| Plan Review Stops For Permit 05080727 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
12 |
Status |
P |
Date |
2008-11-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-11-24 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-11-24 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2008-11-24 10:33:47 | REVISION, A1, A2 MECHANICAL CLOSET DATED 11/10/8 | | | A1, A2 DATED 11/10/8 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
P |
Date |
2008-11-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-11-05 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-11-05 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2008-11-05 09:53:54 | REVISED A1, A2, NEW FS1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
F |
Date |
2008-05-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-05-08 |
Time |
11:37 |
Rev Time |
|
| Received By |
shill |
Date |
2008-05-08 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2008-05-08 11:37:50 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.AS THIS IS A FULLY SPRINKLERED BUILDING, A | | | SPRINKLER HEAD WILL BE REQUIRED IN THE NEW MECHANICAL | | | STORAGE ROOM, NFPA 13, FBC CHAPTER 9. | | | | | | 2.NO IMPACT FEES DUE PER GWEN WHITFIELD/WILLIE SWOPE | | | DUE TO SIZE OF ADDITION; AMOUNT DUE WOULD BE LESS THAN | | | $20, SO NO IMPACT FEES WOULD BE ASSESSED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2008-04-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-04-17 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-04-17 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2008-04-17 13:16:01 | REVISION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-11-09 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-11-09 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2007-11-09 15:54:14 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.PLEASE HAVE DRAWINGS REVIEWED BY DESIGNER OF RECORD | | | (SHOP DRAWING REVIEW STAMP OR LETTER).FAC61G15-30. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-25 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-25 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2007-09-25 08:46:52 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)THE PLANS HAVE SEVERAL REFERENCES TO "ROOF DECK". | | | PLEASE CLARIFY SCOPE OF WORK; ISN'T THIS FOR MEZZANINE | | | FRAMING? | | | | | | 2.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS | | | REQUIRED ON EACH SHEET (ENGINEER). | | | | | | 3.)THE HANDRAIL PLAN DOES NOT MATCH THE ELEVATION. | | | SEE FBC11-4.9.4.EXTENSIONS AT THE TOP OF THE STAIR | | | ARE NOT SHOWN ON THE PLAN, EXTENSIONS AT THE BOTTOM OF | | | THE STAIR ARE TOO SHORT, AND THE DETAIL AT THE LANDING | | | IS NOT CLEAR.PLEASE SEE REFERENCED CODE SECTION, | | | CORRELATE THE FLOOR PLAN WITH THE ELEVATION, AND | | | PROVIDE ADDITIONAL DETAILS IF NECESSARY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-01-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-16 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-16 |
Time |
11:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2006-12-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-12-26 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-12-26 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2006-12-26 13:48:35 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)ENERGY CALCS SUBMITTED ARE FOR FBC2004.THIS | | | PROJECT WAS DESIGNED UNDER FBC2001.PLEASE SUBMIT | | | ENERGY CALCS FOR FBC2001. | | | | | | **NOTE*** | | | | | | THE PERMIT WAS ISSUED WITH NEW ENERGY CALCS AS A | | | PROVISO ITEM.THE OWNER OBJECTED AND REQUESTED THAT | | | THE PERMIT NOT BE ISSUED PENDING A RESPONSE FROM | | | BUILDING OFFICIAL AS TO WHETHER OR NOT THIS IS REALLY | | | REQUIRED.SHE WAS ADVISED THAT ROBERT BROWN AND NEIL | | | MELICK ARE ON VACATION AND THAT IT MAY BE OVER A WEEK | | | BEFORE I GET A RESPONSE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2006-10-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-10-26 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-10-26 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2006-10-26 16:12:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | | | | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO | | | PERMIT PICKUP, FS713.13. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY | | | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL | | | 561-233-5025 FOR MORE INFORMATION. | | | | | | 3.)THIS PERMIT WILL BE ISSUED WITH A PROVISO - SIGNED | | | SEALED ENERGY CALCS TO BE SUBMITTED BEFORE FRAMING | | | INSPECTION. | | | | | | PLANS REDLINED, SINK TO COMLY WITH FBC11-4.24.5 | | | (FORWARD APPROACH), FBC11-4.24.6, EXPOSED PIPES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-08-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-08-04 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-08-04 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2006-08-04 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.561-233-5025 | | | | | | 3-4.)ADDRESSED. | | | | | | 5.)ENERGY CALCS REQUIRED, FBC13. SEE | | | FBC13-400.3.ABCD.2, YOU ARE ADDING FLOOR | | | SPACE SO ENERGY CALCS ARE REQUIRED PRIOR | | | TO RECEIVING A PERMIT TO BEGIN | | | RENOVATION. | | | | | | 6.)ADDRESSED. | | | | | | 7.-13.)COMMENTS RELATED TO | | | ACCESSIBILITY FOR SINK AND BATHROOM IN | | | MEZZANINE; REMOVED FROM PLAN. | | | | | | 14.)PROVIDE FIRE SPRINKLER PLANS FOR | | | THE MEZZANINE.THIS IS DECLARED AS A | | | FULLY SPRINKLED BUILDING. | | | | | | A SPRINKLER LAYOUT PLAN IS REQUIRED | | | BEFORE A PERMIT CAN BE ISSUED, FBC* | | | *106.3.5.1.1(5) | | | | | | NEW COMMENT: | | | | | | SEE PLUMBING REVIEWER'S COMMENT IN | | | REGARDS TO THE BREAK ROOM SINK.PROVIDE | | | A DETAIL; BASE CABINET CANNOT HAVE DOORS | | | BECAUSE THAT DOES NOT ALLOW THE KNEE | | | SPACE FBC11-4.24.3. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-04-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-04-18 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-04-18 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2006-04-18 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)SEE ZONING COMMENTS.NO ADDITIONAL | | | MEZZANINE SPACE IS ALLOWED IN THE | | | BUILDING BASED ON INSUFFICIENT PARKING. | | | NO BUILDING REVIEW WILL BE DONE UNLESS | | | THE ZONING ISSUE IS RESOLVED. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-31 |
Time |
15:23 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2005-08-31 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2005-08-31 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.561-233-5025 | | | | | | 3.)INTERIOR FINISH CLASSIFICATION IN | | | GENERAL NOTES IS FOR F OCCUPANCY.YOU | | | HAVE DECLARED B OCCUPANCY IN GENERAL | | | CODE INFORMATION.PLEASE CLARIFY. | | | | | | 4.)PROVIDE DESIGN LOAD INFORMATION FOR | | | THE MEZZANINE, FBC TABLE 1604.1.WHAT | | | WILL BE STORED HERE? | | | | | | 5.)ENERGY CALCS REQUIRED, FBC13. | | | | | | 6.)DECLARE AN OCCUPANT LOAD FOR THE | | | MEZZANINE. | | | | | | 7.)THE SINK IN THE MEZZANINE IS TO | | | COMPLY WITH FBC11-4.24.1 THROUGH | | | 11-4.24.7.PROVIDE COMPLIANT DETAILS. | | | | | | 8.)THE DOOR SWINGS INTO THE CLEAR | | | FLOOR SPACE FOR THE SINK, FBC11-4.24.5. | | | | | | 9.)SHOW TURNING RADIUS IN THE | | | MEZZANINE BATHROOM, FBC11-4.22.3. | | | | | | 10.)PROVIDE ACCESSIBLE LAV DETAILS FOR | | | THE MEZZANINE BATHROOM, FBC11-4.19. | | | | | | 11.)GRAB BARS REQUIRED IN MEZZANINE | | | BATHROOM, FBC11 FIGURE 29. | | | | | | 12.)PROVIDE A DETAIL FOR THE SHOWER TO | | | COMPLY WITH FBC11-4.21. | | | | | | 13.)PROVIDE A HEIGHT FOR DETAIL C-A9. | | | | | | 14.)PROVIDE FIRE SPRINKLER PLANS FOR | | | THE MEZZANINE.THIS IS DECLARED AS A | | | FULLY SPRINKLED BUILDING. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
11 |
Status |
P |
Date |
2008-12-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-16 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-16 |
Time |
08:27 |
Sent To |
PC |
|
| Notes |
| 2008-12-16 08:29:00 | THE TOTAL ALLOWANCE FOR OFFICE LIGHTING AS SHOWN IS | | | BASED ON TRACK LIGHTING. NO OTHER LIGHTING FIXTURES ARE | | | PERMITTED IN THE SAME AREA FOR GENERAL LIGHTING. THIS | | | IS OT BE VERIFIED IN FIELD. | | | LIGHTING ALLOWANCES SHALL BE PER FBC 13-415.2, AND | | | TABLE 13-4-16. MAXIMUM. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
10 |
Status |
F |
Date |
2008-11-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-11-25 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-11-25 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2008-11-25 12:12:44 | ** FAILED REVISION ** | | | | | | | | | | | | 1) NOTE: PLEASE SEE 13-415.2 OF THE 2001 FBC. PLEASE | | | PROVIDE LIGHTING PERFORMANCE LEVELS FOR NEW INSTALLED | | | NOT FOR EXISTING. IF THERE ARE ANY QUESTIONS PLEASE | | | CALL. | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2008-10-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-20 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-20 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2008-10-20 09:21:26 | | | | ** PROVISO** | | | | | | | | | | | | | | | 1) NOTE: THE LIGHTING LEVELS AT THE STAIRS ARE REQUIRED | | | TO MEET 10FT CANDLES UNDER NORMAL AND ARE PERMITTED TO | | | GO DOWN TO A MINIMUM OF 1FT CANDLE UNDER EMERGENCY. | | | NFPA-101 2003, 7.8.1.3, 7.9.2.1, .2.2 | | | THE OWNER SUBMITTED SPEC SHEETS THAT BATTERY BACK UP | | | BALLAST WILL BE ADDED TO EXISTING FIXTURES TO ACHIEVE | | | LEVELS UNDER EMERGENCY CONDITIONS. | | | THE PLANS WILL NEED TO BE REVISED BEFORE FINAL TO | | | INDICATE THE ACTUAL FIXTURES WHICH THESE UNITS WERE | | | ADDED. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
F |
Date |
2008-10-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-09 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-09 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2008-10-09 13:50:59 | ** DENIED | | | | | | | | | 1) NOTE: ONLY ONE SET OF A-1 AND A-2 SUBMITTED. THREE | | | FS -1 WERE SUBMITTED. | | | FBC 106.1 | | | CALLED AND LEFT MESSAGE ON ANDREW AIKEN'S CELL VOICE | | | MAIL. | | | | | | ** FUTURE REDLINED OF PLANS/PROVISO. WILL NEED TO | | | REVISE INDICATING NEW LIGHTS AND BATTERY BACK UP BEFORE | | | FINAL INSPECTION. ALL LEVELS OF LIGHTING PER LS -101 TO | | | BE VERIFIED. ANY LEVELS BELOW THE MINIMUM WILL REQUIRE | | | ADDITIONAL FIXTURES ETC TO ACHIEVE MINIMUM LEVELS. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2008-04-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-04-29 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-04-29 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2008-04-29 08:44:26 | ** DENIEDREVIEW ** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW DATED | | | 9/22/07 ARE STILL IN NEED OF ADDRESSING. | | | | | | 1) NOTE: PLEASE SEE COMMENTS WITH RESPECT TO | | | PHOTO-METRICS FROM SEPTEMBER 22ND, 2007 HAVE NOT BEEN | | | ADDRESSED. | | | PLEASE SUBMIT PHOTO-METRICS FOR STAIR WAY UNDER NORMAL | | | CONDITIONS SHOWING A MINIMUM OF 10FT CANDLES AND TO A | | | MINIMUM OF 1FT CANDLES UNDER EMERGENCY. | | | PLEASE SEE LS CODE, NFPA-101 7.8.1.3, 7.9.2.2. | | | | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
N |
Date |
2007-11-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-11-21 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
PC |
|
| Notes |
| 2007-11-21 11:20:19 | ELEC, NO CHANGES TO STAIRS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2007-09-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-22 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-22 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2007-09-22 11:01:21 | ** REV DENIED** | | | | | | 1) NOTE:NEEDS TO UPDATE ANY LIGHTING LAY OUTS IF | | | STRUCTURAL CHANGES ARE MADE FOR STAIR LAYOUT FOR EGRESS | | | LIGHTING PER LS 101 7.8.1.3, 7.9.2.2 | | | PLEASE SUBMIT REVISED PHOTO-METRICS/LIGHTING CHANGES. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-10-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-28 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-28 |
Time |
17:18 |
Sent To |
|
|
| Notes |
| 2006-10-28 17:19:22 | PASSED AND STAMPED ON PREVIOUS REVIEW PENDING ZONING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-07-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-06 |
Time |
20:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-06 |
Time |
20:38 |
Sent To |
|
|
| Notes |
| 2006-07-06 00:00:00 | ********* NOTE ********* | | | | | | ** PLEASE KNOW, ELECTRICAL PLANS ARE | | | STAMPED AND PASSED PENDING THE ZONING | | | REVIEW AND IF SCOPE OF WORK IS | | | PERMITTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-04-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-18 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-18 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2006-04-18 00:00:00 | **********UNSAT *********** | | | | | | 1) NOTE:PLEASE SEE COMMENTS FROM | | | ZONING AS THE PROPOSED WORK IS NOT | | | PERMITTED AS STATED. | | | | | | 2) NOTE: PLEASE KNOW, FOR FUTURE | | | REFERENCE, THE USE OF STORAGE AND TYPES | | | OF STORAGE MAY BE LIMITED DUE TO | | | MATERIALS. | | | ** THIS IS ONLY A NOTE** | | | | | | | | | PLEASE ADDRESS ZONING COMMENTS AND | | | ADJUST PLANS ACCORDINGLY. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-08-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-16 |
Time |
19:15 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2005-08-16 |
Time |
18:16 |
Sent To |
|
|
| Notes |
| 2005-08-16 00:00:00 | ************* UNSAT ************** | | | | | | 1)NOTE: PLEASE CORRELATE PLANS WITH | | | PERMIT APPLICATION AND PROPOSED WORK. | | | PLEASE SEE PERMIT APPLICATION MENTIONS | | | TO BUILD A NEW MEZZ STORAGE AREA, | | | HOWEVER ELECTRICAL PLANS SHOWS NEW BATH, | | | KITCHEN AREA, AND ALSO MENTIONS EXSITING | | | TANKLESS WATER HEATERS? | | | 215.5 | | | PLEASE SEE OTHER COMMENTS FROM OTHER | | | TRADES. | | | | | | 2)NOTE: PLEASE CORRELATE INFORMATION | | | SUBMITTED FOR TANKLESS WATER HEATERS. | | | PLEASE SEE ELECTRICAL PLANS SHOWSTWO | | | EXISTING (3KW) UNITS, PANEL SCHEDULE | | | SHOWS A 6KW AND A 3KW AND PLAUMB PLANS | | | INDICATE A 3KW AND 6KW? | | | PLEASE ALSO INDICATE A DISCONNECTING | | | MEANS FOR UNITS. | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE 2002 NEC 210.8B3, IN | | | KITCHENS IN OTHER THAN DWELLING UNITS | | | WHICH REQUIRES ALL 15- AND 20-AMPERE, | | | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE | | | KITCHENS TO BE GFCI PROTECTED. THIS | | | REQUIREMENT APPLIES TO EACH AND EVERY | | | 15- AND 20-AMPERE, 125-VOLT KITCHEN | | | RECEPTACLE, WHETHER OR NOT THE | | | RECEPTACLE SERVES COUNTERTOP APPLIANCES. | | | | | | PLEASE ADJUST. | | | | | | 4)NOTE: PLEASE SEE 700.12E FOR | | | CIRCUITING OF EM/EXT LTS. | | | THE BRANCH CIRCUIT FEEDING THE UNIT | | | EQUIPMENT SHALL BE THE SAME BRANCH | | | CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD | | | OF ANY LOCAL SWITCHES. | | | PLEASE SEE PLANS . | | | | | | 5)NOTE: PLEASE SEE ALLL RECEPTS WITHIN | | | 6' OF SINKS SHALL BE GFI/GFI PROTECTED. | | | PLEASE ALSO SEE ALL RECEPTS SHALL ALSO | | | BE GFI/GFI PROTECTED. | | | 210.8B1 | | | | | | 6)NOTE: PLEASE VERIFY OCP SHOWN FOR 10KW | | | HEATSTRIP IN AHU. | | | PLEASE SEE MIN OCP 125% 424.3B | | | THIS IS ONLY A NOTE:. | | | | | | 7)NOTE: PLEASE SEE PANEL SCHEDULE | | | INDICATES PANEL AS MLO, HOWEVER PARTIAL | | | RISER DIAGRAM SHOWS PANEL AS 150 MCB? | | | PLEASE CORRLELATE. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | PLEASE SUBMIT ONE SET OF OLD/VOIDED | | | SHEETS FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVEIW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
8 |
Status |
P |
Date |
2008-12-03 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-12-03 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-12-03 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2008-12-03 16:00:06 | REVISION #3 DATED 11/7/08. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
P |
Date |
2008-10-24 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-10-24 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-10-24 |
Time |
14:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
F |
Date |
2008-05-16 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-05-16 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-05-16 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2008-05-16 14:01:04 | ***DENIED*** | | | | | | 1) PLEASE SEE BUILDING REVIEW #1 REGARDING FIRE | | | SPRINKLER COVERAGE. PLEASE SHOW ON PLANS. ADDITIONAL | | | PERMIT WOULD NOT BE REQUIRED FOR LESS THAN (5) HEADS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-19 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-19 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2007-11-19 10:37:17 | *****PROVISO***** | | | | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S) | | | TO BE FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN | | | SATISFIED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2007-10-01 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-01 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-01 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2007-10-01 17:18:06 | *****DENIED***** | | | | | | | | | 1.THE NUMERICAL ADDRESS (INCLUDING THE SUITE NUMBER) | | | OF THE PROJECT WORK SITE SHALL BE IN THE TITLE BLOCK OF | | | EACH SUBMITTED PLAN SHEET. | | | | | | 2.PLEASE ADDRESS BUILDING PLAN REVIEW COMMENTS. | | | | | | 3.PLEASE ADDRESS ELECTRICAL PLAN REVIEW COMMENT. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-08-09 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-08-09 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-08-09 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2006-08-09 00:00:00 | ***PROVISO*** | | | | | | PLEASE SEE BUILDING REVIEW COMMENTS | | | REGARDING FIRE SPRINKLER LAYOUT | | | REQUIREMENT. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-04-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-04-21 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-04-21 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2006-04-21 00:00:00 | ******DENIED****** | | | | | | 1) FIRE REVIEW CAN NOT BE DONE AT THIS | | | TIME. PLEASE SEE ZONING REVIEW COMMENTS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-09-01 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-09-01 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2005-09-01 00:00:00 | ******DENIED****** | | | | | | 1) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 2) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS FOR HANDRAILS AND GUARDS. | | | | | | 3) PLEASE CLARIFY OCCUPANCY | | | CLASSIFICATION TO DETERMINE MINIMUM | | | INTERIOR FINISH FOR WALLS AND CEILINGS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2008-12-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-09 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-09 |
Time |
15:16 |
Sent To |
E |
|
| Notes |
| 2008-12-09 15:16:43 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2008-11-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-12 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-12 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2008-11-12 15:09:38 | TO "COMM" BD#41 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2008-10-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-02 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-02 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2008-10-02 09:04:33 | TO "COMM" BD#6 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-04-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-21 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-21 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2008-04-21 16:15:48 | TO "COMM" BD#23 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-04-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-10 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-10 |
Time |
09:32 |
Sent To |
B |
|
| Notes |
| 2008-04-10 09:33:09 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-10-26 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-26 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2007-11-13 09:46:48 | TO "COMM" BD#31 | | 2007-10-26 13:05:56 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-08-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-29 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-29 |
Time |
16:57 |
Sent To |
B |
|
| Notes |
| 2007-09-22 10:47:11 | TO COMM BOARD SPACE #32 | | 2007-08-29 16:57:26 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-07 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-07 |
Time |
11:51 |
Sent To |
B |
|
| Notes |
| 2006-12-07 11:51:34 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-10-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-23 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-23 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2006-10-26 08:35:25 | TO "COMM"BD#1 | | 2006-10-23 09:41:32 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-06-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-25 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-25 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2006-07-06 00:00:00 | TO "COMM" BD#51 | | 2006-06-25 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-03-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-24 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-24 |
Time |
18:39 |
Sent To |
|
|
| Notes |
| 2006-04-18 00:00:00 | TO "COMM" BD#57 | | 2006-03-24 00:00:00 | WAITING FO COMM BOARD, NEEDS Z>B>F>E>P> | | | REVIEWS. | | | | | | CALLED KHOOSHE AIKEN, ORIGINAL PERMIT DI | | | NOT COME BACK IN WITH PLANS, ONLY | | | PHOTO-COPY. MRS. AIKEN MENTIONED SHE | | | WOULD LOOK FOR ORIG APPLICATIONAND BRING | | | IN OR WILL BRING IN DUPLICATE. DV | | | PALMER. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-09-20 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-08-15 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2005-08-15 00:00:00 | TO "COMM" BD#3 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-11-17 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-11-17 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-11-17 |
Time |
14:44 |
Sent To |
PC |
|
| Notes |
| 2008-11-17 14:46:24 | NEW DUCTWORK FOR EXISTING AHU UNDER SUB PERMIT | | | #08110296 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-09-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-09-14 |
Time |
14:37 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2005-09-14 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2005-09-14 00:00:00 | NO MECHANICAL PLANS OR CONTRACTOR | | | INDICATED WITH PERMIT APPLICATION. | | | PLEASE PROVIDE PLANS WITH MECHANICAL | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
N |
Date |
2008-12-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-12-09 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-12-09 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2008-12-09 11:24:56 | PER ANDREW AKIN, THE PLUMBING WORK HAS BEEN DELETED AND | | | THE TOILET ROOMS WERE EXISTING. RISER DIAGRAMS NOT | | | REQUIRED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2008-12-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-12-05 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-12-04 |
Time |
16:57 |
Sent To |
B |
|
| Notes |
| 2008-12-05 10:30:34 | REVISION DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | | | | 1. SHT A-5 THE SANITARY RISER DIAGRAM AND WATER RISER | | | DIAGRAM HAVE BEEN DELETED, BUT THE ONLY FIXTURE DELETED | | | WAS THE SINK. THE TOILET ROOM AND DRINKING FOUNTAIN | | | STILL REMAIN ON THE FLOOR PLAN. PLEASE SUBMIT A | | | SANITARY RISER DIAGRAM AND A WATER RISER DIAGRAM THAT | | | REFLECT THE FLOOR PLAN. SECTION | | | 104.3.1.1(3)(4)(6)(10)(13). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2006-10-28 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-10-28 |
Time |
06:17 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-10-28 |
Time |
06:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2006-08-06 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-08-06 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-08-06 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2006-08-06 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE PLAN | | | REVIEW | | | UNSAT, THIRD TIME | | | | | | PREVIOUS COMMENT (1) NOT ADDRESSED. | | | SHT.A-1 | | | | | | (1)SECTION 11-4 | | | ACCESSIBLE ELEMENTS AND | | | SPACES:SCOPE AND TECHNICAL REQUIREMENTS | | | ?11-4.1 MINIMUM REQUIREMENTS. | | | ?11-4.1.1 APPLICATION. | | | ?11-4.1.1(1) GENERAL. THIS CODE | | | ESTABLISHES THE MINIMUM STANDARDS FOR | | | THE ACCESSIBILITY OF BUILDINGS AND | | | FACILITIES BUILT OR ALTERED WITHIN | | | THE STATE. | | | ?11-4.1.1(1)(A) ALL AREAS OF NEWLY | | | DESIGNED OR NEWLY CONSTRUCTED | | | BUILDINGS AND FACILITIES REQUIRED | | | TO BE ACCESSIBLE BY ?11-4.1.2 AND | | | ?11-4.1.3 AND ALTERED PORTIONS OF | | | EXISTING BUILDINGS AND FACILITIES | | | REQUIRED TO BE ACCESSIBLE BY | | | ?11-4.1.6 SHALL COMPLY WITH THIS CODE, | | | ?11-4.1 THROUGH ?11-4.35, UNLESS | | | OTHERWISE PROVIDED IN THIS | | | SECTION OR AS MODIFIED IN A | | | SPECIAL APPLICATION SECTION. | | | | | | (SPECIFICALY) BREAK ROOM SINK | | | ?11-4.24 SINKS. | | | ?11-4.24.1 GENERAL. SINKS REQUIRED TO | | | BE ACCESSIBLE BY ?11-4.1 SHALL | | | COMPLY WITH ?11-4.24. | | | ?11-4.24.2 HEIGHT. SINKS SHALL BE | | | MOUNTED WITH THE COUNTER OR RIM NO | | | HIGHER THAN 34 IN. (865 MM) ABOVE THE | | | FINISH FLOOR. | | | ?11-4.24.3 KNEE CLEARANCE. KNEE | | | CLEARANCE THAT IS AT LEAST 27 IN. (685 | | | MM) HIGH, 30 IN. (760 MM) WIDE, AND 19 | | | IN (485 MM) DEEP SHALL BE | | | PROVIDED UNDERNEATH SINKS. | | | ?11-4.24.4 DEPTH. EACH SINK SHALL BE A | | | MAXIMUM OF 6-1/2 IN (165 MM) | | | DEEP. | | | ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR | | | FLOOR SPACE AT LEAST 30 IN. BY 48 | | | IN. (760 MM BY 1220 MM) COMPLYING WITH | | | 11-4.2.4 SHALL BE PROVIDED IN | | | FRONT OF A SINK TO ALLOW FORWARD | | | APPROACH.THE CLEAR FLOOR SPACE SHALL | | | BE ON AN ACCESSIBLE ROUTE AND SHALL | | | EXTEND A MAXIMUM OF 19 IN. (485 MM) | | | UNDERNEATH THE SINK (SEE FIGURE | | | 11-32). | | | ?11-4.24.6 EXPOSED PIPES AND SURFACES. | | | HOT WATER AND DRAIN PIPES EXPOSED | | | UNDER SINKS SHALL BE INSULATED OR | | | OTHERWISE CONFIGURED SO AS TO PROTECT | | | AGAINST CONTACT.THERE SHALL BE NO | | | SHARP OR ABRASIVE SURFACES UNDER | | | SINKS. | | | ?11-4.24.7 FAUCETS. FAUCETS SHALL | | | COMPLY WITH ?11-4.27.4.LEVER- | | | OPERATED, PUSH-TYPE, TOUCH-TYPE, OR | | | ELECTRONICALLY CONTROLLED MECHANISMS | | | ARE ACCEPTABLE DESIGNS. | | | | | | PROVIDE A ELEVATION DRAWING SHOWING | | | COMPLIANCE WITH ABOVE COMMENTS. A FOWARD | | | APPROACH, NO DOORS ON CABNET. | | | | | | END OF COMMENTS, QUESTIONS 561-805-6691 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-04-29 |
Time |
06:28 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-04-29 |
Time |
06:28 |
Sent To |
|
|
| Notes |
| 2006-04-29 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE PLAN | | | REVIEW | | | UNSAT | | | PREVIOUS COMMENT (1),(5) NOT ADDRESSED. | | | | | | (1)SECTION 11-4 | | | ACCESSIBLE ELEMENTS AND | | | SPACES:SCOPE AND TECHNICAL REQUIREMENTS | | | ?11-4.1 MINIMUM REQUIREMENTS. | | | ?11-4.1.1 APPLICATION. | | | ?11-4.1.1(1) GENERAL. THIS CODE | | | ESTABLISHES THE MINIMUM STANDARDS FOR | | | THE ACCESSIBILITY OF BUILDINGS AND | | | FACILITIES BUILT OR ALTERED WITHIN | | | THE STATE. | | | ?11-4.1.1(1)(A) ALL AREAS OF NEWLY | | | DESIGNED OR NEWLY CONSTRUCTED | | | BUILDINGS AND FACILITIES REQUIRED | | | TO BE ACCESSIBLE BY ?11-4.1.2 AND | | | ?11-4.1.3 AND ALTERED PORTIONS OF | | | EXISTING BUILDINGS AND FACILITIES | | | REQUIRED TO BE ACCESSIBLE BY | | | ?11-4.1.6 SHALL COMPLY WITH THIS CODE, | | | ?11-4.1 THROUGH ?11-4.35, UNLESS | | | OTHERWISE PROVIDED IN THIS | | | SECTION OR AS MODIFIED IN A | | | SPECIAL APPLICATION SECTION. | | | | | | (SPECIFICALY) BREAK ROOM SINK | | | ?11-4.24 SINKS. | | | ?11-4.24.1 GENERAL. SINKS REQUIRED TO | | | BE ACCESSIBLE BY ?11-4.1 SHALL | | | COMPLY WITH ?11-4.24. | | | ?11-4.24.2 HEIGHT. SINKS SHALL BE | | | MOUNTED WITH THE COUNTER OR RIM NO | | | HIGHER THAN 34 IN. (865 MM) ABOVE THE | | | FINISH FLOOR. | | | ?11-4.24.3 KNEE CLEARANCE. KNEE | | | CLEARANCE THAT IS AT LEAST 27 IN. (685 | | | MM) HIGH, 30 IN. (760 MM) WIDE, AND 19 | | | IN (485 MM) DEEP SHALL BE | | | PROVIDED UNDERNEATH SINKS. | | | ?11-4.24.4 DEPTH. EACH SINK SHALL BE A | | | MAXIMUM OF 6-1/2 IN (165 MM) | | | DEEP. | | | ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR | | | FLOOR SPACE AT LEAST 30 IN. BY 48 | | | IN. (760 MM BY 1220 MM) COMPLYING WITH | | | 11-4.2.4 SHALL BE PROVIDED IN | | | FRONT OF A SINK TO ALLOW FORWARD | | | APPROACH.THE CLEAR FLOOR SPACE SHALL | | | BE ON AN ACCESSIBLE ROUTE AND SHALL | | | EXTEND A MAXIMUM OF 19 IN. (485 MM) | | | UNDERNEATH THE SINK (SEE FIGURE | | | 11-32). | | | ?11-4.24.6 EXPOSED PIPES AND SURFACES. | | | HOT WATER AND DRAIN PIPES EXPOSED | | | UNDER SINKS SHALL BE INSULATED OR | | | OTHERWISE CONFIGURED SO AS TO PROTECT | | | AGAINST CONTACT.THERE SHALL BE NO | | | SHARP OR ABRASIVE SURFACES UNDER | | | SINKS. | | | ?11-4.24.7 FAUCETS. FAUCETS SHALL | | | COMPLY WITH ?11-4.27.4.LEVER- | | | OPERATED, PUSH-TYPE, TOUCH-TYPE, OR | | | ELECTRONICALLY CONTROLLED MECHANISMS | | | ARE ACCEPTABLE DESIGNS. | | | | | | | | | 5) SHT A-5 WATER RISER DIAGRAM: | | | SHOWS AIR CHAMBERS AT THE TOP OF WATER | | | RISERS. COMPLY WITH SEC 604.9 | | | | | | ?P604.9 WATER HAMMER. THE FLOW VELOCITY | | | OF THE WATER DISTRIBUTION SYSTEM | | | SHALL BE CONTROLLED TO REDUCE THE | | | POSSIBILITY OF WATER HAMMER.A WATER- | | | HAMMER ARRESTOR SHALL BE INSTALLED WHERE | | | QUICK-CLOSING VALVES ARE UTILIZED, | | | UNLESS OTHERWISE APPROVED.THE ARRESTOR | | | SHALL BE LOCATED WITHIN AN | | | EFFECTIVE RANGE OF THE QUICK-CLOSING | | | VALVE.WATER-HAMMER ARRESTORS SHALL | | | CONFORM TO ASSE 1010.ACCESS SHALL BE | | | PROVIDED TO WATER-HAMMER ARRESTORS. | | | | | | NEW COMMENTS | | | SHT A-2,A-5 DELETED SHOWER | | | ?P704.5 DEAD ENDS. IN THE INSTALLATION | | | OR REMOVAL OF ANY PART OF A | | | DRAINAGE SYSTEM, DEAD ENDS SHALL BE | | | PROHIBITED. | | | WATER LINES FOR FUTURE SHOWER CAPED AT | | | TEE. | | | END OF COMMENTS QUESTIONS 561`-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-08-20 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-08-20 |
Time |
06:45 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-08-20 |
Time |
06:45 |
Sent To |
M |
|
| Notes |
| 2005-08-20 00:00:00 | PAUL SCHMITZ, | | | PLUMBING PLAN REVIEW EXAMINER | | | [email protected] | | | | | | FBC 2001 DENIED | | | | | | (1)SECTION 11-4 | | | ACCESSIBLE ELEMENTS AND | | | SPACES:SCOPE AND TECHNICAL REQUIREMENTS | | | ?11-4.1 MINIMUM REQUIREMENTS. | | | ?11-4.1.1 APPLICATION. | | | ?11-4.1.1(1) GENERAL. THIS CODE | | | ESTABLISHES THE MINIMUM STANDARDS FOR | | | THE ACCESSIBILITY OF BUILDINGS AND | | | FACILITIES BUILT OR ALTERED WITHIN | | | THE STATE. | | | ?11-4.1.1(1)(A) ALL AREAS OF NEWLY | | | DESIGNED OR NEWLY CONSTRUCTED | | | BUILDINGS AND FACILITIES REQUIRED | | | TO BE ACCESSIBLE BY ?11-4.1.2 AND | | | ?11-4.1.3 AND ALTERED PORTIONS OF | | | EXISTING BUILDINGS AND FACILITIES | | | REQUIRED TO BE ACCESSIBLE BY | | | ?11-4.1.6 SHALL COMPLY WITH THIS CODE, | | | ?11-4.1 THROUGH ?11-4.35, UNLESS | | | OTHERWISE PROVIDED IN THIS | | | SECTION OR AS MODIFIED IN A | | | SPECIAL APPLICATION SECTION. | | | | | | (2) 11-4.22 TOILET ROOMS. | | | ?11-4.22.1 MINIMUM NUMBER. TOILET | | | FACILITIES REQUIRED TO BE ACCESSIBLE | | | BY ?11-4.1 SHALL COMPLY WITH ?11-4.22. | | | ACCESSIBLE TOILET ROOMS SHALL BE | | | ON AN ACCESSIBLE ROUTE. | | | ?11-4.22.2 DOORS. | | | ?11-4.22.2(1) ALL DOORS TO | | | ACCESSIBLE TOILET ROOMS SHALL COMPLY | | | WITH | | | ?11-4.13.DOORS SHALL NOT SWING | | | INTO THE CLEAR FLOOR SPACE REQUIRED | | | FOR ANY FIXTURE. | | | | | | (3) ?11-4.23.3 CLEAR FLOOR SPACE. THE | | | ACCESSIBLE FIXTURES AND CONTROLS | | | REQUIRED IN ?11-4.23.4, ?11-4.23.5, | | | ?11-4.23.6, ?11-4.23.7, ?11-4.23.8, | | | AND ?11-4.23.9 SHALL BE ON AN | | | ACCESSIBLE ROUTE.AN UNOBSTRUCTED | | | TURNING | | | SPACE COMPLYING WITH ?11-4.2.3 SHALL | | | BE PROVIDED WITHIN AN ACCESSIBLE | | | BATHROOM.THE CLEAR FLOOR SPACES AT | | | FIXTURES AND CONTROLS, THE | | | ACCESSIBLE ROUTE, AND THE TURNING | | | SPACE MAY OVERLAP. | | | | | | (4)?11-4.21 SHOWER STALLS. | | | ?11-4.21.1 GENERAL. ACCESSIBLE SHOWER | | | STALLS SHALL COMPLY WITH ?11-4.21. | | | ?11-4.21.2 SIZE AND CLEARANCES. EXCEPT | | | AS SPECIFIED IN ?11-9.1.2, SHOWER | | | STALL SIZE AND CLEAR FLOOR SPACE SHALL | | | COMPLY WITH FIGURE 11-35(A) OR | | | FIGURE 11-35(B).THE SHOWER STALL IN | | | FIGURE 11-35(A) SHALL BE 36 | | | INCHES BY 36 INCHES (915 MM BY 915 | | | MM).SHOWER STALLS REQUIRED BY | | | ?11-9.1.2 SHALL COMPLY WITH FIGURE | | | 11-57(A) OR FIGURE 11-57(B).THE | | | SHOWER STALL IN FIGURE 11-35(B) WILL | | | FIT INTO THE SPACE REQUIRED FOR A | | | BATHTUB. | | | (5) SHT A-5 WATER RISER DIAGRAM: | | | SHOWS AIR CHAMBERS AT THE TOP OF WATER | | | RISERS. COMPLY WITH SEC 604.9 | | | | | | ?P604.9 WATER HAMMER. THE FLOW VELOCITY | | | OF THE WATER DISTRIBUTION SYSTEM | | | SHALL BE CONTROLLED TO REDUCE THE | | | POSSIBILITY OF WATER HAMMER.A WATER- | | | HAMMER ARRESTOR SHALL BE INSTALLED WHERE | | | QUICK-CLOSING VALVES ARE UTILIZED, | | | UNLESS OTHERWISE APPROVED.THE ARRESTOR | | | SHALL BE LOCATED WITHIN AN | | | EFFECTIVE RANGE OF THE QUICK-CLOSING | | | VALVE.WATER-HAMMER ARRESTORS SHALL | | | CONFORM TO ASSE 1010.ACCESS SHALL BE | | | PROVIDED TO WATER-HAMMER ARRESTORS. | | | END OF COMMENTS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
8 |
Status |
P |
Date |
2008-11-18 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2008-11-18 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2008-11-18 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2008-11-18 15:24:25 | RESTAMP 836 SQ. FT. MEZZANINE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
7 |
Status |
N |
Date |
2008-10-03 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2008-10-03 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2008-10-03 |
Time |
08:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2008-04-23 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2008-04-23 |
Time |
19:17 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2008-04-23 |
Time |
19:17 |
Sent To |
|
|
| Notes |
| 2008-04-23 19:18:53 | REVISION NO. 4 - ADDITIONAL 68 SQ. FT. OF MEZZANINE | | | SPACE (ENCLOSED CLOSET) BRINGS TOTAL FOR THIS BAY TO | | | 836 SQ. FT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
N |
Date |
2007-09-26 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-09-26 |
Time |
18:34 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-09-26 |
Time |
18:34 |
Sent To |
|
|
| Notes |
| 2007-09-26 18:34:36 | MEZZANINE STILL SHOWS AS STORAGE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
N |
Date |
2006-11-01 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2006-11-01 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2006-11-01 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2006-11-01 16:47:07 | MEZZININE IS STILL FOR BUSINESS STORAGE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2006-07-17 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2006-07-17 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2006-07-17 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2006-07-17 00:00:00 | MEZZANINE APPROVED FOR STORAGE ONLY. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-04-11 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-04-11 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-04-11 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2006-04-11 00:00:00 | 1) NO ADDITIONAL MEZZANINE SPACE IS | | | ALLOWED IN THE BUILDING BASED ON | | | INSUFFICIENT PARKING FOR THE ADDITINAL | | | SQUARE FOOTAGE. | | | | | | 2) THE MEZZANINE PROPOSED AS PART OF | | | THIS PERMIT MAY NOT BE CALLED BUSINESS | | | STORAGE AS THE MEZZANINE INCLUDES A | | | BATHROOM WITH CLOSET, A REFRIGERATOR, | | | AND A COUNTER AREA WHICH INCLUDES A SINK | | | AND CABINETS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-09-20 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-09-20 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2005-09-20 00:00:00 | DENIED, | | | 1. NEED TO PROVIDE THE APPROVED LIST OF | | | MEZZANINE FOR ALL UNITS AT ADDRESS (1335 | | | OLD OKEECHOBEE). |
|
|