| Plan Review Stops For Permit 05081029 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-03-23 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-03-23 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-03-23 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2006-03-23 00:00:00 | NEW ADDRESS WAS ASSIGNED TO BLDG A AS | | | EXT #0001 : 3810 GEORGIA AVE. | | 2006-03-22 00:00:00 | NEEDS ADDRESSING AS THERE ARE TWO | | | SEPARATE BLGS ON THE SMAE SITE. | | | PLEASE ALSO SEE BLDG UNDER 05011550 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-03-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-03-21 |
Time |
17:44 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-03-21 |
Time |
17:44 |
Sent To |
|
|
| Notes |
| 2007-03-21 17:45:45 | 2/23/07 OFFICE WALL REVISION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-01-23 |
|
|
Cont ID |
|
| Sent By |
rnuquist |
Date |
2007-01-23 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
rnuquist |
Date |
2007-01-23 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-09-01 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-09-01 |
Time |
15:39 |
Rev Time |
2.00 |
| Received By |
alange |
Date |
2006-09-01 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-07-24 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-24 |
Time |
09:41 |
Rev Time |
1.50 |
| Received By |
alange |
Date |
2006-07-24 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2006-07-24 00:00:00 | DENIED | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3.SUBMIT TWO COPIES OF PRODUCT | | | APPROVALS FOR ROOFING. | | | | | | 4.ALL PRODUCT APPROVALS SUBMITTED | | | SHALL HAVE THE FOLLOWING STATE PRODUCT | | | APPROVAL ATTTACHED. | | | | | | NOTE:PLEASE DO NOT ATTACH PRODUCT | | | APPROVALS TO PLANS. | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-04-14 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-04-14 |
Time |
08:28 |
Rev Time |
2.00 |
| Received By |
alange |
Date |
2006-04-14 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2006-04-14 00:00:00 | DENIED | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3.SUBMIT TWO COPIES OF PRODUCT | | | APPROVALS FOR ROOFING AND STORE FRONT. | | | | | | 4.ALL PRODUCT APPROVALS SUBMITTED | | | SHALL HAVE THE FOLLOWING STATE PRODUCT | | | APPROVAL ATTTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG. | | | | | | 5.PERMIT VALUATION IS LOW AND HAS BEEN | | | ADJUST ACCORDING TO SBCCI BUILDING | | | VALUATION DATA. | | | 324 SQ.FT. BUS. X $78.00 = $25,272 | | | 2376 SQ.FT. MERCH. X $56.00 = $133,056 | | | 2700 SQ.FT. WH X $31.00 = $83,700 | | | REVISED PERMIT VALUATION $242,028.00 | | | FBC 104.6.5 WPB AMMENDMENTS | | | | | | NEW COMMENT: | | | A.ALL PAGES SHALL BE SIGNED AND SEALED | | | BY THE DESIGNER OF RECORD. FBC 104.2.2 | | | WPB AMMENDMENTS. | | | | | | B.CHANGES TO PLANS SHALL NOT BE CUT | | | AND PASTED OR HAND WRITTEN OR WHITED | | | OUT. MAKE CHANGES AND INSERT NEW SIGNED | | | AND SEAL PAGES AS NECESSARY. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-12-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-12-07 |
Time |
03:30 |
Rev Time |
2.50 |
| Received By |
alange |
Date |
2005-12-07 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2005-12-07 00:00:00 | DENIED | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3.SUBMIT TWO COPIES OF PRODUCT | | | APPROVALS FOR ROOFING AND STORE FRONT. | | | | | | 4.ALL PRODUCT APPROVALS SUBMITTED | | | SHALL HAVE THE FOLLOWING STATE PRODUCT | | | APPROVAL ATTTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG. | | | | | | 5.PERMIT VALUATION IS LOW AND WILL | | | ADJUSTED WHEN BUILDING TYPE IS SELECTED | | | BY DESIGNER. | | | | | | 6.SHOW TRAVEL DISTANCE AND OCCUPANT | | | LOAD PER FBC CHAPTER 10. | | | | | | 7.SELECT THE CONSTRUCTION TYPE PER FBC | | | 601.2.1 | | | | | | 8.EGRESSS DOOR LOCKS COMPLYING WITH | | | FBC 1012.1.7 AND 1012.1.8 | | | | | | 9.SHOW HOW ACCESSABILITY WILL BE | | | ACHIEVED AT DOORWAYS AND PATH TO PARKING | | | AREA. FBC CH.11 | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-02-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-27 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-27 |
Time |
13:02 |
Sent To |
PC |
|
| Notes |
| 2007-02-27 13:02:23 | REVISED SERVICE RISER |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-07-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-15 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-15 |
Time |
17:15 |
Sent To |
|
|
| Notes |
| 2006-07-15 00:00:00 | REDLINED **** | | | | | | 1) PLACED ADDRESS OF 3810 ON MANY SHEETS | | | AS SOME MOST STILL INDICATED 3802 AND | | | SOME DI NOT INDICATE ADDRESS. | | | | | | | | | 2) AIC RATINGS OF MAINS SHALL BE 22,000 | | | MIN PER FAULT CURRENT CALCULATIONS ON | | | PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-04-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-24 |
Time |
20:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-24 |
Time |
20:18 |
Sent To |
|
|
| Notes |
| 2006-04-24 00:00:00 | ** UNSAT ** | | | | | | 1)NOTE: PLEASE SEE NOTE #1 FROM | | | PREVOUS REVIEW. | | | THIS IS NOTED AS PENDING FROM FPL. | | | PLEASE KNOW, AIC RATINGS CAN BE ADJUSTED | | | AT A LATER DATE? PLEASE VERIFY DISTANCE | | | AND KVA RATING OF EXISTING TRANSFORMER | | | TO VERIFY OR COME TO A CONCLUSION BASED | | | ON MIN CALCS. | | | IF KVA RATING OF TRANSFORMER, DISTANCE, | | | AND CONDUCTOR SIZES ARE KNOWN, THE | | | RATING CAN BE FIGURED. | | | | | | 2) NOTE: PLEASE SEE THAT A NEW ADDRESS | | | OF 3810 WAS ISSUED BY THE CITY | | | ADDRESSING DEPT AND PLANS SHOULD REFLECT | | | NEW ADDRESS AS REQUIRED PER FAC | | | 61G1-16.004. | | | PLEASE ADJUST FOR ALL SHEETS AND ALL | | | REFERENCES TO THIS PERMIT. | | | | | | ** PLEASE KNOW, PLANS ARE COMING BACK | | | FOR COMMENTS BY OTHER REVIEWER(S). | | | PLEASE SUBMIT. | | | | | | ALL OTHER COMMENTS WERE ADDRESSED AND | | | RESPONSES WERE ADDRESSED. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-08-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-31 |
Time |
07:30 |
Rev Time |
0.80 |
| Received By |
dpalmer |
Date |
2005-08-31 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2005-08-31 00:00:00 | *********** UNSAT ************* | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | PLEASE SEE AIC RATING IS INDICATED FOR | | | SUB PANEL, HOWEVER NOT FOR MAIN. | | | | | | 2)NOTE: PLEASE INDICATE ALL CIRCUITING | | | ON PLANS AND CORRELATE WITH THE | | | SUBMITTED PANEL SCHEDULE. | | | PLEASE SEE A COUPLE MISSING AND REDLINED | | | ON PLANS. | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE 700.12E FOR | | | CIRCUITING OF EM/EXT LTS WHICH REQUIRES | | | THE BRANCH CIRCUIT FEEDING THE UNIT | | | EQUIPMENT SHALL BE THE SAME BRANCH | | | CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD | | | OF ANY LOCAL SWITCHES. | | | | | | 4)NOTE: PLEASE SEE 210.62,220.12, FOR | | | SHOW WINDOW RECEPT REQUIREMENTS. PLEASE | | | SEE NO OTHER ELECTRICLA CAN BE ON THIS | | | CIRCUIT. (PLEASE SEE NEXT COMMENT). | | | PLEASE SEE WINDOW ON EAST ELEVATION | | | WHICH DO NOT INDICATE AN RECEPT. | | | | | | 5)NOTE: PLEASE SEE 600.5, WHICH REQUIRES | | | A DEDICATED CIRCUIT FOR SIGNAGE. | | | | | | 6)NOTE: PLEASE SEE POSSIBLE FIRE AND | | | BLDG REVIEW COMMENTS. THERE SEEMS TO BE | | | AN EGRESS/EXIT DOOR WHICH EXITS INTO AN | | | AREA WHERE ELECTRICAL PLANS INDICATE | | | MOTORIZED "DOORS"? PLEASE VERIFY THIS. | | | | | | 7)NOTE: PLEASE SEE FAC 61G15-23.002, | | | WHICH REQUIURES THE PRINTED NAME OF | | | ENGINEER ON TITLE BLOCK. | | | | | | | | | PLEASE SEE POSSIBLE COMMENS FROM OTHER | | | TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABVOE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2005-08-24 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-08-24 |
Time |
10:39 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2005-08-24 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2005-08-24 00:00:00 | PASSED WITH PROVISOS: | | | | | | 1. PLEASE NOTE THAT, THE HANDICAPPED | | | PARKING DETAIL AS SHOWN IS NOT THE | | | LATEST RECOMMENDED BY THE ADA, SEE | | | ATTACHED. | | | 2. REGULAR PARKING STALLS MUST BE | | | PAINTED WITH DOUBLE 4" WIDE WHITE LINES. | | | 3. WOODEN UTILITY POLES AS SHOWN AT | | | DRIVEWAY APPROACH AND NEAR THE PROPOSED | | | DUMPSTER ENCLOSURE MUST BE RELOCATED,IT | | | IS THE CONTRACTOR'RESPONSIBILITY TO | | | CONTACT THE PROPER OWNER FOR THE | | | RELOCATION. | | | 4. PLEASE NOTE THAT A CLEAN-OUT ON SEWER | | | LATERAL ON THE PROPERTY AT BACK OF THE | | | SIDEWALK IS NEEDED IF NOT ALREADY | | | INSTALLED. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-08-09 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-08-09 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-08-09 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2006-08-09 00:00:00 | ***APPROVED*** | | | | | | | | | PLANS STILL SHOW THE ADDRESS FOR | | | BUILDING "A" AS 3210. PLEASE CORRULATE | | | ON ALL DOCUMENTS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-04-26 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-04-26 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-04-26 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2006-04-26 00:00:00 | ******PROVISO****** | | | | | | 1) PLEASE ADD THE ADDRESS NOTE TO THE | | | ELEVATION SHEETS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-08-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-08-31 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-08-31 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2005-08-31 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE NOTE THAT MINIMUM 2A-10B,C | | | RATED FIRE EXTINGUISHERS SHALL BE | | | MOUNTED TO SATISFY THE 75' TRAVEL | | | DISTANCE REQUIREMENT. | | | | | | 2) AN ADDRESS NUMBER IS REQUIRED ON THE | | | BUILDING AND SHALL BE A MINIMUM OF 6" IN | | | HEIGHT AND CONTRASTING TO THE | | | BACKGROUND. | | | | | | 3) WHAT COMMODITIES ARE PLANNED FOR THE | | | STORAGE AREA? | | | | | | 4) PLEASE PROVIDE THE INTERIOR FINISH | | | CLASSIFICATION OF WALLS AND CEILING. | | | | | | 5) PLEASE PROVIDE CLARIFICATION | | | REGARDING MOTORIZED DOOR? ELECTRICAL | | | NOTE #6. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-03-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-03 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-03 |
Time |
16:33 |
Sent To |
P |
|
| Notes |
| 2007-03-03 16:33:48 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-02-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-21 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-21 |
Time |
10:19 |
Sent To |
E |
|
| Notes |
| 2007-02-21 10:20:17 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-12-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-27 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-27 |
Time |
11:49 |
Sent To |
B |
|
| Notes |
| 2006-12-27 11:49:58 | TO "LMARTINEZ" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-08-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-23 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-23 |
Time |
15:25 |
Sent To |
B |
|
| Notes |
| 2006-08-23 00:00:00 | TO "ALANGE" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-06-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-28 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-28 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2006-07-12 00:00:00 | TO "COMM" BD#60 | | 2006-06-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-03-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-21 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-21 |
Time |
17:35 |
Sent To |
|
|
| Notes |
| 2006-04-11 00:00:00 | TO "COMM" BD#46 | | 2006-03-21 00:00:00 | WAITING FOR COMM BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2005-12-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-18 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2005-08-18 00:00:00 | TO "COMM" BD#4 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-08-11 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-08-11 |
Time |
13:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-05-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-05-09 |
Time |
14:14 |
Rev Time |
1.00 |
| Received By |
tgordon |
Date |
2006-05-09 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2006-05-09 00:00:00 | *** DENIED *** | | | 1) ENERGY CAL'S ARE CALLING FOR 8 KW | | | HEAT AND THE MECHANICAL PLANS ARE | | | CALLING FOR 10 KW HEAT, THE TWO MUST | | | COINCIDE PLEASE CORRECT. | | | | | | 2) SHOW ALL SUPPLY AIR GRILL SIZES AND | | | CFM'S ON MECHANICAL PLANS. | | | | | | 3) SHOW A/C SUPPLY AIR DUCTS AND SIZES | | | TO BATHROOMS. | | | | | | 4) SHOW LOCATION OF A/C CONDENSER UNIT | | | ON MECHANICAL PLANS. | | | | | | 5) SHOW CONDENSATE DRAIN LINE ON | | | MECHANICAL PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-09-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-09-22 |
Time |
14:42 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2005-09-22 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2005-09-22 00:00:00 | DENIED: | | | 1.NO MECHANICAL PLANS OR CONTRACTOR | | | INDICATED WITH PERMIT APPLICATION. | | | | | | 2.PLEASE PROVIDE EQUIPMENT SCHEDULE. | | | | | | 3.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS IN ACCORDANCE WITH 2001 | | | FBC(M) TABLE 403.3. | | | | | | 4.PLEASE INDICATE LOCATION OF THE AHU | | | & CONDENSING UNIT. | | | | | | 5.INDICATE LINE SIZE & MATERIAL FOR | | | THE REFRIGERANT & CONDENSATE. | | | | | | 6.PROVIDE LOCATION OF TERMINATION FOR | | | THE CONDENSATE. | | | | | | 7.PLEASE INDICATE WHAT WILL BE STORED | | | IN THE WAREHOUSE AREA. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
|
Date |
2007-03-13 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2007-03-13 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2007-03-13 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2007-03-13 10:35:18 | REVISION FOR VENTS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2005-10-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-10-03 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-10-03 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2006-07-20 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2006-07-19 |
Time |
17:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-09-07 |
|
|
Cont ID |
|
| Sent By |
lshapiro |
Date |
2005-09-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
lshapiro |
Date |
2005-09-07 |
Time |
12:54 |
Sent To |
|
|
| Notes |
|
|