Plan Review Details - Permit 05081141
Plan Review Stops For Permit 05081141
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-06 Cont ID  
Sent By rmcdouga Date 2005-09-06 Time 17:59 Rev Time 0.00
Received By rmcdouga Date 2005-09-06 Time 17:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-22 Cont ID  
Sent By rmcdouga Date 2005-08-22 Time 08:11 Rev Time 0.00
Received By rmcdouga Date 2005-08-22 Time 07:24 Sent To  
Notes
2005-08-22 00:00:00DENIED
  
 1) THE INTERIOR NON-LOAD BEARING WALL
 DETAIL ON SHEET ONE IS INCORRECT. FBC
 609.2.1 TYPE I AND TYPE II CONSTRUCTION.
 PARTITIONS SHALL BE CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIALS.
  
 2) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN PER
 CITY AMENDMENTS TO FBC 104.2.1.
  
 3) THE CONTRACTOR IS A CBC AND IS
 LIMITED TO WORK THAT WILL NOT AFFECT THE
 STRUCTURAL MEMBERS OF THE BUILDING.
 FS 489.105
  
 4) FBC 707.1 COMBUSTIBLES SHALL NOT BE
 PERMITTED IN CONCEALED SPACES OF TYPES
 I, II, OR IV CONSTRUCTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 13:19 Rev Time 0.20
Received By dpalmer Date 2005-09-03 Time 13:19 Sent To  
Notes
2005-09-03 00:00:00REDLINED 210.8A7
 PANEL SCHEDULE ATTACHED FOR REFERENCE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By dpalmer Date 2005-08-23 Time 13:43 Rev Time 0.25
Received By dpalmer Date 2005-08-23 Time 13:43 Sent To  
Notes
2005-08-23 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE INCLUDE CIRCUITS TO
 EXISTING PANELS. DEDICATED? ETC.
 PLEASE ALSO SHOW ALL RECEPTS W/IN 6'S OF
 WET BARS AS GFI/GFI PROTECTED.
 210.8A7
  
 2)NOTE: PLEASE SEE FBC 104.2.1, WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS AND
 DESIGN.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFROMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-08 Cont ID  
Sent By mwennerg Date 2005-09-08 Time 10:02 Rev Time 0.00
Received By mwennerg Date 2005-09-08 Time 10:02 Sent To  
Notes
2005-09-08 00:00:00PLEASE SEE PLANS ARE RED LINED REGARDING
 INTERIOR FINISH CLASSIFICATION FOR WALLS
 AND CEILING APPLICABLE TO THIS PROJECT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-22 Cont ID  
Sent By nmccray Date 2005-08-22 Time 15:29 Rev Time 0.00
Received By nmccray Date 2005-08-22 Time 15:24 Sent To  
Notes
2005-08-22 00:00:00DENIED:
  
 SHALL COMPLY WITH NFPA 101 LIFE SAFETY
 CODE 2003 EDITION
  
 1) INTERIOR WALLS AND CEILINGS FINISH
 SHALL COMPLY WITH SECTION 10.2 INTERIOR
 FINISH SHALL BE CLASS A, CLASS B, OR
 CLASS C.
  
 2) INTERIOR FLOOR FINISH SHALL COMPLY
 WITH 10.2.7.1 OR 10.2.7.2 AS APPLICABLE.
  
 3) DOES THIS INTERIOR ALTERATIONS
 AFFECTS THE FIRE SPRINKLER SYSTEM? IF SO
 SEPARATE PERMIT APPLICATION ALONG WITH
 SHOP DRAWINGS ARE REQUIRED FOR REMODEL.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 13:17 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 13:17 Sent To  
Notes
2005-09-02 00:00:00TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-08-23 Time   Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 10:34 Sent To  
Notes
2005-08-19 00:00:00TO "BOB"#8

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-14 Cont ID  
Sent By jleech Date 2005-09-14 Time 10:47 Rev Time 0.50
Received By jleech Date 2005-09-14 Time 10:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-20 Cont ID  
Sent By pschmitz Date 2005-08-20 Time 06:09 Rev Time 0.00
Received By pschmitz Date 2005-08-20 Time 06:09 Sent To B
Notes
2005-08-20 00:00:00PAUL SCHMITZ, PLUMBING.
 PLAN REVIEW EXAMINER
 561-805-6692 [email protected]
  
 FBC 2001
 DENIED
 SEC 104.2.1 ISOMETRIC DRAWING:
 DRAIN,WASTE, VENT AND WATER PIPING.
 LABEL AND SHOW LOCATION OF BAR SINK.
 END OF COMMENTS