR MR CARLOS
 GONZALES JR ON THE PHONE.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-06-02 Cont ID  
Sent By dpalmer Date 2006-06-02 Time 06:29 Rev Time 0.00
Received By dpalmer Date 2006-06-02 Time 06:00 Sent To M
Notes
2006-06-02 00:00:00************ UNSAT **************
  
  
 1) NOTE: PLEASE SEE RISER IS NOW ON
 PLANS, HOWEVER IS SERVICE NEW OR
 EXISTING???
 ON ONE SET OF PREVIOUS REVIEWED PLANS IT
 WAS STATED AS EXISTING AND AIC RATINGS
 ARE NOT REQUIRED, HOWEVER PREVIOUS PLANS
 HAVE ALSO SHOWN THE SERVICE AS NEW AND
 AIC RATINGS WERE REQUESTED.
 PLEASE INDICATE IF SERVICE IS NEW OR
 EXISTING? IF NEW PROVIDE AIC RATINGS
 FOR MAINS ETC. PER 110.9, 215.5
  
 2) NOTE: PLEASE SEE PLANS STILL DO NOT
 CONTAIN THE PANEL SCHEDULE FOR THE
 CABANA SHOWING THE CIRCUITS, OVERCURRENT
 PROTECTION FOR CIRCUITS AND WIRE SIZES??
 THIS WAS SOMETHING WHICH WAS ON PREVIOUS
 PLANS, HOWEVER IS NOT ON THESE PLANS.??
 PLEASE BE SURE THE REQUIRED DEDICATE AND
 ARC FAULT CIRCUITS ARE SHOWN.
 PLEASE SEE THE A/C SHEETS CONTAIN PANELS
 SCHEDULES FOR HOUSE AND CABANA, HOWEVER
 THESE PANELS SCHEDULES ARE "BLANK"??
 210.12,210.11C3, ETC.
  
 3) NOTE: PLEASE INCLUDE THE OCP FOR THE
 NEW SUB PANEL FEED. THE RISER MENTIONS
 NEW 2-POLE, HOWEVER WHAT SIZE IS THIS??
  
 4) NOTE: PLEASE SEE IF THE SERVICE IS
 NEW, PLEASE PROVIDE A MIN OF TWO GRND
 RODS AND CWP AT MAIN HOUSE. IF THE
 SERVICE IS EXISTING, THEN THIS IS NOT
 NEEDED.
 250.50
  
 5) NOTE: PLEASE SHOW THE LOCATION AND
 DISCONNECTING MEANS FOIR THE AHU AND CU.
 PLEASE SEE THE MECH SHEET SHOWS THE AHU
 IN CLOSET, HOWEVER THE ELECTRICAL PLANS
 ONLY INDICATE THE WATER HEATER.??
 440.11, 215.5
  
 6) NOTE: PLEASE SEE LOCATION OF NEW SUB
 PANEL IS NOT SHOWN ON PLANS??
  
  
 7) NOTE: PLEASE KNOW , IT IS THE
 RESPONSIBILITY OF THE ENGINEER SIGNING
 AND SEALING PLANS ONLY TO SIGN AND SEAL
 PLANS IN WHICH WERE DONE BY SAID
 ENGINEER OR IS UNDER HIS DIRECT
 SUPERVISION.FS 471
 PLEASE KNOW, IT IS ALSO THE
 RESPONSIBILTY TO REVIEW AND CHECK PLANS
 FOR CODE COMPLIANCE BEFORE SIGNING AND
 SEALING SAID PLANS.
 THIS IS THE 7TH REVIEW FOR THIS SCOPE OF
 WORK. PLEASE KNOW IF ALL CORRECTIONS ARE
 NOT MADE FOR THE FOLLOWING REVIEW, A 4X
 FEE WILL BE ACCESSED PER FS 553.80(2)(B)
 AND ALL PLANS RETAINED FOR THIS JOB FROM
 PREVIOUS REVIEWS AND NEW PLANS WILL BE
 TURNED OVER TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS, AND LEGAL
 COUNSEL FOR REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-05-19 Cont ID  
Sent By btrobaug Date 2006-05-19 Time 08:04 Rev Time 0.50
Received By btrobaug Date 2006-05-19 Time 07:22 Sent To M
Notes
2006-05-19 00:00:00 
  
 THE ENGINEER OF RECORD MUST SIGN, SEAL
 AND DATE THE DOCUMENTS PER 471.025
 FLORIDA STATUTES.
  
 WILLIAM R TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/561) 805-6731

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 14:47 Sent To M
Notes
2006-05-14 00:00:00********* UNSAT *************
  
 1) NOTE: PLEASE SEE NEW ELECTRICAL PLANS
 SUBMITTED WITH NEW PANEL SCHEDULES AND
 LOAD CALCULATIONS, HOWEVER PLANS HAVE
 NOW HAD THE ELECTRICAL RISER DIAGRAM
 COMPLETELY REVMOVED????
 ** PLEASE SUBMIT TWO COMPLETE SETS OF
 PLANS.
 PANELS SCHEDULES, RISER DIAGRAM AND
 FLOOR PLANS SHOWING ALL ELECTRICAL.
  
 PLEASE SEE PLANS AND SHEETS WERE NOT
 SUBMITTED IN COMPLETE SETS. PLEASE DO
 NOT SUBMIT PLANS SIGNED AND SEALED BY AN
 ENGINEER WITH AREAS CROSSED OUT.
 PLEASE ALSO SEE MECHNICAL COMMENTS AS
 MECH SHEETS WHICH WERE VOIDED FROM
 PREVIOUS REVIEW ALSO CONTAIN INCOMPLETE
 ELECTRICAL RISER??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-02-14 Time 14:53 Rev Time 0.00
Received By dpalmer Date 2006-02-14 Time 14:47 Sent To  
Notes
2006-05-14 00:00:00REVIEW NEVER DONE, CONTRACTOR PICKED UP
 PLANS WHICH WERE SUBMITTED WITH OUT
 CORRECTIONS.
2006-02-14 00:00:00ON HOLD WAITING FOR CONTRACTOR TO BRING
 IN NEW SHEETS. SPOKE TO CONTRACTOR 6PM
 ON 2/14

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-02-01 Cont ID  
Sent By dpalmer Date 2006-02-01 Time 07:11 Rev Time 0.00
Received By dpalmer Date 2006-02-01 Time 07:02 Sent To P
Notes
2006-02-01 00:00:00**** UNSAT 3RD REVIEW ****
  
 1)NOTE: PLEASE SEE 220.31B FOR MINIMUM
 LOAD CALCUALTIONS.
 PLEASE SEE CALCUALTIONS AS SHOWN DO NOT
 MEET CODE.
 PLEASESEE DERATING FOR A/C LOADS ARE
 NOT CORRECT.
 PLEASE SEE GEN LT AND RECEPT LOADS ARE
 NOT CORRECT.
 PLEASE SEE LOADS FIGURED INTO EXISTING
 MAIN IS NOT CORRECT.
 ETC.
 ** PLEASE SEE 220.31B.
  
 ** PLEASE SEE IF ALL OTHER COMMENTS ARE
 ADDRESSED FROM ALL OTHER REVIEWER(S),
 PLEASE CALL FOR POSSIBLE OPTIONS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-11-21 Cont ID  
Sent By dpalmer Date 2005-11-21 Time 11:41 Rev Time 0.33
Received By dpalmer Date 2005-11-21 Time 11:41 Sent To P
Notes
2005-11-21 00:00:00*** UNSAT ***
  
  
 ** PLEASE SEE ZONING COMMENT. THE
 PROPOSED RESIDENCE IS NOT PERMITTED.
  
  
 1)NOTE: PLEASE SEE PLANS INDICATE
 KITCHEN SM APPLIANCE CIRCUITS, WHICH IS
 ALSO NOT PERMITTED BY ZONING.
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND EXISTING PANEL SCHEDULE.
 PLEASE SEE FEEDERS, #3, #4.
 PLEASE SEE MIN PER 310.15B6
  
 3)NOTE: PLEASE SEE MIN LOAD CALCULATIONS
 PER 220.31B.
 PLEASE REVISE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-01 Cont ID  
Sent By dpalmer Date 2005-09-01 Time 19:00 Rev Time 0.40
Received By dpalmer Date 2005-09-01 Time 18:53 Sent To M
Notes
2005-09-01 00:00:00************* UNSAT **************
  
  
 1)NOTE: PLEASE SEE ZONING COMMENTS AS
 REAR DWELLING/APT MAY NOT BE BUILT AS
 SHOWN. THIS WILL DIRECTLY AFFECT
 ELECTRICAL PLAN.
  
 2)NOTE: PLEASE SUBMIT COMPLETE PLANS TO
 MEET 2002 NEC.
 PLEASE SEE
 210.52,210.11C1,210.11C2,210.11C3,
 210.52D,310.15B6,250.50,250.32,210.8A6,
 424.3B,
 ETC.
 PLEASE SEE LOADS MUST BE DONE PER
 220.31B.
 PLEASE SEE EXISTING HOUSE PANEL DOES NOT
 INCLUDE LOADS OF SUB PANEL, OCP, ETC.
 PLEASE SEE MISSING REQUIRED SD'S.
 NFPA-72 8-1.4.1.6.2
  
 3)NOTE: PLEASE BE SURE ENGINEER SIGNS
 COMPLETE LEGAL SIGNATURE AS ON FILE WITH
 THE CITY.
 FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-05-30 Cont ID  
Sent By adarroug Date 2006-05-30 Time 16:25 Rev Time 0.00
Received By adarroug Date 2006-05-30 Time 16:25 Sent To E
Notes
2006-05-30 00:00:00TO "E" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-05-18 Cont ID  
Sent By adarroug Date 2006-05-18 Time 16:54 Rev Time 0.00
Received By adarroug Date 2006-05-18 Time 16:54 Sent To E
Notes
2006-05-18 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-05-12 Cont ID  
Sent By adarroug Date 2006-05-12 Time 16:16 Rev Time 0.00
Received By adarroug Date 2006-05-12 Time 16:16 Sent To E
Notes
2006-05-12 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-02-14 Cont ID  
Sent By adarroug Date 2006-02-14 Time 16:15 Rev Time 0.00
Received By adarroug Date 2006-02-14 Time 16:15 Sent To E
Notes
2006-02-14 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-31 Cont ID  
Sent By adarroug Date 2006-01-31 Time 14:20 Rev Time 0.00
Received By adarroug Date 2006-01-31 Time 14:20 Sent To E
Notes
2006-01-31 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-23 Cont ID  
Sent By adarroug Date 2006-01-23 Time 16:25 Rev Time 0.00
Received By adarroug Date 2006-01-23 Time 16:24 Sent To Z
Notes
2006-01-23 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-17 Cont ID  
Sent By adarroug Date 2005-11-17 Time 18:42 Rev Time 0.00
Received By adarroug Date 2005-11-17 Time 18:42 Sent To E
Notes
2005-11-17 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 10:55 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 10:55 Sent To Z
Notes
2005-11-14 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 10:52 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 10:52 Sent To E
Notes
2005-09-01 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-23 Cont ID  
Sent By rmcdouga Date 2005-09-23 Time 13:29 Rev Time 0.00
Received By rmcdouga Date 2005-08-19 Time 16:40 Sent To  
Notes
2005-08-19 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-06-02 Cont ID  
Sent By tgordon Date 2006-06-02 Time 09:16 Rev Time 0.30
Received By tgordon Date 2006-06-02 Time 09:16 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-05-19 Cont ID  
Sent By tgordon Date 2006-05-19 Time 09:32 Rev Time 0.25
Received By tgordon Date 2006-05-19 Time 09:32 Sent To B
Notes
2006-05-19 00:00:00*** DENIED ***
 1) AS NOTED IN LAST RIVIEW, AN
 ENGINEER'S NAME (JOHN D. HOLT)
 APPEARS IN THE TITLE BLOCK THERE-FORE HE
 MUST PUT HIS SEAL ON THE PLANS, PER FAC
 61G15-23.002 .
  
 2) PLEASE SEE ELECTRICAL REVIEW NOTE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-05-15 Cont ID  
Sent By tgordon Date 2006-05-15 Time 11:57 Rev Time 0.25
Received By tgordon Date 2006-05-15 Time 11:57 Sent To P
Notes
2006-05-15 00:00:00*** DENIED ***
 1) AN ENGINEER'S NAME (JOHN D. HOLT)
 APPEARS IN THE TITLE BLOCK THERE-FORE HE
 MUST PUT HIS SEAL ON THE PLANS, PER FAC
 61G15-23.002 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-02-08 Cont ID  
Sent By tgordon Date 2006-02-08 Time 09:23 Rev Time 0.30
Received By tgordon Date 2006-02-08 Time 09:23 Sent To  
Notes
2006-02-08 00:00:00*** DENIED ***
 1) REVISED A/C PLAN SHOWS NO A/C DETAIL
 OR EQUIPMENT LISTING. THE OLD APPROVED
 A/C PLAIN CAN NOT BE USED AS THE ROOM
 DESIGNATION IS NOT THE SAME AS THE
 REVISED PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-12 Cont ID  
Sent By tgordon Date 2005-12-12 Time 08:13 Rev Time 0.15
Received By tgordon Date 2005-12-12 Time 08:13 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-09-06 Cont ID  
Sent By prafter Date 2005-09-06 Time 12:21 Rev Time 0.50
Received By prafter Date 2005-09-06 Time 12:21 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-05-15 Cont ID  
Sent By jleech Date 2006-05-15 Time 13:37 Rev Time 0.00
Received By jleech Date 2006-05-15 Time 13:37 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-02-07 Cont ID  
Sent By jleech Date 2006-02-07 Time 14:34 Rev Time 0.25
Received By jleech Date 2006-02-07 Time 14:34 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-12-10 Cont ID  
Sent By pschmitz Date 2005-12-10 Time 09:27 Rev Time 0.00
Received By pschmitz Date 2005-12-10 Time 09:27 Sent To M
Notes
2005-12-10 00:00:00 
 PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
 1.PLEASE SEE PREVIOUS NOTES FROM ALL
 DISIPLINES.
 END OF COMMENTS,QUESTIONS 561-805-6692
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-09-08 Cont ID  
Sent By jleech Date 2005-09-08 Time 09:26 Rev Time 0.00
Received By jleech Date 2005-09-08 Time 09:25 Sent To B
Notes
2005-09-08 00:00:00 
 DENIED;
 1.PLEASE SEE ZONING NOTES. THIS WILL
 CHANGE THE PLUMBING INSTALLED IN UNIT.
 THE APARTMENT IF APPROVED BY ZONING
 WOULD NEED A SORSE OF HOT WATER AND
 AUTOMATIC CLOTHS WASHER TO MEET MINIMUUM
 PLUMBING REQUIREMENTS PER TALBE 403.1.
 2.SEE ELECTRICAL PLANREVIEW NOTE #3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2006-01-30 Cont ID  
Sent By mmclean Date 2006-01-30 Time 18:55 Rev Time 0.00
Received By mmclean Date 2006-01-30 Time 18:55 Sent To I
Notes
2006-01-30 00:00:00CABANA CANNOT BE USE AS A LIVING SPACE,
 ZONED SF7.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-11-17 Cont ID  
Sent By mmclean Date 2005-11-17 Time 09:42 Rev Time 0.15
Received By mmclean Date 2005-11-16 Time 17:37 Sent To I
Notes
2005-11-17 00:00:00DENIED.
 1. MUST PROVIDE TWO NEW COPY OF SURVEY
 SHOWING THE PROPOSED STRUCTURE AS A
 CABANA ONLY.
 2. ZONED SF7
 3. PLEASE REMOVE PROPOSED RESIDENCE
 DECRIPTION ON THE PERMIT APPLICATION AND
 COMPUTER SYSTEM.
 4. ACCESSORY STRUCTURE CANNOT BE USED
 FOR LIVING SPACE (ZONED SF7).
 5. NO ELECTRICAL 2/20 FOR ACCESSORY
 STRUCTURE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
2005-11-16 00:00:00PLANNING DEPT.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-31 Cont ID  
Sent By mmclean Date 2005-08-31 Time 10:14 Rev Time 0.00
Received By mmclean Date 2005-08-31 Time 10:14 Sent To I
Notes
2005-08-31 00:00:00DENIED, - ZONED SF7
 1. CANNOT HAVE AN ACCESSORY USE FOR
 LIVING SPACE.
 2. MUST REMOVE THE KITCHEN & BEDROOM
 FROM PLANS (REF MUST BE AN U/C REF.).
 3. MUST PROVIDE TWO COPIES OF ALL FLOOR
 PLANS/ELEC/PLUMBING PLANS CHANGING THE
 USE OF THE ACCESSORY STRUCTURE TO
 REFLECT CABANA.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720