| Plan Review Stops For Permit 05081247 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-10-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-10-26 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-10-26 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-09-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-09-12 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-09-12 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2006-09-12 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)SEE PREVIOUS TWO CORRECTION LISTS | | | IN REGARDS TO USE OF REMOVABLE SHUTTERS | | | AND RESULTING DELAYS IN PERMITTING.AS | | | ADVISED PREVIOUSLY, THE PLANS CANNOT BE | | | APPROVED SHOWING REMOVABLE SHUTTERS | | | UNTIL AND INSTALLATION PLAN HAS BEEN | | | SUBMITTED AND APPROVED BY BUILDING | | | OFFICIAL.THIS PLAN MAY BE SUBMITTED | | | SEPARATELY FROM THE RESUBMITTAL OF THE | | | PLANS FOR PERMIT. | | | | | | 2.)PLEASE KEEP THE IMPACT FEE RECEIPT | | | AND STAMPED PLANS IN THE PACKAGE WHEN | | | RESUBMITTING. | | | | | | 3.)SEE ELECTRIC REVIEW #2 IN REGARDS | | | TO A COFA REQUIRED FOR THE ENGINEER, MR. | | | GARGUILO, PROFESSIONAL ENGINEERS.I | | | HAVE CONFIRMED THIS REQUIREMENT WITH | | | FBPE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-03-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-03-06 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-03-06 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2006-03-06 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | FROM PREVIOUS REVIEW: | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED, FS713.13. | | | | | | MUST BE FILED PRIOR TO PERMIT PICKUP. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 | | | | | | THE PLANS WERE STAMPED.PLEASE PROVIDE | | | THE RECEIPT. | | | | | | 3.)ADDRESSED. | | | | | | 4.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVALS REQUIRED IN ADDITION TO THE | | | NOAS PROVIDED, FAC9B72. | | | WWW.FLORIDABUILDING.ORG. | | | | | | PRODUCT APPROVALS NOT SUBMITTED FOR THE | | | FRENCH DOOR.ANY PRODUCT APPROVALS NOT | | | REVIEWED PRIOR TO PERMIT ISSUANCE WILL | | | REQUIRE SEPARATE PERMITS. | | | | | | | | | 5.)IMPACT PROTECTION REQUIRED, | | | FBC1606.1.4.REMOVABLE SHUTTERS ON | | | COMMERCIAL PROPERTIES REQUIRE APPROVAL | | | BY THE BUILDING OFFICIAL.SEE ATTACHED | | | IMPLEMENTATION STANDARD, ITEM #13. | | | SUBMIT AN INSTALLATION PLAN.SEE ALSO | | | ATTACHED SCHEDULE FOR INSTALLATION OF | | | OPENING PROTECTIVE DEVICES AND | | | PROCEDURES #1. | | | | | | THE PLANS SHOW THE USE OF REMOVABLE | | | SHUTTERS.THE PERMIT CANNOT BE ISSUED | | | UNTIL THIS IS APPROVED BY THE BUILDING | | | OFFICIAL.SUBMIT A PLAN AS PREVIOUSLY | | | REQUESTED TO AVOID FURTHER DELAYS. | | | | | | 6.)ADDRESSED. | | | | | | 7.)ADDRESSED. | | | | | | 8.)ADDRESSED. | | | | | | 9.)THE ENTRY DOOR APPEARS TO HAVE A | | | STEP.ACCESSIBLE ENTRANCE/EGRESS IS | | | REQUIRED, FBC11-4.1.3(9), | | | 11-4.1.6(1)(B).PROVIDE FLOOR | | | ELEVATIONS, DOOR WIDTH. | | | | | | THE NOTE REGARDING A 5' LANDING AND A 5" | | | HIGH LANDING.THE 5" HIGH LANDING WOULD | | | BE CONSIDERED A STEP, NOT PART OF AN | | | ACCESSIBLE ROUTE. | | | | | | NEW COMMENT: | | | | | | 10.)SEE ATTACHED FS553.80(2)(B).A 4X | | | PLAN REVIEW FEE WILL BE CHARGED IF CODE | | | COMMENTS NOT PROPERLY ADDRESSED (ITEM #9 | | | ABOVE). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-10-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-10-14 |
Time |
14:13 |
Rev Time |
1.50 |
| Received By |
shill |
Date |
2005-10-14 |
Time |
13:37 |
Sent To |
PC |
|
| Notes |
| 2005-10-14 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED, FS713.13. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 | | | | | | 3.)ADDITIONAL FEES DUE (RADON, FIRE | | | FEE), SEE ATTACHED. | | | | | | 4.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVALS REQUIRED IN ADDITION TO THE | | | NOAS PROVIDED, FAC9B72. | | | WWW.FLORIDABUILDING.ORG. | | | | | | 5.)IMPACT PROTECTION REQUIRED, | | | FBC1606.1.4.REMOVABLE SHUTTERS ON | | | COMMERCIAL PROPERTIES REQUIRE APPROVAL | | | BY THE BUILDING OFFICIAL.SEE ATTACHED | | | IMPLEMENTATION STANDARD, ITEM #13. | | | SUBMIT AN INSTALLATION PLAN.SEE ALSO | | | ATTACHED SCHEDULE FOR INSTALLATION OF | | | OPENING PROTECTIVE DEVICES AND | | | PROCEDURES #1. | | | | | | 6.)THE SLAB IS TO BE 4" ABOVE GRADE, | | | FBC*1804.1.7. | | | | | | 7.)WATERSTOP OF 1.5 INCH REQUIRED, | | | FBC*2111.1.9. | | | | | | 8.)BOTTOM OF FOOTING TO BE 12" BELOW | | | GRADE, FBC1804.1.3. | | | | | | 9.)THE ENTRY DOOR APPEARS TO HAVE A | | | STEP.ACCESSIBLE ENTRANCE/EGRESS IS | | | REQUIRED, FBC11-4.1.3(9), | | | 11-4.1.6(1)(B).PROVIDE FLOOR | | | ELEVATIONS, DOOR WIDTH. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-10-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-19 |
Time |
19:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-19 |
Time |
19:29 |
Sent To |
|
|
| Notes |
| 2006-10-19 19:40:52 | TITLE BLOCKS CORRECTED. | | | ELECTRICAL PLANS OK, AND STAMPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-09-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-09 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-09 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2006-09-09 00:00:00 | ** UNSAT ** | | | | | | **** PLEASE KNOW, THE E-1 SHEET WAS | | | STAMPED AS OK ONLY. | | | | | | 1) NOTE: PLEASE SEE THE OTHER SHEETS | | | ARE STILL MISSING THE REQUIRED | | | "CERTIFICATE OF AUTHORIZATION" NUMBER | | | FOR ENGINEERING FIRM AS REQUESTED AND | | | REQUIRED ON PREVIOUS REVIEW(S). | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE | | | 61G15-23.002 AND FS 471.023, IF OTHER | | | THAN AN "INDIVIDUAL", THEN A CA NUMBER | | | IS REQUIRED. PLEASE KNOW PLANS ARE BEING | | | RETAINED AS CONTACT WITH THE FLORIDA | | | BOARD OF PROFESSIONAL ENGINEERS AND | | | LEGAL COUNSEL TO THE BOARDWILL TAKE | | | PLACE, PLANS RETAINED WILL BE TURNED | | | OVER. | | | THIS WAS THE SAME AS ALL PREVIOUSLY | | | SUBMITTED PLANS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-02-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-02-28 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-02-28 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2006-02-28 00:00:00 | ********** UNSAT 2ND REVIEW ******** | | | | | | ** PLEASE SOME NOTES FROM PERVIOUS | | | REVIEW STILL NEED TO BE ADDRESSED. | | | PLEASE SEE NOTES BELOW ARE TAKEN | | | DIRECTLY FROM THE PREVIOUS REVIEW WITH | | | ADDED NOTING FOR CLARIFICATION. | | | PLEASE SEE NEW NOTES FOR DESIGNERS. | | | | | | | | | 1)NOTE: NOTE #1 NO, PLEASE SHOW ALL | | | CIRCUITING, SOME NEW CIRCUITS ARE SHOWN | | | , HOWEVER THERE ARE STILL SOME MISSING. | | | PLEASE SEE 700.12E FOR CIRCUITING OF EM/ | | | EXT LTS. | | | THE BRANCH CIRCUIT FEEDING THE LOCAL | | | BRANCH CIRCUIT LIGHTING SHALL ALSO FEED | | | THE EM / EXT LTS IN THAT AREA. | | | | | | ** PLEASE SHOW NEW CIRCUITING ON PLANS | | | AND CORRELATE WITH EXISTING PANEL | | | SCHEDULE TO BE SUBMITTED. | | | 215.5 | | | | | | 2)NOTE: NOTE #2, NO, PLEASE SEE THE LOAD | | | CALCULATIONS FROM PREVIOOUS PLANS WERE | | | REMOVED FROM NEW SHEETS AND ONLY | | | CONNECTED LOADS? ARE SHOWN. PLEASE KNOW, | | | EVEN SHOWING SOME OF THESE LOADS AS | | | CONNECTED LOADS, STILL DO NOT CORRELATE | | | WITH THE MIN LOADS REQUIRED PER NEC. | | | PLEASE SEE 220.3,220.10,220.13, ETC AND | | | CONTINUOUS LOADS PER 215.3,230.42 ETC. | | | | | | ** PLEASE SEE NEC 220.13 FOR KNOWN | | | RECEPT LOADS FOR LOAD CALCS. | | | PLEASE SHOW ALL CONTINUOUS LOADS AT | | | 125%, 215.3,230.42 ETC. | | | PLEASE SEE ANY DEDICATED RECEPT LAODS | | | MAY BE OF A HIGHER VALUE. | | | | | | 3)NOTE: NOTE #3 OK, PLANS INDICATE THE | | | DOOR BEING LOCATED INSIDE FOR THE | | | ELEVATION AS SHOWN? | | | RESPONSE LTR MENTIOSN THE REVISED | | | DETAIL. | | | | | | ** PLEASE CORRELATE SEC AA FOR | | | ELEVATION AND FLR PLANS. PLEASE SEE BLDG | | | REVIEW COMMENTS AS ONE SHOWS A NEW | | | FRENCH DOOR AND THE OTHER SHOWS A | | | WINDOW? | | | IF THERE WILL BE AN EGRESS DOOR, PLEASE | | | INCLUDE ANY ELECTRICAL REQUIRED. | | | (EXIT, LT)? | | | | | | 4)NOTE: PLEASE SEE MISSING CERTIFICATE | | | OF AUTHORIZATION FOR ENGINEERING FIRM AS | | | SHOWN ON PLANS. PLEASE SEE FAC | | | 61G15-23.002, FS 471.023. | | | THIS IS REQUIRED FOR ALL TRADES AND FOR | | | ALL SHEETS CONTAINING THE TITLE BLOCK | | | FOR SAID ENGINEERING FIRM. | | | | | | 5)NOTE: PLEASE SEE "SEALS RULE" FROM THE | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS | | | WHICH PER RULING DATE FEB 5, 2004 , | | | 61G15-23.001REQUIRED ALL SEALS WITH | | | THE WORDING OF "CERTIFICATE" TO BE | | | CHANGED TO THE USE OF "LICENSE" IN SAID | | | SEAL. PLEASE KNOW, AN EXTENSION WAS | | | GIVEN TO THE DATE OF DEC 31ST, 2005. | | | PLEASE KNOW AS OF JAN 1ST, 2006 ALL | | | SEALS SHALL ONLY CONTAIN THE WORDING OF | | | "LICENSE". PLEASE ADJUST ACCORDINGLY. | | | | | | 6)NOTE: PLEASE SEEA NOTICE IS GIVEN AT | | | THIS TIME WITH RESPECT TO THE DESIGN | | | PROFESSIONAL(S) TO FS 553.80(2)(B) AND | | | REPEAT COMMENTS FOR CODE COMPLIANCE. | | | THIS IS ONLY A NOTICE GIVEN AT THIS | | | TIME. | | | PLEASE BE SURE TO ADDRESS ALL COMMETS. | | | | | | | | | **PLEASE SEE ANY COMMENTS FROM OTHER | | | TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-09-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-02 |
Time |
15:58 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2005-09-02 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2005-09-02 00:00:00 | ********* UNSAT ******** | | | | | | PLEASE SEE PLANS ARE COMING BACK FOR | | | OTHER COMMENTS, PLEASE MAKE THE ABOVE | | | CORRECTIONS AT THIS TIME. | | | | | | 1)NOTE: PLEASE SHOW NEW CIRCUITING ON | | | PLANS AND CORRELATE WITH EXISTING PANEL | | | SCHEDULE TO BE SUBMITTED. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE NEC 220.13 FOR KNOWN | | | RECEPT LOADS FOR LOAD CALCS. | | | PLEASE SHOW ALL CONTINUOUS LOADS AT | | | 125%, | | | 215.3,230.42 ETC. | | | PLEASE SEE ANY DEDICATED RECEPT LAODS | | | MAY BE OF A HIGHER VALUE. | | | | | | 3)NOTE: PLEASE CORRELATE SEC AA FOR | | | ELEVATION AND FLR PLANS. PLEASE SEE BLDG | | | REVIEW COMMENTS AS ONE SHOWS A NEW | | | FRENCH DOOR AND THE OTHER SHOWS A | | | WINDOW? | | | IF THERE WILL BE AN EGRESS DOOR, PLEASE | | | INCLUDE ANY ELECTRICAL REQUIRED. | | | (EXIT, LT)? | | | | | | PLEASE SEE ANY COMMENTS FROM OTHER | | | TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-12-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-14 |
Time |
12:32 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-14 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2006-12-14 12:37:24 | *****APPROVED****** | | | | | | | | | | | | | | | PLANSSTAMPED, SIGNED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-03-03 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-03-03 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-03-03 |
Time |
11:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-09-09 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-09-09 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-09-09 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2005-09-09 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE ELECTRICAL REVIEW COMMENT | | | #3. PLEASE CLARIFY WHAT IS PROPOSED FOR | | | REFERENCED WALL. IF DOOR IS PLANNED, | | | PLEASE SHOW APPROPRIATE EXIT MARKING. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-04 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-04 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2006-10-19 16:12:06 | TO "COMM" BD#3 | | 2006-10-04 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-09-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-28 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-28 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2006-09-05 00:00:00 | TO "COMM" BD#42 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-01-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-27 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-27 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2006-02-22 00:00:00 | TO "COMM" BD#58 | | 2006-01-27 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-01 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-01 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2005-09-01 00:00:00 | TO "COMM" BD#25 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-10-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-10-14 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-08-19 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2005-08-19 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2006-10-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-19 |
Time |
19:37 |
Rev Time |
|
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2006-10-19 19:38:05 | NO MECH IN SCOPE PF WORK, NO MECH PERMIT APPLIED FOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2006-10-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-19 |
Time |
19:37 |
Rev Time |
|
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2006-10-19 19:37:37 | NO PLUMING WORK IN SCOPE, NO PLUMBING PERMIT APPLIED | | | FOR. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2006-10-24 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-10-24 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-10-24 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2006-10-24 17:39:30 | NOTE: SEE THE ATTACHED NOTE FROM DEAN | | | LAUDERMILK APPROVING THE OFF STREET | | | PARKING. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2006-09-19 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-09-19 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-09-19 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2006-09-19 00:00:00 | NOTE: SEE THE ATTACHED NOTE FROM DEAN | | | LAUDERMILK APPROVING THE OFF STREET | | | PARKING. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-02-27 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-02-27 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-02-23 |
Time |
17:56 |
Sent To |
|
|
| Notes |
| 2006-02-27 00:00:00 | DENIED, | | | 1. NEED TO PROVIDE A LETTER SIGNED BY | | | THE ENGINEERING DEPT WITH THE CITY OF | | | WEST PALM BEACH, APPROVING THE ON STREET | | | PARKING (ON 26TH STREET) | | | 2. THE 2ND RESUB SHOWS TWO EXISTING | | | DRIVEWAY WITHIN THE CIRCULAR DRIVE. | | | CANNOT HAVE THE SECOND PARKING WITHIN A | | | CIRCULAR. (THE FIRST PLANS ONLY SHOWED | | | ONE HANDICAP PARKING), SECOND PARKING | | | WAS NOT ON PLANS. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-09-01 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-09-01 |
Time |
11:11 |
Sent To |
I |
|
| Notes |
| 2005-09-01 00:00:00 | DENIED, | | | 1. NEED TO PROVIDE PLANS FOR THE | | | REQUIRED 2 PARKING SPACE FOR STRUCTURE | | | THAT IS OVER 1000SQ FT. | | | OR | | | 2. REDUCE THE ADDITIONBY 50SQ FT. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|