| Plan Review Stops For Permit 05081277 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-23 |
Time |
18:16 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2005-09-10 |
Time |
14:25 |
Sent To |
P |
|
| Notes |
| 2005-08-23 00:00:00 | TO "P" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-09-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-09-10 |
Time |
14:26 |
Rev Time |
1.25 |
| Received By |
jleech |
Date |
2005-09-10 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2005-09-10 00:00:00 | DENIED; | | | 1.AN APPLICATION FOR COM. REMODEL, FOR | | | THE REMODELING OF THE BATHROOMS SHALL BE | | | SUBMITED BY AN APPROIATE CONTRACTOR TO | | | DEMO THE EXISTING FLOOR PLAN AND | | | CONSTRUCT NEW WALLS ETC. SECTION 104.1. | | | 2.SUBMIT A DETAIL FOR THE BATHROOMS | | | SHOWING COMPLIANCE WITH SECTIONS | | | 11-4.16, 11-4.19, AND ALL SUBSECTIONS. | | | 3.A DRINKING FOUNTAIN IS REQUIRED IN | | | EACH SPACE TABLE 403.1. | | | 4.SUBMIT A WATER RISER DIAGRAM SHOWING | | | ALL PIPE SIZES,VAVES, WATER HAMMER | | | ARRESTORS, WHERE REQUIRED BY 604.9 AND | | | POINT OF CONNECTION. | | | 5. A RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE TO THE BUILDING. PLEASE | | | INDICATE IF THERE IS AN EXISTING RPZ ON | | | WATER SERVICE. SEC.608.12.2. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
|