Plan Review Details - Permit 05080679
Plan Review Stops For Permit 05080679
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-11-30 Cont ID  
Sent By hpiskura Date 2007-11-30 Time 16:02 Rev Time 0.00
Received By hpiskura Date 2007-11-30 Time 16:01 Sent To  
Notes
2008-05-05 16:03:28FINAL EXTENSION GRANTED TO 5/31/08.
 THE ENTRY DATES WERE ADJUSTED TO COINCIDE WITH THE
 AUTOMATED PERMIT EXPIRATION PROCESS.
 HAROLD PISKURA

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-01 Cont ID  
Sent By rbrown Date 2007-06-01 Time 18:42 Rev Time 0.00
Received By rbrown Date 2007-06-01 Time 18:42 Sent To  
Notes
2007-06-01 18:42:48REQUEST GRANTED FOR EXTENSION OF PERMIT APPLICATION.
 SEE LETTER DATED 5/31/07.UPDATED EXPIRATION DATE IS
 9/2/07.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-20 Cont ID  
Sent By jwitmer Date 2006-04-20 Time 13:19 Rev Time 6.66
Received By jwitmer Date 2006-04-20 Time 07:37 Sent To  
Notes
2006-04-20 00:00:00PERMIT: 05080679
 ADD: 719 EXECUTIVE CENTER DR
 (TOWER# 3)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 105.8* PROVIDE NOC RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3A)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING WILL REQUIRE A THRESHOLD
 INSPECTOR.FORMS WILL NEED TO BE FILED
 OUT FOR THE THRESHOLD INSPECTOR, CONTACT
 HAROLD PISKURA, INSPECTION SERVICES
 MANAGER @ (561)805-6711 TO SEET UP AN
 APPOINTMENT.
  
 3B) 109.3.6.1* THE ENFORCING AGENCY
 SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCINGAGENCY PRIOR
 TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD
 BUILDING.THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLANS IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 3C) 109.3.6.4.4.105.13.4.4 ALL PLANS FOR
 THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTES.
  
 3D) NOTE: SINCE THIS BUILDING WILL BE A
 THRESHOLD STRUCTURE SUBMIT (3) OF ALL
 DOCUMENTS FOR REVIEW.
  
 4) 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5) SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL JOHN HIGGINS FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. JOHN HIGGINS
 CONTACT NUMBER IS (561)822-1239.
  
 6) THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
 7) COMPLIED
  
 8) COMPLIED
  
 9) PROVISO
  
 10) PROVISO
  
 11) COMPLIED
  
 12A) COMPLIED
  
 12B) COMPLIED
  
 12C) 2ND REQUEST, PORTE COCHERE:
 THE PLANS DO NOT INDICATE AN ACCESSIBLE
 LOADING ZONE UNDER THE PORTE COCHERE.
 FAIR HOUSING ANSI 4.6
  
 12D) 2ND REQUEST, PROVIDE SIGNAGE FOR
 HANDICAPPED PARKING, AND HANDICAPPED VAN
 PARKING. RESPONCE SEE CIVEL, WHERE?
 SHEET 9 HAS HANDICAPPED ELEMENTS ON THIS
 SHEET BUT ONLY A STOP SIGN.
  
 12E) 2ND REQUEST,PLANS DO NOT INDICATE
 REACH RANGESFOR THE COMMON USE MAIL
 BOXES.
  
 12F) 2ND REQUEST, THERE ARE NO KITCHEN
 DETAILS INDICATING AN ACCESSIBLE SINK
 WITH FORWARD APPROACH. RESPONCE, SEE
 AC1.2 & AB1.1. THERE ARE NO SUCH SHEETS
 LISTED IN THE INDEX.
  
 12G) 2ND REQUEST, MISSING T-3 A4.1.14
 THE INDIVIDUAL UNITS WITH ENTRYS
 WITH 45 DEGREE WALLS MISSING THE
 REQUIRED 18" ON THE PULL SIDE OF DOOR.
 SEE ANSI 4.13.6, ONLY REQUIED ON THE
 EXTERIOR SIDE.
 THE UNIT ENTRY DOORS WITH 45 DEGREE
 WALLS ADJACENT TO THE FRONT ENTRY DOOR
 DO NOT MEET THE FAIR HOUSING GUIDELINE
 FOR AN ACCESSIBLE FRONT ENTRY, SEE
 ANSI 4.13FOR THE EXTERIOR SIDE LATCH
 SIDE OF DOOR ONLY.
  
 12H) COMPLIED.
  
 13) COMPLIED.
  
 14) COMPLIED.
  
 15A) COMPLIED.
  
 15B) COMPLIED.
  
 15C) 2ND REQUEST, UNIT B, UNIT C AND
 UNIT D ARE WITHIN A CORRIDOR NOT A
 BALCONY WALKWAY REQUIRING OPENING
 PROTECTIVES SEE TABLE 1016.1. SHEET FOR
 THE 3RD FLOOR BRIDGE MISSING THE RATED
 WINDOWS.A2.3.1.
  
 15D) 2ND REQUEST,
 15D) NOTE IF WINDOWS REQUIRES FIRE RATED
 GLASS, AS FAR AS I'M AWARE NO
 MANUFACTURER MAKES FIRE RATED AND LARGE
 MISSLE IMPACT RATED GLAZING!!!! SEE
 THE BUILDING OFFICIALS INTERPRETATION ON
 LARGE OR HIGH RISE BUILDINGS AS FAR AS
 SHUTTERS VS LARGE OR SMALL MISSLE RATED
 GLASS.
 *************************
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY,
  
 SUBMIT: PRE-STORM PREPARATION:
  
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE
 PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS
 APPROPRIATE FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 15E) COMPLIED.
  
 16) COMPLIED.
  
 17A) COMPLIED.
  
 17B) COMPLIED.
  
 17C) 2ND REQUEST,ROOF TOP MECHANICAL
 UNITS AS SHOWN ON A6.1.3 DETAIL 8
 INDICATES A MINIMUM OF 18" FROM ROOF,
 SEE TABLE 1509.7 FOR MINIMUM VERTICAL
 HEIGHT.
  
 18) 2ND REQUEST, REWORD PHRASE
 "PEDESTRIAN BRIDGE TO GARAGE (UNDER
 SEPERATE PERMIT)" THIS APPEARS ON BOTH
 T3A3.1.2 AND T3A3.1.3.
  
 18B) PEDESTRIAN BRIDGE INTERFACE WILL
 REQUIRE A 1 1/2 HR RATED PROTECTIVE
 (706.7) SEE FIGURE 3104.5 CODE
 COMMENTARY.
 3104.5 FIRE BARRIERS BETWEEN PEDESTRIAN
 WALKWAYS AND BUILDINGS.
 WALKWAYS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING BY FIRE BARRIER
 WALLS WITH A FIRE-RESISTANCE RATING OF
 NOT LESS THAN 2 HOURS. THIS PROTECTION
 SHALL EXTEND VERTICALLY FROM A POINT 10
 FEET (3048 MM) ABOVE THE WALKWAY ROOF
 SURFACE OR THE CONNECTED BUILDING ROOF
 LINE, WHICHEVER IS LOWER, DOWN TO A
 POINT 10 FEET (3048 MM) BELOW THE
 WALKWAY AND HORIZONTALLY 10 FEET (3048
 MM) FROM EACH SIDE OF THE PEDESTRIAN
 WALKWAY. OPENINGS WITHIN THE L0-FOOT
 (3048 MM) HORIZONTAL EXTENSION OF THE
 PROTECTED WALLS BEYOND THE WALKWAY SHALL
 BE EQUIPPED WITH DEVICES PROVIDING A
 ?-HOUR FIRE PROTECTION RATING IN
 ACCORDANCE WITH SECTION 715 .
  
 19) COMPLIED.
  
 20) 2ND REQUEST,
 20) THE ELEVATION SHEETS AND A6.1.1
 DEPICT DETAILS WITH CAST RESIN CORNICE
 AND BANDS ON THE EXTERIOR OF THE
 BUILDING. 1406.2.2 ARCHITECTURAL TRIM
 THAT EXCEEDS 40FT IN HEIGHT ABOVE GRADE
 PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE
 SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.
  
 21)COMPLIED.
  
 22) 2ND REQUEST,RESPONCE, SEE STRUCTURAL
 SHEETS, WHERE?
 T-3 A6.1.3 DETAIL# 11 ALSO INDICATES
 THE USE OF INTEGRAL ROOF DECK PROVIDE
 ADDITIONAL INFORMATION.
  
 23) 2ND REQUEST, RESPONCE ,SEE
 STRUCTURAL WHERE?
 SAME DETAIL AS ABOVE WHAT SPANS CAN
 THE GALVANIZED METAL FURRING SPAN @ 12"
 O. C. PROVIDE THE PSF APPLIED LOAD, AND
 THICKNESS OF HI HAT IN MIL. SPANS TO BE
 TAKEN AS MULTIPLE SPANS?
  
 24A) COMPLIED.
  
 24B) COMPLIED.
  
 24C) COMPLIED.
  
 24D) COMPLIED.
  
 25: T-3 A5.1.5
 25A) 2ND REQUEST,
 DETAILS SHOW A DROPPED CEILING OVER THE
 WALKWAYS WITH METAL FRAMING NO
 INDICATION AS TO ATTACHMENT TO THE DECK
 ABOVE, SPACING OF ATTACHMENT, GAUGE OR
 SIZE OF FRAMING, OR SPACING OF FRAMING.
  
 25B) COMPLIED.
  
 26) COMPLIED.
  
 27) COMPLIED.
  
 28) COMPLIED.
  
 29) COMPLIED.
  
 30) 2ND REQUEST,
 30)SHEET M2.5 HAS NO INDICATION OF A
 SMOKEPROOF EXIT ENCLOSURE, SEE 403.13
 ALSO SEE 1019.1.3 FOR REQUIRED
 VENTILATION, AND 909.20 FOR PRESSURIZED
 STAIRS.
 KAMM RESPONE: SMOKE PROOF ENCLOSURE NOT
 REQUIRED. PLEASE REFER TO ARCHITECTURAL
 DRAWINGS AND OR ARCHITECTS RESPONCE
 LETTER. NO ARCHITECTURAL RESPONCE.
 HIGH-RISE 403
 403.13 SMOKEPROOF EXIT ENCLOSURES.
 EVERY REQUIRED STAIRWAY SERVING FLOORS
 MORE THAN 75 FEET (22 860 MM) ABOVE THE
 LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE
 ACCESS SHALL COMPLY WITH SECTIONS 909.20
 AND 1019.1.8 .
 1019.1.8 SMOKEPROOF ENCLOSURES.
 IN BUILDINGS REQUIRED TO COMPLY WITH
 SECTION 403 OR 405, EACH OF THE EXITS OF
 A BUILDING THAT SERVES STORIES WHERE THE
 FLOOR SURFACE IS LOCATED MORE THAN 75
 FEET (22 860 MM) ABOVE THE LOWEST LEVEL
 OF FIRE DEPARTMENT VEHICLE ACCESS OR
 MORE THAN 30 FEET (9144 MM) BELOW THE
 LEVEL OF EXIT DISCHARGE SERVING SUCH
 FLOOR LEVELS SHALL BE A SMOKEPROOF
 ENCLOSURE OR PRESSURIZED STAIRWAY IN
 ACCORDANCE WITH SECTION 909.20 .
  
 31) 2ND REQUEST,
 31) PRODUCT APPROVALS:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 32) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXT LOUVER DOORS
 B) EXT SOLID DOORS
 C) EXT GLAZED DOORS SWING
 D) EXT GLAZED DOORS W/ TRANSOMS, SWING
 E) CASEMENT WINDOWS
 F) MULLIONS HORIZONTAL
 G) EXT RAILINGS
 H) LOUVERS
 I) TRUSS ANCHORS
 J) ROOFING ASSEMBLIES
 1) FLAT ROOF
 2) CEMENT TILE & TYPE OF INSTALATION
 NOTE THE FLAT ROOF INFORMATION SUBMITTED
 IS REDUCED TO 1/2 SHEET, NOT READABLE TO
 COPY FOR RECORD RETENTION.
 THE CONTRACTOR DID NOT HIGHLIGHT WHICH
 SUBSYSTEM TO BE USED NOR DID THEY
 HIGHLIGHT WHICH FASTENING OPTIONS TO BE
 USED.
  
 33) COMPLIED.
  
 34) COMPLIED.
  
 35) THE WIND TUNNEL TEST DOESN'T
 INDICATE ANY PRESSURES FOR THE FLAT
 ROOF?
  
 36)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-17 Cont ID  
Sent By jwitmer Date 2005-11-17 Time 14:05 Rev Time 15.55
Received By jwitmer Date 2005-11-17 Time 14:05 Sent To  
Notes
2005-11-17 00:00:00PERMIT: 05080679
 ADD: 719 EXECUTIVE CENTER DR
 (TOWER# 3)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 105.8* PROVIDE NOC RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3A)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING WILL REQUIRE A THRESHOLD
 INSPECTOR.FORMS WILL NEED TO BE FILED
 OUT FOR THE THRESHOLD INSPECTOR, CONTACT
 HAROLD PISKURA, INSPECTION SERVICES
 MANAGER @ (561)805-6711 TO SEET UP AN
 APPOINTMENT.
  
 3B) 109.3.6.1* THE ENFORCING AGENCY
 SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCINGAGENCY PRIOR
 TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD
 BUILDING.THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLANS IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 3C) 109.3.6.4.4.105.13.4.4 ALL PLANS FOR
 THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTES.
  
 3D) NOTE: SINCE THIS BUILDING WILL BE A
 THRESHOLD STRUCTURE SUBMIT (3) OF ALL
 DOCUMENTS FOR REVIEW.
  
 4) 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5) SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL JOHN HIGGINS FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. JOHN HIGGINS
 CONTACT NUMBER IS (561)822-1239.
  
 6) THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
 7) SHEETT-3 A-1.1.2 BUILDING DATA FOR
 TOWER#3 INDICATES 143 UNITS WHERE AS THE
 SAME SHEET THE SITE PLAN INDICATES 142,
 CORRECT DESCRIPANCY.
  
 8) GEOTECHNICAL REPORT THAT WORK WAS
 PREFORMED BY ARDAMAN NEEDS TO BE AN
 ORIGINAL WITH SIGNATURE AND RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10)109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 11) SHEET T-3 A2.1.1
 11A) ELEVATORS, PLEASE INDICATE THAT THE
 ELEVATORS CAN ACCOMODATE AMBULANCE
 STRETCHERS. 3002.4.
  
 12)SHEET T-3 A2.1.1 FAIR HOUSING/
 ACCESIBLITY
 12A)PLANS DO NOT PROVIDE AN ACCESSIBLE
 PATH TO THE BUS STOP. THE SIDEWALK STOPS
 SHORT OF BUS STOP BENCH. THERE IS NO
 PEDESTRIAN CROSSWALK CONNECTING THE
 SIDEWALKS TO PUBLIC TRANS PORTATION.
  
 12B) PROVIDE HOW THE HANDICAPPED
 ACCESSIBLE PATH (SIDEWALKS) WILL BE
 MAINTAINED DURING THE PHASING, PROVIDE A
 SITE PLAN INDICATING ACCESSIBLITY TO THE
 PUBLIC WAY.
  
 12C) PORTE COCHERE: THE PLANS DO NOT
 INDICATE THERE IS A ACCESSIBLE LOADING
 ZONE UNDER THE PORTE COCHERE. FAIR
 HOUSING ANSI 4.6
  
 12D) PROVIDE SIGNAGE FOR HANDICAPPED
 PARKING, AND VAN ACCESSIBLE PARKING.
  
 12E) PLANS DO NOT INDICATE REACH RANGES
 FOR THE COMMON USE MAIL BOXES.
  
 12F) THERE IS NO KITCHEN DETAILS
 INDICATING AN ACCESSIBLE SINK WITH
 FORWARD APPOARCH.
  
 12G) THE INDIVIDUAL UNITS WITH ENTRYS
 WITH 45 DEGREE WALLS MISSING THE
 REQUIRED 18" ON THE PULL SIDE OF DOOR.
 SEE ANSI 4.13.6, ONLY REQUIED ON THE
 EXTERIOR SIDE.
 THE UNIT ENTRY DOORS WITH 45 DEGREE
 WALLS ADJACENT TO THE FRONT ENTRY DOOR
 DO NOT MEET THE FAIR HOUSING GUIDELINE
 FOR AN ACCESSIBLE FRONT ENTRY, SEE
 ANSI 4.13FOR THE EXTERIOR SIDE LATCH
 SIDE OF DOOR ONLY.
  
 12H) IN BOTH STAIR TOWER 1 & 2 FIRST
 FLOOR REDUCED HEAD CLEARENCE UNDER
 STAIR,CORRECT THE PROBLEM WITH REDUCED
 VERTICAL CLEARENCE UNDER THE STAIRS.
 ANSI 117.1
 SECTION 307.4 REQUIRING EITHER A
 GUARDRAIL OR OTHER BARRIER WHERE THE
 VERTICAL HEIGHT IS REDUCED LESS THAN
 80".
  
 13) PLANS INDICATE VARIOUS SITE
 AMENITIES STRICK FROM PLANS, WILL
 REQUIRE A SEPERATE PERMIT.
  
 14) SHEET A2.1.1/ A2.1.3
 STAIR TOWER# 1& STAIR TOWER# 2 IN BOTH
 CASES ONCE THE STAIR TOWER DOOR OPENS
 LEAVES THE OCCUPANTS WITHIN THE CONFINES
 OF THE BUILDING. THE DOORS AND WINDOWS
 ON THE OPPOSITE WALL ARE NOT RATED. THE
 LIFE SAFETY PLAN INDICATES IN BOTH CASES
 A SINGLE MEANS OF EGRESS.
 SEE 1013.5.1. THIS SECTION IS FOR
 BALCONIES, THE SAME CONCERNS ABOUT
 EGRESS APPLIES THAT THE OPENINGS WOULD
 REQUIRE OPENING PROTECTIVES.
  
 15) SHEET T-3 A2.2.1.
 15A) THE 2ND FLOOR AND HIGHER FLOORS
 HAVE THE SAME PROBLEM WITH NOT HAVING AN
 ELEVATOR LOBBY. THE AREA THAT SURROUNDS
 THE ELEVATORS AND IS ENCLOSED NOT
 MEETING THE DIFINITION OF AN OPEN
 BALCONY (SEE 1013.5.2) AND WILL BE
 CONSIDERED AS A CORRIDOR REQUIRING
 A 1HR RATING SEE TABLE 1016.1.
  
 15B) ELEVATOR LOBBIES SHALL MEET THE
 REQUIREMENTS OF 707.1.14.1.THE LOBBY
 SHALL SEPERATE THE ELEVATOR FROM THE
 CORRIDOR BY FIRE PARTITIONS AND THE
 REQUIRED OPENING PPROTECTION.
  
 15C) UNIT B, UNIT C,&UNIT D, ARE
 EITHER TOTALLY WITHIN A CORRIDOR OR
 PARTIALLY WITHIN A CORRIDOR REQUIRING
 RATED OPENING PROTECTIVES SEE TABLE
 1016.1.
  
 15D) NOTE IF WINDOWS REQUIRES FIRE RATED
 GLASS, AS FAR AS I'M AWARE NO
 MANUFACTURER MAKES FIRE RATED AND LARGE
 MISSLE IMPACT RATED GLAZING!!!! SEE
 THE BUILDING OFFICIALS INTERPRETATION ON
 LARGE OR HIGH RISE BUILDINGS AS FAR AS
 SHUTTERS VS LARGE OR SMALL MISSLE RATED
 GLASS.
 *************************
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE
 PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS
 APPROPRIATE FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 15E) THE HANDRAIL SECTIONS ON BOTH SIDES
 OF THE ELEVATOR APPEAR TO HAVE A KNEE
 WALL INDICATED WHAT IS THE HEIGHT OF THE
 KNEE WALL?
  
 16)T-3 A.2.2.3 CODE REVIEW FOR HIGH RISE
 BLDG DOES NOT INDICATE AS TO WHICH CODE
 THIS BUILDING WAS DESIGNED TO.
  
 17)SHEET T3-A2.4.1:
 17A) THIS PLAN HAS THE TERM "WALL
 ANCHOR" PLEASE EXPLAIN?
  
 17B) TERM E.O.S. EMERGENCY OVERFLOW
 SCUPPER DOES NOT INDICATE ANY SECTIONS
 THROUGH NOR GIVE SIZES, ADDITIONAL
 INFORMATION REQUIRED.
  
 17C) ROOF TOP MECHANICAL UNITS AS SHOWN
 ON A6.1.3 DETAIL 8 INDICATES A MINIMUM
 OF 18" FROM ROOF, SEE TABLE 1509.7 FOR
 MINIMUM VERTICAL HEIGHTS.
  
 18) T-3 A.2.5.1-A2.5.3 ARE FOR AN AREAL
 COVERED WALKWAY . SHEET T-4 A.3.1.3,
 NOTE, THAT A SEPERATE PERMIT WILL BE
 SUBMITTED FOR CONSTRUCTION OF AREAL
 COVED WALKWAY. THESE PAGES WILL BE
 STRUCK "VOID" AND THE ASSOCIATED
 STRUCTURAL PAGES.
  
 19) SHEET T-3 A2.4.2 INDICATES 3 ATTIC
 AREAS NO USEAGE INDICATED. 1509.2 A
 PENTHOUSE, BULKHEAD OR ANY OTHER SIMILAR
 PROJECTION ABOVE THE ROOF SHALL NOT BE
 USSED FOR PURPOSES OTHER THAN SHELTERING
 OF MECHANICAL EQUIPMENT OR SHELTEROF
 VERTICAL SHAFT OPENINGS IN THE ROOF.
 PENT HOUSES USSED FOR PURPOSES OTHER
 THAN PERMITTED BY THIS SECTION SHALL
 CONFORM TO THE REQUIREMENTS OFTHIS CODE
 FOR AN ADDITIONAL STORY.
  
 20) THE ELEVATION SHEETS AND A6.1.1
 DEPICT DETAILS WITH CAST RESIN CORNICE
 AND BANDS ON THE EXTERIOR OF THE
 BUILDING. 1406.2.2 ARCHITECTURAL TRIM
 THAT EXCEEDS 40FT IN HEIGHT ABOVE GRADE
 PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE
 SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.
  
 21)T-3A6.1.3 DETAIL# 11/ A5.1.3 BOTH SEC
 TIONS INDICATE USE OF R-19 INSULATION.
 THE INSULATION IS DEPICTED TO BE IN THE
 TOP CHORD OF THE METAL TRUSS. THE
 TRUSSES ARE CENTERED @ 48" O. C. HOW
 WILL THE INSULATION BE ATTACHED AND TO
 WHAT?
  
 22) T-3 A6.1.3 DETAIL# 11 ALSO INDICATES
 THE USE OF INTEGRAL ROOF DECK PROVIDE
 ADDITIONAL INFORMATION.
  
 23) SAME DETAIL AS ABOVE WHAT SPANS CAN
 THE GALVANIZED METAL FURRING SPAN @ 12"
 O. C. PROVIDE THE PSF APPLIED LOAD, AND
 THICKNESS OF HI HAT IN MIL. SPANS TO BE
 TAKEN AS MULTIPLE SPANS?
  
 24) T-3 A7.2.1 THE DOOR SCHEDULE UNDER
 REMARKS HAS NO NOTATIONS, AS TO REQUIRED
 HARDWARE, SELF-CLOSING DOORS AND DROP
 SEALS PLEASE PROVIDE THIS ADDITIONAL
 INFORMATION.
  
 24A) 709.3 FIRE-RESISTANCE RATING. A1
 HOUR FIRE-RESISTANCE RATING IS REQUIRED
 FOR SMOKE BARRIERS.
  
 24B) 710.5.2 SMOKE AND DRAFT-CONTROL
 DOORS. WHERE REQUIRED ELSEWHERE IN THE
 CODE, DOORS IN SMOKE PARTITIONS SHALL BE
 TESTED IN ACCORDANCE WITH UL 1784 WITH
 AN ARTIFICIAL BOTTOM SEAL INSTALLED
 ACROSS THE FULL WIDTH OF THE BOTTOM OF
 THE DOOR ASSEMBLY.
  
 24C) DOOR A-129 STYLE"K" IS LOUVER THIS
 CORRIDOR TO BE 1HR RATED, CORRECT.
  
 24D) DOOR 104,107, 110 & 112 FOR 2ND
 FLOOR & ABOVE WILL ALL REQUIRE RATED
 DOORS IN CORRIDOR.
  
 25) T-3 A5.1.5:
 25A) DETAILS SHOW A DROPPED CEILING OVER
 WALKWAYS WITH METAL FRAMING NO
 INDICATION AS TO THE ATTACHMENT TO THE
 DECK ABOVE, SPACING OF ATTACHMENET,
 GAUGE OR SIZE OF FRAMING OR SPACING OF
 FRAMING.
 25B) PLANS INDICATE THAT THE FINISH WILL
 BE A CEMENT PLASTER FINISH THIS MEANS A
 TRUE CEMENT PLASTER FINISH AND NOT EFIS?
 EFIS SYSTEMS INDICATE NOT TO BE USED ON
 HORIZONTAL SURFACES.
  
 26)FIRE SPRINKLER PLANS:
 26A)FS1.1 INDICATES THAT THERE IS NO
 FIRE PUMP LOCATED IN HIGHRISE TOWER# 3.
  
 403.8 & 911 BOTH DEAL WITH THE FIRE
 COMMAND CENTER WHICH REQUIRES BOTH A
 FIRE PUMP AND GENERATOR. FS.1 INDICATES
 A SHARED FIRE PUMP FOR THREE BUILDINGS,
 THE CODE ISN'T CLEAR AS TO IF THE FIRE
 PUMP CAN BE SHARED OF NOT. IN SPEAKING
 WITH THE FIRE REVIEWERS THIS MAY NOT BE
 AN ACCEPTABLE METHOD OR APPLICATION.
 THE PRESENT LOCATION OF THE FIRE PUMP IS
 IN A PARKING GARAGE THAT HASN'T EVEN
 APPLIED FOR A PERMIT. THE SECOND ISSUE
 WILL BE THE SIZE OF THE FIRE PUMP IF THE
 LOCATION IS ACCEPTED, PROVIDE THE
 DOCUMENTATION FOR THE SIZE OF THE FIRE
 PUMP REQUIRED FOR THE 3 BUILDINGS IT
 WILL SERVICE.
  
 27) T3 A2.1.1 DOESN'T INDICATE THE
 LOCATION OF THE EMERGENCY GENERATOR,
 403.10 A STANDBY POWER SYSTEM COMPLYING
 WITH 2702 SHALL BE PROVIDED FOR STANDBY
 POWER LOADS SPECIFIED IN SECTION
 403.10.2 AND ALSO NFPA 110 & 111.
  
 28) FS2.1 IS MISSING THE FIRE SPRINKLERS
 IN THE CORRIDORS THAT FRONT EACH UNIT.
 ALSO REMOVE THE LIGHTING SYMBLES THAT
 ARE LOCATED IN THE SAME CORRIDOR.
  
 29) SECTION 911.1 OF THE CODE DEALS WITH
 THE FIRE COMMAND CENTER AND THE
 ASSOCIATED SYSTEMS (15) THAT ARE
 REQUIRED FOR A HIGH RISE BUILDING.
 SUBMIT A LAYOUT OF THE FIRE COMMAND
 CENTER AND ALL FEATURES REQUIRED BY THE
 SECTION TO BE CONTAINED THEREIN SHALL BE
 SUBMITTED FOR APPROVAL PRIOR TO
 INSTALLATION.
  
 30)SHEET M2.5 HAS NO INDICATION OF A
 SMOKEPROOF EXIT ENCLOSURE, SEE 403.13
 ALSO SEE 1019.1.3 FOR REQUIRED
 VENTILATION, AND 909.20 FOR PRESSURIZED
 STAIRS.
  
 31) PRODUCT APPROVALS:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 32) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXT LOUVER DOORS
 B) EXT SOLID DOORS
 C) EXT GLAZED DOORS SWING
 D) EXT GLAZED DOORS W/ TRANSOMS, SWING
 E) CASEMENT WINDOWS
 F) MULLIONS
 G) EXT RAILINGS
 H) LOUVERS
 I) TRUSS ANCHORS
 J) ROOFING ASSEMBLIES
 1) FLAT
 2) CEMENT TILE & TYPE OF INSTALATION
  
 33) 1714.5.5/1714.5.5.1 MULLIONS
 OCCURRING BETWEEN INDIVIDUAL WINDOW AND
 GLASS DOOR ASSEMBLIES. TESTING REPORTS
 ARE REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 34)1714.5.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 35) SHEET S-13 BUILDING ZONE MAP
 DESIGNED BY C.P.P. DOES NOT PROVIDE WHAT
 DESIGN PARAMETERS THAT WERE USED?
 PROVIDE REPORT FROM PROJECT # 05-3164.
 ASCE 7-02 ONCE THIS INFORMATION IS
 RESEARCHED THE SUBMITTED PRODUCT
 APPROVALS WILL BE REVIEWED.
  
 36)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-04 Cont ID  
Sent By dpalmer Date 2006-05-04 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2006-04-27 Time 16:57 Sent To  
Notes
2006-05-04 00:00:00****** UNSAT 2ND REVIEW ********
  
  
 SAIL CLUB TOWER 3.
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW AND SOME NEW COMMENTS
 DUE TO CHANGES IN PLANS.
  
 ** PLEASE SEE NOTE BELOW ARE TAKEN
 DIRECTLY FROM THE PREVIOUS REVIEW AND
 NEW COMMENTS ARE AT THE END.
  
 ** PLEASE SEE COMMENT WITH RESPECT TO
 THE REMOVAL OF ALL OLD/VOIDED SHEETS
 FROM SETS.
  
 1)NOTE:NOTE #1, NO, PLEASE SEE SCOVER
 SHEET STILL REFLECTS THE 1999 NEC AND
 PLEASE SEE REVISED SHEET E.1 SHOULD
 INDICATE THE CURRENT CODES IN EFFECT FOR
 DESIGN.
  
 ** PREVIOUS NOTE **
 PLEASE SEE CODE REFERENCED ON PLANS
 LIST THE 1999 NEC. PLEASE KNOW, AS OF
 JULY 1ST 2003, THE STATE ADOPTED THE
 2002 NEC.
 PLEASE ALSO SEE WE ARE UNDER THE 2003
 NFPA-101 AND 2002 NFPA-72
 PLEASE ADJUST.
  
 2)NOTE: NOTE #2 OK, HOWEVER PLEASE SEE
 NEW NOTE WITH RESPECT TO VAULT AREA.
  
 ** PREVIOUS NOTE **
 PLEASE SEE BLDG /FIRE REVIEW COMMENTS
 FOR STAIR TOWER EXITING WHICH WILL
 AFFECT ELECTRICAL LAYOUT.
 EXITS BACK INTO HALL WAY AREAS IN FRONT
 OF UNITS.
  
 3)NOTE:NOTE #3 OK, THIS SEE TO BE
 DONE, PLEASE SEE OTHER NOTES FOR A
 COUPLE ITEMS MISSING FOR RECEPTSETC.
  
  
 ** PREVISOU NOTE **
 PLEASE SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE SOME AREAS WHICH ELECTRICAL
 FIXTURES SEEM TO BE MISSINGTHIS.
 PLEASE ALSO SEE CIRCUITING FOR UNITS.
 PLEASE KNOW, A "TYPICAL" UNIT LAYOUT MAY
 BE PROVIDED, HOWEVER A LAYOUT WOULD BE
 REQUIRED FOR EACH UNIT TYPE, INCLUDING
 STUDIO UNIT.
 CIRCUITING FOR SOME UNITS/ITEMS CAN NOT
 BE VERIFIED AT THIS TIME.
  
 4)NOTE: NOTE #4 NO/YES, SOME
 PHOTOMETRICS WERE SUBMITTED, HOWEVER
 PLEASE SEE SOME OF THESE ARE NOT CLEAR
 AND VISABLE FOR STAIRS FOR VERIFICATION.
 PLEASE ALSO SEE NONE COULD BE LOCATED
 FOR EGRESS PATHS INCLUDING
 HALLS/CORRIDORS?
 PLEASE SEE A MIN OF 10FT CANDLES AVG IS
 REQUIRED UNDER NORMAL FOR STAIRS WHICH
 DOES NOT SEEM TO BE THE AVG AS SHOWN?
 PLEASE SEE NOT INDICATION FOR MINS UNDER
 EM LIGHTING CONDITIONS COOULD BE
 LOCATED.
  
 ** PREVIOUS **
 PLEASE PROVIDE PHOTO-METRICS FOR
 STAIR TOWERS ON NORMAL PWR AND STAND-BY.
 ALONG WITH WALK AREAS.
 PLEASE SEE STAIR TOWERS UNDER NORMAL PWR
 SHALL MEET A MIN OF 10FT CANDLES. PLEASE
 SEE ARES FOR HALLS ETC ARE PERMITTED TO
 BE LESS. .
 PLEASE SEE NFPA-101 7.8.1.3,7.9.2.1
  
 5)NOTE: NOTE #5 YES/ NO, PLEASE SEE A
 MIN OF ONE FIXTURE CONTAINING A BATTERY
 BACK UP WILL BE REQUIRED AT EVERY OTHER
 LEVEL IN STAIR TOWERS AND EGRESS PATHS
 TO THE PUBLIC RIGHT OF WAY.
  
 ** PREVIOUS NOTE **
 PLEASE SEE ONE STAIR TOWER SHOWS
 CIRCUITING FOR LTS FROM NORMAL POWER
 PANEL AND CIRCUTING.
 PLEASE SEE THESE ARE REQUIRED TO BE ON
 EM POWER PANEL.
 PLEASE KNOW, BATTERY BACK FIXTURES WILL
 BE REQUIRED AT EVERY OTHER LEVEL(MIN).
 PLEASE SEE LS 101 WHICH MENTIONS THE
 TRIPPING/THROW OF A SINGLE BRKR SAHLL
 NOT LEAVE ANY EGRESS AREA IN TOTAL
 DARKNESS. PLEASE CALL ELECTRICAL PLAN
 REVIEW AND FIRE MARSHALS OFFICE TO GO
 OVER OPTIONS PERMITTED.
 A BATTERY BACK-UP FIXTURE AT EVERY OTHER
 LEVEL WILL SATISFY THIS OFFICE AND AHJ.
 PLEASE BE SURE TO MEET THE MIN OF 1
 FT/CANDLE UNDER EM.
 PLEASE BE SURE TO SEE PREVIOUS NOTE #4
 FOR LIGHTING LEVELS.(MIN)
  
 6)NOTE:NOTE #6 YES/NO, PLEASE SEE MOST
 ROOMS WERE DONE, HOWEVER THE ELEVATOR RM
 DOES NOT INCLUDE A BATTERY BACK UP
 FIXTURE.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE BATTERY BACK-UP
 FIXTURES IN MAIN ELECTRICAL RMS AND
 ELEVATOR ROOM(S), GENERATOR AND FIRE
 PUMP ROOM. PLEASE ALSO PROVIDE
 CIRCUITING FOR THESE
 RMS.
  
 7)NOTE: NOTE #7 NO, ? RESPONSE MENTIONS
 TO SEE 5.1, HOWEVER NO CURB DETAIL WAS
 LOCATED.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE CURB DETAIL FOR
 BUS-DUCT RISER AND FLOOR PENATRATIONS.
 368.6
  
 8)NOTE: NOTE #8 , PLEASE EXPAND NOTE FOR
 ALL CLEARENCES TO BE MET PER 110.26.
 PLEASE KNOW, THE NOTE ADDDED WAS OK AND
 SHOULD REMAIN ALSO.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE NOTES ON RISER AND
 ELECTRICAL ROOM SHEETS FOR REQUIREMENTS
 OF 110.26 FOR PANIC HARDWARE AND DOOR
 SWINGS.
 PLEASE SEE MIN CLEARENCE PER 110.26
  
 9)NOTE:NOTE # 9 OK, PLEASE SEE
 RESPONSE MENTIONS "ALREADY CHNGED PER
 REV#1", HOWEVER WE ARE NOT AWARE OF ANY
 "REV#1" SUBMITTED FOR REVIEW?
 OK, AS CHANGED ON RISER.
  
 ** PREVIOUS NOTE **
 PLEASE SEE RISER INDICATES ALL BUS-DUCT
 FROM FPL VAULT TO MAIN ELECTRICAL ROOM
 AS OVER-HEAD. PLEASE SEE 230.70, 230.6,
 NO MORE THAN 8' OF UNPROTECTED
 CONDUCTORS/ OR BUS DUCT
 PERMITTED "INSIDE THE BLDG.
 PLEASE SEE ROUTING OF BUS-DUCT APPEARS
 TO SHOW INSTALLATION INSIDE CONDO
 UNITS??
  
 10)NOTE:NOTE #10 OK,? PLEASE CLARIFY
 IF THE EQUIPMENT WHICH IS NOTED IN
 RESPONSE CONTAINS A MANUAL MEANS OF
 DISCONNECT LOCATED ON THE OUTSIDE.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE INFORMATION ON BUS -DUCT
 RISER MAINS. APPEARS TO SHOW THESE AS
 "SHUNT-TRIP" AND NOT CONTAINING A MANUAL
 MEANS OF DISCONNECT LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT. PLEASE SEE
 MAIN PANEL SCHEDULE(S), THESE DO NOT
 SEEM TO INDICATE A MCB.
 230.76,230.79
  
 11)NOTE:NOTE #11 NO, PLEASE SEE RISER
 HAS BEEN REVISED, HOWEVER PLEASE SEE 5.2
 AS BUS-DUCT RISER IS STILL SHOWN AS 2500
 A'S WITH 5.1 SHOWING 3000A'S.
  
 ** PREVIOUS NOTE **
 PLEASE CORRELATE ALL MAINS ETC FOR
 SIZING. PLEASE SEE KEY NOTES MENTIONS
 2500A AND PLANS ALSO INDICATE 3000A.?
  
 12)NOTE: NOTE #12 NO, PLEASE SEE NOTES
 ON E.01 HAVE BEEN REVISED TO INDICATE
 ALL COPPER BUS-DUCT, HOWEVER NO SPEC
 BOOKS, AND RISER STILL SHOWS ALUMINUM.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE SPECIFIC INFORMATION ON
 BUS-DUCT, PLEASE SEE AN ALUM EQUIPMENT
 GROUNDING CONDUCTOR/ MATERIAL IS NOT
 PERMITED. 310.2. LOCAL AMENDMENTS.
  
 13)NOTE:NOTE #13 NO.
 PLEASE KNOW, REVIEW AND PERMITTING OF
 TOWERS SHALL NOT PASSED UNITLA REVIEW
 OF ALL SPECS ARE DONE. IF THIS EQUIPMENT
 IS BEING DONE UNDER THE GARAGE PERMITS,
 ALL WILL DEPEND ON THE REVIEW, PASSING
 AND ISSUANCE OF THE GARAGE BUIDLINGS.
 PLEASE KNOW, NO PERMITS FOR TOWERS WILL
 BE GRANTED UNTIL ALL ABOVE FOR GARAGES
 ARE MET.
 THE SPECIFICA INFORMATION FOR FIRE PUMPS
 , GENERATORS ETC SHOULD BE REFERENCE ON
 EACH SET OF TOWER PLANS AND PERHAPS NOTE
 FOR "SCOPE UNDER SEPARATE PERMIT".
  
 ** PREVIOUS NOTE:
 PLEASE SUBMIT ALL MANUFACTURE
 SPECS AND CUT SHEETS FOR GENERATOR, ATS,
 FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE ALSO SUBMIT THE SAME FOR ANYSUB
 BASE FUEL TANK.
 PLEASE KNOW, DUE TO THE INFORMATION NOT
 BEING SUBMITTED AT THIS TIME, REVIEW FOR
 SOME ITEMS FOR CODE COMPLIANCE CAN NOT
 BE DONE.
 UNABLE TO VERIFY CODE COMPLIANCE FOR
 MANY ITEMS UNDER NFPA, 20,70,101,110
 ETC.
  
 14)NOTE:NOTE #14 NO , AS NOTED ABOVE
 ONNOTE #13.
  
 ** PREVIOUS NOTE **
 PLEASE SEE ELECTRICAL RISER DIAGRAM DOES
 NOT CONTIAN ANY INFORMATION FOR FIRE
 PUMP OR FIRE PUMP CONTROLLER,
 SERVICE, SIZING , CONDUCTORS ETC.
 PLEASE COMPLETE.
 ENCASEMENT IN CONCRETE, OUTSIDE THE
 BLDGS, ETC
  
 15)NOTE: NOTE #15 NO, PLEASE SEE NOTE
 UNDER TOWER #4, THESE ROOMS AND MIN
 REQUIRMENTS SHOULD BE DETAILED IN EACH
 SET. GEN RM WS SEEN ON TOWER #4, HOWEVER
 SEE NOTES FOR FP RM ETC.
 PHOTO-METRICS FOR 30 FT CANDLES MIN ETC.
  
 ** PREVIOUS NOTE **
 PLEASE SEE AREA FOR GARAGE CONTAINING
 THE LOCATION OF FIRE PUMP AND GENERATOR
 WILL BE REQUIRED TO BE SUBMITTED FOR
 PERMIT AND REVIEW.
 PLEASE SEE LOCATIONS FOR FIRE
 SEPARATIONS, ACCESS, LIGHTING, ETC CAN
 NOT BE REVIEWED AT THIS TIME.
  
 16)NOTE: NOTE #16 OK, SO NOTED IN OTHER
 COMMENTS AND PLANS.
  
 ** PREVIOUS NOTE**
 PLEASE VERIFY LOCATION OF GENERATOR.
 PLEASE SEE PLANS SEEM TO INDICATE FIRE
 PUMP AND GEN RM LOCATED AT FIRST FLR
 LEVEL, HOWEVER RISER SEEMS TO SHOW THESE
 AT 2ND FLR LEVEL?
 PLEASE CLARIFY.
  
 17)NOTE: NOTE #17 YES/ NO, PLEASE SEE
 THE FIRST PART OF THE NOTE WAS
 ADDRESSED, HOWEVER CORRELATION OF A/C
 EQUIPMENT FOR 2ND PART OF NOTE DID NOT
 SEEM CORRRECTED AS MECHNICAL PLANS
 INDICATE DIFFERENT LOADS THAN ELECTRICAL
 PLANS.
 PLEASE SEE NOTE #40
 PLEASE SEE NEW NOTES FOR LOADS.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE DISCONNECTING MEANS FOR
 ALL A/C EQUIPMENT AT ROOF TOP LEVEL. A
 "TYPICAL" DETAIL MAY BE GIVEN FOR
 THESE.440.11
 PLEASE ALSO INDICATE ALL ROOF TOP GFI
 RECEPTS PER 210.63
 PLEASE CORRELATE ALL A/ KW RATINGS AND
 LOADS WITH MECHANICNAL PLANS . (KW
 RATINGS ETC).
  
 18)NOTE:NOTE #18? NO, PLEASE SEE FIRE
 COMMAND ROOM AND ALL EQUIPMENT ETC
 REQUIRED PER HIGH-RISES AS NOTED. PLEASE
 LIST ACCORDINGLY.
  
 ** PREVIOUS NOTE **
 PLEASE SEE FIRE REVIEW NOTES
 ALSO: PLEASE PROVIDE A LAYOUT FOR
 CENTRAL STATION RM(FIRE COMMAND RM)
 SHOWING ALL DEVICES/ PANELS/ STATUS
 PANELS ETC.
 PLEASE LIST ALL ITEMS AS SPECIFIED IN
 NFPA- 101 11.8.5,
  
 19)NOTE:NOTE #19 OK.
  
 20)NOTE: NOTE #20 OK.
  
 21)NOTE: NOTE #21 OK.
  
 22)NOTE:NOTE #22 NO, ? COULD NOT
 LOCATE THE NOTE AND INSTALLATION
 REQUIREMENTS/NOTE.
 RESPONSE MENTIONS TO SEE REVISED E.01
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE NOTE ON PLANS FOR SMOKE
 DETECTOR PLACEMENT PER REQUIREMENTS OF
 NFPA -72 11.8.3.5.
  
 23)NOTE: NOTE #23 OK.
  
 24)NOTE: NOTE #24 OK, HOWEVER SEE ISLAND
 FOR UNIT "E". THIS IS SHOWN ON THE THE
 TYPICAL DETAIL AND CAN BE REDLINED.
  
 25)NOTE: NOTE #25 OK, SEE RESPONSE
 MENTIONS GAS APPLIANCES, HOWEVER PLEASE
 INDICATE ON PLANS/PANEL SCHEDULE WHICH
 APPLIANCES ARE GOING TO BE GAS.
 PLEASE SEE NEW COMMENT WITH RESPECT TO
 WH.
  
 ** PREVIOUS NOTE **
 PLEASE SEE A 70A BRKR IS BEING SHOWN FOR
 RANGE?? PLEASE SEE 210.23,422.11B
 50A RANGE RECEPT, 50A BRKR MAX.
  
 26)NOTE: NOTE #26 ? UNCLEAR HOW THE
 SINGLE PHASE IS"A" AND "C" PHASE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE PANEL SCHEDULES SEEM TO SHOW
 "A" AND "C" PHASE FOR SINLGLE PHASE
 SERVICE AND UNITS??
 PLEASE CLARIFY / ADJSUT.215.5
  
 27)NOTE: NOTE #27 NO, PLEASE SEE AREAS
 SHOUDL BE CLEAR FOR DINING ROOM/AREA AND
 LIVING RM. PLEASE SEE THE LR/DR
 NOTTATIONS ON PLANS ARE CROSSED ON SOME
 UNITS .PLEASE SEPARATE FOR CLARITY
  
 ** PREVIOUS NOTE **
 PLEASE LABEL AND /OR CLARIFY "DINING"
 AREAS IN ALL UNITS.
 UNABLE TO VERIFY CIRCUITING AS DINING
 /LIVING ARE SEEMED TO BE COMBINED.'
 PLEASE SEE 210.52B1
  
 28)NOTE: NOTE #28 OK, PLEASE SEE MMOST
 WERE DONE, HOVER PLEASE SEE REDLINED
 PLANS AS THERE A FEW.
 PLEASE KNOW, AS SOME RECEPTS MAY BE
 MISSING FOR HALL AREAS AND 210.52C ON
 THE SMAE SHEET PLEASE REVISE AT THIS
 TIME.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 210.52D FOR SOME UNITS
 MISSING GFI'S WITH IN 3' OF LAV'S.
 PLEASE ALSO SEE A GFI MAY NOT PERMITTED
 ON THE OTHER SIDE OF A LAV TO MEET
 210.52D (3').
 GFI 'S MAY BE MOVED IN BETWEEN BOTH
 LAV'S OR AN ADDITIONALRECEPT MAY BE
 ADDED.
  
 29)NOTE: NOTE #29, NO, PLEASE SEE SOME
 STILL REDLINED AT LOCATIONS AS NOTED.
  
 ** PREVIOUS NOTE **
 PLEASE SEE MISSING RECEPTS IN HALLWAY
 AREAS, 10' OR MORE OF CONTINUOUS
 WALL. 210.52H.
  
 30)NOTE: NOTE #30 ?? PLEASE SEE RISER
 SHOWS PANEL, HOWEVER NOT NOTED AS FUTURE
 OR ?? 2MD FLR COULD NOT LOCATE THIS
 PANEL.
  
 ** PREVIOUS NOTE **
 PLEASE SEE RISER SEEMS TO INDICATE A
 POOL PANEL, HOWEVER NO OTHER INFORMATION
 WAS SUBMITTED AND PANEL COULD NOT
 LOCATED ON PLANS.
 LOADS ETC.
 215.5, 220
  
 31)NOTE: NOTE #31 OK
  
 32)NOTE: NOTE #32 N, HOWEVER PLEASE
 KNOW, NOTE WAS NOT COMPLETE WHEN TYPED
 FROM PREVIOUS REVIEW IN ERROR. PLEASE
 KNOW, THE COMMENT SHOULD HAVE READ. "
 PLEASE PROVIDE A NOTE ON ROOF TOP PLANS;
 " ANY AND ALL LIGHTNING PROTECTION
 SYSTEM PROPOSED OR INSTALLED SAHLL BE
 UNDER A SEPARATE PERMIT AND SHALL BE
 INSTALLED PER NFPA-780" OR WORDS TO THAT
 AFFECT.
 IT IS KNOWN TO THIS OFFICE THATTHE
 CODE DOES NOT REQUIRE LP ON THIS TYOE OF
 BUILDING AS LP IS REQUIRED ON SOME OTHER
 STRUCTURS PER THE FBC.
  
 ** PREVIOUS NOTE **
 PLEASE PLACE NOTE ON "ROOF
 PLANS" WHICH WILL REQUIRE ALL LIGHTNING
 PROTECTION
  
  
 33)NOTE: NOTE #33 OK.
  
 34)NOTE: NOTE #34 NO, PLEASE SEE SOME
 PANELS ARE NOTED AS CONTAINING
 "FEED-THRU LUGS" , HOWEVER SOME ARE ALSO
 SHOWING A MAIN W/ FEED THRU LUGS.CIRCUIT
 BREAKER?
 PLEASE SEE NEW COMMENTS FOR SOME PANELS.
  
 ** PREVIOUS NOTE **
 PLEASE INDICATE IF PANELS EH2A-
 EH12A ARE FEED THRU LUGS OR DOES EACH
 PANEL CONTAIN OCP FOR EACH.?
 PLEASE ALSO SEE PANELS H5A-9, 12 ETC.
 215.5
  
 35)NOTE: NOTE # 35 OK, HOWEVER SEE NEW
 NOTE.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE PANEL SCHEDULE FOR PANEL
 H2AA ON RISER. 215.5
  
 36) NOTE:NOTE # 36 OK, HOVER SEE NEW
 NOTE FOR 16B
  
 ** PREVIOUS NOTE ** PLEASE SEE PANEL
 H16A INDICATES H12A AND H12B ON LOAD
 CALCS?? RISER APPEARS TO SHOW H16A BEING
 FED FROM SBA AND SHOWS H12A FROM H9A
 ETC. 215.5
  
 37)NOTE: NOTE #37 OK.
  
 38)NOTE: NOTE #38 OK.
  
 39)NOTE: NOTE #39 NO.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT "SPEC BOOKS' FORREVIEW OF
 PROJECT. THESE WOULD CONTAIN JOBSITE
 SPECS.
  
 40)NOTE: NOTE # 40 OK.
  
 41)NOTE: NOTE #41 ? NO, PLEASE SEE NOTE
 WITH RESPECT TO CORRELATTION OF KW FOR
 AHU'S. ONCE THIS IS DONE, VERIFICATION
 OF THE OCP CAN BE DONE.
 SEE NEW NOTES FOR LOADS.
  
 ** PREVIOUS NOTE **
 NOTE ADDED AFTER REVIEW OF TOWER #4,
 PLEASE SEE MIN OCP FOR AHU HEAT TO BE
 125%. 424.3B SHOWS 50A OCP.
  
  
 *************** NEW NOTES **********
  
 1) NOTE: PLEASE PROVIDE A LETTER FROM
 FPL REPRESENITIVE FOR VAULT AND VAULT
 LOCATION SINCE REVISED PLANS.
 PLEASE SEE VAULT IN UNCLEAR AS ONCE
 SHEET APPEARS TO LABEL IN A SMALLER ROOM
 WITH SOEM OTHER EQUIPMENT/ ELECTRICAL IN
 THE VAULT. PLEASE KNOW, FPL DOES NOT
 PERMIT ANY ITEMS, ELECTRICAL FIRE
 SPRINKLER ETC IN VAULT.
 PLEASE ALSO SEE IS OUTSIDE AS SHOWN ON
 ANOTHER SHEET, PLEASE VERIFY LOCATION AS
 THIS SEEMS TO BE LOCATED IN THE TRASH
 DRAIN,A ND ACCESS AREA?
  
 2) NOTE: PLEASE SEE PANEL SCHEDULES FOR
 UNITSDO NOT APPEAR TO INDICATE ANY
 WATER HEATERS?? PLEASE SEE PANEL
 SCHEDULES DO SHOW TWO AHU'S BRANCH
 CIRCUITS?
 PLEASE KNOW THIS WAS MISSED ON FIRST
 REVIEW AS ORIGINAL PLANS INDICATE THE
 SAME.
 PLEASE ADJUST LOADS AS NEEDED.
 215,220,422
  
 3) NOTE: PLEASE SEE ONCE LOADS FOR AHU'S
 ARE CORRELATED, PLEASE ADJUST AS NEEDED.
 ** PLEASE KNOW, THE PLANS HAVE BEEN
 REVISED TO NOW ONLY INCLUDE ONE
 BUS-RISER, AND PLEASE SEE LOADS SHOWN
 NOW AFTER ALL DERATING HAS BEEN TAKEN
 STANDS AT 2936A'S ON A 3000A RATED BUS
 AND MAIN. PLEASE SEE IF LOADS FOR AHU'S
 ARE INDEED HIGHER, THIS WILL NEW
 ADJUSTED LOAD MAY CERTAINLY TAKE LOAD
 OVER THE 3000A RATING OF EQUIPMENT.
 PLEASE KNOW, THESE UNITS ARE GOING TO
 HAVE OWNERSHIP AS "CONDOS" AND
 REMODELING ETC ALMOST ALWAYS TAKES
 PLACE.
 PLEASE SEE SERVICE IS BEING SIZED WITH
 NO ALLOTMENT FOR FUTURE EXPANSION.
 **ELECTRICAL APPLIANCES, JACUZZI TUBS
 ETC'
 PLEASE SEE 90.8A "DISTRIBUTION CENTERS
 SHOULD CONTAIN ADDITIONAL SPACE AND
 "CAPACITY" FOR FUTURE ADDITIONS AND
 SHOULD BE CONVENIENTLY LOCATED FOR EASY
 ACCESSIBILITY."
 THIS EXCERPT IS TAKEN FROM THE 2002
 HANDBOOK.
  
 4) NOTE: PLEASE SEE PANEL SCHEDULE FOR
 16A DOES NOT INDICATE "FEED THRU LUGS"
 AND RISER DOES NOT SHOWN "16B" BEING FED
 FROM 16A?
 PLEASE SHOW.
  
 5) NOTE: PLEASE SEE MISSING DOOR
 "OVERLAY" ON 3.2.
  
 6) NOTE: PLEASE SEE NEW NOTE #19 AS
 NOTED ON GENERATOR RISER WHICH MENTIONS
 TO SEE NOTE #19 ON "KEYNOTES", HOWEVER
 KEY NOTE #19 IS BLANK?
 215.5
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE. THIS IS ONLY A NOTE:
  
 ** PLEASE KNOW, MANY OF THE ABOVE ITEMS
 ARE "REDLINED" AT LOCATIONS ON PLANS FOR
 NOTES.
  
 ** PLEASE KNOW, A RESPONSE LETTER IN
 TYPE WRITTEN FORM WILL HELP IN RESPONSES
 TO ELECTRICAL COMMENTS.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE KNOW, ALL OLD/OR VOIDED SHEETS
 MUST BE COMPLETELY REMOVED FROM SETS
 BEFORE RSUBMITTING PLANS.
 PLEASE ONLY SUBMIT ONE SET OF ALL
 OLD/VOIDED SHEETS FOR REFERENCE ONLY.
 ONLY THE NEW REVISED SHEETS SHOULD BE
 INSERTED INTO THE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SEE THIS WAS NOT DONE AS
 REQUESTED FROM PREVIOUS REVIEW
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-05-03 00:00:00REVIEWING
2006-05-01 00:00:00REVIEW IN PROGRESS.
2006-04-27 00:00:00IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-21 Cont ID  
Sent By dpalmer Date 2005-09-21 Time 17:45 Rev Time 30.00
Received By dpalmer Date 2005-09-11 Time 11:25 Sent To  
Notes
2005-09-26 00:00:00SAIL CLUB TOWER #3
  
 **** UNSAT ****
  
  
 1)NOTE: PLEASE SEE CODE REFERENCED ON
 PLANS LIST THE 1999 NEC. PLEASE KNOW, AS
 OF JULY 1ST 2003, THE STATE ADOPTE DTHE
 2002 NEC.
 PLEASE ALSO SEE WE ARE UNDER THE 2003
 NFPA-101 AND 2002 NFPA-72
 PLEASE ADJUST.
  
 2)NOTE: PLEASE SEE BLDG /FIRE REVIEW
 COMMENTS FOR STAIR TOWER EXITING WHICH
 WILL AFFECT ELECTRICAL LAYOUT.
 EXITS BACK INTO HALL WAY AREAS IN FRONT
 OF UNITS.
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE SOME AREAS WHICH ELECTRICAL
 FIXTURES SEEM TO BE MISSINGTHIS.
 PLEASE ALSO SEE CIRCUITING FOR UNITS.
 PLEASE KNOW, A "TYPICAL" UNIT LAYOUT MAY
 BE PROVIDED, HOWEVER A LAYOUT WOULD BE
 REQUIRED FOR EACH UNIT TYPE, INCLUDING
 STUDIO UNIT.
 CIRCUITING FOR SOME UNITS/ITEMS CAN NOT
 BE VERIFIED AT THIS TIME.
  
 4)NOTE: PLEASE PROVIDE PHOTO-METRICS FOR
 STAIR TOWERS ON NORMAL PWR AND STAND-BY.
 ALONG WITH WALK AREAS.
 PLEASE SEE STAIR TOWERS UNDER NORMAL PWR
 SHALL MEET A MIN OF 10FT CANDLES. PLEASE
 SEE ARES FOR HALLS ETC ARE PERMITTED TO
 BE LESS. .
 PLEASE SEE NFPA-101 7.8.1.3,7.9.2.1
  
 5)NOTE: PLEASE SEE ONE STAIR TOWER SHOWS
 CIRCUITING FOR LTS FROM NORMAL POWER
 PANEL AND CIRCUTING.
 PLEASE SEE THESE ARE REQUIRED TO BE ON
 EM POWER PANEL.
 PLEASE KNOW, BATTERY BACK FIXTURES WILL
 BE REQUIRED AT EVERY OTHER LEVEL(MIN).
 PLEASE SEE LS 101 WHICH MENTIONS THE
 TRIPPING/THROW OF A SINGLE BRKR SAHLL
 NOT LEAVE ANY EGRESS AREA IN TOTAL
 DARKNESS. PLEASE CALL ELECTRICAL PLAN
 REVIEW AND FIRE MARSHALS OFFICE TO GO
 OVER OPTIONS PERMITTED.
 A BATTERY BACK-UP FIXTURE AT EVERY OTHER
 LEVEL WILL SATISFY THIS OFFICE AND AHJ.
 PLEASE BE SURE TO MEET THE MIN OF 1
 FT/CANDLE UNDER EM.
 PLEASE BE SURE TO SEE PREVIOUS NOTE #4
 FOR LIGHTING LEVELS.(MIN)
  
 6)NOTE: PLEASE PROVIDE BATTERY BACK-UP
 FIXTURES IN MAIN ELECTRICAL RMS AND
 ELEVATOR ROOM(S), GENERATOR AND FIRE
 PUMP ROOM. PLEASE ALSO PROVIDE
 CIRCUITING FOR THESE
 RMS.
  
 7)NOTE: PLEASE PROVIDE CURB DETAIL FOR
 BUS-DUCT RISER AND FLOOR PENATRATIONS.
 368.6
  
 8)NOTE: PLEASE PROVIDE NOTES ON RISER
 AND ELECTRICAL ROOM SHEETS FOR
 REQUIREMENTS OF 110.26 FOR PANIC
 HARDWARE AND DOOR SWINGS.
 PLEASE SEE MIN CLEARENCE PER 110.26
  
 9)NOTE: PLEASE SEE RISER INDICATES ALL
 BUS-DUCT FROM FPL VAULT TO MAIN
 ELECTRICAL ROOM AS OVER-HEAD. PLEASE SEE
 230.70, 230.6, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTORS/ OR BUS DUCT
 PERMITTED "INSIDE THE BLDG.
 PLEASE SEE ROUTING OF BUS-DUCT APPEARS
 TO SHOW INSTALLATION INSIDE CONDO
 UNITS??
  
 10)NOTE: PLEASE PROVIDE INFORMATION ON
 BUS -DUCT RISER MAINS. APPEARS TO SHOW
 THESE AS "SHUNT-TRIP" AND NOT CONTAINING
 A MANUAL MEANS OF DISCONNECT LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT. PLEASE SEE
 MAIN PANEL SCHEDULE(S), THESE DO NOT
 SEEM TO INDICATE A MCB.
 230.76,230.79
  
 11)NOTE: PLEASE CORRELATE ALL MAINS ETC
 FOR SIZING. PLEASE SEE KEY NOTES
 MENTIONS 2500A AND PLANS ALSO INDICATE
 3000A.?
  
 12)NOTE: PLEASE PROVIDE SPECIFIC
 INFORMATION ON BUS-DUCT, PLEASE SEE AN
 ALUM EQUIPMENT GROUNDING CONDUCTOR/
 MATERIAL IS NOT PERMITED.
 310.2. LOCAL AMENDMENTS.
  
 13)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS AND CUT SHEETS FOR GENERATOR, ATS,
 FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE ALSO SUBMIT THE SAME FOR ANYSUB
 BASE FUEL TANK.
 PLEASE KNOW, DUE TO THE INFORMATION NOT
 BEING SUBMITTED AT THIS TIME, REVIEW FOR
 SOME ITEMS FOR CODE COMPLIANCE CAN NOT
 BE DONE.
 UNABLE TO VERIFY CODE COMPLIANCE FOR
 MANY ITEMS UNDER NFPA, 20,70,101,110
 ETC.
  
 14)NOTE: PLEASE SEE ELECTRICAL RISER
 DIAGRAM DOES NOT CONTIAN ANY INFORMATION
 FOR FIRE PUMP OR FIRE PUMP CONTROLLER,
 SERVICE, SIZING , CONDUCTORS ETC.
 PLEASE COMPLETE.
 ENCASEMENT IN CONCRETE, OUTSIDE THE
 BLDGS, ETC
  
 15)NOTE: PLEASE SEE AREA FOR GARAGE
 CONTAINING THE LOCATION OF FIRE PUMP AND
 GENERATOR WILL BE REQUIRED TO BE
 SUBITTED FOR PERMIT AND REVIEW.
 PLEASE SEE LOCATIONS FOR FIRE
 SEPARATIONS, ACCESS, LIGHTING, ETC CAN
 NOT BE REVIEWED AT THIS TIME.
  
 16)NOTE: PLEASE VERIFY LOCATION OF
 GENERATOR.
 PLEASE SEE PLANS SEEM TO INDICATE FIRE
 PUMP AND GEN RM LOCATED AT FIRST FLR
 LEVEL, HOWEVER RISER SEEMS TO SHOW THESE
 AT 2ND FLR LEVEL?
 PLEASE CLARIFY.
  
 17)NOTE: PLEASE PROVIDE DISCONNECTING
 MEANS FOR ALL A/C EQUIPMENT AT ROOF TOP
 LEVEL. A"TYPICAL" DETAIL MAY BE GIVEN
 FOR THESE.440.11
 PLEASE ALSO INDICATE ALL ROOF TOP GFI
 RECEPTS PER 210.63
 PLEASE CORRELATE ALL A/ KW RATINGS AND
 LOADS WITH MECHANICNAL PLANS . (KW
 RATINGS ETC).
  
 18)NOTE: PLEASE SEE FIRE REVIEW NOTES
 ALSO: PLEASE PROVIDE A LAYOUT FOR
 CENTRAL STATION RM(FIRE COMMAND RM)
 SHOWING ALL DEVICES/ PANELS/ STATUS
 PANELS ETC.
 PLEASE LIST ALL ITEMS AS SPECIFIED IN
 NFPA- 101 11.8.5,
  
 19)NOTE: PLEASE SEE RECEPTS MISSING PER
 210.52
 SEE REDLINED PLANS.
  
 20)NOTE: PLEASE CALRIFY THE "P" LOCATED
 NEXT TO SMOKE DETECTORS?
  
 21)NOTE: PLEASE VERIFY CIRCUITING OF
 LAUNDRY RM/ WASHER CIRCUIT.
 PLEASE SEE 210.11C2,210.52F,220.16
 PLEASE ALSO SEE MIN 1500VA.
 PLEASE VERIFY LOAD FOR WASHER.
  
 22)NOTE:PLEASE PROVIDE NOTE ON PLANS
 FOR SMOKE DETECTOR PLACEMENT PER
 REQUIREMENTS NFPA -72 11.8.3.5.
  
 23): PLEASE PROVIDE NOTE FOR ALL
 ELECTRICAL DEVICES TO BE INSTALLED PER
 FAIR HOUSING ACT REGULATIONS, (FHAR) 24
 CFR 100.205
  
 24)NOTE: PLEASE SEE 210.52C1 FOR SOME
 MISSING KITCHEN COUNTERSPACE RECEPTS.
 PLEASE ALSO SEE COUNTERSPACE APPEARS TO
 SHOW A DEDICATED CIRCUIT (19) FOR
 MICROWAVE WHICH ALSO APPEARS TO BE THE
 RECEPT FOR KITCHEN COUNTERSPACE?
 IF THE MICROWAVE IS A DEDICATED RECEPT,
 THEN AN ADDTIONAL GFI WOULD BE REQUIRED.
 210.8A16.
  
 25)NOTE: PLEASE SEE A 70A BRKR IS BEING
 SHOWN FOR RANGE??
 PLEASE SEE 210.23,422.11B
 50A RANGE RECEPT, 50A BRKR MAX.
  
 26)NOTE: PLEASE SEE PANEL SCHEDULES SEEM
 TO SHOW "A" AND "C" PHASE FOR SINLGLE
 PHASE SERVICE AND UNITS??
 PLEASE CLARIFY / ADJSUT.
 215.5
  
 27)NOTE: PLEASE LABEL AND /OR CLARIFY
 "DINING" AREAS IN ALL UNITS.
 UNABLE TO VERIFY CIRCUITING AS DINING
 /LIVING ARE SEEMED TO BE COMBINED.'
 PLEASE SEE 210.52B1
  
 28)NOTE: PLEASE SEE 210.52D FOR SOME
 UNITS MISSING GFI'S WITH IN 3' OF LAV'S.
 PLEASE ALSO SEE A GFI MAY NOT PERMITTED
 ON THE OTHER SIDE OF A LAV TO MEET
 210.52D (3').
 GFI 'S MAY BE MOVED IN BETWEEN BOTH
 LAV'S OR AN ADDITIONALRECEPT MAY BE
 ADDED.
  
 29)NOTE: PLEASE SEE MISSING RECEPTS IN
 HALLWAY AREAS, 10' OR MORE OF CONTINUOUS
 WALL.
 210.52H.
  
 30)NOTE: PLEASE SEE RISER SEEMS TO
 INDICATE A POOL PANEL, HOWEVER NO OTHER
 INFORMATION WAS SUBMITTED AND PANEL
 COULD NOT LOCATED ON PLANS.
 LOADS ETC.
 215.5, 220
  
 31)NOTE: PLEASE VERIFY BATH CIRCUITS
 BEING SHOWN WITH ARC FAULT PROTECTION??
 210.8 REQUIRES GFI PROTECTION FOR BATHS
 AND 210.12 ARC FAULT PROTECTION FOR
 BEDROOM CIRCUITS?
 THIS IS ONLY A NOTE:
  
 32)NOTE: PLEASE PLACE NOTE ON "ROOF
 PLANS" WHICH WILL REQUIRE ALL LIGHTNING
 PROTECTION
  
  
 33)NOTE: PLEASE IDICATE ON PLANS/RISER
 IF GENERATOR WILL BE A "SEPARATELY
 DERIVED SYSTEM" OR A " NON SEPARATELY
 DERIVEDSYSTEM.
 IF SD, PLEASE INCLUDE GROUNDING
 ELECTRODE SYSTEM PER 250.30
  
 34)NOTE: PLEASE INDICATE IF PANELS EH2A-
 EH12A ARE FEED THRU LUGS OR DOS EACH
 PANEL CONTAIN OCP FOE EACH.?
 PLEASE ALSO SEE PANELS H5A-9, 12 ETC.
 215.5
  
 35)NOTE: PLEASE PROVIDE PANEL SCHEDULE
 FOR PANEL H2AA ON RISER.
 215.5
  
 36) NOTE: PLEASE SEE PANEL H16A
 INDICATES H12A AND H12B ON LOAD CALCS??
 RISER APPEARS TO SHOW H16A BEING FED
 FROM SBA AND SHOWS H12A FROM H9A ETC.
 215.5
  
 37)NOTE: PLEASE CLARIFY NOTES # 5 AND #6
 ON GROUNDING RISER?
 250.50
  
 38)NOTE: PLEASE SEE RISER DIAGRAM WHICH
 SHOWS GENERATOR FEEDING TOWER #3 (THIS
 TOWER) AND ALSO SHOWS FEEDING TOWER #1??
 PLEASE SEE ELECTRICAL ROOM PLANS SHOW
 FEEDING TOWERS #3 AND #4??
 PLEASE CORRELATE.
 215.5
  
 39)NOTE: PLEASE SUBMIT "SPEC BOOKS' FOR
 REVIEW OF PROJECT.
 THESE WOULD CONTAIN JOBSITE SPECS.
  
 40)NOTE: PLEASE BE SURE ALL CONTINUOUS
 LOADS ARE SHOWN AT 125%.
 215.3,230.42 ETC.
  
 41)NOTE: NOTE ADDED AFTER REVIEW OF
 TOWER #4,
 PLEASE SEE MIN OCP FOR AHU HEAT TO BE
 125%. 424.3B
 SHOWS 50A OCP.
  
 ** PLEASE SEE THAT NO PLANS, PERMIT
 APPLICATION ETC WAS SUBMITTED FOR GARAGE
 BLDGS.
  
 ** PLEASE KNOW, MANY OF THE ABOVE ITEMS
 ARE "REDLINED" AT LOCATIONS ON PLANS FOR
 NOTES.
  
 ** PLEASE KNOW, A RESPONSE LETTER IN
 TYPE WRITTEN FORM WILL HELP IN RESPONSES
 TO ELECTRICAL COMMENTS.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO "REMOVE" ALL OLD
 VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO THE COMPLETED SETS
 FOR REVIEW AND STAMPING.
  
 ** PLEASE SEE BLDG REVIEW COMMENTS WHICH
 WILL REQUIRE ALL PRODUCT APPROVALS,
 SUBMITTALS ETC TO BE DETACHED FROM
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-09-21 00:00:00************ UNSAT *********
  
 SAIL CLUB
 TOWER #3- 16- STORY
  
 NOTES TO FOLLOW.
2005-09-16 00:00:00REVIEW STARTED.
2005-09-11 00:00:00IN ELECTRIC FOR REVIEW.
 REVIEWS IN PROGRESS .

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By mamini Date 2005-08-23 Time 10:20 Rev Time 0.50
Received By mamini Date 2005-08-23 Time 10:20 Sent To  
Notes
2005-08-23 00:00:00FAILED;
  
 1. PLEASE SEE REVIEW NOTES UNDER PERMIT
 # 05080676
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-06-13 Cont ID  
Sent By mwennerg Date 2006-06-13 Time 11:17 Rev Time 0.00
Received By mwennerg Date 2006-06-13 Time 11:17 Sent To  
Notes
2006-06-13 00:00:00***DENIED***
  
 1) PLEASE SEE THAT NOTE IS STILL ON
 PLANS. PLEASE REMOVE OR MAKE CORRECTION.
  
 2) NO REVISION FOUND ON FP SHEETS.
  
 3) OK
  
 4) OK
  
 5) OK
  
 6) OK
  
 7) NO RESPONSE FOUND ON A-1.1.2.
  
 8) OK
  
 9) OK
  
 10) OK
  
 11) OK
  
 12) OK
  
 13) PLEASE INDICATE THE TOTAL BUILDING
 COVERAGE EXPECTED BY (1) FIRE PUMP AT
 1000 GPM.
  
 14) OK
  
 15) NO MENTION OF SURVIVABILITY
 REQUIREMENT ON FA0.1.
  
 16) PLEASE NOTE THAT NFPA 13R IS
 REFERENCED ON FS0.1. THIS HAS BEEN
 IDENTIFIED ON THE PLANS FOR YOUR
 CONVENIENCE. PLEASE REMOVE FROM PLANS.
  
 17) OK
  
 18) OK
  
 19) OK
  
 20) OK
  
 21) OK
  
 22) OK
  
 23) IS THE AREA SHOWN THE ONLY COVERED
 WALKWAY ASSOCIATED WITH THIS PROJECT?
  
 24) OK
  
 25) PLEASE SEE COMMENT #13.
  
 26-32) NO RESPONSES FOUND ON PLANS OR
 LETTERS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-10-14 Cont ID  
Sent By mwennerg Date 2005-10-14 Time 15:05 Rev Time 0.00
Received By mwennerg Date 2005-10-14 Time 15:05 Sent To  
Notes
2005-10-14 00:00:00******DENIED******
  
 TOWER #3
  
 1) FOR REFERENCE, HIGHRISE IS DEFINED AS
 BUILDING GREATER THAN 75' IN HEIGHT.
  
 2) TWO FIRE DEPARTMENT CONNECTIONS ARE
 REQUIRED FOR HIGHRISE BUILDINGS. PLEASE
 SHOW LOCATIONS ON PLANS. LOCKING CAPS
 ARE REQUIRED.
  
 3) DOUBLE CHECK DETECTOR ASSEMBLY TO BE
 ELECTRONICALLY SUPERVISED AND BE SECURED
 WITH CHAIN AND LOCK.
  
 4) ELEVATORS TO COMPLY WITH ASME/ANSI A
 17.1. ELEVATOR WARNING SIGNS ARE
 REQUIRED.
  
 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 6) NOTE REGARDING ADDRESS HEIGHT
 ACKNOWLEDGED. PLEASE ILLUSTRATE ON
 ELEVATION SHEETS FOR FUTURE REFERENCE
 AND FURTHER PLAN REVIEWS.
  
 7) PLEASE INDICATE IF ELEVATORS ARE
 STRETCHER ACCESSIBLE.
  
 8) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS IN TERMS OF CLASS A, B, OR C.
  
 9) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN BUILDING REACHES 3 STORIES OR 30'
 IN HEIGHT.
  
 10) STANDPIPE CONNECTIONS SHALL BE 2
 1/2"- 1 1/2" REDUCERS WITH CHAINS.
  
 11) FIRE SPRINKLER HEADS ARE MISSING IN
 ELECTRICAL/PHONE ROOMS.
  
 12) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS. HYDRAULIC CALC SHEETS
 WILL BE REQUIRED.
  
 13) FIRE PUMP SERVING A HIGHRISE
 BUILDING SHALL BE A MINIMUM OF 1250 GPM.
  
 14) FIRE ALARM MONITORING SHALL BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
 15) FIRE ALARM SYSTEM TO MEET NFPA-72
 REQUIREMENTS FOR SURVIVABILITY.
  
 16) NFPA 13R IS REFERENCED ON SHT FS0.1.
 THAT CODE IS APPLICABLE TO BUILDINGS UP
 TO AND INCLUDING 4 STORIES IN HEIGHT.
  
 17) SMOKE DETECTOR IS MISSING IN FIRE
 COMMAND ROOM.
  
 18) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS WHERE
 PROVIDED SHALL BE WIRED TO THE FIRE
 ALARM SYSTEM TO CAUSE A GENERAL FIRE
 ALARM CONDITION WHEN ACTIVATED.
  
 19) FIRE ALARM SYSTEM SHALL BE CLASS A
 STYLE D, OR FULLY ADDRESSABLE.
  
 20) EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 21) NO CUTTING OR WELDING OPERATIONS ARE
 PERMITTED WITHOUT APPROVAL OF THE FIRE
 PREVENTION BUREAU AND COMPLIANCE WITH
 NFPA 51B.
  
 22) BUILDING IS TO MEET HIGHRISE
 REQUIREMENTS OF THE APPLICABLE BUILDING
 AND FIRE CODES.
  
 23) FIRE SPRINKLER HEADS APPEAR TO BE
 MISSING IN COVERED WALKWAYS. PLEASE
 INDICATE CODE REFERENCE WHERE THIS
 ARRANGEMENT IS ACCEPTABLE.
  
 24) EMERGENCY LIGHTING IS PROVIDED ON
 FIRST FLOOR ELECTRICAL/PHONE ROOM, BUT
 NOT ON UPPER FLOORS.
  
 25) PLEASE NOTE THAT THE FIRE PUMP IS
 SHOWN IN THE PARKING GARAGE THAT ISN'T
 PART OF THIS PHASE. ADDITIONAL
 INFORMATION REGARDING WHAT ARRANGEMENT
 BY THIS OFFICE HAS BEEN ACCEPTED IS
 REQUIRED. THE FIRE PUMP SHALL BE 1250
 GPM MINIMUM FOR A HIGHRISE BUILDING.
 PLEASE CONTACT THE BUREAU OF FIRE
 PREVENTION AT (561) 804-4724.
  
 26) FIRE HYDRANTS TO BE WET AND
 OPERATIONAL PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 27) THE ANTICIPATED STACK EFFECT NOTE
 WORDING SHALL BE ADDED TO THE
 MEACHANICAL DRAWINGS.
  
 28) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO BE IN COMPLIANCE WITH NFPA
 241.
  
 29) ALL SHAFTS LARGE ENOUGH FOR PERSONS
 TO FALL INTO MUST BE MARKED SHAFTWAY IN
 6" LETTERS.
  
 30) TACTILE SIGNAGE IS REQUIRED AT EXIT
 DOORS.
  
 31) SIGNS ARE REQUIRED IN STAIWELLS
 INDICATING TOP, BOTTOM, FLOOR
 IDENTIFICATION AND ROOF ACCESS.
  
 32) UL CERTIFICATION SHALL BE PROVIDED
 AT THE TIME OF THE FIRE ALARM ACCEPTANCE
 TEST FINAL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-05-10 Cont ID  
Sent By kstevens Date 2006-05-10 Time 18:35 Rev Time 0.00
Received By kstevens Date 2006-05-10 Time 18:34 Sent To  
Notes
2006-05-10 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 FROM PLUMBING PLAN REVIEW:
  
 26. THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CUT SECTIONS NOT SHOWN
 AND MOST RISERS NOT SHOWN.
 ***RESPONSE NOTED, BUT THE LENGTHS OF
 EACH CUT SECTION HAVE NOT BEEN SUBMITTED
 AS REQUESTED.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ***RESPONSE NOTED, BUT NO CALCULATION
 WERE SUBMITTED FOR THE CLOTHS DRYERS.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT MANUF. SHEET HAVE
 NOT BEEN FOUND.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REMOVE ALL VOIDED SHEETS FROM SETS OF
 PLANS AND RESUBMIT ONE SET OF "OLD
 SHEETS" SEPARATELY FOR COMPARISON.
  
 **************NEW COMMENT***************
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By kstevens Date 2005-11-09 Time 18:49 Rev Time 0.00
Received By kstevens Date 2005-11-09 Time 18:49 Sent To  
Notes
2006-05-08 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 FROM PLUMBING REVIEW:
  
 26. THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CUT SECTIONS NOT SHOWN
 AND MOST RISERS NOT SHOWN.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 E. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-07 Cont ID  
Sent By adarroug Date 2006-03-07 Time 09:30 Rev Time 0.00
Received By adarroug Date 2006-03-07 Time 09:30 Sent To  
Notes
2006-03-30 00:00:00TO "COMM" BD#7
2006-03-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-01 Cont ID  
Sent By kstevens Date 2005-12-01 Time 07:35 Rev Time 0.00
Received By kstevens Date 2005-08-16 Time 11:17 Sent To  
Notes
2005-08-16 00:00:00TO "COMM" BD#12/PLANS ON RACK/5 ROLLS
 AND BOOKS.
 5 SEPARATE APPLICATIONS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-04-18 Cont ID  
Sent By pkrauss Date 2006-04-18 Time 07:15 Rev Time 0.00
Received By pkrauss Date 2006-04-18 Time 07:15 Sent To  
Notes
2006-04-18 00:00:00DENIED:TOWER #3
 RESPONSE TO COMMENTS DATED 10-11-05.
 COMMENT #1:
 PLAN SHEET M2.1, RESPONSE INDICATES
 THE INTAKE DUCT FOR THE TOILET & DRYER
 EXHAUST CHASE IS FOR THE MAKE-UP AIR.
 PLEASE CLARIFY THE FOLLOWING:
 1) SIZE OF THE BRANCH DUCT.
 2) PLEASE CLARIFY THE PENETRATION
 BETWEEN THE RESIDENCE AND THE WALKWAY.
 DOES THIS HAVE THE PENETRATION HAVE A
 FIRE, SMOKE OR BOTH RATING? SHOW
 COMPLIANCE WITH 2004 FBC 716.
  
 COMMENT #5:
 RESPONSE INDICATES ANNOTATION ON PLAN
 SHEET M0.1 "NO COMBUSTIBLES ALLOWED
 IN THE RETURN AIR PLENUM".PLEASE
 COORDINATE WITH THE ARCHITECT.
 ACCORDING TO THE DOOR SCHEDULE (PLAN
 SHEET A7.2.1 & A7.2.2), THE DOORS TO THE
 A/C CLOSET ARE CONSTRUCTED OF HOLLOW
 WOOD.DOES THIS MEET THE REQUIREMENT OF
 NON-COMBUSTIBLE?
  
 PLEASE ALSO REFERENCE THE NOTE ON PLAN
 SHEET M7.1, RETURN AIR THROUGH LOUVERED
 DOOR.THE DOOR TO THE A/C CLOSET OPENS
 INTO THE LAUNDRY ROOM WITH.RETURN AIR
 SHALL NOT BE LOCATED IN THE LAUNDRY
 ROOM, 2004 FMC 601.3 & 601.4 EXCEPTION
 #3.
  
  
 NEW COMMENTS:
 1.PLAN SHEET P6.4 INDICATES GAS
 APPLICANCES, SPECIFICALLY THE WATER
 HEATER.PLEASE CLARIFY THE VENTING OF
 THE GAS WATER HEATER.PLEASE NOTE, PER
 2004 FMC 602.1, FUEL FIRED APPLIANCES
 SHALL NOT BE INSTALLED WITHIN A PLENUM.
  
 2.PLEASE NOTE, PER 2004 FMC 504.5,
 INSTALLATIONS EXHAUSTING GREATER THAN
 200 CFM SHALL BE PROVIDED WITH MAKE-UP
 AIR.
  
 3.PROVIDE ADDITIONAL INFORMATION FOR
 THE VENTILATION/PRESSURIZATION OF THE
 EXIT STAIRWAY.SHOW COMPLIANCE WITH
 2004 FBC 909.20 & 1019.1.8.
  
 4.PER 2004 FBC 903.2.10.2 &
 903.2.12.1, SPRINKLER SYSTEMS RQUIRED
 FOR TRASH CHUTES & DRYER EXHAUST
 (SUB-DUCT).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-11 Cont ID  
Sent By pkrauss Date 2005-10-11 Time 14:24 Rev Time 0.00
Received By pkrauss Date 2005-10-11 Time 14:14 Sent To  
Notes
2005-10-11 00:00:00DENIED:2004 FBC / TOWER 3
 1.PLAN SHEET M2.1, PLEASE CLARIFY
 DUCTWORK IN THE COVERED WALKWAY.PLAN
 INDICATES RETURN AIR GRILLES IN THE
 COVERED WALKWAY AND ALSO SHOWS DUCT
 BRANCHING OF INTO THE INDIVIDUAL CONDO
 UNITS THAT ARE IDENTIFIED AS 'TX' OR
 'DX' WHICH ACCORDING TO THE SCHEDULE ARE
 TOILET & DRYER EXHAUST RISERS.ARE ALL
 THESE EXHAUST RISERS TIED IN TOGETHER?
  
 2.PLEASE CLARIFY IN THE KEY NOTES THE
 ACRONYM E/A (EXHAUST AIR)? THIS IS NOT
 INDICATED ON ON THE HVAC ABBREVIATIONS
 LISTED ON SHEET M0.1.
  
 3.PLAN SHEET M2.1, NOT ALL UNITS
 INDICATE DRYER EXHAUST DUCT LAYOUT.
 PLAN SHEET M5.1 & M5.2 INDICATES INTAKES
 ON THE EXHAUST SHAFTS.PLEASE CLARIFY,
 IT APPEARS ALL THESE SHAFTS ARE TIED IN
 TOGETHER?
  
 4.PLAN SHEET M7.1 DETAIL 2, AUXILIARY
 DRAIN PAN WITH OVERFLOW PROTECTION
 REQUIRED PER 2001 FMC 307.2.3.PLEASE
 INDICATE AUXILIARY DRAIN LINE OR WATER
 LEVEL DETECTOR.
  
 5.DETAIL 2 ON M7.1 ALSO INDICATES
 LOUVERED DOOR.PLEASE NOTE, NO
 COMBUSTIBLES ALLOWED IN THE RETURN AIR
 PLENUM.THIS ALSO INCLUDES THE DOOR.
 2004 FMC 602.2.1.
  
 6.PLAN SHEET M5.1 DETAIL 1 AND 2
 REFERENCES THE ARCH PLANS FOR SHAFT
 DETAIL.THIS IS NOT SHOWN IN THE ARCH.
  
 7.PIPING CHASE INDICATED ON PLAN M5.1
 SHALL COMPLY WITH 2004 FMC 1107.2.1,
 WHERE PIPING PASSES THROUGH CONCRETE
 FLOORS, THE PIPING SHALL BE PROVIDED
 WITH SLEEVES OR THIMBLES.
  
 8.REFRIGERANT PIPING PENETRATING
 FLOORS SHALL COMPLY WITH ASHRAE 15-2001
 SECTION 8.10.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-05-10 Cont ID  
Sent By kstevens Date 2006-05-10 Time 17:22 Rev Time 0.00
Received By kstevens Date 2006-05-08 Time 18:52 Sent To  
Notes
2006-05-10 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2005 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 1. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED & DATED AS
 REQUIRED BY FS. SECTION 106.1
 ***NO RESPONSE FROM ARCHITECT NOTED, BUT
 SEE THE FOLLOWING SHEETS: BOUNDARY
 SURVEY, PP1 OF 9 THRU PP9 OF 9, ALL
 LA-POOL AND LA-FW SHEETS HAVE NOT
 ADDRESSED THE COMMENT.
  
 3. SHT T-3 A2.4.1 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SHOW THE SQUARE FOOTAGE FOR EACH AREA &
 SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ALONG WITH THE AREA
 OF ROOF THAT DRAINS ONTO THE ROOF FROM
 ABOVE FOR EACH AREA IN CALCLATIONS.
 SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS.
 ***RESPONSE NOTED, BUT NO REFERENCE TO
 THE AREAS OF ROOFS DRAINING ON TO THE
 ROOF AREAS FROM ABOVE. SEE STAIR ROOF,
 MECHANICAL ROOM ROOF, HIP ROOFS, AND
 OCTAGON ROOF.
  
 4. SHTS T-3 A4.1.1 THRU T-3 A4.1.8 UNITS
 A, B, C, D, E, H, F, G & K SHALL COMPLY
 WITH REQUIREMENTS 1 THRU 7 OF THE FHA-98
 DESIGN MANUAL. INDICATE SPECIFICATION
 "A" OR "B" FOR EACH UNIT. SHOW THE W/C
 OPENING, (MINIMUM 33"), SHOW THE W/C AT
 18" OFF THE WALL TO THE CENTER OF THE
 FIXTURE WHERE APPLICABLE, AND 18"
 MINIMUM OFF AN ADJACENT FIXTURE. SEE
 PAGES 6.7 7.43 & 7.44. - SHOW CLEAR
 FLOOR SPACE FOR ALL USABLE FIXTURES. -
 SUBMIT A DETAIL FOR BACKING FOR W/C'S,
 TUBS, SHOWERS ECT. PER REQUIREMENT 6. -
 CLEAR FLOOR SPACE FOR SHOWERS SHALL BE
 PARALLEL TO SHOWER & FLUSH WITH CONTROL
 WALL. INDICATE CONTROL WALL ON UNIT
 FLOOR PLAN. (SEE PAGE 7.56).
 ***NO RESPONSE FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED.
  
 5. SHT T-3 A4.1.9 MEN'S & WOMEN'S TOILET
 ROOMS SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.22 WITH ALL
 SUBSECTIONS. SUBMIT A DETAIL SHOWING
 COMPLIANCE.
 ***NO RESPONSE FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED.
  
 6. SUBMIT CALCULATIONS FOR ALL
 AMENITITES AREAS FOR MINIMUM FACILITIES
 PER TABLES 1004.2 (BLDG) AND 403.1
 (PLMG). SHOW THE SQUARE FOOTAGE FOR ALL
 COMMON USE AREAS ALONG WITH THE
 OCCUPANCY LOAD OF EACH AREA. INDICATE
 THE LOCATION OF THE SANITARY FACILITIES
 FOR THE POOL AREA.
 ***NO RESPONSE FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED.
  
 8. SHT T-3 A4.19 SINK IN CATERING
 KITCHEN SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. PROVIDE A
 DETAIL.
 ***NO RESPONSE FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED.
 9. SHTS T-3 A4.1.13 THRU T-3 A4.1.17
 SHALL COMPLY WITH FHA-98 DESIGN MANUAL
 REQUIREMENTS 1 THRU 7. INDICATE
 SPECIFICATION "A" OR "B". SHOW CLEAR
 FLOOR SPACE FOR ALL USABLE FIXTURES.
 SHOW ALL W/C'S TO BE 18" OFF THE WALL TO
 THE CENTER OF THE FIXTURE . SHOW ALL
 OPENINGS TO BE MINIMUM 33". INDICATE
 MEASUREMENT FROM THE CENTER LINE OF THE
 W/C'S TO THE ADJONINING FIXTURES.
 ***NO RESPONSE FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED.
  
 10. SHT T-3 A6.1.1 DETAIL #4 TRASH CHUTE
 WATER SUPPLY SHALL HAVE BACKFLOW
 PROTECTION. INDICATE THE METHOD OF
 BACKFLOW PROTECTION REQUIRED IN SECTION
 608 AND TABLE 608.1.
 ***RESPONSE NOTED, BUT NO REFERENCE TO
 BACKFLOW PROTECTION WAS LOCATED ON SHT
 P3.3
  
 11. SHT T-3 A6.1.3 DETAIL #10 ROOF DRAIN
 DETAIL, INDICATE MEASUREMENT FROM THE
 ROOF TO THE TOP OF THE SECONDARY ROOF
 DRAIN PIPI, (EMERGENCY OVERFLOW PIPE).
 ***NO RESPONSE FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED.
  
 12. SHT T-3 A8.1.1 SHOW THE BACKING FOR
 THE W/C'S PER FHA DESIGN MANUAL PAGES
 6.3 & 6.4. SHOW BACKING FOR THE TUBS PER
 PAGE 6.9.
 ***NO RESPONSED FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED. NO INFORMATION
 SHOWN AS REQUIRED BY DESIGN MANUAL. NO
 MEASUREMENTS INDICATED.
  
 13. SHT P0.1 PLUMBING NOTES #1 & #24
 REFER TO FBC-2001, CODE ADOPTED FOR THIS
 JOB IS FBC-2004. PLEASE CHANGE REFERENCE
 ***RESPONSE NOTED, BUT PLUMBING NOTE
  
 17. SHT P2.4 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. (SEE
 COMMENT #3).
 ***RESPONSE NOTED, BUT R0OFS THAT DRAIN
 ON TO ROOF FROM ABOVE HAVE NOT BEEN
 SHOWN IN THE CALCULATIONS. (SEE COMMENT
 NUMBER 3).
  
 20. SHTS P5.1 & P5.2 SUBMIT SOVENT
 DESIGN MANUAL FOR THE SOVENT SYSTEM. THE
 SOVENT SYSTEM SHALL BE APPROVED. SECTION
 106.1.1.
 ***RESPONSE NOTED, BUT THIS SYSTEM AND
 FITTINGS ARE NOT APPROVED.
  
 21. SHT P5.3 BLDG DRAIN ISOMETRIC RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE TUB IS MISSING DOWNTREAM OF RISER
 S/33 AND TUB IS NOT VENTED AS SHOWN.
 SECTIONS 106.1.1 & 901.2.1. - W/C, LAV &
 SHOWER ARE NOT SHOWN DOWNSTREAM OF RISER
 S/34 (ROOM G 110). - MEN'S & WOMEN'S
 TOILET ROOMS , (108 & 109), ARE NOT
 SHOWN ON RISER. - THE TUB DOWNSTREAM OF
 RISER S/43 IS NOT VENTED AS SHOWN.
 SECTION 901.2.1. - LAUNDRY (103) IS NOT
 SHOWN DOWNSTREAM OF RISER S/42. - PIPING
 TO STUDIO K W/M & BATHROOM (105)
 DOWNSTREAM OF RISER S/23 NOT SHOWN.
 SECTION 106.1.1.
 ***RESPONSE NOTED, BUT MEN'S AND WOMEN'S
 TOILET ROOMS ARE STILL NOT SHOWN ON THE
 RISER, NOR IS THE LAUNDRY ROOM PIPING
 SHOWN.
  
 22. SHT P5.3 SHOW DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLE 710.1(1)
 ***RESPONSE NOTED, BUT SOME PIPE SIZES
 ARE NOT CORRECT AND SOME DFU'S ARE NOT
 CORRECT. (SEE RED LINE CORRECTIONS ON
 ONE SET OF PLANS).
  
 26. THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CUT SECTIONS NOT SHOWN
 AND MOST RISERS NOT SHOWN.
 ***RESPONSE NOTED, BUT THE LENGTHS OF
 EACH CUT SECTION HAVE NOT BEEN SUBMITTED
 AS REQUESTED.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ***RESPONSE NOTED, BUT NO CALCULATION
 WERE SUBMITTED FOR THE CLOTHS DRYERS.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT MANUF. SHEET HAVE
 NOT BEEN FOUND.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REMOVE ALL VOIDED SHEETS FROM SETS OF
 PLANS AND RESUBMIT ONE SET OF "OLD
 SHEETS" SEPARATELY FOR COMPARISON.
  
 **************NEW COMMENT***************
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-09 Cont ID  
Sent By kstevens Date 2005-11-09 Time 15:33 Rev Time 0.00
Received By kstevens Date 2005-11-09 Time 15:33 Sent To  
Notes
2005-11-09 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2005 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED & DATED AS
 REQUIRED BY FS. SECTION 106.1
 2. SHTS LA-POOL 3 & LA-POOL 4 PLANS &
 PERMIT ARE REQUIRED. PLANS SHALL BE
 REVIEWED & STAMPED BY THE PALM BEACH
 COUNTY HEALTH DEPT. PRIOR TO SUBMITTING
 FOR REVIEW.
 3. SHT T-3 A2.4.1 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SHOW THE SQUARE FOOTAGE FOR EACH AREA &
 SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ALONG WITH THE AREA
 OF ROOF THAT DRAINS ONTO THE ROOF FROM
 ABOVE FOR EACH AREA IN CALCLATIONS.
 SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS.
 4. SHTS T-3 A4.1.1 THRU T-3 A4.1.8 UNITS
 A, B, C, D, E, H, F, G & K SHALL COMPLY
 WITH REQUIREMENTS 1 THRU 7 OF THE FHA-98
 DESIGN MANUAL. INDICATE SPECIFICATION
 "A" OR "B" FOR EACH UNIT. SHOW THE W/C
 OPENING, (MINIMUM 33"), SHOW THE W/C AT
 18" OFF THE WALL TO THE CENTER OF THE
 FIXTURE WHERE APPLICABLE, AND 18"
 MINIMUM OFF AN ADJACENT FIXTURE. SEE
 PAGES 6.7 7.43 & 7.44. - SHOW CLEAR
 FLOOR SPACE FOR ALL USABLE FIXTURES. -
 SUBMIT A DETAIL FOR BACKING FOR W/C'S,
 TUBS, SHOWERS ECT. PER REQUIREMENT 6. -
 CLEAR FLOOR SPACE FOR SHOWERS SHALL BE
 PARALLEL TO SHOWER & FLUSH WITH CONTROL
 WALL. INDICATE CONTROL WALL ON UNIT
 FLOOR PLAN. (SEE PAGE 7.56).
 5. SHT T-3 A4.1.9 MEN'S & WOMEN'S TOILET
 ROOMS SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.22 WITH ALL
 SUBSECTIONS. SUBMIT A DETAIL SHOWING
 COMPLIANCE.
 6. SUBMIT CALCULATIONS FOR ALL
 AMENITITES AREAS FOR MINIMUM FACILITIES
 PER TABLES 1004.2 (BLDG) AND 403.1
 (PLMG). SHOW THE SQUARE FOOTAGE FOR ALL
 COMMON USE AREAS ALONG WITH THE
 OCCUPANCY LOAD OF EACH AREA. INDICATE
 THE LOCATION OF THE SANITARY FACILITIES
 FOR THE POOL AREA.
 7. SHT T-3 A7.1.1 FLOORS AND WALLS IN
 TOILET ROOM SHALL BE NONABSORBENT PER
 SECTIONS 1210.1 & 1210.2. PLEASE
 INDICATE HOW THIS WILL BE ACCOMPLISHED
 WITH EXPOSED CONCRETE, GYP. BOARD AND NO
 BASE AS SHOWN IN GROUND LEVEL ROOM
 FINISH SCHEDULE.
 8. SHT T-3 A4.19 SINK IN CATERING
 KITCHEN SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. PROVIDE A
 DETAIL.
 9. SHTS T-3 A4.1.13 THRU T-3 A4.1.17
 SHALL COMPLY WITH FHA-98 DESIGN MANUAL
 REQUIREMENTS 1 THRU 7. INDICATE
 SPECIFICATION "A" OR "B". SHOW CLEAR
 FLOOR SPACE FOR ALL USABLE FIXTURES.
 SHOW ALL W/C'S TO BE 18" OFF THE WALL TO
 THE CENTER OF THE FIXTURE . SHOW ALL
 OPENINGS TO BE MINIMUM 33". INDICATE
 MEASUREMENT FROM THE CENTER LINE OF THE
 W/C'S TO THE ADJONINING FIXTURES.
 10. SHT T-3 A6.1.1 DETAIL #4 TRASH CHUTE
 WATER SUPPLY SHALL HAVE BACKFLOW
 PROTECTION. INDICATE THE METHOD OF
 BACKFLOW PROTECTION REQUIRED IN SECTION
 608 AND TABLE 608.1.
 11. SHT T-3 A6.1.3 DETAIL #10 ROOF DRAIN
 DETAIL, INDICATE MEASUREMENT FROM THE
 ROOF TO THE TOP OF THE SECONDARY ROOF
 DRAIN PIPI, (EMERGENCY OVERFLOW PIPE).
 12. SHT T-3 A8.1.1 SHOW THE BACKING FOR
 THE W/C'S PER FHA DESIGN MANUAL PAGES
 6.3 & 6.4. SHOW BACKING FOR THE TUBS PER
 PAGE 6.9.
 13. SHT P0.1 PLUMBING NOTES #1 & #24
 REFER TO FBC-2001, CODE ADOPTED FOR THIS
 JOB IS FBC-2004. PLEASE CHANGE REFERENCE
 14. SUBMIT A STORM BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM. SHOW ALL SQUARE
 FOOTAGE AS IT ACCUMULATES. INDICATE THE
 RISER NUMBER CONNECTING TO STORM DRAIN.
 INDICATE ALL PIPE SIZES AND SLOPE OF
 PIPE.
 15. SHT P2.1 NO SANITARY BRANCH LINE
 SHOWN TO RISERS S/6, S/9, S/10 OR S/46
 FROM THE BUILDING SANT. DRAIN. PLEASE
 SHOW ALL PIPING ON FLOOR PLAN. SECTION
 106.1.1.
 16. SHT P2.3 6" RWL (2200SF) SHOWN IN
 THE HALLWAY. PLEASE CLARIFY. SECTION
 106.1.1.
 17. SHT P2.4 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. (SEE
 COMMENT #3).
 18. SHT P4.1 AN RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE TO EACH
 BUILDING.
 19. SHT P4.1 SHOWS 3" WATER SERVICE TO
 EACH TOWER, BUT CIVIL PLANS, SHTS P3.1,
 AND P6.4 SHOW 4" WATER SERVICE. PLEASE
 CORRELATE PLANS. SECTION 106.1.1.
 20. SHTS P5.1 & P5.2 SUBMIT SOVENT
 DESIGN MANUAL FOR THE SOVENT SYSTEM. THE
 SOVENT SYSTEM SHALL BE APPROVED. SECTION
 106.1.1.
 21. SHT P5.3 BLDG DRAIN ISOMETRIC RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE TUB IS MISSING DOWNTREAM OF RISER
 S/33 AND TUB IS NOT VENTED AS SHOWN.
 SECTIONS 106.1.1 & 901.2.1. - W/C, LAV &
 SHOWER ARE NOT SHOWN DOWNSTREAM OF RISER
 S/34 (ROOM G 110). - MEN'S & WOMEN'S
 TOILET ROOMS , (108 & 109), ARE NOT
 SHOWN ON RISER. - THE TUB DOWNSTREAM OF
 RISER S/43 IS NOT VENTED AS SHOWN.
 SECTION 901.2.1. - LAUNDRY (103) IS NOT
 SHOWN DOWNSTREAM OF RISER S/42. - PIPING
 TO STUDIO K W/M & BATHROOM (105)
 DOWNSTREAM OF RISER S/23 NOT SHOWN.
 SECTION 106.1.1.
 22. SHT P5.3 SHOW DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLE 710.1(1)
 23. SHTS P6.1, P6.2, & P6.3 WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN 'EFFECTIVE RANGE" NOT IN
 THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 24. SUBMIT A CONDENSATE BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TERMINATION POINTS FOR THE
 CONDENSATE DRAIN AND VENT. SECTION
 106.3.5.1.3. - SUBMIT CONDENSATE RISER
 DIAGRAMS. SHOW ALL PIPE SIZES.
 25. SUBMIT STORM RISER DIAGRAMS AND A
 BUILDING DRAIN ISOMETRIC RISER DIAGRAM.
 SHOW ALL PIPE SIZES, LOCATION OF ALL
 RISER CONNECTIONS, SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM, TERMINATION
 POINT OF STORM WATER ECT. SECTION
 106.3.5.1.3.
 26. THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CUT SECTIONS NOT SHOWN
 AND MOST RISERS NOT SHOWN.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 E. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-02 Cont ID  
Sent By jroach Date 2006-07-02 Time 17:23 Rev Time 0.00
Received By jroach Date 2006-07-02 Time 17:23 Sent To  
Notes
2006-07-02 00:00:007/2/06 ***FAILED***
  
 1) INDICATE ON THE PHASING PLAN THAT THE
 TURQUOISE NECKLACE WILL BE DESIGNED,
 PERMITTED AND CONSTRUCTED AS PART OF
 PHASE 2.
  
 2) THE TURQUOISE NECKLACE SHALL BE
 PROVIDED ON THE CIVIL DRAWINGS.A NOTE
 MAY BE PROVIDED INDICATING THAT IT WILL
 BE DESIGNED, PERMITTED AND CONSTRUCTED
 AS PART OF PHASE 2.
  
 3) UNITY OF TITLE SHALL BE RECORDED IN
 THE PUBLIC RECORD OF PALM BEACH COUNTY.
 A COPY SHALL BE INCLUDED WITH ALL PERMIT
 PACKAGES.
  
 4) PARKING STALL DETAIL SHALL CONFORM TO
 THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.A WHEEL STOP SHALL BE
 SHOWN 2 FEET FROM THE HEAD OF THE STALL.
 IF NO WHEEL STOP IS PROVIDED, SIDEWALKS
 LOCATED AT THE HEAD OF THE STALL NEED TO
 BE 7 FEET IN WIDTH TO ALLOW FOR 2 FEET
 OF VEHICLE OVERHANG.IF THE OVERHANG
 OCCURS OVER LANDSCAPING, THE LANDSCAPING
 SHALL NOT EXCEED 6 INCHES ABOVE THE
 HEIGHT OF THE CURB.DETAIL OF DOUBLE
 STRIPING NEEDS TO SHOW 12 INCHES FROM
 INSIDE OF STRIP TO INSIDE OF STRIPE.
  
 5) ALL LANDSCAPE SHEETS NEED TO BE
 SIGNED AND SEALED BY A REGISTERED
 LANDSCAPE ARCHITECT, NOT JUST THE COVER
 SHEET.
  
 6) LANDSCAPE PLANS NEED TO BE ADJUSTED
 TO INDICATE THAT TOWNHOUSE #7 IS PART OF
 PHASE 1.
  
 7) THE LIFT STATION SHOWN ON THE CIVIL
 PLANS DOES NOT MATCH THAT SHOWN ON THE
 LANDSCAPE PLAN.LANDSCAPING NEEDS TO BE
 ADJUSTED ACCORDINGLY.
  
 8) AS A RESULT OF EACH BUILDING BEING
 CO'D SEPARATELY, AN INSPECTION PLAN
 SHALL BE PROVIDED INDICATING WHICH AREAS
 OF LANDSCAPING WILL BE INSPECTED WITH
 EACH BUILDING CO.
  
 9) THE AREAS BETWEEN THE TOWERS ARE
 SHOWN AS FA GRASS.THIS SHALL BE
 MODIFIED AS THE BOARDWALKS ARE NO LONGER
 BEING PROPOSED.
  
 10) THE SIDEWALK CONFIGURATION ON THE
 LANDSCAPE PLANS AND THE CIVIL PLANS
 SHALL CORRESPOND WITH THE SITE PLAN.
  
 11) THE LANDSCAPE PLANS SHWO THE BUS
 SHELTER AND ENTRANCE WALL/LANDSCAPING AS
 PART OF PHASE 1.THE PHASING PLAN
 INDICATES OTHERWISE.
  
 12) FYI...IN DEVELOPING THE SIGNAGE FOR
 THE FRONT ENTRY WALL, THE AREA SHALL NOT
 EXCEED 48 SQUARE FEET.
  
 13) A PHOTOMETRIC PLAN SHALL BE PROVIDED
 FOR SITE LIGHTING ON THE ENTIRE
 PROPERTY.THE PHOTOMETRIC LEVELS SHALL
 BE SHOWN AT THE PROPERTY LINES AND SHALL
 NOT EXCEED 0.5 FOOTCANDLES AT PROPERTY
 LINES ADJACENT TO RESIDENTIAL PROPERTY.
  
 THE FOLLOWING COMMENTS HAVE BEEN
 PROVIDED BY ALAN BARATTA, LANDSCAPE
 PLANNER:
  
 1) PLANTING DIAGRAMS SHALL BE MODIFIED
 TO REFLECT WHAT WAS AGREED TO IN THE
 TREE REMOVAL/RELOCATION LICENSE.
  
 2) IN ORDER TO PREVENT DESTRUCTION TO
 CURBING, PAVING AND PARKED VEHICLES,
 REPLACE THE MOHOGANY TREES IN THE
 LANDSCAPE ISLANDS IN FRONT OF THE
 TOWNHOMES WITH A SMALLER/ALTERNATE
 SPECIES.MINOR PD AMENDMENT (PB CASE
 NO. 1242E) APPROVED ON JULY 2, 2006,
 INDICATED GREEN BUTTONWOODS.
  
 3) ADDITIONAL LANGUAGE SHALL BE PROVIDED
 INDICATING REMOVAL OF SUPPORT MATERIAL
 FROM TREES/PALMS SHALL OCCUR AFTER
 ESTABLISHMENT OR HURRICANE SEASON,
 WHICHEVER COMES LATER.
  
 4) LANDSCAPING IN THE EXECUTIVE CENTER
 DRIVE CUL-DE-SAC SHALL BE COORDINATED
 WITH THE PUBLIC UTILITIES/ENGINEERING
 DEPARTMENT.
  
 MISCELLANEOUS COMMENTS:
  
 1) WORKFORCE HOUSING RESTRICTION ON THE
 LOFTS AND TOWNHOMES, FOLLOWING APPROVAL
 BY THE CITY OF WEST PALM BEACH, SHALL BE
 IN PLACE PRIOR TO THE ISSUANCE OF A CO
 FOR SUCH STRUCTURES.
  
 COMMENTS SPECIFIC TO TOWER 3:
  
 1) THE BACK-LIT LOGO AT THE TOP OF THE
 FRONT ELEVATION SHALL BE REMOVED AS WALL
 SIGNS ARE NOT PERMITTED WITHIN
 RESIDENTIAL ZONING DISTRICTS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-20 Cont ID  
Sent By jroach Date 2005-09-20 Time 14:50 Rev Time 0.00
Received By jroach Date 2005-09-20 Time 14:49 Sent To  
Notes
2005-09-20 00:00:009/20/2005 ***FAILED***
  
 IN ADDITION TO THE COMMENTS BELOW, REFER
 TO ALL ZONING COMMENTS ON PERMIT
 #05080675, LISTED UNDER "ALL PERMITS"
 AND "MISCELLANEOUS COMMENTS."
  
 TOWER #3
  
 1. BACK LIT LOGO AT THE TOP OF THE FRONT
 ELEVATION SHALL NOT BE PROVIDED?WALL
 SIGNS ARE NOT PERMITTED WITHIN
 RESIDENTIAL ZONING DISTRICTS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.