Plan Review Details - Permit 05080680
Plan Review Stops For Permit 05080680
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-01 Cont ID  
Sent By shill Date 2005-12-01 Time 13:31 Rev Time 0.50
Received By shill Date 2005-12-01 Time 12:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-06 Cont ID  
Sent By shill Date 2005-09-06 Time 12:57 Rev Time 1.00
Received By shill Date 2005-09-06 Time 12:57 Sent To  
Notes
2005-09-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)ELEVATORS ARE TO CONFORM TO
 ASME17.1, FBC3001.1.IS OTHER EQUIPMENT
 PERMITTED IN THE ELEVATOR MACHINE ROOM?
  
 3.)SHEET 2 OF 7 INDICATES THAT THE
 DETAIL FOR THE MOUNTING OF THE CABLES ON
 THE ROOFTOP ARE ON SHEET 6.SOME
 DETAILS SHOW PATCHING OF THE ROOF.IF
 THE ROOF IS TO BE PATCHED, PROVIDE
 DESIGN PRESSURES FOR THE ROOF AND
 PRODUCT APPROVALS FOR THE ROOF ASSEMBLY.
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-03-18 Cont ID  
Sent By dpalmer Date 2006-03-18 Time 20:13 Rev Time 0.00
Received By dpalmer Date 2006-03-18 Time 20:02 Sent To PC
Notes
2006-03-18 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE SEE SIGNATURE AND SEAL ON
 PLANS IS NOT THAT OF THE ORIGINAL
 ENGINEER OF RECORD. PLEASE KNOW, AS PER
 FS THE NEW ENGINEER PART OF THE SAME
 ENGINEERING FIRM MAY SIGN, DATE AND SEAL
 PLANS, HOWEVER PLANS MUST BE SIGNED WITH
 A LEGAL SIGNATURE. PLANS APPEAR TO BE
 INITIALS? IF INDEED THIS IS THE LEGAL
 SIGNATURE OF ENGINEER, PLEASE HAVE
 ENGINEER PROVIDE A SIGNED, DATED, SEALED
 AND NOTORIZED LETTER FOR LEGAL SIGNATURE
 CONFORMATION AND THIS LETTER WILL BE
 PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE.
 PLEASE KNOW, THE LETTER MUST BE PROPERLY
 NOTORIZED AS REQUIRED UNDER FS117.05.
  
 2)NOTE: PLEASE PROVIDE INFORMATION
 REQUARDING TAP ON THE LOAD SIDE OF 800A
 MAIN. PLEASE CLARIFY LUGS AND/OR HOW TAP
 IS BEING MADE.
  
 BOTH OF THE ABOVE CAN BE ADDRESSED IN
 LTR FORM.
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-30 Cont ID  
Sent By dpalmer Date 2005-11-30 Time 16:50 Rev Time 0.00
Received By dpalmer Date 2005-11-30 Time 16:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-16 Cont ID  
Sent By dpalmer Date 2005-08-16 Time 07:42 Rev Time 0.75
Received By dpalmer Date 2005-08-16 Time 07:37 Sent To  
Notes
2005-08-16 00:00:00***** UNSAT ******
  
 1)NOTE: PLEASE SEE BLDG AND FIRE REVIEW
 NOTES, NEW TELEPHONE/CELL EQUIPMENT MAY
 NOT BE LOCATED IN ELEVATOR EQUIPMENT
 ROOM. PLEASE SEE STATE OF FLORIDA
 ELEVATOR CODE. ONLY EQUIPMENT,
 ELECTRICAL OR OTHERWISE IS PERMITTED IN
 ELEVATOR EQUIPMENT ROOM. REQUIRED AT
 THIS TIME AND SUBMITTED WITH PLANS BY
 THE ENGINEER OF RECORD.
 215.5,220
  
 3)NOTE: PLEASE LOAD CALCULATIONS
 SUBMITTED FOR NEW 200A PANEL INDICATE A
 80A LOAD. PLEASE CLARIFY RECEPT AND
 PORTABLE GENERATORS MENTIONS 50A?
 215.5
  
 4)NOTE: PLEASE SUBMIT MANUFACTURE
 CUT/SPEC SHEETS FOR TRANSFER SWITCH.
 PLEASE ALSO SEE A DISCONNECTING MEANS
 WILL BE REQUIRED AT ELECTRICAL ROOM
 LOCATION GROUPED WITH EXISTING
 ELECTRICAL EQUIPMENT. PLEASE SEE DISC
 MEANS SHALL BE RATED AS "SERVICE
 EQUIPMENT".
 225.31, THRU 225.36
  
 PLEASE BE SURE TO SEE NOTES FROM OTHER
 REIVEWER(S) WHICH WILL AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-02 Cont ID  
Sent By mwennerg Date 2005-12-02 Time 15:07 Rev Time 0.00
Received By mwennerg Date 2005-12-02 Time 15:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-09 Cont ID  
Sent By mwennerg Date 2005-09-09 Time 13:20 Rev Time 0.00
Received By mwennerg Date 2005-09-09 Time 13:20 Sent To  
Notes
2005-09-09 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW NOTES
 REGARDING STORAGE AND OTHER EQUIPMENT
 NOT DEDICATED TO ELEVATOR OPERATIONS IN
 ELEVATOR EQUIPMENT ROOM. PLEASE VERIFY
 AND INDICATE WHERE THIS PRACTICE WOULD
 BE PERMITTED.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-15 Cont ID  
Sent By adarroug Date 2006-03-15 Time 14:22 Rev Time 0.00
Received By adarroug Date 2006-03-15 Time 14:22 Sent To E
Notes
2006-03-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-05 Cont ID  
Sent By adarroug Date 2005-12-05 Time 09:29 Rev Time 0.00
Received By adarroug Date 2005-12-05 Time 09:29 Sent To Z
Notes
2005-12-05 00:00:00TAKEN OFF "COMM" BD#27/ SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-19 Time 10:17 Rev Time 0.00
Received By adarroug Date 2005-10-19 Time 10:17 Sent To  
Notes
2005-11-16 00:00:00TO "COMM" BD#27
2005-10-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-20 Cont ID  
Sent By pkrauss Date 2005-09-20 Time 07:46 Rev Time 0.00
Received By pkrauss Date 2005-08-15 Time 09:31 Sent To  
Notes
2005-08-15 00:00:00TO "COMM" BD#47

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-03 Cont ID  
Sent By rregueir Date 2005-12-03 Time 12:02 Rev Time 0.00
Received By rregueir Date 2005-12-03 Time 12:02 Sent To  
Notes
2005-12-03 00:00:00COMMENTS FROM PREVIOUS REVIEW HAVE BEEN
 ADDRESSED ADEQUATELY IN RESPONSE LETTER
 FORM ENGINEER.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-20 Cont ID  
Sent By pkrauss Date 2005-09-20 Time 07:22 Rev Time 0.55
Received By pkrauss Date 2005-09-20 Time 07:20 Sent To  
Notes
2005-09-20 00:00:00DENIED:
 1.PLAN SHEET 2 OF 7; GENERAL NOTES &
 SPECIFICATIONS, PENETRATIONS THROUGH
 FIRE RATED ASSEMBLIES.PLEASE INDICATE
 RATING OF WALL WHERE PLAN 3 OF 7
 INDICATES THE 'WINDOW UNIT' IS TO BE
 INSTALLED.2001 FBC(M)607.
  
 2.INDICATE ELEVATION OF THE 'WINDOW
 UNIT' FROM THE ROOF LEVEL.
  
 3.PROVIDE DETAIL FOR THE MOUNTING OF
 THE 'WINDOW UNIT'.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2005-12-05 Cont ID  
Sent By mmclean Date 2005-12-05 Time 16:53 Rev Time 0.00
Received By mmclean Date 2005-12-05 Time 16:53 Sent To B
Notes
2005-12-05 00:00:00APPROVED BASE ON THE ZONING LETTER FROM
 ANTHONY LONG, SENIOR PLANNER IFSR#05-19

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By mmclean Date 2005-08-23 Time 16:48 Rev Time 0.00
Received By mmclean Date 2005-08-23 Time 16:48 Sent To  
Notes
2005-08-23 00:00:00DENIED,
 1. NEED TO PROVIDE THE CORRECT SHEETS
 BASE ON THE APPROVED INFORMAL LETTER
 FROM THE PLANNING & ZONING DEPT.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720