| 2005-08-19 00:00:00 | ********** UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SHOW GROUNDING ATTACHMENT |
| | AT SECONDARY SIDE OF TRANSFORMER FOR THE |
| | SEPRATELY DERIVED SYSTE. |
| | 250.30,250.24, 250.122, 250.6 SIZING OF |
| | GROUNDING SHALL BE PER 250.66 |
| | |
| | 2)NOTE: PLEASE PROVIDE INFORMATION FOR |
| | LOAD OF NEW CHILLER. |
| | PLEASE CLARIFY IF LOAD IS THE SAME AS |
| | PREVIOUS OR IF THERE IS ANY LOAD |
| | INCREASE. 215.5,220 |
| | PLEASE BE SURE LARGEST MOTOR IS 125%. |
| | 215.3,230.42 ETC. |
| | |
| | 3)NOTE: PLEASE INCLUDED NEW PROPOSED LOW |
| | VOLTAGE WORK BEING DONE. |
| | |
| | 4)NOTE: PLEASE SEE 300.19(A) FOR |
| | POSSIBLE "PULL-BOXES" AND VERTICAL |
| | SUPPORTS REQUIRED FOR CONDUCTORS. |
| | |
| | 5)NOTE: PLEASE SHOW ANY EXISITNG AS |
| | EXISITNG. IT IS THIS OFFICES |
| | UNDERSTANDING THE CONDUCTORS, AND SOME |
| | DISCONNECTS ARE EXISTING, HOWEVER PLANS |
| | INDICATE THESE AS NEW? |
| | |
| | 6)NOTE: PLEASE SHOW THE LOCATION OF THE |
| | NEW TRANSFORMER IN BLDG. PLEASE SEE |
| | 450.13, 450.9,450.21 ETC FOR MIN RATINGS |
| | OF ROOM, CLEARENCES ETC. |
| | |
| | 7)NOTE: PLEASE BE SURE PLANS ARE SIGNED |
| | BY THE ENGINEER OF RECORD AS ON FILE. |
| | PLEASE SEE FS 471.025 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |