Plan Review Details - Permit 05080948
Plan Review Stops For Permit 05080948
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-04-25 Cont ID  
Sent By lursu Date 2006-04-25 Time 12:04 Rev Time 0.00
Received By lursu Date 2006-04-17 Time 16:12 Sent To  
Notes
2006-04-25 00:00:00THE CAR WASH CAN MAINTAIN THE
 ADDRESS:1300 N TAMARIND AVE.
 BASED ON THE CONVERSTAION WITH FIRE
 SAFETY ,THE ENTIRE SITE FOR THIS CARWASH
 WILL HAVE THE SAME ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-11-05 Cont ID  
Sent By shill Date 2006-11-05 Time 12:57 Rev Time 0.00
Received By shill Date 2006-11-05 Time 12:57 Sent To  
Notes
2006-11-05 13:05:21REVISED S1 THROUGH S6 DATED 8/3/6

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-05-24 Cont ID  
Sent By shill Date 2006-05-24 Time 15:15 Rev Time 0.00
Received By shill Date 2006-05-24 Time 15:15 Sent To  
Notes
2006-06-01 00:00:00SEPARATE PERMIT FOR DUMPSTER ENCLOSURE
 REVISE S2 & S3 (EXPIRED SEAL)
  
 ROOF PRODUCT APPROVAL, GAF MODIFIED NOA
 #03-0430.13, ASSEMBLY PAGE 27 OF 41

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-05-04 Cont ID  
Sent By shill Date 2006-05-04 Time 16:16 Rev Time 0.00
Received By shill Date 2006-05-04 Time 15:19 Sent To  
Notes
2006-05-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS REVIEW:
  
 1.)THE NOC IS EXPIRED, OVER 90 DAYS
 WITHOUT COMMENCING WORK, FS713.13(2).
 THIS CAN BE ADDRESSED PRIOR TO PERMIT
 PICKUP AND DOES NOT PREVENT THE PERMIT
 FROM BEING ISSUED.
  
 11.)THE DUMPSTER ENCLOSURE GATE CANNOT
 SWING OVER THE PROPERTY LINE,
 FBC3206.1.1.THE PLAN HAS BEEN REVISED
 AND SHOWS THE GATE ENDING AT THE
 PROPERTY LINE.HOWEVER, THE GATE IN THE
 OPEN POSITION WHEN SCALED IS 10', BUT
 THE GATE IN THE CLOSED POSITION IS SHOWN
 AS 13'.A2 DOOR SCHEDULE GIVES A
 DIMENSION OF 12' FOR THIS GATE, IN WHICH
 CASE IT WILL SWING OVER THE PROPERTY
 LINE AND WILL NOT FULLY ENCLOSE THE
 DUMPSTER.ADDRESS.
  
 L2 AND THE SL SHEETS HAVE NOT BEEN
 REVISED TO SHOW THE NEW DUMPSTER GATE
 DETAIL.
  
  
 17.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FAC9B72.THE SHEET
 PROVIDED FOR ARCH ALUMINUM PRODUCTS AND
 THE HURST AWNING ARE NOT THE PRODUCT
 APPROVALS, THEY ARE LISTS OF ALL
 PRODUCTS FOR THAT MANUFACTURER.PLEASE
 PRINT THE STATE PRODUCT APPROVAL AS YOU
 DID FOR THE GAF MODIFIED.
  
 18.)THE FIRST REVIEW STATED THAT A
 HURRICANE SHUTTER INSTALLATION PLAN
 WOULD BE REQUIRED AND MUST BE APPROVED
 BY THE BUILDING OFFICIAL IF REMOVABLE
 PANELS WERE USED.THE SECOND REVIEW
 STATED THAT SINCE ALL PRODUCT APPROVALS
 WERE FOR IMPACT GLASS, THE PLAN WAS NOT
 NECESSARY.NOW ON THE THIRD REVIEW
 THERE IS A NEW COMMENT ON A5 STATING
 THAT NON IMPACT OPENINGS WILL BE
 SHUTTERED AND STORM PANELS WILL BE
 STORED IN THE EQUIPMENT ROOM.THE PLAN
 CANNOT BE APPROVED UNTIL A HURRICANE
 INSTALLATION PLAN IS SUBMITTED AND
 APPROVED BY THE BUILDING OFFICIAL.ALL
 PRODUCT APPROVALS SUBMITTED ARE FOR
 IMPACT GLASS.
  
 IF YOU ARE GOING TO USE NONIMPACT
 PRODUCTS, PLEASE SUBMIT A PLAN AS
 REQUESTED IN THE FIRST REVIEW AND SUBMIT
 PRODUCT APPROVALS FOR THE NON IMPACT
 WINDOWS AND STORM PANELS.IF YOU ARE
 USING ALL IMPACT GLASS, REMOVE THE NOTE
 FROM THE PLAN.
  
 26.SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE IS REQUIRED TO BE
 CHARGED IF COMMENT 11 ABOVE IS NOT
 ADDRESSED A THIRD TIME.
  
 NEW COMMENT:
  
 19.)SP-2, PROVIDE A DIMENSION OF
 ENCROACHMENT OVER THE PROPERTY LINE FOR
 THE MOULDING AT THE TOP OF THE WALL,
 FBC3206.1.1, EXCEPTION.
  
 20.)SEPARATE PERMITS REQUIRED FOR THE
 AWNINGS.THIS COMMENT DOES NOT NEED TO
 BE ADDRESSED AT THIS TIME; INFORMATIONAL
 ONLY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-17 Cont ID  
Sent By shill Date 2006-04-17 Time 11:44 Rev Time 0.00
Received By shill Date 2006-04-17 Time 11:44 Sent To  
Notes
2006-04-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 SECOND REVIEW; NUMBERING REMAINING THE
 SAME FOR CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 THE NOC IS EXPIRED, 90 DAYS WITHOUT
 COMMENCING WORK, FS713.13(2).REFILE TO
 GET A NEW DATE.
  
 2.)ADDRESSED.
  
 3-6.)ADDRESSED.
  
 7.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1804.2.2.
  
 SIGNATURE TO BE A WET SIGNATURE, NOT A
 PHOTOCOPY PER FBPE.
  
 8.)ENERGY CALCS REQUIRED.
  
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALC PROVIDED.
  
 9-10.) ADDRESSED.
  
 11.)THE RECYCLING BIN GATE CANNOT
 SWING OVER THE PROPERTY LINE,
 FBC3206.1.1.
  
 MY APOLOGIES, BUT THIS COMMENT SHOULD
 HAVE REFERRED TO THE BIN AND THE
 DUMPSTER ENCLOSURE.YOU HAVE CHANGED
 THE BIN AS REQUESTED BUT THE DUMPSTER IS
 NOT COMPLIANT.
  
 12-13.) ADDRESSED.
  
 14.)STRUCTURAL NOTES, S3, DECLARES
 THIS AS A PARTIALLY ENCLOSED BUILDING.
  
 THE NOTE STATING THAT THE CAR WAS BAY IS
 OPEN IS ACKNOWLEDGED. PLEASE PROVIDE
 CALCULATIONS AS PER DEFINITION OF
 PARTIALLY ENCLOSED.
  
 ALSO NOTE THAT THE ARCHITECT ON A5
 DECLARES AN INTERNAL COEFFICIENT OF
 -.18, WHICH INDICATES AN ENCLOSED
 BUILDING.IF THE ENGINEER IS CORRECT IN
 DETERMINING THAT THIS IS A PARTIALLY
 ENCLOSED BUILDING, REVISE A5.THE TWO
 DESIGN PROFESSIONALS SHOULD BE USING THE
 SAME DESIGN ASSUMPTIONS.
  
 THE ARCHITECT INDICATES ON A5 THAT ALL
 OPENINGS INCLUDING THE ENTRY/EXIT OF THE
 CAR WASH TUNNEL ARE TO BE PROTECTED.
 THE ELEVATION STATES THAT WINDOW F WILL
 NOT HAVE GLASS BUT IT IS LISTED ON THE
 SCHEDULE A5 AS HAVING POSITIVE AND
 NEGATIVE PRESSURES.S4 SHOWS THESE
 WINDOWS AS IMPACT GLASS.WINDOW C, THE
 WINDOWS BETWEEN THE A/C SPACE AND THE
 CAR WASH TUNNEL, ARE NOT SHOWN ON THE
 WALL OPENING SCHEDULE.IF THE TUNNEL IS
 PARTIALLY ENCLOSED, THESE WINDOWS WILL
 BE SUBJECT TO PRESSURES AND POSSIBLY
 IMPACT.IF THE TUNNEL IS FULLY
 ENCLOSED, WINDOW F SHOULD HAVE GLASS AND
 THE ENGINEER SHOULD DECLARE AN ENCLOSED
 BUILDING.PLEASE MAKE THE VARIOUS
 SPECIFICATIONS CONSISTENT AND THE DESIGN
 CONSISTENT WITH THE ENCLOSURE CATEGORY.
  
 15-16.) ADDRESSED.
  
 17.)SUBMIT FLORIDA STATE OR LOCAL
 PRODUCT APPROVALS FAC9B72 ALONG WITH THE
 EVALUATION OR TEST REPORT FOR THE
 FOLLOWING:
 PAIR OF LOUVERED DOORS
 OVERHEAD DOORS
 STOREFRONT DOORS, WINDOWS AND MULLIONS
 ROOF
 IMPACT PROTECTION IF APPROVED (SEE
 FOLLOWING COMMENT)
  
 PROVIDE FLORIDA STATE PRODUCT APPROVALS
 FOR ALL PRODUCTS, FAC9B72,
 WWW.FLORIDABUILDING.ORG.IF A STATE
 PRODUCT APPROVAL IS NOT AVAILABLE,
 PLEASE ADVISE AND A LOCAL PA WILL BE
 ISSUED.
  
 FOR THE GAF MODIFIED, THE PRODUCT
 APPROVAL IS INCOMPLETE.INCLUDE THE
 LAST PAGES.
  
 FOR THE GAF MODIFIED, CHOOSE THE
 APPROVED ASSEMBLY YOU ARE USING.
  
 IF ALL GLASS PRODUCTS ARE IMPACT, WHAT
 IS THE ROLL UP SHUTTER FOR?
  
 A6 AND A5 REQUIRE PRODUCT APPROVALS FOR
 THE OVERHEAD DOOR.A SHOP DRAWING
 STATING THAT PRODUCT APPROVALS ARE NOT
 REQUIRED WAS SUBMITTED.ADDRESS AND
 CLARIFY WITH A RESPONSE LETTER IF
 NECESSARY.
  
 18.)SEE ATTACHED POLICY FOR MISSILE
 IMPACT PROTECTION, ITEM NUMBER 13.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL
 BUILDINGS MUST BE APPROVED BY THE
 BUILDING OFFICIAL.IF THE GLAZING IS
 NOT IMPACT, SUBMIT A PLAN FOLLOWING THE
 GUIDELINES.
  
 NOTE - ADDRESSED, ALL
 COMPONENTS & CLADDING IMPACT RESISTANT.
  
 19-23.)ADDRESSED.
  
 NEW COMMENTS:
  
 24.)PARKING IS TO COMPLY WITH CITY OF
 WEST PALM BEACH STANDARD, SEE ATTACHED.
  
 25.)SEPARATE PERMIT REQUIRED FOR THE
 WALL AT THE PROPERTY LINE.
  
 26.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-12 Cont ID  
Sent By shill Date 2005-09-12 Time 15:16 Rev Time 4.00
Received By shill Date 2005-09-09 Time 08:25 Sent To  
Notes
2005-09-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3.)ADDITIONAL FEES DUE (RADON).SEE
 ATTACHED.
  
 4.)SUBMIT SEPARATE PERMIT APPLICATIONS
 FOR THE SERVICE BUILDING AND DUMPSTER
 ENCLOSURE/RECYCLING BIN.SEPARATE
 PERMIT NUMBERS WILL BE ISSUED FOR
 INSPECTION AND RECORD KEEPING PURPOSES.
  
 5.)THE PROPOSED IMPROVEMENT CROSSES
 OVER THE PROPERTY LINES.A UNITY OF
 TITLE IS REQUIRED.
  
 6.)THE SURVEY IS NOT ENTIRELY LEGIBLE.
 ALSO PLEASE PROVIDE A SIGNATURE (NOT A
 STAMP).PLEASE PROVIDE NEW COPIES.
  
 7.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1804.2.2.
  
 8.)ENERGY CALCS REQUIRED.
  
 9.)SEE FAC61G1-16.004.THE
 ARCHITECT?S PRINTED NAME IS REQUIRED.
  
 10.)THE SEAL FOR THE LANDSCAPE
 ARCHITECT IS TO BE DATED, FS481.306,
 FAC61G10-11.010.
  
 11.)THE RECYCLING BIN GATE CANNOT
 SWING OVER THE PROPERTY LINE,
 FBC3206.1.1.
  
 12.)THE WIND DESIGN CRITERIA T-1 IS
 NOT CLEAR.GOVERNING CODES SECTION
 GIVES A "BASIC" WIND SPEED OF 120, WIND
 EXPOSURE B, "DESIGN" WIND SPEED OF 140,
 AND GENERAL NOTES, STRUCTURAL DESIGN
 CRITERIA ITEM 3 AND BUILDING DATA SHEET
 A5 GIVE A WIND SPEED OF 140, EXPOSURE C.
 SEE FBC1606.1.6.PROVIDE ALL
 INFORMATION REQUIRED BY FBC1606.1.7.
  
 13.)DESIGN LOADS, T1, IS LACKING THE
 DESIGN PRESSURES FOR ZONE 3 GROSS WIND
 UPLIFT LOADS, AND ROOF DEAD LOAD IS
 INCOMPLETE.
  
 14.)STRUCTURAL NOTES, S3, DECLARES
 THIS AS A PARTIALLY ENCLOSED BUILDING.
  
 15.)ACCESSIBLE ROUTE FBC11-4.1.2(1) IS
 NOT CLEAR.THERE IS A PEDESTRIAN
 WALKWAY ON SP1 WHICH REFERS TO SECTION
 3-SP2.HOW DOES THIS LEAD TO THE LOBBY?
  
 16.)THE TOWEL CLEANING ROOM 108 IS TO
 HAVE A DOOR TO COMPLY WITH FBC1012.1.2.
  
 17.)SUBMIT FLORIDA STATE OR LOCAL
 PRODUCT APPROVALS FAC9B72 ALONG WITH THE
 EVALUATION OR TEST REPORT FOR THE
 FOLLOWING:
 PAIR OF LOUVERED DOORS
 OVERHEAD DOORS
 STOREFRONT DOORS, WINDOWS AND MULLIONS
 ROOF
 IMPACT PROTECTION IF APPROVED (SEE
 FOLLOWING COMMENT)
  
 18.)SEE ATTACHED POLICY FOR MISSILE
 IMPACT PROTECTION, ITEM NUMBER 13.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL
 BUILDINGS MUST BE APPROVED BY THE
 BUILDING OFFICIAL.IF THE GLAZING IS
 NOT IMPACT, SUBMIT A PLAN FOLLOWING THE
 GUIDELINES.
  
 19.)THE AWNINGS ARE TO COMPLY WITH
 FBC3106.2(1) AND (3).
  
 20.)A SEPARATE PERMIT IS REQUIRED FOR
 THE AWNINGS.
  
 21.)ROOF ZONE KEY, SHEET S3, DOES NOT
 INCLUDE A ZONE 3.
  
 22.)THE FOOTERS FOR THE PERIMETER
 WALLS CANNOT ENCROACH THE PROPERTY LINE.
 REVISE DETAIL 7-S6 TO SHOW THE PROPERTY
 LINE.
  
 23.)SHEET M2.01 PROVIDES A BUILDING
 HEIGHT OF <15 FT.BOTH BUILDINGS ARE
 OVER 20FT.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-01-13 Cont ID  
Sent By dpalmer Date 2007-01-13 Time 13:21 Rev Time 0.00
Received By dpalmer Date 2007-01-13 Time 13:12 Sent To PC
Notes
2007-01-13 13:22:32REDLINED 230.70/230.71 AS BREAKER WAS REMOVED FOR RTU,
 NO MORE THAN 6 MAINS ARE PERMITTED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-12-26 Cont ID  
Sent By dpalmer Date 2006-12-26 Time 07:57 Rev Time 0.00
Received By dpalmer Date 2006-12-26 Time 07:13 Sent To PC
Notes
2006-12-26 07:59:48** UNSAT **
  
 1) NOTE: PLEASE SEE THE TAPS ON THE SECONDARY SIDE OF
 THE NEW TRANSFORMER FEEDING THE RTU DOES NOT CONTAIN
 OCP WITHIN THE PERMITTED DISTANCES AS STATED IN
 240.21C.
 PLEASE SEE MAX LENGTHS PERMITTED. SHALL TERMINATE IN
 OCP.
 PLEASE KNOW BASED ON THE PLANS ON FILE THE RTU IS TOO
 FAR AWAY.
  
 2) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM OCP FOR THE
 SAME TRANSFORMER SHALL BE 125%. PLEASE SEE ONLY IF THE
 TRANSFORMER MEETS THE EXCEPTION #3 CAN THE OCP BE SET
 HIGHER.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-05-03 Cont ID  
Sent By dpalmer Date 2006-05-03 Time 11:34 Rev Time 0.00
Received By dpalmer Date 2006-05-03 Time 08:48 Sent To I
Notes
2006-05-03 00:00:00REDLINED,
  
 DEADFRONT SHALL BE FACTORY INSTALLED OR
 CONTIAN A MCB.
 230.70,230.71

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 21:46 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 20:50 Sent To  
Notes
2006-03-24 00:00:00ELEC FOR REVIEW
 *** UNSAT ***
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND NEW NOTE DUE TO NOTE ON
 PLANS.
  
  
  
 1) NOTE: PLEASE SEE NOTE #1, WHICH
 MENTIONED ALL SHEETS TO CONTAIN ALL
 LICENSING FOR TITLE BLOCKS , ALL
 INFORMATION AS REQUIRED PER FAC
 61G1-16.004,61G15-23.002,
 FS471.023,481.219,
 PLEASE SEE LANDSCAPE PLANS, NO
 FIRM/CERTIFICATE OF AUTHORIZATION
 NUMBER??
 PLEASE SEE SURVEY SHEETS ARE STILL
 SEALED "PHOTO-COPIES" OF SIGNED SURVEYS.
 NEITHER OF WHICH ARE NEEDED FOR
 ELECTRICALPLANS. THIS IS ONLY A NOTE
 AND WILL NOT AFFECT ELECTRICLA PLANS.
  
 ELEC NOTES.
  
 1)NOTE: PLEASE PROVIDE WIND LOAD
 CALCULATIONS FOR LIGHT POLES, INCLUDING
 FIXTURES.
 PLEASE KNOW, THESE CALCULATIONS ARE
 REQUIREDTO BE SIGNED, DATED AND SEALED
 BY A FL LICENSED PE.
 SHEET ATTACHED TO SITE PLAN DOES NOT
 MEET REQUIREMENTS.
  
 2) NOTE: PLEASE KNOW, ALL SIGNAGE SHALL
 CONTAIN "1-INCH" LETTERS ON CONTRASTING
 BACKGROUND. ELECTRICAL SHEETS CONTAINING
 THIS NOTE, CAN BE REDLINED, OR SHEETS
 MAY BE REVISED AT THIS TIME.
  
 3)NOTE: PLEASE SEE SPACES 5 AND 6 WILL
 BE REQUIRED TO HAVE A PERMANANT/
 UN-REMOVEABLE DEAD FRONT.
 230.71, 230.70
  
 4)NOTE: PLEASE SEE 225.31,225.31
 , A MCB WILL BE REQUIRED IN PANEL "L".
 THIS WAS NOT ON PREVIOUS REVIEW, HOWEVER
 AS THIS IS A SEPARATE BLDG THIS WILL BE
 REQUIRED.
  
 PLEASE SUBMIT THE ABOVE. PLANS ARE
 COMING BACK FOR "SITE-POLES COMMENT
 MAINLY AND THESE ITEMS SHOUDL BE
 ADDRESSED AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATIO FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ***********NOTE ADDED **********
  
  
 PLEASE HAVE ENGINEER TO CALL TO GO OVER
 ELECTRICAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-04 Cont ID  
Sent By dpalmer Date 2005-09-04 Time 19:05 Rev Time 1.65
Received By dpalmer Date 2005-09-04 Time 17:28 Sent To  
Notes
2005-09-04 00:00:00************* UNSAT **************
  
  
 GENERAL COMMENT FOR ALL.
  
 1)NOTE: PLEASE SEE ALL TITLE BLOCKS ON
 PLANS SHALL CONTAIN ALL INFORMATION AS
 REQUIRED UNDER FAC 61G15-23.002, FAC
 61G1-16.004
 PLEASE SEE MISSING FIRM LICENSE NUMBER
 FOR CIVIL PLANS.
 PLEASE SEE ARCHITECTURAL. FIRMS TITLE
 BLOCKS SHALL CONTAIN THE PRINTED NAME
 AND LICENSE NUMBER FOR ARCHITECT OF
 RECORD.
 PLEASE SEE BLDG REVIEW COMMENTS
 PERTAINING TO SURVEY. SURVEY ATTACHED
 SHALL CONTAIN AN ORIGINAL SIGNATURE FROM
 SURVEYOR OF RECORD AS REQUIRED UDNER FS
 472.025, FAC 61G17-7.002
  
 ** PLEASE SEE ABOVE INFORMATION IS
 REQUIRED OF ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
 ** PLEASE KNOW TITLE BLOCK FOR FORMICA &
 ASSCOIATES IS NOT INCLUDED IN NOTES
 ABOVE.
 PLEASE SEE TITLE BLOCK FOR ARCHITECTURAL
 FIRM ON E-SHEETS NEEDS ABOVE AS
 MENTIONED.
  
 2)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS C-STORE?? CONVENIENCE? PLEASE
 CLARIFY. COULD NOT LOCATE ANY PLANS FOR
 SUCH STORE.
  
 ***ELECTRICAL REVIEW NOTES ***
  
 1)NOTE: PLEASE PROVIDE WIND LOADING
 INFORMATION FOR SITE LIGHITNG POLES AND
 FIXTURES. CALCULATIONS FOR THESE ARE
 REQUUIRED AT THIS TIME. MUST MEET FBC
 140 MPH MIN.
 THIS WILL BE REVIEWED BY STRUCTURAL
 REVIEWER WHEN SUBMITTED.
  
 2)NOTE: PLEASE PROVIDE AN EMERGENCY
 BATTERY BACK-UP TYOE OF LT FIXTURE IN
 MAIN EQUIPMENT RM. A WALL MOUNTED
 FIXTURE IS ACCEPTABLE.
 700.16, NFPA-101 7-9
  
 3)NOTE: PLEASE PROVIDE A NOTE WHICH WILL
 REQUIRED "SIGNAGE" AT DOORS TO EQUIPMENT
 ROOM. THE SIGNAGE WILL BE REQUIRED TO
 DENOTE THE SERVCICE DISCONNECTING MEANS
 AND LOCATION.
 PLEASE ALSO THAT A "KNOX BOX" MAY BE
 REQUIRED BY THE FIRE DEPT, IF MAINS ARE
 TO BE LOCATED INSIDE A LOCKED ENCLOSURE
 WITHOUT READY ACCESS. 230.70
  
 4)NOTE: PLEASE SEE MDP SHOWN CONTAINS
 MORE THAN SIX SPACES AS PERMITTED IN
 230.71. PLEASE SEE THAT A NOTE WILL BE
 REQUIRED ON PLANS THAT EQUIPMENT SHALL
 HAVE THE ADDTIONAL SPACES MADE FROM
 MANUFACTURE WITH A PERMANANT DEAD FRONT
 IN ORDER TO ALLEAVIATE THE ADDTION OF
 ADDITIONAL SERVICE MEANS OF DISCONNECT.
 PLEASE SEE THE OTHER OPTION, WOULD BE A
 MCB IN MDP.
  
 5)NOTE: PLEASE CLARIFY OCP SHOWN FEEDING
 MCC. MDP SHOWS 500A OCP FEEDING 400A
 RATED MCC.?
 PLEASE CORRLEATE 282.2A'S SHOWN ON MCC
 WITH AMERAGE ON MDP.
 KVA ADDED ON MDP FOR MCC SEEMS TO BE
 HIGHER THAN 282A'S?
 PLEASE SEE MDP SCHEDULE SHOWS FEEDERS AS
 #2 AWG?
 PLEASE SEE RISER SHOWS FEEDERS AS
 PARALLEL 3/0'S. PLEASE SEE PARALLEL
 3/0'S ARE OK, DEPEDNING ON OCP FEEDING
 MCC.
 PLEASE SEE #2'S ARE NOT RATED FOR OCP AS
 SHOWN.
 PLEASE SEE 240.4,310.16,215.5 FOR ABOVE
 COMMENTS.
  
 6)NOTE: PLEASE SEE MDP PANEL SCHEDULE
 MENTIONS"EQUIPMENT GROUNDING
 CONDUCTORS" FROM METER/FPL TO FIRST
 MEANS OF DISCONNECT. PLEASE SEE 250.6,
 250.24, EQUIPMENT GROUNDING CONDUCTORS
 AREONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
  
 7)NOTE: PLEASE SEE FEEDERS ON THE
 LINE-SIDE OF PANEL "L"; ALSO LOAD-SIDE
 OF DISCONNECT LOCATED FROM T-1.
 PLEASE SEE A 225A OCPIS SHOWN TO PANEL
 "L", HOWEVER FEEDERS ARE ONLY RATED FOR
 150A'S. (1/0'S) 310.16, 240.4
  
 8)NOTE: PLEASE SEE 450.3(TABLE), MAX OCP
 OF 125% FOR T-2. (15A'S). PLEASE SEE 20A
 OCP IS SHOWN.
  
 9)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM AT DETACHED BLDG.
 IT IS NOTED THAT GRND ROD IS SHOWN,
 HOWEVER PLEASE SEE ANY COLD WATER PIPES
 (METAL) AND NEW FOOTER STEEL OF DEATCHED
 BLDG WILL ALSO BE TO BE PART OF THE
 GROUNDING ELECTRODE SYSTEM AT THAT
 LOCATION.
 250.50
  
 10)NOTE: PLEASE SEE POSSIBLE MECHANICAL
 COMMENTS WHICH MAY REQUIRE "WALK-IN
 COOLER TO BE UNDER SEPARATE PERMIT.
 NO CORRECTION NEEDED FOR ELECTRICAL.
  
 11)NOTE: PLEASE INDICATE IF ALL
 CONTINUOUS LOADS AND LARGEST MOTORS
 LOADS ARE ALREADY SHOWN AT 125% ? IF
 NOT, PLEASE ADJUST CALCULATIONS.
 PLEASE CLARIFY IF THEY ARE.
 215.3,230.42 ETC.
  
 PLEASE SEE ANY POSSIBEL COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESTIATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REWVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-05-30 Cont ID  
Sent By lmartine Date 2006-05-25 Time 11:59 Rev Time 0.00
Received By lmartine Date 2006-05-25 Time 11:59 Sent To  
Notes
2006-05-25 00:00:00SEE #05080948 FOR COMMENTS

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-08-29 Cont ID  
Sent By mamini Date 2005-08-29 Time 15:02 Rev Time 1.00
Received By mamini Date 2005-08-29 Time 15:02 Sent To  
Notes
2005-08-29 00:00:00PASSED WITH PROVISOS:
  
 1. PLEASE NOTE THAT ALL BROKEN SIDEWALKS
 ALONG THE PROPERTY ( ALL SIDE ) MUST BE
 REPLACED. SIDEWALKS MUST BE CONSTRUCTED
 WITH ACCESSIBLERAMP COMPLYING WITH ADA
 REQUIREMENTS.
 2. ALL DRIVEWAYS THAT WILL NOT BE USED
 MUST BE REMOVED AND THE REGULAR CURBS(&
 GUTERS) MUST BE REPLACED.
 3. WORK WITHIN PUBLIC R.O.W REQUIRES A
 SEPARATE PERMIT FROM PUBLIC UTILITIES
 AND ENGINEERING, PLEASE CONTACT WINDEL
 PALMER AT 494-1086. YOU MAY REQUIRE TO
 SUBMIT M.O.T PLAN.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-04-18 Cont ID  
Sent By mwennerg Date 2006-04-18 Time 10:42 Rev Time 0.00
Received By mwennerg Date 2006-04-18 Time 10:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-14 Cont ID  
Sent By mwennerg Date 2005-09-14 Time 09:23 Rev Time 0.00
Received By mwennerg Date 2005-09-14 Time 09:23 Sent To  
Notes
2005-09-14 00:00:00******DENIED******
  
 1) PLEASE PROVIDE MORE DETAILS AND
 LOCATION OF REMOTE FUEL FILL STATION.
  
 2) PLANS SHOW NEW PROPOSED UNDERGROUND
 TANKS. MORE INFORMATION AND CUT SHEETS
 ARE REQUIRED.
  
 3) PLEASE PROVIDE FLAME SPREAD
 INFORMATION FOR FABRIC SHELTER.
  
 4) PLEASE ILLUSTRATE EXISTING FIRE
 HYDRANT LOCATIONS CLOSEST TO PROPERTY.
  
 5) ADDRESS NUMBER ON THE BUILDING IS
 REQUIRED, AND SHALL BE A MINIMUM OF 6"
 IN HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 6) PLEASE SEE OTHER COMMENTS REGARDING
 FS AND FAC REQUIREMENTS.
  
 7) PLEASE CONTACT THE BUREAU OF FIRE
 PREVENTION REGARDING KNOX BOX
 APPLICATIONS. A KNOX BOX MAY BE REQUIRED
 IF ACCESS BECOMES PROBLEMATIC,
 PARTICULARLY AFTER NORMAL BUSINESS
 HOURS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-01-11 Cont ID  
Sent By adarroug Date 2007-01-11 Time 15:29 Rev Time 0.00
Received By adarroug Date 2007-01-11 Time 15:29 Sent To E
Notes
2007-01-11 15:29:20TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-12-20 Cont ID  
Sent By adarroug Date 2006-12-20 Time 08:48 Rev Time 0.00
Received By adarroug Date 2006-12-20 Time 08:48 Sent To E
Notes
2006-12-20 08:49:20TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 10:19 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 10:18 Sent To B
Notes
2006-10-27 10:19:15TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-10 Cont ID  
Sent By adarroug Date 2006-05-10 Time 09:44 Rev Time 0.00
Received By adarroug Date 2006-05-10 Time 09:44 Sent To Z
Notes
2006-05-24 00:00:005/24/06-TAKEN OFF "COMM" BD AND ROUTED
 TO "ENG"
2006-05-23 00:00:005/23/06-TO "COMM" BD#36
2006-05-10 00:00:00TO "Z" BOX/RESUB--NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-08 Cont ID  
Sent By adarroug Date 2006-05-08 Time 16:52 Rev Time 0.00
Received By adarroug Date 2006-05-08 Time 16:52 Sent To P
Notes
2006-05-08 00:00:00TO "PSCHMITZ" DESK--PLANS NEED TO BE
 STAMPED FOR PLUMBING.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 11:23 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 11:23 Sent To  
Notes
2006-04-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-21 Cont ID  
Sent By adarroug Date 2006-02-21 Time 16:54 Rev Time 0.00
Received By adarroug Date 2006-02-21 Time 16:54 Sent To  
Notes
2006-03-21 00:00:00TO COMM BOARD #59
2006-02-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-21 Cont ID  
Sent By adarroug Date 2005-10-20 Time 16:43 Rev Time 0.00
Received By adarroug Date 2005-08-17 Time 13:43 Sent To  
Notes
2005-08-18 00:00:00TO "COMM" BD#13
2005-08-17 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-04-12 Cont ID  
Sent By pkrauss Date 2006-04-12 Time 07:37 Rev Time 0.00
Received By pkrauss Date 2006-04-12 Time 07:08 Sent To  
Notes
2006-04-12 00:00:00PROVISO:
 RTU CURB SHALL BE A MINIMUM OF 8" ABOVE
 THE ROOF SURFACE PER 2001 FBC 1511.7.
  
 PLEASE NOTE, CUT SHEET FOR THE WALK-IN
 COOLER DOES NOT INDICATE LOCATION OF THE
 CONDENSOR.SHOULD CONDENSOR BE REMOTE
 AND MOUNTED ON A STAND LOCATED ON THE
 ROOF, THE HEIGHT FROM THE ROOF SURFACE
 TO THE BOTTOM OF THE SUPPORT RAIL SHALL
 COMPLY WITH 2001 FBC TABLE 1511.7
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-23 Cont ID  
Sent By pkrauss Date 2005-09-23 Time 08:50 Rev Time 1.15
Received By pkrauss Date 2005-09-23 Time 08:36 Sent To  
Notes
2005-09-23 00:00:00DENIED:
 1.PLAN SHEET A-6 INDICATES MECHANICAL
 EQUIPMENT LOCATED ON THE ROOF OF VARIOUS
 BUILDINGS.PLEASE NOTE PER 2001 FBC(M)
 306.5 EQUIPMENT LOCATED ON ELEVATED
 STRUCTURES AT A HEIGHT GREATER THAN 16
 FEET, A PERMANENT MEANS OF ACCESS IS
 REQUIRED.
  
 2.PLEASE PROVIDE ENERGY CALCULATIONS
 IN ACCORDANCE WITH 2001 FBC CHAPTER 13
 SUB-CHAPTER 400.
  
 3.ADDITIONAL PERMIT REQUIRED FOR
 WALK-IN COOLER.PLEASE PROVIDE
 MANUFACTURER'S INSTALLATION & SUBMITTAL
 DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-03-31 Cont ID  
Sent By pschmitz Date 2006-03-31 Time 13:16 Rev Time 0.00
Received By pschmitz Date 2006-03-31 Time 13:16 Sent To  
Notes
2006-03-31 00:00:00RECEIVED GREASE TRAP REQUIRMENTS FROM
 RODNEY COMPO

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-03-25 Cont ID  
Sent By pschmitz Date 2006-03-25 Time 09:07 Rev Time 0.00
Received By pschmitz Date 2006-03-25 Time 09:07 Sent To  
Notes
2006-03-25 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODE PLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
  
 !) PREVIOUS NOTE #6, NOT ADDRESED.
 PROVIDE COPY OF LETTER FOR THE TYPE AND
 SIZE OF OIL AND GREASE SEPERATOR,
 FROM
 CONTACT W P BEACH,WATERPLANT LAB
 SUPERVISORINDUSTRIAL COORDINATOR,
 LYNN MASSON OFFICE 561-822-2271
 E-MAIL [email protected]
 REQUIRMENTS FOE OIL AND GREASE
 SEPERATOR.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-20 Cont ID  
Sent By pschmitz Date 2005-10-20 Time 11:21 Rev Time 0.00
Received By pschmitz Date 2005-10-20 Time 11:20 Sent To  
Notes
2005-10-01 00:00:00PAUL SCHMITZ
 FBC 2001 PLUMBING CODE PLAN REVIEW
 FBC 2001 CH 11, FL ACESSIBILITY CODE
 DENIED
 1) SHT L-2 IRRIGATION NOTE #11, BACK
 FLOW PREVENTER SHALL BE INSTALLED BY
 LICENSED PLUMBING CONTRACTOR.
 2)SHOW LOCATION OF CONTROLLER.
 3)CLARIFY WATER SUPPLY, WELL OR CITY
 WATER.
 4)SEC 314.1 SPRINKLER HEADS SHALL BE ONE
 FOOT FROM BUILDING WALL.
 5)SHT A-1, TAB 403.1 MINIMUM FACILITIES,
 SHOW NUMBER OF EMPLOYEES AND CUSTOMERS
 FOR REST ROOM FACILITIES.
 6) CONTACT W P BEACH,WATERPLANT LAB
 SUPERVISORINDUSTRIAL COORDINATOR,
 LYNN MASSON OFFICE 561-822-2271
 E-MAIL [email protected]
 REQUIRMENTS FOE OIL AND WATER SEPERATOR.
 7)SHT P2.1SEC608 WATER SUPPLY TO CAR
 WASH EQUIPMENT, REQUIRES A BACK FLOW
 PREVENTER. (RPZV)
 8)PLUMBING NOTE #15, DISSIMULAR METALS
 SEPERATION. DIELETRIC COUPLING OR NIPPLE
 9)WATER RISER:WATER SHOCK ARRESTORS,TO
 BE LOCATED AT THE END OF EACH RUN OR
 BETWEEN THE LAST TWO FIXTURES.
 " NOT IN THE CEILING"
 END OF COMMENTS, QUESTIONS 561- 805-6692

Review Stop Z ZONING
Rev No 3 Status P Date 2006-05-31 Cont ID  
Sent By jroach Date 2006-05-31 Time 21:28 Rev Time 0.00
Received By jroach Date 2006-05-31 Time 21:28 Sent To  
Notes
2006-05-31 00:00:00**********PROVISO**********
  
 5/31/2006
  
 GATE ON DUMPSTER ENCLOSURE SHALL BE
 MODIFIED TO PROVIDE A MINIMUM CLEAR
 OPENING OF 12 FEET 6 INCHES.
  
 ADDITIONALLY, THE FOLLOWING CONDITIONS
 OF THE SPECIAL USE PERMIT SHALL BE
 COMPLETED PRIOR TO THE ISSUANCE OF A
 C.O.:
  
 1) VINES SHALL BE PLANTED ON THE EAST
 SIDE OF THE EAST SECTION OF THE SIX FOOT
 HIGH STUCCO WALL.
  
 2) PROOF OF LOCAL ADVERTISING, FOR THE
 PURPOSE OF EMPLOYING THE CITIZENS OF THE
 SURROUNDING NEIGHBORHOOD, MUST BE
 PRESENTED TO THE PLANNING DIRECTOR.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-05-23 Cont ID  
Sent By jroach Date 2006-05-23 Time 17:26 Rev Time 0.00
Received By jroach Date 2006-05-23 Time 17:26 Sent To  
Notes
2006-05-23 00:00:005/23/06 ***FAILED***
  
 1) DUMPSTER ENCLOSURE SHALL HAVE A
 MINIMUM CLEAR GATE OPENING OF
 12'6"...PROPOSED GATE IS ONLY 12'.
  
 KEEP IN MIND THE PREVIOUS CONDITIONS OF
 APPROVAL (PER ZBA CASE NO. 3115)...
  
 1) VINES SHALL BE PLANTED ON THE EAST
 SIDE OF THE EAST SECTION OF THE SIX FOOT
 HIGH STUCCO WALL.
  
 2) PROOF OF LOCAL ADVERTISING, FOR THE
 PURPOSE OF EMPLOYING THE CITIZENS OF THE
 SURROUNDING NEIGHBORHOOD, MUST BE
 PRESENTED TO THE PLANNING DIRECTOR.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-07 Cont ID  
Sent By jlong Date 2005-09-07 Time 16:10 Rev Time 0.00
Received By jlong Date 2005-09-07 Time 16:10 Sent To  
Notes
2005-09-07 00:00:00SITE PLAN AND CLASS B SPECIAL USE PERMIT
 FOR CONVENIENCE STORE APPROVED BY ZBA
 CASE NO. 3115.
  
 CONDITIONS ON APPROVAL:
 1. VINES SHALL BE PLANTED ON THE EAST
 SIDE OF THE EAST SECTION OF THE SIX FOOT
 HIGH STUCCO WALL.
 2. PROOF OF LOCAL ADVERTISING, FOR THE
 PURPOSE OF EMPLOYING THE CITIZENS OF THE
 SURROUNDING NEIGHBORHOOD, IS PRESENTED
 TO THE PLANNING DEPARTMENT DIRECTOR.


Account Summary | Usage Policy | Privacy Policy