Plan Review Details - Permit 05081029
Plan Review Stops For Permit 05081029
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-03-23 Cont ID  
Sent By lursu Date 2006-03-23 Time 11:14 Rev Time 0.00
Received By lursu Date 2006-03-23 Time 11:13 Sent To  
Notes
2006-03-23 00:00:00NEW ADDRESS WAS ASSIGNED TO BLDG A AS
 EXT #0001 : 3810 GEORGIA AVE.
2006-03-22 00:00:00NEEDS ADDRESSING AS THERE ARE TWO
 SEPARATE BLGS ON THE SMAE SITE.
 PLEASE ALSO SEE BLDG UNDER 05011550

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-03-21 Cont ID  
Sent By lmartine Date 2007-03-21 Time 17:44 Rev Time 0.00
Received By lmartine Date 2007-03-21 Time 17:44 Sent To  
Notes
2007-03-21 17:45:452/23/07 OFFICE WALL REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-01-23 Cont ID  
Sent By rnuquist Date 2007-01-23 Time 14:41 Rev Time 0.00
Received By rnuquist Date 2007-01-23 Time 14:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-09-01 Cont ID  
Sent By alange Date 2006-09-01 Time 15:39 Rev Time 2.00
Received By alange Date 2006-09-01 Time 15:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-07-24 Cont ID  
Sent By alange Date 2006-07-24 Time 09:41 Rev Time 1.50
Received By alange Date 2006-07-24 Time 09:41 Sent To  
Notes
2006-07-24 00:00:00DENIED
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR ROOFING.
  
 4.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTTACHED.
  
 NOTE:PLEASE DO NOT ATTACH PRODUCT
 APPROVALS TO PLANS.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-14 Cont ID  
Sent By alange Date 2006-04-14 Time 08:28 Rev Time 2.00
Received By alange Date 2006-04-14 Time 08:28 Sent To  
Notes
2006-04-14 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR ROOFING AND STORE FRONT.
  
 4.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 5.PERMIT VALUATION IS LOW AND HAS BEEN
 ADJUST ACCORDING TO SBCCI BUILDING
 VALUATION DATA.
 324 SQ.FT. BUS. X $78.00 = $25,272
 2376 SQ.FT. MERCH. X $56.00 = $133,056
 2700 SQ.FT. WH X $31.00 = $83,700
 REVISED PERMIT VALUATION $242,028.00
 FBC 104.6.5 WPB AMMENDMENTS
  
 NEW COMMENT:
 A.ALL PAGES SHALL BE SIGNED AND SEALED
 BY THE DESIGNER OF RECORD. FBC 104.2.2
 WPB AMMENDMENTS.
  
 B.CHANGES TO PLANS SHALL NOT BE CUT
 AND PASTED OR HAND WRITTEN OR WHITED
 OUT. MAKE CHANGES AND INSERT NEW SIGNED
 AND SEAL PAGES AS NECESSARY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-07 Cont ID  
Sent By shill Date 2005-12-07 Time 03:30 Rev Time 2.50
Received By alange Date 2005-12-07 Time 12:58 Sent To  
Notes
2005-12-07 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR ROOFING AND STORE FRONT.
  
 4.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 5.PERMIT VALUATION IS LOW AND WILL
 ADJUSTED WHEN BUILDING TYPE IS SELECTED
 BY DESIGNER.
  
 6.SHOW TRAVEL DISTANCE AND OCCUPANT
 LOAD PER FBC CHAPTER 10.
  
 7.SELECT THE CONSTRUCTION TYPE PER FBC
 601.2.1
  
 8.EGRESSS DOOR LOCKS COMPLYING WITH
 FBC 1012.1.7 AND 1012.1.8
  
 9.SHOW HOW ACCESSABILITY WILL BE
 ACHIEVED AT DOORWAYS AND PATH TO PARKING
 AREA. FBC CH.11
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-27 Cont ID  
Sent By dpalmer Date 2007-02-27 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2007-02-27 Time 13:02 Sent To PC
Notes
2007-02-27 13:02:23REVISED SERVICE RISER

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 17:52 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 17:15 Sent To  
Notes
2006-07-15 00:00:00REDLINED ****
  
 1) PLACED ADDRESS OF 3810 ON MANY SHEETS
 AS SOME MOST STILL INDICATED 3802 AND
 SOME DI NOT INDICATE ADDRESS.
  
  
 2) AIC RATINGS OF MAINS SHALL BE 22,000
 MIN PER FAULT CURRENT CALCULATIONS ON
 PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-24 Cont ID  
Sent By dpalmer Date 2006-04-24 Time 20:39 Rev Time 0.00
Received By dpalmer Date 2006-04-24 Time 20:18 Sent To  
Notes
2006-04-24 00:00:00** UNSAT **
  
 1)NOTE: PLEASE SEE NOTE #1 FROM
 PREVOUS REVIEW.
 THIS IS NOTED AS PENDING FROM FPL.
 PLEASE KNOW, AIC RATINGS CAN BE ADJUSTED
 AT A LATER DATE? PLEASE VERIFY DISTANCE
 AND KVA RATING OF EXISTING TRANSFORMER
 TO VERIFY OR COME TO A CONCLUSION BASED
 ON MIN CALCS.
 IF KVA RATING OF TRANSFORMER, DISTANCE,
 AND CONDUCTOR SIZES ARE KNOWN, THE
 RATING CAN BE FIGURED.
  
 2) NOTE: PLEASE SEE THAT A NEW ADDRESS
 OF 3810 WAS ISSUED BY THE CITY
 ADDRESSING DEPT AND PLANS SHOULD REFLECT
 NEW ADDRESS AS REQUIRED PER FAC
 61G1-16.004.
 PLEASE ADJUST FOR ALL SHEETS AND ALL
 REFERENCES TO THIS PERMIT.
  
 ** PLEASE KNOW, PLANS ARE COMING BACK
 FOR COMMENTS BY OTHER REVIEWER(S).
 PLEASE SUBMIT.
  
 ALL OTHER COMMENTS WERE ADDRESSED AND
 RESPONSES WERE ADDRESSED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-31 Cont ID  
Sent By dpalmer Date 2005-08-31 Time 07:30 Rev Time 0.80
Received By dpalmer Date 2005-08-31 Time 07:30 Sent To  
Notes
2005-08-31 00:00:00*********** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE AIC RATING IS INDICATED FOR
 SUB PANEL, HOWEVER NOT FOR MAIN.
  
 2)NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.
 PLEASE SEE A COUPLE MISSING AND REDLINED
 ON PLANS.
 215.5
  
 3)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS WHICH REQUIRES
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 4)NOTE: PLEASE SEE 210.62,220.12, FOR
 SHOW WINDOW RECEPT REQUIREMENTS. PLEASE
 SEE NO OTHER ELECTRICLA CAN BE ON THIS
 CIRCUIT. (PLEASE SEE NEXT COMMENT).
 PLEASE SEE WINDOW ON EAST ELEVATION
 WHICH DO NOT INDICATE AN RECEPT.
  
 5)NOTE: PLEASE SEE 600.5, WHICH REQUIRES
 A DEDICATED CIRCUIT FOR SIGNAGE.
  
 6)NOTE: PLEASE SEE POSSIBLE FIRE AND
 BLDG REVIEW COMMENTS. THERE SEEMS TO BE
 AN EGRESS/EXIT DOOR WHICH EXITS INTO AN
 AREA WHERE ELECTRICAL PLANS INDICATE
 MOTORIZED "DOORS"? PLEASE VERIFY THIS.
  
 7)NOTE: PLEASE SEE FAC 61G15-23.002,
 WHICH REQUIURES THE PRINTED NAME OF
 ENGINEER ON TITLE BLOCK.
  
  
 PLEASE SEE POSSIBLE COMMENS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABVOE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-08-24 Cont ID  
Sent By mamini Date 2005-08-24 Time 10:39 Rev Time 0.50
Received By mamini Date 2005-08-24 Time 10:39 Sent To  
Notes
2005-08-24 00:00:00PASSED WITH PROVISOS:
  
 1. PLEASE NOTE THAT, THE HANDICAPPED
 PARKING DETAIL AS SHOWN IS NOT THE
 LATEST RECOMMENDED BY THE ADA, SEE
 ATTACHED.
 2. REGULAR PARKING STALLS MUST BE
 PAINTED WITH DOUBLE 4" WIDE WHITE LINES.
 3. WOODEN UTILITY POLES AS SHOWN AT
 DRIVEWAY APPROACH AND NEAR THE PROPOSED
 DUMPSTER ENCLOSURE MUST BE RELOCATED,IT
 IS THE CONTRACTOR'RESPONSIBILITY TO
 CONTACT THE PROPER OWNER FOR THE
 RELOCATION.
 4. PLEASE NOTE THAT A CLEAN-OUT ON SEWER
 LATERAL ON THE PROPERTY AT BACK OF THE
 SIDEWALK IS NEEDED IF NOT ALREADY
 INSTALLED.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-08-09 Cont ID  
Sent By mwennerg Date 2006-08-09 Time 10:54 Rev Time 0.00
Received By mwennerg Date 2006-08-09 Time 10:54 Sent To  
Notes
2006-08-09 00:00:00***APPROVED***
  
  
 PLANS STILL SHOW THE ADDRESS FOR
 BUILDING "A" AS 3210. PLEASE CORRULATE
 ON ALL DOCUMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-04-26 Cont ID  
Sent By mwennerg Date 2006-04-26 Time 16:01 Rev Time 0.00
Received By mwennerg Date 2006-04-26 Time 16:01 Sent To  
Notes
2006-04-26 00:00:00******PROVISO******
  
 1) PLEASE ADD THE ADDRESS NOTE TO THE
 ELEVATION SHEETS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-31 Cont ID  
Sent By mwennerg Date 2005-08-31 Time 14:24 Rev Time 0.00
Received By mwennerg Date 2005-08-31 Time 14:24 Sent To  
Notes
2005-08-31 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT MINIMUM 2A-10B,C
 RATED FIRE EXTINGUISHERS SHALL BE
 MOUNTED TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 2) AN ADDRESS NUMBER IS REQUIRED ON THE
 BUILDING AND SHALL BE A MINIMUM OF 6" IN
 HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 3) WHAT COMMODITIES ARE PLANNED FOR THE
 STORAGE AREA?
  
 4) PLEASE PROVIDE THE INTERIOR FINISH
 CLASSIFICATION OF WALLS AND CEILING.
  
 5) PLEASE PROVIDE CLARIFICATION
 REGARDING MOTORIZED DOOR? ELECTRICAL
 NOTE #6.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-03 Cont ID  
Sent By adarroug Date 2007-03-03 Time 16:33 Rev Time 0.00
Received By adarroug Date 2007-03-03 Time 16:33 Sent To P
Notes
2007-03-03 16:33:48TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-21 Cont ID  
Sent By adarroug Date 2007-02-21 Time 10:20 Rev Time 0.00
Received By adarroug Date 2007-02-21 Time 10:19 Sent To E
Notes
2007-02-21 10:20:17TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 11:49 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 11:49 Sent To B
Notes
2006-12-27 11:49:58TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-23 Cont ID  
Sent By adarroug Date 2006-08-23 Time 15:25 Rev Time 0.00
Received By adarroug Date 2006-08-23 Time 15:25 Sent To B
Notes
2006-08-23 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-28 Cont ID  
Sent By adarroug Date 2006-06-28 Time 14:43 Rev Time 0.00
Received By adarroug Date 2006-06-28 Time 14:43 Sent To  
Notes
2006-07-12 00:00:00TO "COMM" BD#60
2006-06-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 17:35 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 17:35 Sent To  
Notes
2006-04-11 00:00:00TO "COMM" BD#46
2006-03-21 00:00:00WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-12-07 Time   Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 14:10 Sent To  
Notes
2005-08-18 00:00:00TO "COMM" BD#4

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-11 Cont ID  
Sent By pkrauss Date 2006-08-11 Time 14:27 Rev Time 0.00
Received By pkrauss Date 2006-08-11 Time 13:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-05-09 Cont ID  
Sent By tgordon Date 2006-05-09 Time 14:14 Rev Time 1.00
Received By tgordon Date 2006-05-09 Time 14:14 Sent To  
Notes
2006-05-09 00:00:00*** DENIED ***
 1) ENERGY CAL'S ARE CALLING FOR 8 KW
 HEAT AND THE MECHANICAL PLANS ARE
 CALLING FOR 10 KW HEAT, THE TWO MUST
 COINCIDE PLEASE CORRECT.
  
 2) SHOW ALL SUPPLY AIR GRILL SIZES AND
 CFM'S ON MECHANICAL PLANS.
  
 3) SHOW A/C SUPPLY AIR DUCTS AND SIZES
 TO BATHROOMS.
  
 4) SHOW LOCATION OF A/C CONDENSER UNIT
 ON MECHANICAL PLANS.
  
 5) SHOW CONDENSATE DRAIN LINE ON
 MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-22 Cont ID  
Sent By pkrauss Date 2005-09-22 Time 14:42 Rev Time 0.30
Received By pkrauss Date 2005-09-22 Time 14:39 Sent To  
Notes
2005-09-22 00:00:00DENIED:
 1.NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
  
 2.PLEASE PROVIDE EQUIPMENT SCHEDULE.
  
 3.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001
 FBC(M) TABLE 403.3.
  
 4.PLEASE INDICATE LOCATION OF THE AHU
 & CONDENSING UNIT.
  
 5.INDICATE LINE SIZE & MATERIAL FOR
 THE REFRIGERANT & CONDENSATE.
  
 6.PROVIDE LOCATION OF TERMINATION FOR
 THE CONDENSATE.
  
 7.PLEASE INDICATE WHAT WILL BE STORED
 IN THE WAREHOUSE AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 2 Status   Date 2007-03-13 Cont ID  
Sent By pschmitz Date 2007-03-13 Time 10:35 Rev Time 0.00
Received By pschmitz Date 2007-03-13 Time 10:34 Sent To  
Notes
2007-03-13 10:35:18REVISION FOR VENTS

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-10-03 Cont ID  
Sent By pschmitz Date 2005-10-03 Time 15:16 Rev Time 0.00
Received By pschmitz Date 2005-10-03 Time 15:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-20 Cont ID  
Sent By eschneid Date 2006-07-20 Time 09:06 Rev Time 0.00
Received By eschneid Date 2006-07-19 Time 17:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-07 Cont ID  
Sent By lshapiro Date 2005-09-07 Time   Rev Time 0.00
Received By lshapiro Date 2005-09-07 Time 12:54 Sent To  
Notes
***NONE***