Plan Review Details - Permit 05080765
Plan Review Stops For Permit 05080765
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-11-23 Cont ID  
Sent By jgomez Date 2005-11-23 Time 14:45 Rev Time 0.50
Received By jgomez Date 2005-11-23 Time 14:45 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-16 Cont ID  
Sent By btrobaug Date 2005-11-23 Time 10:50 Rev Time 0.50
Received By jgomez Date 2005-09-16 Time 18:21 Sent To E
Notes
2005-09-16 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- STRUCTURAL NOTE BELOW GRAVITY LOAD
 NEEDS TO BE MORE SPECIFIC. SPECIFY ALL
 DEAD LOADS. GENERAL SPECIFICATION SAYING
 "ALL DEAD LOADS PLUS 30PSF LIVE LOAD"
 DOESN'T PROVIDE CLEAR INFORMATION. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 3- UPDATE YEAR REFERENCED FOR ACI
 STANDARD. SEE CHAPTER 35 FBC 2001 FOR
 PROPER EDITION TO BE USED.
  
 4- PLANS NEED TO SPECIFY ROOF
 MATERIAL."NEW ROOF TO MATCH EXISTING"
 DOESN'T PROVIDE ANY INFORMATION. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 5- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ROOF TO BE INSTALLED.
  
 B) SIMPSON CONNECTORS SPECIFIED ON
 PLANS.
  
 6- CLARIFY IF USING PREFABRICATED ROOF
 TRUSSES OR CONVENTIONAL HAND FRAMING.
 SECTION #3 CALLS FOR TRUSSES WHILE
 FRAMING PLAN CALLS FOR 2X6 RAFTERS.
 REVISE PLANS AS REQUIRED. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 7- DETAIL #1: FOOTING NEEDS TO BE 12"
 BELOW GRADE AS REQUIRED BY SEC. 1804.1.3
 FBC 2001. INDICATE LINE OF FINISH GRADE.
  
 8- PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS FOR TOP AND BOTTOM
 CONNECTIONS OF STEEL COLUMNS NEXT TO THE
 EXTERIOR WALL. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-23 Cont ID  
Sent By btrobaug Date 2005-11-23 Time 10:44 Rev Time 0.33
Received By btrobaug Date 2005-11-23 Time 10:42 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-09-19 Cont ID  
Sent By btrobaug Date 2005-09-19 Time 09:55 Rev Time 0.33
Received By btrobaug Date 2005-09-19 Time 09:39 Sent To PC
Notes
2005-09-19 00:00:00 
  
 PLEASE NOTE THAT AN ELECTRICAL PERMIT IS
 REQUIRED TO RELOCATE CIRCUITS AS SHOWN
 ON PLAN. OWNER ACTING AS A CONTRACTOR
 MAY APPLY TO DO THE WORK. IF YOUR
 INTENTION IS TO DO THE WORK, PLEASE SIGN
 THE ELECRICAL CONTRACTOR PORTION ON THE
 APPLICATION, ALSO ANY OTHER AREAS OF
 WORK UNDER THIS APPLICATION YOU'RE
 DOING, AND NOT HIRING A CONTRACTOR, NEED
 TO BE SIGNED IN THAT (GREEN) SECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-21 Cont ID  
Sent By adarroug Date 2005-11-21 Time 11:21 Rev Time 0.00
Received By adarroug Date 2005-11-21 Time 11:21 Sent To E
Notes
2005-11-21 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 18:56 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 18:56 Sent To Z
Notes
2005-11-14 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-22 Cont ID  
Sent By adarroug Date 2005-08-22 Time 08:46 Rev Time 0.00
Received By adarroug Date 2005-08-22 Time 08:46 Sent To B
Notes
2005-08-22 00:00:00TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-19 Cont ID  
Sent By btrobaug Date 2005-09-19 Time 10:00 Rev Time 0.00
Received By btrobaug Date 2005-08-15 Time 11:19 Sent To PC
Notes
2005-08-15 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2005-11-18 Cont ID  
Sent By mmclean Date 2005-11-18 Time 16:21 Rev Time 0.00
Received By mmclean Date 2005-11-18 Time 16:20 Sent To I
Notes
2005-11-18 00:00:00NOTE: MUST HAVE 25FT WITHIN THE FRONT
 SETBACK.
  
 ONLY RECEIVED 1 SET OF PLANS IN PACKAGE.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-19 Cont ID  
Sent By mmclean Date 2005-08-19 Time 16:39 Rev Time 0.00
Received By mmclean Date 2005-08-19 Time 16:39 Sent To I
Notes
2005-08-19 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF SURVEY,
 SHOWING (HIGHLIGHT)THE AREA OF WORK WITH
 SETBACKS.
 **THIS IS NEEDED TO MAKE SURE THAT THE
 SETBACK IS MEETS THE ZONING CODE**
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720