| 2006-04-15 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05080677 |
| | ADD: 719 EXECUTIVE CENTER DR |
| | (CLUBHOUSE) |
| | CONT: THE WEITZ CO. |
| | TEL: (561)686-5511 |
| | CELL:(954)675-4302 |
| | |
| | ARCHITECT: ACI ARCHITECRTURALGROUP |
| | PAUL M. TWITTY |
| | TEL:(561)832-5599 |
| | STRUC ENGINEER: ONM&J |
| | PHILLIP RIZZO |
| | TEL:(561)835-9994 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | NOTES: 1-10 TOTALLY IGNORED, NOT IN |
| | RESPONCE COMMENTS. |
| | |
| | 1)*******IMPORTANT NOTE IGNORED****** |
| | EITHER THE CONTRACTOR OR THE DESIGN |
| | PROFESSIONAL HAS TO TAKE RESPONSIBILITY |
| | FORTHIS PROJECT AND COMPLY WITH THIS |
| | REQUEST, AND REMOVE ALL VOIDED SHETTS |
| | FROM THE PERMIT DOCUMENTS. |
| | 2ND REQUEST: |
| | WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE |
| | ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2)NOTE:105.8* FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3)109.3.7*THIS PARTICUAL TYPE OF |
| | BUILDING "WILL NOT" REQUIRE A SPECIAL |
| | INSPECTOR, ALTHOUGH THERE WILL BE A |
| | THRESHOLD INSPECTOR FOR THE MID RISE AND |
| | HIGH RISE BUILDINGS.WILL THIS INSPECTOR |
| | ALSO BE INSPECTING THIS BUILDING? IF SO |
| | THREE (3) SET OF ALL DOCUMENTS WILL NEED |
| | TO BE SUBMITTED AS IF FOR ATHRESHOLD |
| | BUILDING.WILL THIS INSPECTOR BE THE SAME |
| | PERSON AS THE THRESHOLD INSPECTOR? OR |
| | WILL THERE BE TWO INDIVIDUALS? |
| | FORMS WILL NEED TO BE FILLED OUT FOR THE |
| | SPECIAL INSPECTOR, CONTACT HAROLD |
| | PISKURA, INSPECTION SERVICES MANAGER @ |
| | (561)805-6711 TO SEET UP AN APPOINTMENT. |
| | |
| | 4)2ND REQUEST COMMENT# 4 PREVIOUS REVIEW |
| | 106.3.3* PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| | WRITTING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR " JURISDICTIONAL |
| | APPROVAL", (LOCAL PRODUCT APPROVAL). |
| | |
| | 5)2ND REQUEST COMMENT# 5 PREVIOUS REVIEW |
| | SITE PLAN NEEDS TO BE SUBMITTED TO |
| | ADDRESSING PERSONEL JOHN HIGGINS FOR |
| | ADDRESSING AS WELL AS NEW PLAT MAP FOR |
| | THE COMBINATION OF LOTS. JOHN HIGGINS |
| | CONTACT NUMBER IS (561)822-1239. |
| | |
| | 6A)2ND REQUEST COMMENT 6A PREVIOUS |
| | REVIEW:THERE IS A DISCREPANCY IN THE |
| | PLANS SINCE THE BOUNDRY SURVEY FOR |
| | PARCEL# 7, ONLY INDICATES 2 LOTS PARCEL |
| | 1&2.NOTE: FOR TOWNHOUSES EACH UNIT WILL |
| | REQUIRE INDIVIDUAL PROPERTY CONTROL |
| | NUMBERS WITH ASSOCIATED PROPERTY LINE. |
| | |
| | 6B)2ND REQUEST COMMENT6B PREVIOUS REVIEW |
| | THE SURVEY DOES SHOW 2 SEPERATE LOTS |
| | WHICH APPEAR TO CUT THROUGH BULDING "B" |
| | AND BUILDING "C". A UNITY OF TITLE SHALL |
| | BE REQUIRED, TABLE 601 AND 602. |
| | |
| | |
| | 7) ENERGY COMPLIANCE FORMS: |
| | 7A)2ND REQUEST COMMENT 7A FROM THE |
| | PREVIOUS REVIEW: |
| | UPDATE FORM TO FORM 400A-04. |
| | |
| | 8)COMPLIED. |
| | |
| | 9A)2ND REQUEST : SHEET A3.2.1 WALL |
| | SECTIONS DO NOT INDICATE WHAT TYPE OF |
| | TERMITE TREATMENT FOR SOILS WILL BE |
| | USED, SEE 1816.1. |
| | |
| | 9B)2ND REQUEST: |
| | THIS SAME SHEET INDICATES THE USE OF |
| | A VAPOR BARRIER, MUST BE A MINIMUM OF 6 |
| | MIL TO BE USED WITH CHEMICALLY TREATED |
| | TERMITE TREATMENT FOR SOILS BENEATH |
| | SLAB.1806.1.4.NOTE SOILS REPORT |
| | RECOMMENDS (8.4.2) THE USE OF A HEAVIER |
| | 10MIL POLYOLEFIN. |
| | |
| | 9C) 2ND REQUEST, TO ADD THIS NOTE TO |
| | PLANS, 1816.1.6 IF SOIL TREATMENT IS |
| | USED FOR SUBTERRANEAN TERMITE |
| | PREVENTION, CHEMICAL SOIL TREATMENT |
| | SHALL BE APPLIED UNDER ALL EXTERIOR |
| | CONCRETE OR GRADE WITHIN 1 FT OF THE |
| | PRIMARY STRUCTURE SIDEWALLS. |
| | |
| | 10) SHEET A6.1.1: |
| | 10A) 1203.2.ATTIC SPACE. TRUE THIS SPACE |
| | IS NOT ATTIC SPACE. 1203.1 SEE CODE |
| | COMMENTARY ABOUT THIS TYPE OF USAGE OR |
| | SPACE.EVERY ROOM OR SPACE MUST BE |
| | PROVIDED WITH VENTILATION. THE SELECTION |
| | OF NATURAL VENTILATION ON A ROOM BY ROOM |
| | OR SPACE BY SPACE IS THE DESIGNER'S |
| | PREROGATIVE. INDICATE HOW VENTILATION |
| | WILL BE ACCOLPLISHED, BY TRANSFER |
| | GRILLES, ETC? |
| | |
| | 10B) 2ND REQUEST, DETAIL# 8 DOESN'T |
| | MATCH SHEET A3.2.1OR VARIOUS CUT |
| | SECTIONS THROUGH THE ROOF SHEATHING, THE |
| | PLANS REVEAL 2 THICKNESSES OF SHEATHING |
| | &USE OF 1/2" THICK HIGH DENSITY |
| | SUBTRATE, PLEAASE CORRECT ALL DETAILS TO |
| | THE SAME THICKNESS AND COMPLY WITH |
| | TABLE2304.7(5) |
| | |
| | 10C) 2ND REQUEST. DETAIL# 8 WAS |
| | CORRECTED, DETAIL# 9 STILL INDICATES |
| | HIGH DENSITY SUBSTRATE. TABLE 2304.7(5) |
| | FOOTNOTE (A) PLYWOOD STRUCTURAL PANELS |
| | ARE 5-PLY, 5LAYER UNLESS OTHERWISE |
| | NOTED. CHANGE IN FOOTNOTE NEW YELLOW |
| | PAGES. |
| | |
| | 10D) COMPLIED. |
| | |
| | 10E) BOTH THIS SHEET AND A2.1.1 ARE |
| | MISSING THE ATTIC ACCESS |
| | |
| | 10F) THE FLOOR PLAN NOR WALL SECTIONS |
| | INDICATE ATTIC ACCESS? |
| | |
| | 10G) NEW COMMENT, DEALS WITH HIP AND |
| | RIDGE ATTACHMENT, 1507.3.7 ATTACHMENT & |
| | 1507.3.8 APPLICATION BOTH TO BE IN |
| | ACCORDANCE WITH FRSA/ TRI 07320, THE |
| | NEWEST STANDARD 08-05.SEE TABLE 11 FOR |
| | NUMBER OF CLIPS, SPACING AND FASTENERS. |
| | |
| | |
| | 11) 2ND REQUEST, A PERMIT APPLICATION |
| | WILL BE REQUIRED FOR SITE AMENITIES, |
| | SEPERATE PLANS WILL BE REQUIRED FOR THIS |
| | PACKAGE. THE PERMITS APPLIED FOR AT THIS |
| | TIME ARE FOR BUILDINGS ONLY!!!!!!!!! |
| | PLANS SUBMITTED ALSO INDICATE A BUS |
| | SHELTER (A6.13)THIS WILL BE STRUCK SINCE |
| | THE BUS SHELTER SHOULD BE PART OF A SITE |
| | AMENITIES PACKAGE THAT WOULD BE |
| | PERMITTED SEPARATELY. |
| | |
| | 12A) 2ND REQUEST: |
| | PRODUCT APPROVALS REQUIRE; |
| | RULE 9B-72- PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE WITH THE ASSOCIATED REPORT. IF |
| | THE PRODUCT DOES NOT HAVE STATEWIDE |
| | APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL ON THE CITY FORM |
| | PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 12B)2ND REQUEST, CONTRACTOR SUBMITTED |
| | PRODUCT APPROVALS WHICH WILL NOT BE USED |
| | ON THIS PROJECT, PLEASE REMOVE FROM |
| | PACKAGE: SBS MODIFIED BITUMEN SYSTEM |
| | OVER LIGHT WEIGHT CONCRETE DECK.. |
| | |
| | 12C)@ND REQUEST,FL BLD CODE |
| | 1602/COMPONENTS & CLADDING, 1609.6 : |
| | COMPONENTS & CLADDING, PROVIDE 2 |
| | COPIES(3 IF THRESHOLD OR RESIDENT |
| | INSPECTOR) OF PRODUCT TESTING |
| | REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) GLAZED FRONT ENTRY DOORS |
| | B) SOLID SWING DOOR |
| | C) TRUSS ANCHORS |
| | D) ROOF ASSEMBLIES TILE ROOF |
| | E) DENSEGLASS SHEATHING |
| | |
| | 13) SHEET S-3 : |
| | 13A) COMPLIED. |
| | . |
| | 13B) COMPLIED. |
| | |
| | 14) 2ND REQUEST NOT ON RESPONCE SHEET. |
| | 1503.6 PROTECTION AGAINST DECAY & |
| | TERMITES. CONDENSATE LINES & ROOF DOWN |
| | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| | TENSIONS, OR SPLASH BLOCKS. |
| | |
| | 15)2ND REQUEST, WILL CONTINUE TO BE A |
| | COMMENT UNTIL PAYMENT IS MADE AT PALM |
| | BEACH COUNTY IMPACT FEE OFFICE. |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |