Plan Review Details - Permit 05081247
Plan Review Stops For Permit 05081247
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-26 Cont ID  
Sent By shill Date 2006-10-26 Time 15:11 Rev Time 0.00
Received By shill Date 2006-10-26 Time 14:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-09-12 Cont ID  
Sent By shill Date 2006-09-12 Time 09:41 Rev Time 0.00
Received By shill Date 2006-09-12 Time 09:30 Sent To  
Notes
2006-09-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SEE PREVIOUS TWO CORRECTION LISTS
 IN REGARDS TO USE OF REMOVABLE SHUTTERS
 AND RESULTING DELAYS IN PERMITTING.AS
 ADVISED PREVIOUSLY, THE PLANS CANNOT BE
 APPROVED SHOWING REMOVABLE SHUTTERS
 UNTIL AND INSTALLATION PLAN HAS BEEN
 SUBMITTED AND APPROVED BY BUILDING
 OFFICIAL.THIS PLAN MAY BE SUBMITTED
 SEPARATELY FROM THE RESUBMITTAL OF THE
 PLANS FOR PERMIT.
  
 2.)PLEASE KEEP THE IMPACT FEE RECEIPT
 AND STAMPED PLANS IN THE PACKAGE WHEN
 RESUBMITTING.
  
 3.)SEE ELECTRIC REVIEW #2 IN REGARDS
 TO A COFA REQUIRED FOR THE ENGINEER, MR.
 GARGUILO, PROFESSIONAL ENGINEERS.I
 HAVE CONFIRMED THIS REQUIREMENT WITH
 FBPE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-06 Cont ID  
Sent By shill Date 2006-03-06 Time 13:50 Rev Time 0.00
Received By shill Date 2006-03-06 Time 13:42 Sent To  
Notes
2006-03-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS REVIEW:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 MUST BE FILED PRIOR TO PERMIT PICKUP.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 THE PLANS WERE STAMPED.PLEASE PROVIDE
 THE RECEIPT.
  
 3.)ADDRESSED.
  
 4.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED IN ADDITION TO THE
 NOAS PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 PRODUCT APPROVALS NOT SUBMITTED FOR THE
 FRENCH DOOR.ANY PRODUCT APPROVALS NOT
 REVIEWED PRIOR TO PERMIT ISSUANCE WILL
 REQUIRE SEPARATE PERMITS.
  
  
 5.)IMPACT PROTECTION REQUIRED,
 FBC1606.1.4.REMOVABLE SHUTTERS ON
 COMMERCIAL PROPERTIES REQUIRE APPROVAL
 BY THE BUILDING OFFICIAL.SEE ATTACHED
 IMPLEMENTATION STANDARD, ITEM #13.
 SUBMIT AN INSTALLATION PLAN.SEE ALSO
 ATTACHED SCHEDULE FOR INSTALLATION OF
 OPENING PROTECTIVE DEVICES AND
 PROCEDURES #1.
  
 THE PLANS SHOW THE USE OF REMOVABLE
 SHUTTERS.THE PERMIT CANNOT BE ISSUED
 UNTIL THIS IS APPROVED BY THE BUILDING
 OFFICIAL.SUBMIT A PLAN AS PREVIOUSLY
 REQUESTED TO AVOID FURTHER DELAYS.
  
 6.)ADDRESSED.
  
 7.)ADDRESSED.
  
 8.)ADDRESSED.
  
 9.)THE ENTRY DOOR APPEARS TO HAVE A
 STEP.ACCESSIBLE ENTRANCE/EGRESS IS
 REQUIRED, FBC11-4.1.3(9),
 11-4.1.6(1)(B).PROVIDE FLOOR
 ELEVATIONS, DOOR WIDTH.
  
 THE NOTE REGARDING A 5' LANDING AND A 5"
 HIGH LANDING.THE 5" HIGH LANDING WOULD
 BE CONSIDERED A STEP, NOT PART OF AN
 ACCESSIBLE ROUTE.
  
 NEW COMMENT:
  
 10.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF CODE
 COMMENTS NOT PROPERLY ADDRESSED (ITEM #9
 ABOVE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-14 Cont ID  
Sent By shill Date 2005-10-14 Time 14:13 Rev Time 1.50
Received By shill Date 2005-10-14 Time 13:37 Sent To PC
Notes
2005-10-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)ADDITIONAL FEES DUE (RADON, FIRE
 FEE), SEE ATTACHED.
  
 4.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED IN ADDITION TO THE
 NOAS PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 5.)IMPACT PROTECTION REQUIRED,
 FBC1606.1.4.REMOVABLE SHUTTERS ON
 COMMERCIAL PROPERTIES REQUIRE APPROVAL
 BY THE BUILDING OFFICIAL.SEE ATTACHED
 IMPLEMENTATION STANDARD, ITEM #13.
 SUBMIT AN INSTALLATION PLAN.SEE ALSO
 ATTACHED SCHEDULE FOR INSTALLATION OF
 OPENING PROTECTIVE DEVICES AND
 PROCEDURES #1.
  
 6.)THE SLAB IS TO BE 4" ABOVE GRADE,
 FBC*1804.1.7.
  
 7.)WATERSTOP OF 1.5 INCH REQUIRED,
 FBC*2111.1.9.
  
 8.)BOTTOM OF FOOTING TO BE 12" BELOW
 GRADE, FBC1804.1.3.
  
 9.)THE ENTRY DOOR APPEARS TO HAVE A
 STEP.ACCESSIBLE ENTRANCE/EGRESS IS
 REQUIRED, FBC11-4.1.3(9),
 11-4.1.6(1)(B).PROVIDE FLOOR
 ELEVATIONS, DOOR WIDTH.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-19 Cont ID  
Sent By dpalmer Date 2006-10-19 Time 19:40 Rev Time 0.00
Received By dpalmer Date 2006-10-19 Time 19:29 Sent To  
Notes
2006-10-19 19:40:52TITLE BLOCKS CORRECTED.
 ELECTRICAL PLANS OK, AND STAMPED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-09 Cont ID  
Sent By dpalmer Date 2006-09-09 Time 15:52 Rev Time 0.00
Received By dpalmer Date 2006-09-09 Time 15:28 Sent To  
Notes
2006-09-09 00:00:00** UNSAT **
  
 **** PLEASE KNOW, THE E-1 SHEET WAS
 STAMPED AS OK ONLY.
  
 1) NOTE: PLEASE SEE THE OTHER SHEETS
 ARE STILL MISSING THE REQUIRED
 "CERTIFICATE OF AUTHORIZATION" NUMBER
 FOR ENGINEERING FIRM AS REQUESTED AND
 REQUIRED ON PREVIOUS REVIEW(S).
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 AND FS 471.023, IF OTHER
 THAN AN "INDIVIDUAL", THEN A CA NUMBER
 IS REQUIRED. PLEASE KNOW PLANS ARE BEING
 RETAINED AS CONTACT WITH THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS AND
 LEGAL COUNSEL TO THE BOARDWILL TAKE
 PLACE, PLANS RETAINED WILL BE TURNED
 OVER.
 THIS WAS THE SAME AS ALL PREVIOUSLY
 SUBMITTED PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-28 Cont ID  
Sent By dpalmer Date 2006-02-28 Time 07:39 Rev Time 0.00
Received By dpalmer Date 2006-02-28 Time 07:00 Sent To  
Notes
2006-02-28 00:00:00********** UNSAT 2ND REVIEW ********
  
 ** PLEASE SOME NOTES FROM PERVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM THE PREVIOUS REVIEW WITH
 ADDED NOTING FOR CLARIFICATION.
 PLEASE SEE NEW NOTES FOR DESIGNERS.
  
  
 1)NOTE: NOTE #1 NO, PLEASE SHOW ALL
 CIRCUITING, SOME NEW CIRCUITS ARE SHOWN
 , HOWEVER THERE ARE STILL SOME MISSING.
 PLEASE SEE 700.12E FOR CIRCUITING OF EM/
 EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE LOCAL
 BRANCH CIRCUIT LIGHTING SHALL ALSO FEED
 THE EM / EXT LTS IN THAT AREA.
  
 ** PLEASE SHOW NEW CIRCUITING ON PLANS
 AND CORRELATE WITH EXISTING PANEL
 SCHEDULE TO BE SUBMITTED.
 215.5
  
 2)NOTE: NOTE #2, NO, PLEASE SEE THE LOAD
 CALCULATIONS FROM PREVIOOUS PLANS WERE
 REMOVED FROM NEW SHEETS AND ONLY
 CONNECTED LOADS? ARE SHOWN. PLEASE KNOW,
 EVEN SHOWING SOME OF THESE LOADS AS
 CONNECTED LOADS, STILL DO NOT CORRELATE
 WITH THE MIN LOADS REQUIRED PER NEC.
 PLEASE SEE 220.3,220.10,220.13, ETC AND
 CONTINUOUS LOADS PER 215.3,230.42 ETC.
  
 ** PLEASE SEE NEC 220.13 FOR KNOWN
 RECEPT LOADS FOR LOAD CALCS.
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%, 215.3,230.42 ETC.
 PLEASE SEE ANY DEDICATED RECEPT LAODS
 MAY BE OF A HIGHER VALUE.
  
 3)NOTE: NOTE #3 OK, PLANS INDICATE THE
 DOOR BEING LOCATED INSIDE FOR THE
 ELEVATION AS SHOWN?
 RESPONSE LTR MENTIOSN THE REVISED
 DETAIL.
  
 ** PLEASE CORRELATE SEC AA FOR
 ELEVATION AND FLR PLANS. PLEASE SEE BLDG
 REVIEW COMMENTS AS ONE SHOWS A NEW
 FRENCH DOOR AND THE OTHER SHOWS A
 WINDOW?
 IF THERE WILL BE AN EGRESS DOOR, PLEASE
 INCLUDE ANY ELECTRICAL REQUIRED.
 (EXIT, LT)?
  
 4)NOTE: PLEASE SEE MISSING CERTIFICATE
 OF AUTHORIZATION FOR ENGINEERING FIRM AS
 SHOWN ON PLANS. PLEASE SEE FAC
 61G15-23.002, FS 471.023.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS CONTAINING THE TITLE BLOCK
 FOR SAID ENGINEERING FIRM.
  
 5)NOTE: PLEASE SEE "SEALS RULE" FROM THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 WHICH PER RULING DATE FEB 5, 2004 ,
 61G15-23.001REQUIRED ALL SEALS WITH
 THE WORDING OF "CERTIFICATE" TO BE
 CHANGED TO THE USE OF "LICENSE" IN SAID
 SEAL. PLEASE KNOW, AN EXTENSION WAS
 GIVEN TO THE DATE OF DEC 31ST, 2005.
 PLEASE KNOW AS OF JAN 1ST, 2006 ALL
 SEALS SHALL ONLY CONTAIN THE WORDING OF
 "LICENSE". PLEASE ADJUST ACCORDINGLY.
  
 6)NOTE: PLEASE SEEA NOTICE IS GIVEN AT
 THIS TIME WITH RESPECT TO THE DESIGN
 PROFESSIONAL(S) TO FS 553.80(2)(B) AND
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
 PLEASE BE SURE TO ADDRESS ALL COMMETS.
  
  
 **PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-02 Cont ID  
Sent By dpalmer Date 2005-09-02 Time 15:58 Rev Time 0.33
Received By dpalmer Date 2005-09-02 Time 15:53 Sent To  
Notes
2005-09-02 00:00:00********* UNSAT ********
  
 PLEASE SEE PLANS ARE COMING BACK FOR
 OTHER COMMENTS, PLEASE MAKE THE ABOVE
 CORRECTIONS AT THIS TIME.
  
 1)NOTE: PLEASE SHOW NEW CIRCUITING ON
 PLANS AND CORRELATE WITH EXISTING PANEL
 SCHEDULE TO BE SUBMITTED.
 215.5
  
 2)NOTE: PLEASE SEE NEC 220.13 FOR KNOWN
 RECEPT LOADS FOR LOAD CALCS.
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%,
 215.3,230.42 ETC.
 PLEASE SEE ANY DEDICATED RECEPT LAODS
 MAY BE OF A HIGHER VALUE.
  
 3)NOTE: PLEASE CORRELATE SEC AA FOR
 ELEVATION AND FLR PLANS. PLEASE SEE BLDG
 REVIEW COMMENTS AS ONE SHOWS A NEW
 FRENCH DOOR AND THE OTHER SHOWS A
 WINDOW?
 IF THERE WILL BE AN EGRESS DOOR, PLEASE
 INCLUDE ANY ELECTRICAL REQUIRED.
 (EXIT, LT)?
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-12-14 Cont ID  
Sent By mawillia Date 2006-12-14 Time 12:32 Rev Time 0.00
Received By mawillia Date 2006-12-14 Time 12:32 Sent To  
Notes
2006-12-14 12:37:24*****APPROVED******
  
  
  
  
 PLANSSTAMPED, SIGNED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-03-03 Cont ID  
Sent By mwennerg Date 2006-03-03 Time 11:19 Rev Time 0.00
Received By mwennerg Date 2006-03-03 Time 11:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-09 Cont ID  
Sent By mwennerg Date 2005-09-09 Time 15:41 Rev Time 0.00
Received By mwennerg Date 2005-09-09 Time 15:41 Sent To  
Notes
2005-09-09 00:00:00******DENIED******
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENT
 #3. PLEASE CLARIFY WHAT IS PROPOSED FOR
 REFERENCED WALL. IF DOOR IS PLANNED,
 PLEASE SHOW APPROPRIATE EXIT MARKING.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-04 Cont ID  
Sent By adarroug Date 2006-10-04 Time 14:13 Rev Time 0.00
Received By adarroug Date 2006-10-04 Time 14:13 Sent To  
Notes
2006-10-19 16:12:06TO "COMM" BD#3
2006-10-04 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-08-28 Time 16:03 Rev Time 0.00
Received By adarroug Date 2006-08-28 Time 16:03 Sent To  
Notes
2006-09-05 00:00:00TO "COMM" BD#42

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 09:36 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 09:36 Sent To  
Notes
2006-02-22 00:00:00TO "COMM" BD#58
2006-01-27 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 13:06 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 13:06 Sent To  
Notes
2005-09-01 00:00:00TO "COMM" BD#25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-14 Cont ID  
Sent By shill Date 2005-10-14 Time 14:14 Rev Time 0.00
Received By shill Date 2005-08-19 Time 15:37 Sent To  
Notes
2005-08-19 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-10-19 Cont ID  
Sent By dpalmer Date 2006-10-19 Time 19:37 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2006-10-19 19:38:05NO MECH IN SCOPE PF WORK, NO MECH PERMIT APPLIED FOR.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-10-19 Cont ID  
Sent By dpalmer Date 2006-10-19 Time 19:37 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2006-10-19 19:37:37NO PLUMING WORK IN SCOPE, NO PLUMBING PERMIT APPLIED
 FOR.

Review Stop Z ZONING
Rev No 4 Status P Date 2006-10-24 Cont ID  
Sent By mmclean Date 2006-10-24 Time 17:39 Rev Time 0.00
Received By mmclean Date 2006-10-24 Time 17:39 Sent To  
Notes
2006-10-24 17:39:30NOTE: SEE THE ATTACHED NOTE FROM DEAN
 LAUDERMILK APPROVING THE OFF STREET
 PARKING.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-09-19 Cont ID  
Sent By mmclean Date 2006-09-19 Time 15:14 Rev Time 0.00
Received By mmclean Date 2006-09-19 Time 09:35 Sent To  
Notes
2006-09-19 00:00:00NOTE: SEE THE ATTACHED NOTE FROM DEAN
 LAUDERMILK APPROVING THE OFF STREET
 PARKING.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-02-27 Cont ID  
Sent By mmclean Date 2006-02-27 Time 14:16 Rev Time 0.00
Received By mmclean Date 2006-02-23 Time 17:56 Sent To  
Notes
2006-02-27 00:00:00DENIED,
 1. NEED TO PROVIDE A LETTER SIGNED BY
 THE ENGINEERING DEPT WITH THE CITY OF
 WEST PALM BEACH, APPROVING THE ON STREET
 PARKING (ON 26TH STREET)
 2. THE 2ND RESUB SHOWS TWO EXISTING
 DRIVEWAY WITHIN THE CIRCULAR DRIVE.
 CANNOT HAVE THE SECOND PARKING WITHIN A
 CIRCULAR. (THE FIRST PLANS ONLY SHOWED
 ONE HANDICAP PARKING), SECOND PARKING
 WAS NOT ON PLANS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-01 Cont ID  
Sent By mmclean Date 2005-09-01 Time 11:11 Rev Time 0.00
Received By mmclean Date 2005-09-01 Time 11:11 Sent To I
Notes
2005-09-01 00:00:00DENIED,
 1. NEED TO PROVIDE PLANS FOR THE
 REQUIRED 2 PARKING SPACE FOR STRUCTURE
 THAT IS OVER 1000SQ FT.
 OR
 2. REDUCE THE ADDITIONBY 50SQ FT.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720