Plan Review Details - Permit 05081035
Plan Review Stops For Permit 05081035
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-09-07 Cont ID  
Sent By shill Date 2005-09-07 Time 11:49 Rev Time 0.50
Received By shill Date 2005-09-07 Time 11:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-04-17 Cont ID  
Sent By dpalmer Date 2006-04-17 Time 08:59 Rev Time 0.00
Received By dpalmer Date 2006-04-17 Time 08:55 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-03-16 Cont ID  
Sent By dpalmer Date 2006-03-16 Time 17:12 Rev Time 0.00
Received By dpalmer Date 2006-03-16 Time 17:07 Sent To  
Notes
2006-03-16 00:00:00********** UNSAT **************
  
  
 1)NOTE: PLEASE SEE IT IS BEING NOTED BY
 OUR FEILD INSPECTORS THAT THE ADDRESS
 FOR THIS SCOPE OF WORK IS INCORRECT.
 PLEASE SEE PERMIT APPLICATION AND PCN
 ORIGINAL SET FORTH ON PERMIT APPLICATION
 SUBMITTED WAS FOR 1300 N FLAGLER DR.
 PLEASE VERIFY IF THIS WORK IS AT THIS
 ADDRESS.
 PLEASE ALSO INCLUDE JOBSITE ADDRESS ON
 PLANS AS REQUIRED PER FAC 61G15-23.002
  
 2)NOTE: PLEASE SEE PREVIOUS ELECTRICAL
 REVIEW WAS PASSEDON THE CONDITION THAT
 THE CORRECT VALUATION FOR SCOPE OF WORK
 BE INCREASED FOR ALL LABOR AND MATERIALS
 BEFORE ISSUING OF PERMIT BY THE
 CONTRACTOR. THIS WAS NOT DONE.
 PLEASE SEE FBC 104.6.5 AS ADOPTED CITY
 WIDE ADMINISTRATIVE CODE.
 THIS NOTE WAS TAKEN DIRECTLY FROM
 PREVIOUS REVIEW.
  
 **VALUE FOR SCOPE OF WORK TO INCLUDE ALL
 LABOR, EQUIPMENT AND MATERIALS, EVEN IF
 EQUIPMENT IS OWNER SUPPLIED.
 FBC 104.6.5 ADMINISTRATIVE AMENDMENTS.
  
 3)NOTE: PLEASE SEE PLANS MUST BE
 RE-SEALED AS THE SEAL AS SHOWN IS NO
 LONGER ACCEPTABLE AS PUBLIC RECORD FOR
 THE FLORIDA BOARD OF PROFESSINAL
 ENGINEER'S. PLEASE SEE FAC 61G15-23.001
 WHICH IN FEB 04 CHANGED TO NOW REQUIRE
 ALL SEALS TO CONTAIN THE WORDING OF
 "LICENSE" AND COULD NO LONGER USE
 "CERTIFICATE". PLEASE KNOW, AN EXTENSION
 WAS GRANTED TO THE DATE OF 12/31/05 TO
 GIVE ALL ENGINEERS 2 YRS TO OBTAIN NEW
 SEALS. WE CAN NO LONGER ACCEPT OLD
 SEALS.
  
 PLEASE UP VALUE, AND PLEASE SUBMIT
 REVISED CORRECTED SHEETS FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
 PLEASE KNOW, PERMIT MAY BE REVOKED IF
 FIRST TWO COMMENTS ARE NOT ADDRESSED IN
 A TIMELY FASHION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-09-01 Cont ID  
Sent By dpalmer Date 2005-09-01 Time 17:11 Rev Time 1.00
Received By dpalmer Date 2005-08-31 Time 22:03 Sent To  
Notes
2005-09-01 00:00:00VALUE FOR SCOPE OF WORK TO INCLUDE ALL
 LABOR, EQUIPMENT AND MATERIALS, EVEN IF
 EQUIPMENT IS OWNER SUPPLIED.
 FBC 104.6.5 ADMINISTRATIVE AMENDMENTS.
2005-08-31 00:00:00IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-16 Cont ID  
Sent By mawillia Date 2006-05-16 Time 15:11 Rev Time 0.00
Received By mawillia Date 2006-05-16 Time 15:11 Sent To  
Notes
2006-05-16 00:00:00REVISION DATED 02/08/2006

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-09-12 Cont ID  
Sent By mcarsill Date 2005-09-12 Time 11:27 Rev Time 0.00
Received By mcarsill Date 2005-09-12 Time 11:27 Sent To  
Notes
2005-09-12 00:00:001. WRONG LIFE SAFETY CODE REFERENCED.
 SHOULE READ 2003 EDITION INSTEAD OF
 2000 EDITION.
  
 2.
 1. WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 2003 EDITION INSTEAD OF
 THE 2000 EDITION.
  
 2. SEPERATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE ALARM SYSTEM REMODEL.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
  
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-04-24 Cont ID  
Sent By adarroug Date 2006-04-24 Time 09:13 Rev Time 0.00
Received By adarroug Date 2006-04-24 Time 09:13 Sent To FIRE
Notes
2006-04-24 00:00:00TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-15 Cont ID  
Sent By adarroug Date 2006-04-15 Time 15:06 Rev Time 0.00
Received By adarroug Date 2006-04-15 Time 15:06 Sent To M
Notes
2006-04-15 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-15 Cont ID  
Sent By adarroug Date 2006-04-15 Time 15:04 Rev Time 0.00
Received By adarroug Date 2006-04-15 Time 15:04 Sent To E
Notes
2006-04-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-06 Cont ID  
Sent By adarroug Date 2006-04-06 Time 15:52 Rev Time 0.00
Received By adarroug Date 2006-04-06 Time 15:52 Sent To M
Notes
2006-04-06 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 17:44 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 17:44 Sent To  
Notes
2006-03-13 00:00:00TO "COMM" BD#55
2006-02-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 11:42 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 11:42 Sent To P
Notes
2005-09-29 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-20 Cont ID  
Sent By pkrauss Date 2005-09-20 Time 07:01 Rev Time 0.00
Received By pkrauss Date 2005-08-17 Time 15:29 Sent To  
Notes
2005-08-19 00:00:00TO "COMM" BD#33
2005-08-17 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-04-17 Cont ID  
Sent By tgordon Date 2006-04-17 Time 09:29 Rev Time 0.30
Received By tgordon Date 2006-04-17 Time 09:29 Sent To  
Notes
2006-04-17 00:00:00*** PROVISO ***
 1) PLEASE NOTE THE LOCATION OF CU-1 &
 CH-1 ARE LOCATED IN A FLOOD ZONE
 CLASSIFIED 'A5'. EQUIPMENT LOCATED IN
 THESE AREAS SHELL BE PLACED ABOVED THE
 FLOOD ELEVATION OR PROTECTED IN A MANNER
 TO PREVENT WATER FROM ENTERING OR
 ACCULMULATING WITHIN THE EQUIPMENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-04-07 Cont ID  
Sent By tgordon Date 2006-04-07 Time 14:35 Rev Time 0.45
Received By tgordon Date 2006-04-07 Time 14:35 Sent To  
Notes
2006-04-07 00:00:00*** DENIED ***
 1) WAVE GUIDE THRU RF SHIELDING IS
 MISSING FROM DUCTS IN MRI ROOM #2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-04-05 Cont ID  
Sent By pkrauss Date 2006-04-05 Time 07:23 Rev Time 0.00
Received By pkrauss Date 2006-04-05 Time 07:23 Sent To  
Notes
2006-04-05 00:00:00PROVISO:
 PLEASE NOTE THE LOCATION OF THE CU-1 &
 CH-1 ARE LOCATED IN THE FLOOD ZONE
 CLASSIFIED 'A5'.EQUIPMENT LOCATED IN
 THESE AREAS SHALL BE PLACED ABOVE THE
 FLOOD ELEVATION OR PROTECTED IN A MANNER
 TO PREVENT WATER FROM ENTERING OR
 ACCULMULATING WITHIN THE EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-09-15 Cont ID  
Sent By pkrauss Date 2005-09-15 Time 09:48 Rev Time 1.45
Received By pkrauss Date 2005-09-15 Time 07:40 Sent To Z
Notes
2005-09-15 00:00:00PROVISO:
 PLEASE NOTE THE LOCATION OF THE CU-1 &
 CH-1 ARE LOCATED IN THE FLOOD ZONE
 CLASSIFIED 'AE'.EQUIPMENT LOCATED IN
 THESE AREAS SHALL BE PLACED ABOVE THE
 FLOOD ELEVATION OR PROTECTED IN A MANNER
 TO PREVENT WATER FROM ENTERING OR
 ACCULMULATING WITHIN THE EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-04-17 Cont ID  
Sent By jleech Date 2006-04-17 Time 12:45 Rev Time 0.00
Received By jleech Date 2006-04-17 Time 12:45 Sent To  
Notes
2006-04-17 00:00:00REVISED PLUMBING PLAN P-5 OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-10-15 Cont ID  
Sent By kstevens Date 2005-10-15 Time 16:33 Rev Time 0.80
Received By kstevens Date 2005-10-15 Time 16:33 Sent To  
Notes
2005-10-15 00:00:00PASSED/PROVISO
  
 BACKFLOW PREVENTER SHALL BE INSTALLED
 MAXIMUM 4' ABOVE THE FLOOR FOR SERVICE
 AND TESTING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-09-10 Cont ID  
Sent By kstevens Date 2005-09-10 Time 21:50 Rev Time 1.25
Received By kstevens Date 2005-09-10 Time 21:50 Sent To  
Notes
2005-09-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P5.1 INDICATES THE REMOVAL OF THE
 DRINKING FOUNTAIN. MINIMUM FACILITIES
 REQUIRE DRINKING FOUNTAINS FOR THIS
 OCCUPANCY PER TABLE 403.1. PLEASE SHOW
 THE SQUARE FOOTAGE OF THE BUILDING AND
 INDICATE THE NUMBER OF DRINKING
 FOUNTAINS EXISTING IN THE BUILDING TO
 SHOW COMPLIANCE WITH MINIMUM FIXTURE
 FACILITIES.
 2. PER SECTION 104.3.1.1 A SANITARY AND
 A WATER RISER DIAGRAM ARE REQUIRED FOR
 PLAN REVIEW.
 3. INDIRECT WASTE SHALL DRAIN TO A FLOOR
 SINK OR A HUB DRAIN PER SECTIONS 802.3
 AND 802.3.2. FLOOR DRAINS ARE NOT
 APPROVED FOR INDIRECT WASTE.
 4. ALL DEVICES, APPURTENANCES,
 APPLIANCES AND APPARATUS INTENDED TO
 SERVE SOME SPECIAL FUNCTION, SUCH AS
 STERILIZATION, DISTILLATION, PROCESSING,
 COOLING, OR STORAGE OF ICE OR FOODS AND
 THAT CONNECT TO THE WATER SUPPLY SYSTEM,
 SHALL BE PROVIDED WITH PROTECTION
 AGAINST BACKFLOW AND CONTAMINATION OF
 THE WATER SUPPLY SYSTEM. SECTION 608.3.
 SHT P5.1 INDICATES WATER TO THE SHIELD
 COOLER AND TO THE HUMIDIFIER. INDICATE
 METHOD OF BACKFLOW PROTECTION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]