Plan Review Details - Permit 05080727
Plan Review Stops For Permit 05080727
Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2008-11-24 Cont ID  
Sent By shill Date 2008-11-24 Time 10:31 Rev Time 0.00
Received By shill Date 2008-11-24 Time 10:31 Sent To  
Notes
2008-11-24 10:33:47REVISION, A1, A2 MECHANICAL CLOSET DATED 11/10/8
 A1, A2 DATED 11/10/8
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2008-11-05 Cont ID  
Sent By shill Date 2008-11-05 Time 09:53 Rev Time 0.00
Received By shill Date 2008-11-05 Time 09:53 Sent To  
Notes
2008-11-05 09:53:54REVISED A1, A2, NEW FS1

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2008-05-08 Cont ID  
Sent By shill Date 2008-05-08 Time 11:37 Rev Time  
Received By shill Date 2008-05-08 Time 11:02 Sent To  
Notes
2008-05-08 11:37:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.AS THIS IS A FULLY SPRINKLERED BUILDING, A
 SPRINKLER HEAD WILL BE REQUIRED IN THE NEW MECHANICAL
 STORAGE ROOM, NFPA 13, FBC CHAPTER 9.
  
 2.NO IMPACT FEES DUE PER GWEN WHITFIELD/WILLIE SWOPE
 DUE TO SIZE OF ADDITION; AMOUNT DUE WOULD BE LESS THAN
 $20, SO NO IMPACT FEES WOULD BE ASSESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-04-17 Cont ID  
Sent By shill Date 2008-04-17 Time 13:11 Rev Time 0.00
Received By shill Date 2008-04-17 Time 13:11 Sent To  
Notes
2008-04-17 13:16:01REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2007-11-09 Cont ID  
Sent By shill Date 2007-11-09 Time 15:52 Rev Time 0.00
Received By shill Date 2007-11-09 Time 15:52 Sent To  
Notes
2007-11-09 15:54:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PLEASE HAVE DRAWINGS REVIEWED BY DESIGNER OF RECORD
 (SHOP DRAWING REVIEW STAMP OR LETTER).FAC61G15-30.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-09-25 Cont ID  
Sent By shill Date 2007-09-25 Time 08:42 Rev Time 0.00
Received By shill Date 2007-09-25 Time 08:42 Sent To  
Notes
2007-09-25 08:46:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)THE PLANS HAVE SEVERAL REFERENCES TO "ROOF DECK".
 PLEASE CLARIFY SCOPE OF WORK; ISN'T THIS FOR MEZZANINE
 FRAMING?
  
 2.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS
 REQUIRED ON EACH SHEET (ENGINEER).
  
 3.)THE HANDRAIL PLAN DOES NOT MATCH THE ELEVATION.
 SEE FBC11-4.9.4.EXTENSIONS AT THE TOP OF THE STAIR
 ARE NOT SHOWN ON THE PLAN, EXTENSIONS AT THE BOTTOM OF
 THE STAIR ARE TOO SHORT, AND THE DETAIL AT THE LANDING
 IS NOT CLEAR.PLEASE SEE REFERENCED CODE SECTION,
 CORRELATE THE FLOOR PLAN WITH THE ELEVATION, AND
 PROVIDE ADDITIONAL DETAILS IF NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-01-16 Cont ID  
Sent By shill Date 2007-01-16 Time 11:32 Rev Time 0.00
Received By shill Date 2007-01-16 Time 11:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-12-26 Cont ID  
Sent By shill Date 2006-12-26 Time 12:23 Rev Time 0.00
Received By shill Date 2006-12-26 Time 12:23 Sent To  
Notes
2006-12-26 13:48:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)ENERGY CALCS SUBMITTED ARE FOR FBC2004.THIS
 PROJECT WAS DESIGNED UNDER FBC2001.PLEASE SUBMIT
 ENERGY CALCS FOR FBC2001.
  
 **NOTE***
  
 THE PERMIT WAS ISSUED WITH NEW ENERGY CALCS AS A
 PROVISO ITEM.THE OWNER OBJECTED AND REQUESTED THAT
 THE PERMIT NOT BE ISSUED PENDING A RESPONSE FROM
 BUILDING OFFICIAL AS TO WHETHER OR NOT THIS IS REALLY
 REQUIRED.SHE WAS ADVISED THAT ROBERT BROWN AND NEIL
 MELICK ARE ON VACATION AND THAT IT MAY BE OVER A WEEK
 BEFORE I GET A RESPONSE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-10-26 Cont ID  
Sent By shill Date 2006-10-26 Time 16:04 Rev Time 0.00
Received By shill Date 2006-10-26 Time 16:04 Sent To  
Notes
2006-10-26 16:12:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 3.)THIS PERMIT WILL BE ISSUED WITH A PROVISO - SIGNED
 SEALED ENERGY CALCS TO BE SUBMITTED BEFORE FRAMING
 INSPECTION.
  
 PLANS REDLINED, SINK TO COMLY WITH FBC11-4.24.5
 (FORWARD APPROACH), FBC11-4.24.6, EXPOSED PIPES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-04 Cont ID  
Sent By shill Date 2006-08-04 Time 13:04 Rev Time 0.00
Received By shill Date 2006-08-04 Time 13:04 Sent To  
Notes
2006-08-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3-4.)ADDRESSED.
  
 5.)ENERGY CALCS REQUIRED, FBC13. SEE
 FBC13-400.3.ABCD.2, YOU ARE ADDING FLOOR
 SPACE SO ENERGY CALCS ARE REQUIRED PRIOR
 TO RECEIVING A PERMIT TO BEGIN
 RENOVATION.
  
 6.)ADDRESSED.
  
 7.-13.)COMMENTS RELATED TO
 ACCESSIBILITY FOR SINK AND BATHROOM IN
 MEZZANINE; REMOVED FROM PLAN.
  
 14.)PROVIDE FIRE SPRINKLER PLANS FOR
 THE MEZZANINE.THIS IS DECLARED AS A
 FULLY SPRINKLED BUILDING.
  
 A SPRINKLER LAYOUT PLAN IS REQUIRED
 BEFORE A PERMIT CAN BE ISSUED, FBC*
 *106.3.5.1.1(5)
  
 NEW COMMENT:
  
 SEE PLUMBING REVIEWER'S COMMENT IN
 REGARDS TO THE BREAK ROOM SINK.PROVIDE
 A DETAIL; BASE CABINET CANNOT HAVE DOORS
 BECAUSE THAT DOES NOT ALLOW THE KNEE
 SPACE FBC11-4.24.3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-18 Cont ID  
Sent By shill Date 2006-04-18 Time 08:48 Rev Time 0.00
Received By shill Date 2006-04-18 Time 08:48 Sent To  
Notes
2006-04-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SEE ZONING COMMENTS.NO ADDITIONAL
 MEZZANINE SPACE IS ALLOWED IN THE
 BUILDING BASED ON INSUFFICIENT PARKING.
 NO BUILDING REVIEW WILL BE DONE UNLESS
 THE ZONING ISSUE IS RESOLVED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-31 Cont ID  
Sent By shill Date 2005-08-31 Time 15:23 Rev Time 2.00
Received By shill Date 2005-08-31 Time 14:09 Sent To  
Notes
2005-08-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3.)INTERIOR FINISH CLASSIFICATION IN
 GENERAL NOTES IS FOR F OCCUPANCY.YOU
 HAVE DECLARED B OCCUPANCY IN GENERAL
 CODE INFORMATION.PLEASE CLARIFY.
  
 4.)PROVIDE DESIGN LOAD INFORMATION FOR
 THE MEZZANINE, FBC TABLE 1604.1.WHAT
 WILL BE STORED HERE?
  
 5.)ENERGY CALCS REQUIRED, FBC13.
  
 6.)DECLARE AN OCCUPANT LOAD FOR THE
 MEZZANINE.
  
 7.)THE SINK IN THE MEZZANINE IS TO
 COMPLY WITH FBC11-4.24.1 THROUGH
 11-4.24.7.PROVIDE COMPLIANT DETAILS.
  
 8.)THE DOOR SWINGS INTO THE CLEAR
 FLOOR SPACE FOR THE SINK, FBC11-4.24.5.
  
 9.)SHOW TURNING RADIUS IN THE
 MEZZANINE BATHROOM, FBC11-4.22.3.
  
 10.)PROVIDE ACCESSIBLE LAV DETAILS FOR
 THE MEZZANINE BATHROOM, FBC11-4.19.
  
 11.)GRAB BARS REQUIRED IN MEZZANINE
 BATHROOM, FBC11 FIGURE 29.
  
 12.)PROVIDE A DETAIL FOR THE SHOWER TO
 COMPLY WITH FBC11-4.21.
  
 13.)PROVIDE A HEIGHT FOR DETAIL C-A9.
  
 14.)PROVIDE FIRE SPRINKLER PLANS FOR
 THE MEZZANINE.THIS IS DECLARED AS A
 FULLY SPRINKLED BUILDING.
  

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2008-12-16 Cont ID  
Sent By dpalmer Date 2008-12-16 Time 08:27 Rev Time 0.00
Received By dpalmer Date 2008-12-16 Time 08:27 Sent To PC
Notes
2008-12-16 08:29:00THE TOTAL ALLOWANCE FOR OFFICE LIGHTING AS SHOWN IS
 BASED ON TRACK LIGHTING. NO OTHER LIGHTING FIXTURES ARE
 PERMITTED IN THE SAME AREA FOR GENERAL LIGHTING. THIS
 IS OT BE VERIFIED IN FIELD.
 LIGHTING ALLOWANCES SHALL BE PER FBC 13-415.2, AND
 TABLE 13-4-16. MAXIMUM.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2008-11-25 Cont ID  
Sent By dpalmer Date 2008-11-25 Time 12:12 Rev Time 0.00
Received By dpalmer Date 2008-11-25 Time 12:12 Sent To  
Notes
2008-11-25 12:12:44** FAILED REVISION **
  
  
  
 1) NOTE: PLEASE SEE 13-415.2 OF THE 2001 FBC. PLEASE
 PROVIDE LIGHTING PERFORMANCE LEVELS FOR NEW INSTALLED
 NOT FOR EXISTING. IF THERE ARE ANY QUESTIONS PLEASE
 CALL.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2008-10-20 Cont ID  
Sent By dpalmer Date 2008-10-20 Time 09:21 Rev Time 0.00
Received By dpalmer Date 2008-10-20 Time 09:21 Sent To  
Notes
2008-10-20 09:21:26 
 ** PROVISO**
  
  
  
  
 1) NOTE: THE LIGHTING LEVELS AT THE STAIRS ARE REQUIRED
 TO MEET 10FT CANDLES UNDER NORMAL AND ARE PERMITTED TO
 GO DOWN TO A MINIMUM OF 1FT CANDLE UNDER EMERGENCY.
 NFPA-101 2003, 7.8.1.3, 7.9.2.1, .2.2
 THE OWNER SUBMITTED SPEC SHEETS THAT BATTERY BACK UP
 BALLAST WILL BE ADDED TO EXISTING FIXTURES TO ACHIEVE
 LEVELS UNDER EMERGENCY CONDITIONS.
 THE PLANS WILL NEED TO BE REVISED BEFORE FINAL TO
 INDICATE THE ACTUAL FIXTURES WHICH THESE UNITS WERE
 ADDED.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2008-10-09 Cont ID  
Sent By dpalmer Date 2008-10-09 Time 13:49 Rev Time 0.00
Received By dpalmer Date 2008-10-09 Time 13:49 Sent To  
Notes
2008-10-09 13:50:59** DENIED
  
  
 1) NOTE: ONLY ONE SET OF A-1 AND A-2 SUBMITTED. THREE
 FS -1 WERE SUBMITTED.
 FBC 106.1
 CALLED AND LEFT MESSAGE ON ANDREW AIKEN'S CELL VOICE
 MAIL.
  
 ** FUTURE REDLINED OF PLANS/PROVISO. WILL NEED TO
 REVISE INDICATING NEW LIGHTS AND BATTERY BACK UP BEFORE
 FINAL INSPECTION. ALL LEVELS OF LIGHTING PER LS -101 TO
 BE VERIFIED. ANY LEVELS BELOW THE MINIMUM WILL REQUIRE
 ADDITIONAL FIXTURES ETC TO ACHIEVE MINIMUM LEVELS.
  
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-04-29 Cont ID  
Sent By dpalmer Date 2008-04-29 Time 08:44 Rev Time 0.00
Received By dpalmer Date 2008-04-29 Time 08:44 Sent To  
Notes
2008-04-29 08:44:26** DENIEDREVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW DATED
 9/22/07 ARE STILL IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE COMMENTS WITH RESPECT TO
 PHOTO-METRICS FROM SEPTEMBER 22ND, 2007 HAVE NOT BEEN
 ADDRESSED.
 PLEASE SUBMIT PHOTO-METRICS FOR STAIR WAY UNDER NORMAL
 CONDITIONS SHOWING A MINIMUM OF 10FT CANDLES AND TO A
 MINIMUM OF 1FT CANDLES UNDER EMERGENCY.
 PLEASE SEE LS CODE, NFPA-101 7.8.1.3, 7.9.2.2.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status N Date 2007-11-21 Cont ID  
Sent By dpalmer Date 2007-11-21 Time 11:19 Rev Time 0.00
Received By dpalmer Date   Time   Sent To PC
Notes
2007-11-21 11:20:19ELEC, NO CHANGES TO STAIRS.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-09-22 Cont ID  
Sent By dpalmer Date 2007-09-22 Time 10:58 Rev Time 0.00
Received By dpalmer Date 2007-09-22 Time 10:58 Sent To  
Notes
2007-09-22 11:01:21** REV DENIED**
  
 1) NOTE:NEEDS TO UPDATE ANY LIGHTING LAY OUTS IF
 STRUCTURAL CHANGES ARE MADE FOR STAIR LAYOUT FOR EGRESS
 LIGHTING PER LS 101 7.8.1.3, 7.9.2.2
 PLEASE SUBMIT REVISED PHOTO-METRICS/LIGHTING CHANGES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-28 Cont ID  
Sent By dpalmer Date 2006-10-28 Time 17:18 Rev Time 0.00
Received By dpalmer Date 2006-10-28 Time 17:18 Sent To  
Notes
2006-10-28 17:19:22PASSED AND STAMPED ON PREVIOUS REVIEW PENDING ZONING.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-06 Cont ID  
Sent By dpalmer Date 2006-07-06 Time 20:38 Rev Time 0.00
Received By dpalmer Date 2006-07-06 Time 20:38 Sent To  
Notes
2006-07-06 00:00:00********* NOTE *********
  
 ** PLEASE KNOW, ELECTRICAL PLANS ARE
 STAMPED AND PASSED PENDING THE ZONING
 REVIEW AND IF SCOPE OF WORK IS
 PERMITTED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-18 Cont ID  
Sent By dpalmer Date 2006-04-18 Time 12:05 Rev Time 0.00
Received By dpalmer Date 2006-04-18 Time 11:47 Sent To  
Notes
2006-04-18 00:00:00**********UNSAT ***********
  
 1) NOTE:PLEASE SEE COMMENTS FROM
 ZONING AS THE PROPOSED WORK IS NOT
 PERMITTED AS STATED.
  
 2) NOTE: PLEASE KNOW, FOR FUTURE
 REFERENCE, THE USE OF STORAGE AND TYPES
 OF STORAGE MAY BE LIMITED DUE TO
 MATERIALS.
 ** THIS IS ONLY A NOTE**
  
  
 PLEASE ADDRESS ZONING COMMENTS AND
 ADJUST PLANS ACCORDINGLY.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-16 Cont ID  
Sent By dpalmer Date 2005-08-16 Time 19:15 Rev Time 1.00
Received By dpalmer Date 2005-08-16 Time 18:16 Sent To  
Notes
2005-08-16 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE CORRELATE PLANS WITH
 PERMIT APPLICATION AND PROPOSED WORK.
 PLEASE SEE PERMIT APPLICATION MENTIONS
 TO BUILD A NEW MEZZ STORAGE AREA,
 HOWEVER ELECTRICAL PLANS SHOWS NEW BATH,
 KITCHEN AREA, AND ALSO MENTIONS EXSITING
 TANKLESS WATER HEATERS?
 215.5
 PLEASE SEE OTHER COMMENTS FROM OTHER
 TRADES.
  
 2)NOTE: PLEASE CORRELATE INFORMATION
 SUBMITTED FOR TANKLESS WATER HEATERS.
 PLEASE SEE ELECTRICAL PLANS SHOWSTWO
 EXISTING (3KW) UNITS, PANEL SCHEDULE
 SHOWS A 6KW AND A 3KW AND PLAUMB PLANS
 INDICATE A 3KW AND 6KW?
 PLEASE ALSO INDICATE A DISCONNECTING
 MEANS FOR UNITS.
 215.5
  
 3)NOTE: PLEASE SEE 2002 NEC 210.8B3, IN
 KITCHENS IN OTHER THAN DWELLING UNITS
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 PLEASE ADJUST.
  
 4)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE SEE PLANS .
  
 5)NOTE: PLEASE SEE ALLL RECEPTS WITHIN
 6' OF SINKS SHALL BE GFI/GFI PROTECTED.
 PLEASE ALSO SEE ALL RECEPTS SHALL ALSO
 BE GFI/GFI PROTECTED.
 210.8B1
  
 6)NOTE: PLEASE VERIFY OCP SHOWN FOR 10KW
 HEATSTRIP IN AHU.
 PLEASE SEE MIN OCP 125% 424.3B
 THIS IS ONLY A NOTE:.
  
 7)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES PANEL AS MLO, HOWEVER PARTIAL
 RISER DIAGRAM SHOWS PANEL AS 150 MCB?
 PLEASE CORRLELATE.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVEIW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2008-12-03 Cont ID  
Sent By mwennerg Date 2008-12-03 Time 15:59 Rev Time 0.00
Received By mwennerg Date 2008-12-03 Time 15:59 Sent To  
Notes
2008-12-03 16:00:06REVISION #3 DATED 11/7/08.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-10-24 Cont ID  
Sent By mwennerg Date 2008-10-24 Time 14:34 Rev Time 0.00
Received By mwennerg Date 2008-10-24 Time 14:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status F Date 2008-05-16 Cont ID  
Sent By mwennerg Date 2008-05-16 Time 13:52 Rev Time 0.00
Received By mwennerg Date 2008-05-16 Time 13:52 Sent To  
Notes
2008-05-16 14:01:04***DENIED***
  
 1) PLEASE SEE BUILDING REVIEW #1 REGARDING FIRE
 SPRINKLER COVERAGE. PLEASE SHOW ON PLANS. ADDITIONAL
 PERMIT WOULD NOT BE REQUIRED FOR LESS THAN (5) HEADS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-11-19 Cont ID  
Sent By mawillia Date 2007-11-19 Time 10:38 Rev Time 0.00
Received By mawillia Date 2007-11-19 Time 10:29 Sent To  
Notes
2007-11-19 10:37:17*****PROVISO*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S)
 TO BE FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN
 SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2007-10-01 Cont ID  
Sent By mawillia Date 2007-10-01 Time 17:18 Rev Time 0.00
Received By mawillia Date 2007-10-01 Time 17:09 Sent To  
Notes
2007-10-01 17:18:06*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS (INCLUDING THE SUITE NUMBER)
 OF THE PROJECT WORK SITE SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.
  
 2.PLEASE ADDRESS BUILDING PLAN REVIEW COMMENTS.
  
 3.PLEASE ADDRESS ELECTRICAL PLAN REVIEW COMMENT.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-08-09 Cont ID  
Sent By mwennerg Date 2006-08-09 Time 10:29 Rev Time 0.00
Received By mwennerg Date 2006-08-09 Time 10:29 Sent To  
Notes
2006-08-09 00:00:00***PROVISO***
  
 PLEASE SEE BUILDING REVIEW COMMENTS
 REGARDING FIRE SPRINKLER LAYOUT
 REQUIREMENT.
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-04-21 Cont ID  
Sent By mwennerg Date 2006-04-21 Time 11:12 Rev Time 0.00
Received By mwennerg Date 2006-04-21 Time 11:12 Sent To  
Notes
2006-04-21 00:00:00******DENIED******
  
 1) FIRE REVIEW CAN NOT BE DONE AT THIS
 TIME. PLEASE SEE ZONING REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-01 Cont ID  
Sent By mwennerg Date 2005-09-01 Time 09:53 Rev Time 0.00
Received By mwennerg Date 2005-09-01 Time 09:53 Sent To  
Notes
2005-09-01 00:00:00******DENIED******
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 2) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND GUARDS.
  
 3) PLEASE CLARIFY OCCUPANCY
 CLASSIFICATION TO DETERMINE MINIMUM
 INTERIOR FINISH FOR WALLS AND CEILINGS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-12-09 Cont ID  
Sent By adarroug Date 2008-12-09 Time 15:16 Rev Time 0.00
Received By adarroug Date 2008-12-09 Time 15:16 Sent To E
Notes
2008-12-09 15:16:43TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-11-12 Cont ID  
Sent By adarroug Date 2008-11-12 Time 15:07 Rev Time 0.00
Received By adarroug Date 2008-11-12 Time 15:07 Sent To  
Notes
2008-11-12 15:09:38TO "COMM" BD#41

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-10-02 Cont ID  
Sent By adarroug Date 2008-10-02 Time 09:04 Rev Time 0.00
Received By adarroug Date 2008-10-02 Time 09:04 Sent To  
Notes
2008-10-02 09:04:33TO "COMM" BD#6

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-04-21 Cont ID  
Sent By adarroug Date 2008-04-21 Time 16:15 Rev Time 0.00
Received By adarroug Date 2008-04-21 Time 16:15 Sent To  
Notes
2008-04-21 16:15:48TO "COMM" BD#23

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-04-10 Cont ID  
Sent By adarroug Date 2008-04-10 Time 09:32 Rev Time 0.00
Received By adarroug Date 2008-04-10 Time 09:32 Sent To B
Notes
2008-04-10 09:33:09TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-26 Cont ID  
Sent By shill Date 2007-10-26 Time 13:05 Rev Time 0.00
Received By shill Date 2007-10-26 Time 13:05 Sent To  
Notes
2007-11-13 09:46:48TO "COMM" BD#31
2007-10-26 13:05:56WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 16:57 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 16:57 Sent To B
Notes
2007-09-22 10:47:11TO COMM BOARD SPACE #32
2007-08-29 16:57:26WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-07 Cont ID  
Sent By adarroug Date 2006-12-07 Time 11:51 Rev Time 0.00
Received By adarroug Date 2006-12-07 Time 11:51 Sent To B
Notes
2006-12-07 11:51:34TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-23 Cont ID  
Sent By adarroug Date 2006-10-23 Time 09:41 Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 09:41 Sent To  
Notes
2006-10-26 08:35:25TO "COMM"BD#1
2006-10-23 09:41:32WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-25 Cont ID  
Sent By adarroug Date 2006-06-25 Time 16:31 Rev Time 0.00
Received By adarroug Date 2006-06-25 Time 16:31 Sent To  
Notes
2006-07-06 00:00:00TO "COMM" BD#51
2006-06-25 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 18:40 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 18:39 Sent To  
Notes
2006-04-18 00:00:00TO "COMM" BD#57
2006-03-24 00:00:00WAITING FO COMM BOARD, NEEDS Z>B>F>E>P>
 REVIEWS.
  
 CALLED KHOOSHE AIKEN, ORIGINAL PERMIT DI
 NOT COME BACK IN WITH PLANS, ONLY
 PHOTO-COPY. MRS. AIKEN MENTIONED SHE
 WOULD LOOK FOR ORIG APPLICATIONAND BRING
 IN OR WILL BRING IN DUPLICATE. DV
 PALMER.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-20 Cont ID  
Sent By mmclean Date 2005-09-20 Time 10:25 Rev Time 0.00
Received By mmclean Date 2005-08-15 Time 13:58 Sent To  
Notes
2005-08-15 00:00:00TO "COMM" BD#3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-11-17 Cont ID  
Sent By rregueir Date 2008-11-17 Time 14:44 Rev Time 0.00
Received By rregueir Date 2008-11-17 Time 14:44 Sent To PC
Notes
2008-11-17 14:46:24NEW DUCTWORK FOR EXISTING AHU UNDER SUB PERMIT
 #08110296

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-14 Cont ID  
Sent By pkrauss Date 2005-09-14 Time 14:37 Rev Time 0.25
Received By pkrauss Date 2005-09-14 Time 14:30 Sent To  
Notes
2005-09-14 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
 PLEASE PROVIDE PLANS WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 6 Status N Date 2008-12-09 Cont ID  
Sent By kstevens Date 2008-12-09 Time 11:23 Rev Time 0.00
Received By kstevens Date 2008-12-09 Time 11:23 Sent To  
Notes
2008-12-09 11:24:56PER ANDREW AKIN, THE PLUMBING WORK HAS BEEN DELETED AND
 THE TOILET ROOMS WERE EXISTING. RISER DIAGRAMS NOT
 REQUIRED.

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-12-05 Cont ID  
Sent By kstevens Date 2008-12-05 Time 10:25 Rev Time 0.00
Received By kstevens Date 2008-12-04 Time 16:57 Sent To B
Notes
2008-12-05 10:30:34REVISION DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1. SHT A-5 THE SANITARY RISER DIAGRAM AND WATER RISER
 DIAGRAM HAVE BEEN DELETED, BUT THE ONLY FIXTURE DELETED
 WAS THE SINK. THE TOILET ROOM AND DRINKING FOUNTAIN
 STILL REMAIN ON THE FLOOR PLAN. PLEASE SUBMIT A
 SANITARY RISER DIAGRAM AND A WATER RISER DIAGRAM THAT
 REFLECT THE FLOOR PLAN. SECTION
 104.3.1.1(3)(4)(6)(10)(13).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-10-28 Cont ID  
Sent By pschmitz Date 2006-10-28 Time 06:17 Rev Time 0.00
Received By pschmitz Date 2006-10-28 Time 06:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-08-06 Cont ID  
Sent By pschmitz Date 2006-08-06 Time 11:46 Rev Time 0.00
Received By pschmitz Date 2006-08-06 Time 11:45 Sent To  
Notes
2006-08-06 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 UNSAT, THIRD TIME
  
 PREVIOUS COMMENT (1) NOT ADDRESSED.
 SHT.A-1
  
 (1)SECTION 11-4
 ACCESSIBLE ELEMENTS AND
 SPACES:SCOPE AND TECHNICAL REQUIREMENTS
 ?11-4.1 MINIMUM REQUIREMENTS.
 ?11-4.1.1 APPLICATION.
 ?11-4.1.1(1) GENERAL. THIS CODE
 ESTABLISHES THE MINIMUM STANDARDS FOR
 THE ACCESSIBILITY OF BUILDINGS AND
 FACILITIES BUILT OR ALTERED WITHIN
 THE STATE.
 ?11-4.1.1(1)(A) ALL AREAS OF NEWLY
 DESIGNED OR NEWLY CONSTRUCTED
 BUILDINGS AND FACILITIES REQUIRED
 TO BE ACCESSIBLE BY ?11-4.1.2 AND
 ?11-4.1.3 AND ALTERED PORTIONS OF
 EXISTING BUILDINGS AND FACILITIES
 REQUIRED TO BE ACCESSIBLE BY
 ?11-4.1.6 SHALL COMPLY WITH THIS CODE,
 ?11-4.1 THROUGH ?11-4.35, UNLESS
 OTHERWISE PROVIDED IN THIS
 SECTION OR AS MODIFIED IN A
 SPECIAL APPLICATION SECTION.
  
 (SPECIFICALY) BREAK ROOM SINK
 ?11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
  
 PROVIDE A ELEVATION DRAWING SHOWING
 COMPLIANCE WITH ABOVE COMMENTS. A FOWARD
 APPROACH, NO DOORS ON CABNET.
  
 END OF COMMENTS, QUESTIONS 561-805-6691

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-04-29 Cont ID  
Sent By pschmitz Date 2006-04-29 Time 06:28 Rev Time 0.00
Received By pschmitz Date 2006-04-29 Time 06:28 Sent To  
Notes
2006-04-29 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 UNSAT
 PREVIOUS COMMENT (1),(5) NOT ADDRESSED.
  
 (1)SECTION 11-4
 ACCESSIBLE ELEMENTS AND
 SPACES:SCOPE AND TECHNICAL REQUIREMENTS
 ?11-4.1 MINIMUM REQUIREMENTS.
 ?11-4.1.1 APPLICATION.
 ?11-4.1.1(1) GENERAL. THIS CODE
 ESTABLISHES THE MINIMUM STANDARDS FOR
 THE ACCESSIBILITY OF BUILDINGS AND
 FACILITIES BUILT OR ALTERED WITHIN
 THE STATE.
 ?11-4.1.1(1)(A) ALL AREAS OF NEWLY
 DESIGNED OR NEWLY CONSTRUCTED
 BUILDINGS AND FACILITIES REQUIRED
 TO BE ACCESSIBLE BY ?11-4.1.2 AND
 ?11-4.1.3 AND ALTERED PORTIONS OF
 EXISTING BUILDINGS AND FACILITIES
 REQUIRED TO BE ACCESSIBLE BY
 ?11-4.1.6 SHALL COMPLY WITH THIS CODE,
 ?11-4.1 THROUGH ?11-4.35, UNLESS
 OTHERWISE PROVIDED IN THIS
 SECTION OR AS MODIFIED IN A
 SPECIAL APPLICATION SECTION.
  
 (SPECIFICALY) BREAK ROOM SINK
 ?11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
  
  
 5) SHT A-5 WATER RISER DIAGRAM:
 SHOWS AIR CHAMBERS AT THE TOP OF WATER
 RISERS. COMPLY WITH SEC 604.9
  
 ?P604.9 WATER HAMMER. THE FLOW VELOCITY
 OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE
 POSSIBILITY OF WATER HAMMER.A WATER-
 HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED,
 UNLESS OTHERWISE APPROVED.THE ARRESTOR
 SHALL BE LOCATED WITHIN AN
 EFFECTIVE RANGE OF THE QUICK-CLOSING
 VALVE.WATER-HAMMER ARRESTORS SHALL
 CONFORM TO ASSE 1010.ACCESS SHALL BE
 PROVIDED TO WATER-HAMMER ARRESTORS.
  
 NEW COMMENTS
 SHT A-2,A-5 DELETED SHOWER
 ?P704.5 DEAD ENDS. IN THE INSTALLATION
 OR REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED.
 WATER LINES FOR FUTURE SHOWER CAPED AT
 TEE.
 END OF COMMENTS QUESTIONS 561`-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-20 Cont ID  
Sent By pschmitz Date 2005-08-20 Time 06:45 Rev Time 0.00
Received By pschmitz Date 2005-08-20 Time 06:45 Sent To M
Notes
2005-08-20 00:00:00PAUL SCHMITZ,
 PLUMBING PLAN REVIEW EXAMINER
 [email protected]
  
 FBC 2001 DENIED
  
 (1)SECTION 11-4
 ACCESSIBLE ELEMENTS AND
 SPACES:SCOPE AND TECHNICAL REQUIREMENTS
 ?11-4.1 MINIMUM REQUIREMENTS.
 ?11-4.1.1 APPLICATION.
 ?11-4.1.1(1) GENERAL. THIS CODE
 ESTABLISHES THE MINIMUM STANDARDS FOR
 THE ACCESSIBILITY OF BUILDINGS AND
 FACILITIES BUILT OR ALTERED WITHIN
 THE STATE.
 ?11-4.1.1(1)(A) ALL AREAS OF NEWLY
 DESIGNED OR NEWLY CONSTRUCTED
 BUILDINGS AND FACILITIES REQUIRED
 TO BE ACCESSIBLE BY ?11-4.1.2 AND
 ?11-4.1.3 AND ALTERED PORTIONS OF
 EXISTING BUILDINGS AND FACILITIES
 REQUIRED TO BE ACCESSIBLE BY
 ?11-4.1.6 SHALL COMPLY WITH THIS CODE,
 ?11-4.1 THROUGH ?11-4.35, UNLESS
 OTHERWISE PROVIDED IN THIS
 SECTION OR AS MODIFIED IN A
 SPECIAL APPLICATION SECTION.
  
 (2) 11-4.22 TOILET ROOMS.
 ?11-4.22.1 MINIMUM NUMBER. TOILET
 FACILITIES REQUIRED TO BE ACCESSIBLE
 BY ?11-4.1 SHALL COMPLY WITH ?11-4.22.
 ACCESSIBLE TOILET ROOMS SHALL BE
 ON AN ACCESSIBLE ROUTE.
 ?11-4.22.2 DOORS.
 ?11-4.22.2(1) ALL DOORS TO
 ACCESSIBLE TOILET ROOMS SHALL COMPLY
 WITH
 ?11-4.13.DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED
 FOR ANY FIXTURE.
  
 (3) ?11-4.23.3 CLEAR FLOOR SPACE. THE
 ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN ?11-4.23.4, ?11-4.23.5,
 ?11-4.23.6, ?11-4.23.7, ?11-4.23.8,
 AND ?11-4.23.9 SHALL BE ON AN
 ACCESSIBLE ROUTE.AN UNOBSTRUCTED
 TURNING
 SPACE COMPLYING WITH ?11-4.2.3 SHALL
 BE PROVIDED WITHIN AN ACCESSIBLE
 BATHROOM.THE CLEAR FLOOR SPACES AT
 FIXTURES AND CONTROLS, THE
 ACCESSIBLE ROUTE, AND THE TURNING
 SPACE MAY OVERLAP.
  
 (4)?11-4.21 SHOWER STALLS.
 ?11-4.21.1 GENERAL. ACCESSIBLE SHOWER
 STALLS SHALL COMPLY WITH ?11-4.21.
 ?11-4.21.2 SIZE AND CLEARANCES. EXCEPT
 AS SPECIFIED IN ?11-9.1.2, SHOWER
 STALL SIZE AND CLEAR FLOOR SPACE SHALL
 COMPLY WITH FIGURE 11-35(A) OR
 FIGURE 11-35(B).THE SHOWER STALL IN
 FIGURE 11-35(A) SHALL BE 36
 INCHES BY 36 INCHES (915 MM BY 915
 MM).SHOWER STALLS REQUIRED BY
 ?11-9.1.2 SHALL COMPLY WITH FIGURE
 11-57(A) OR FIGURE 11-57(B).THE
 SHOWER STALL IN FIGURE 11-35(B) WILL
 FIT INTO THE SPACE REQUIRED FOR A
 BATHTUB.
 (5) SHT A-5 WATER RISER DIAGRAM:
 SHOWS AIR CHAMBERS AT THE TOP OF WATER
 RISERS. COMPLY WITH SEC 604.9
  
 ?P604.9 WATER HAMMER. THE FLOW VELOCITY
 OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE
 POSSIBILITY OF WATER HAMMER.A WATER-
 HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED,
 UNLESS OTHERWISE APPROVED.THE ARRESTOR
 SHALL BE LOCATED WITHIN AN
 EFFECTIVE RANGE OF THE QUICK-CLOSING
 VALVE.WATER-HAMMER ARRESTORS SHALL
 CONFORM TO ASSE 1010.ACCESS SHALL BE
 PROVIDED TO WATER-HAMMER ARRESTORS.
 END OF COMMENTS

Review Stop Z ZONING
Rev No 8 Status P Date 2008-11-18 Cont ID  
Sent By eschneid Date 2008-11-18 Time 15:23 Rev Time 0.00
Received By eschneid Date 2008-11-18 Time 15:23 Sent To  
Notes
2008-11-18 15:24:25RESTAMP 836 SQ. FT. MEZZANINE.

Review Stop Z ZONING
Rev No 7 Status N Date 2008-10-03 Cont ID  
Sent By eschneid Date 2008-10-03 Time 08:54 Rev Time 0.00
Received By eschneid Date 2008-10-03 Time 08:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 6 Status P Date 2008-04-23 Cont ID  
Sent By eschneid Date 2008-04-23 Time 19:17 Rev Time 0.00
Received By eschneid Date 2008-04-23 Time 19:17 Sent To  
Notes
2008-04-23 19:18:53REVISION NO. 4 - ADDITIONAL 68 SQ. FT. OF MEZZANINE
 SPACE (ENCLOSED CLOSET) BRINGS TOTAL FOR THIS BAY TO
 836 SQ. FT.

Review Stop Z ZONING
Rev No 5 Status N Date 2007-09-26 Cont ID  
Sent By eschneid Date 2007-09-26 Time 18:34 Rev Time 0.00
Received By eschneid Date 2007-09-26 Time 18:34 Sent To  
Notes
2007-09-26 18:34:36MEZZANINE STILL SHOWS AS STORAGE.

Review Stop Z ZONING
Rev No 4 Status N Date 2006-11-01 Cont ID  
Sent By eschneid Date 2006-11-01 Time 16:46 Rev Time 0.00
Received By eschneid Date 2006-11-01 Time 16:46 Sent To  
Notes
2006-11-01 16:47:07MEZZININE IS STILL FOR BUSINESS STORAGE.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-07-17 Cont ID  
Sent By eschneid Date 2006-07-17 Time 17:06 Rev Time 0.00
Received By eschneid Date 2006-07-17 Time 17:06 Sent To  
Notes
2006-07-17 00:00:00MEZZANINE APPROVED FOR STORAGE ONLY.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-04-11 Cont ID  
Sent By mmclean Date 2006-04-11 Time 11:47 Rev Time 0.00
Received By mmclean Date 2006-04-11 Time 11:47 Sent To  
Notes
2006-04-11 00:00:001) NO ADDITIONAL MEZZANINE SPACE IS
 ALLOWED IN THE BUILDING BASED ON
 INSUFFICIENT PARKING FOR THE ADDITINAL
 SQUARE FOOTAGE.
  
 2) THE MEZZANINE PROPOSED AS PART OF
 THIS PERMIT MAY NOT BE CALLED BUSINESS
 STORAGE AS THE MEZZANINE INCLUDES A
 BATHROOM WITH CLOSET, A REFRIGERATOR,
 AND A COUNTER AREA WHICH INCLUDES A SINK
 AND CABINETS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-20 Cont ID  
Sent By mmclean Date 2005-09-20 Time 10:23 Rev Time 0.00
Received By mmclean Date 2005-09-20 Time 10:23 Sent To  
Notes
2005-09-20 00:00:00DENIED,
 1. NEED TO PROVIDE THE APPROVED LIST OF
 MEZZANINE FOR ALL UNITS AT ADDRESS (1335
 OLD OKEECHOBEE).