Plan Review Details - Permit 05080699
| Plan Review Stops For Permit 05080699 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2005-08-29 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-08-29 |
Time |
14:21 |
Rev Time |
0.33 |
| Received By |
alange |
Date |
2005-08-29 |
Time |
14:14 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-08-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-08-18 |
Time |
11:56 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-08-18 |
Time |
11:37 |
Sent To |
M |
|
| Notes |
| 2005-08-18 00:00:00 | | | | PLEASE SUBMIT LOAD CALCULATIONS FOR | | | LOADS TO BE SERVED FROM THE GENERATOR. | | | SEE 702.5. LIGHTING LOAD MAY TAKE THE | | | DEMAND, ALL OTHERS @ 100%. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-08-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-17 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-17 |
Time |
09:25 |
Sent To |
E |
|
| Notes |
| 2005-08-17 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-15 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-15 |
Time |
15:07 |
Sent To |
Z |
|
| Notes |
| 2005-08-15 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-29 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-08-29 |
Time |
09:35 |
Rev Time |
1.00 |
| Received By |
prafter |
Date |
2005-08-29 |
Time |
09:35 |
Sent To |
P |
|
| Notes |
| 2005-08-29 00:00:00 | MECH. PLAN REVIEW: | | | PROVISO: | | | | | | 1. GENERATOR MANF. RECOMATIONS FOR | | | SERVICE CLEARANCE/VENELATION IN | | | FEET/INCHES IN ALL DIRECTIONS MUST | | | ACCOM. GENERATOR PERMIT APP. NEC 70 | | | 110.3 B . | | | 2. GENERATOR EXHAUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENING, AND TEN | | | FEET AWAY FROM ADJECENT BUILDING | | | OPENINGS. 2001 FBC/M 804.3.3 | | | TERMINATION. | | | 2001 FBC/M SECTION 915 REQUIREMENT OF | | | NFPA 37 8.2.3.2 EXHAUST SYSTEM | | | TERMINATION. | | | .3 INFORMATION ON TYPE OF FUEL. | | | 4. LP/NAT GAS REQUIRE PERMIT, FROM | | | LICENED GAS CONTRACTOR. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-30 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-08-29 |
Time |
10:51 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2005-08-30 |
Time |
07:07 |
Sent To |
B |
|
| Notes |
| 2005-08-30 00:00:00 | GAS PERMIT REQUIRED. PLEASE HAVE GAS | | | CONTRACTOR PROVIDE A DRAWING SHOWING THE | | | MODEL AND BTU'S OF THE GENERATOR, TIPE | | | OF GAS USED, GAS PRESSURE, LONGEST RUN | | | INCLUDING THE GAS APPLIANCES INSIDE THE | | | HOUSE. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-08-16 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-08-16 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-08-16 |
Time |
18:33 |
Sent To |
B |
|
| Notes |
|
|
|