| 2005-09-16 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- STRUCTURAL NOTE BELOW GRAVITY LOAD |
| | NEEDS TO BE MORE SPECIFIC. SPECIFY ALL |
| | DEAD LOADS. GENERAL SPECIFICATION SAYING |
| | "ALL DEAD LOADS PLUS 30PSF LIVE LOAD" |
| | DOESN'T PROVIDE CLEAR INFORMATION. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 3- UPDATE YEAR REFERENCED FOR ACI |
| | STANDARD. SEE CHAPTER 35 FBC 2001 FOR |
| | PROPER EDITION TO BE USED. |
| | |
| | 4- PLANS NEED TO SPECIFY ROOF |
| | MATERIAL."NEW ROOF TO MATCH EXISTING" |
| | DOESN'T PROVIDE ANY INFORMATION. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 5- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) ROOF TO BE INSTALLED. |
| | |
| | B) SIMPSON CONNECTORS SPECIFIED ON |
| | PLANS. |
| | |
| | 6- CLARIFY IF USING PREFABRICATED ROOF |
| | TRUSSES OR CONVENTIONAL HAND FRAMING. |
| | SECTION #3 CALLS FOR TRUSSES WHILE |
| | FRAMING PLAN CALLS FOR 2X6 RAFTERS. |
| | REVISE PLANS AS REQUIRED. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | 7- DETAIL #1: FOOTING NEEDS TO BE 12" |
| | BELOW GRADE AS REQUIRED BY SEC. 1804.1.3 |
| | FBC 2001. INDICATE LINE OF FINISH GRADE. |
| | |
| | 8- PROVIDE COMPLETE DETAIL AND |
| | SPECIFICATIONS FOR TOP AND BOTTOM |
| | CONNECTIONS OF STEEL COLUMNS NEXT TO THE |
| | EXTERIOR WALL. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |