Plan Review Details - Permit 05080718
Plan Review Stops For Permit 05080718
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-08 Cont ID  
Sent By alange Date 2005-09-08 Time 14:13 Rev Time 0.50
Received By alange Date 2005-09-08 Time 14:04 Sent To  
Notes
2005-09-08 00:00:00DENIED
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 2.SHOW SLAB DETAIL.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-01 Cont ID  
Sent By dpalmer Date 2005-09-01 Time 06:33 Rev Time 0.40
Received By dpalmer Date 2005-09-01 Time 06:32 Sent To  
Notes
2005-09-01 00:00:00********** UNSAT ************
  
  
 1)NOTE: PLEASE SEE ZOING COMMENTS
 PERTAINING TO SITE PLAN.
 THIS SITE PLAN WILL ALSO INDICATE MIN
 CLEARENCE FROM DWELLING UNIT PER
 MANUFACTURES SPECS.
 PLEASE SEE BLDG COMMENTS FOR SLAB/TIE
 DOWN DETAIL REQUIRED.
  
 2)NOTE: PLEASE SUBMIT TWO COPIES OF
 MANUFACTURES SPECS/CUT SHEETS FOR
 GENERATOR AND ATS.
  
 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM
 FOR ELECTRICAL SERVICE SHOWING
 INSTALLATION OF NEW EQUIPMENT. THIS
 SHOULD INCLUDE CONDUCTORS, CONDUIT,
 GROUNDING ETC.
  
 4)NOTE: PLEASE SEE 225.31 FOR MISSING
 MEANS OF DISCONNECT. PLEASE SEE 225.34
 FOR GROUPING OF THIS MEANS OF DISCONNECT
 WITH EXISTING MAIN.
 PLEASE SEE 225.36, THIS DISCONNECTING
 MEANS SHALL BE LISED AS "SERVICE
 EQUIPMENT".
  
 5)NOTE: PLEASE PROVIDE
 LOADS/CALCULATIONS FOR ITEMS INSTALLED
 ON NEW PANEL.
 GEN LT AND RECEPTS LOADS ARE THE ONLY
 LOADS THAT MAY BE DE-RATED.
 ALL APPLIANCE, MOTOR, CONNECTED LOADS
 INCLUDING HEAT LOAD FROM A/C SHALL BE
 FIGURED AT 100%.
 702.5
  
 6)NOTE: PLEASE BE SURE ALL
 PLANS/DRAWINGS CONTAIN THE PRINTED ANME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR PLANS/ DESIGN.
 FBC 104.2.1, ADMINISTRATIVE CODE
 CITY-WIDE AMENDMENTS.
  
 7)NOTE: PLEASE SEE THE VALUATION FOR
 PERMIT APPLICATION SHALL INCLUDE ALL
 LABOR AND MATERIALS EVEN IF MATERIALS
 (GEN) IS OWNER SUPPPLIED.
 104.6.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2005-08-24 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1) PR

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-22 Cont ID  
Sent By btrobaug Date 2005-08-24 Time 07:14 Rev Time 0.00
Received By adarroug Date 2005-08-22 Time 08:51 Sent To E
Notes
2005-08-22 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-15 Cont ID  
Sent By mmclean Date 2005-08-19 Time 10:51 Rev Time 0.00
Received By adarroug Date 2005-08-15 Time 15:39 Sent To Z
Notes
2005-08-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-08 Cont ID  
Sent By prafter Date 2005-09-08 Time 08:08 Rev Time 1.00
Received By prafter Date 2005-09-08 Time 08:08 Sent To B
Notes
2005-09-08 00:00:00MECH. PLAN REVIEW:
  
 1. GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS, AND TEN
 FEET FROM ADJACENT BUILDING OPENINGS.
 2001 FBC/M 804.3.3 TERMINATION.
 2001 FBC/M SECTION 915 REQUIREMENT
 OF NFPA 378.2.3.2 EXHAUST SYSTEM
 TERMINATION.
  
 2. GENERATOR MANF. RECOMATIONS FOR
 SERVICE CLERANCES/VENELATIONS IN
 FEET/INCHES IN ALL DIRECTIONS MUST
 ACCOM. GENERATOR PERMIT APP.NEC 70
 110.3 B .
  
 3.INFORMATION ON TYPE OF FUEL.
 LP/NAT. GAS REQUIRE PERMIT, FROM LICEND
 GAS CONTRACTOR.
  
 4. CURRENT PROPERTY SERVEY WITH
 LOCATION OF GENERATOR REFLECTED ON
 SURVEY MUST ACCM. PERMIT APP.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-24 Cont ID  
Sent By mmclean Date 2005-08-19 Time 10:48 Rev Time 0.00
Received By btrobaug Date 2005-08-19 Time 10:48 Sent To I
Notes
2005-08-19 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY WITH SETBACKS & DIMENSION OF
 GENERATOR.
  
 **GENERATOR CAN ONLY ENCROACH 4FT INTO
 ANY SETBACK.**
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720