Plan Review Details - Permit 05080677
Plan Review Stops For Permit 05080677
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-15 Cont ID  
Sent By jwitmer Date 2006-04-15 Time 08:35 Rev Time 3.33
Received By jwitmer Date 2006-04-15 Time 07:45 Sent To  
Notes
2006-04-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080677
 ADD: 719 EXECUTIVE CENTER DR
 (CLUBHOUSE)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
  
 NOTES: 1-10 TOTALLY IGNORED, NOT IN
 RESPONCE COMMENTS.
  
 1)*******IMPORTANT NOTE IGNORED******
 EITHER THE CONTRACTOR OR THE DESIGN
 PROFESSIONAL HAS TO TAKE RESPONSIBILITY
 FORTHIS PROJECT AND COMPLY WITH THIS
 REQUEST, AND REMOVE ALL VOIDED SHETTS
 FROM THE PERMIT DOCUMENTS.
 2ND REQUEST:
 WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2)NOTE:105.8* FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING "WILL NOT" REQUIRE A SPECIAL
 INSPECTOR, ALTHOUGH THERE WILL BE A
 THRESHOLD INSPECTOR FOR THE MID RISE AND
 HIGH RISE BUILDINGS.WILL THIS INSPECTOR
 ALSO BE INSPECTING THIS BUILDING? IF SO
 THREE (3) SET OF ALL DOCUMENTS WILL NEED
 TO BE SUBMITTED AS IF FOR ATHRESHOLD
 BUILDING.WILL THIS INSPECTOR BE THE SAME
 PERSON AS THE THRESHOLD INSPECTOR? OR
 WILL THERE BE TWO INDIVIDUALS?
 FORMS WILL NEED TO BE FILLED OUT FOR THE
 SPECIAL INSPECTOR, CONTACT HAROLD
 PISKURA, INSPECTION SERVICES MANAGER @
 (561)805-6711 TO SEET UP AN APPOINTMENT.
  
 4)2ND REQUEST COMMENT# 4 PREVIOUS REVIEW
 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5)2ND REQUEST COMMENT# 5 PREVIOUS REVIEW
 SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL JOHN HIGGINS FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. JOHN HIGGINS
 CONTACT NUMBER IS (561)822-1239.
  
 6A)2ND REQUEST COMMENT 6A PREVIOUS
 REVIEW:THERE IS A DISCREPANCY IN THE
 PLANS SINCE THE BOUNDRY SURVEY FOR
 PARCEL# 7, ONLY INDICATES 2 LOTS PARCEL
 1&2.NOTE: FOR TOWNHOUSES EACH UNIT WILL
 REQUIRE INDIVIDUAL PROPERTY CONTROL
 NUMBERS WITH ASSOCIATED PROPERTY LINE.
  
 6B)2ND REQUEST COMMENT6B PREVIOUS REVIEW
 THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
  
 7) ENERGY COMPLIANCE FORMS:
 7A)2ND REQUEST COMMENT 7A FROM THE
 PREVIOUS REVIEW:
 UPDATE FORM TO FORM 400A-04.
  
 8)COMPLIED.
  
 9A)2ND REQUEST : SHEET A3.2.1 WALL
 SECTIONS DO NOT INDICATE WHAT TYPE OF
 TERMITE TREATMENT FOR SOILS WILL BE
 USED, SEE 1816.1.
  
 9B)2ND REQUEST:
 THIS SAME SHEET INDICATES THE USE OF
 A VAPOR BARRIER, MUST BE A MINIMUM OF 6
 MIL TO BE USED WITH CHEMICALLY TREATED
 TERMITE TREATMENT FOR SOILS BENEATH
 SLAB.1806.1.4.NOTE SOILS REPORT
 RECOMMENDS (8.4.2) THE USE OF A HEAVIER
 10MIL POLYOLEFIN.
  
 9C) 2ND REQUEST, TO ADD THIS NOTE TO
 PLANS, 1816.1.6 IF SOIL TREATMENT IS
 USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CHEMICAL SOIL TREATMENT
 SHALL BE APPLIED UNDER ALL EXTERIOR
 CONCRETE OR GRADE WITHIN 1 FT OF THE
 PRIMARY STRUCTURE SIDEWALLS.
  
 10) SHEET A6.1.1:
 10A) 1203.2.ATTIC SPACE. TRUE THIS SPACE
 IS NOT ATTIC SPACE. 1203.1 SEE CODE
 COMMENTARY ABOUT THIS TYPE OF USAGE OR
 SPACE.EVERY ROOM OR SPACE MUST BE
 PROVIDED WITH VENTILATION. THE SELECTION
 OF NATURAL VENTILATION ON A ROOM BY ROOM
 OR SPACE BY SPACE IS THE DESIGNER'S
 PREROGATIVE. INDICATE HOW VENTILATION
 WILL BE ACCOLPLISHED, BY TRANSFER
 GRILLES, ETC?
  
 10B) 2ND REQUEST, DETAIL# 8 DOESN'T
 MATCH SHEET A3.2.1OR VARIOUS CUT
 SECTIONS THROUGH THE ROOF SHEATHING, THE
 PLANS REVEAL 2 THICKNESSES OF SHEATHING
 &USE OF 1/2" THICK HIGH DENSITY
 SUBTRATE, PLEAASE CORRECT ALL DETAILS TO
 THE SAME THICKNESS AND COMPLY WITH
 TABLE2304.7(5)
  
 10C) 2ND REQUEST. DETAIL# 8 WAS
 CORRECTED, DETAIL# 9 STILL INDICATES
 HIGH DENSITY SUBSTRATE. TABLE 2304.7(5)
 FOOTNOTE (A) PLYWOOD STRUCTURAL PANELS
 ARE 5-PLY, 5LAYER UNLESS OTHERWISE
 NOTED. CHANGE IN FOOTNOTE NEW YELLOW
 PAGES.
  
 10D) COMPLIED.
  
 10E) BOTH THIS SHEET AND A2.1.1 ARE
 MISSING THE ATTIC ACCESS
  
 10F) THE FLOOR PLAN NOR WALL SECTIONS
 INDICATE ATTIC ACCESS?
  
 10G) NEW COMMENT, DEALS WITH HIP AND
 RIDGE ATTACHMENT, 1507.3.7 ATTACHMENT &
 1507.3.8 APPLICATION BOTH TO BE IN
 ACCORDANCE WITH FRSA/ TRI 07320, THE
 NEWEST STANDARD 08-05.SEE TABLE 11 FOR
 NUMBER OF CLIPS, SPACING AND FASTENERS.
  
  
 11) 2ND REQUEST, A PERMIT APPLICATION
 WILL BE REQUIRED FOR SITE AMENITIES,
 SEPERATE PLANS WILL BE REQUIRED FOR THIS
 PACKAGE. THE PERMITS APPLIED FOR AT THIS
 TIME ARE FOR BUILDINGS ONLY!!!!!!!!!
 PLANS SUBMITTED ALSO INDICATE A BUS
 SHELTER (A6.13)THIS WILL BE STRUCK SINCE
 THE BUS SHELTER SHOULD BE PART OF A SITE
 AMENITIES PACKAGE THAT WOULD BE
 PERMITTED SEPARATELY.
  
 12A) 2ND REQUEST:
 PRODUCT APPROVALS REQUIRE;
 RULE 9B-72- PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE WITH THE ASSOCIATED REPORT. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL ON THE CITY FORM
 PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 12B)2ND REQUEST, CONTRACTOR SUBMITTED
 PRODUCT APPROVALS WHICH WILL NOT BE USED
 ON THIS PROJECT, PLEASE REMOVE FROM
 PACKAGE: SBS MODIFIED BITUMEN SYSTEM
 OVER LIGHT WEIGHT CONCRETE DECK..
  
 12C)@ND REQUEST,FL BLD CODE
 1602/COMPONENTS & CLADDING, 1609.6 :
 COMPONENTS & CLADDING, PROVIDE 2
 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING
 REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) GLAZED FRONT ENTRY DOORS
 B) SOLID SWING DOOR
 C) TRUSS ANCHORS
 D) ROOF ASSEMBLIES TILE ROOF
 E) DENSEGLASS SHEATHING
  
 13) SHEET S-3 :
 13A) COMPLIED.
 .
 13B) COMPLIED.
  
 14) 2ND REQUEST NOT ON RESPONCE SHEET.
 1503.6 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 15)2ND REQUEST, WILL CONTINUE TO BE A
 COMMENT UNTIL PAYMENT IS MADE AT PALM
 BEACH COUNTY IMPACT FEE OFFICE.
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-17 Cont ID  
Sent By jwitmer Date 2005-11-17 Time 10:06 Rev Time 3.33
Received By jwitmer Date 2005-11-17 Time 10:06 Sent To PC
Notes
2005-11-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080677
 ADD: 719 EXECUTIVE CENTER DR
 (CLUBHOUSE)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 105.8* PROVIDE NOC RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING "WILL NOT" REQUIRE A SPECIAL
 INSPECTOR, ALTHOUGH THERE WILL BE A
 THRESHOLD INSPECTOR FOR THE MID RISE AND
 HIGH RISE BUILDINGS.WILL THIS INSPECTOR
 ALSO BE INSPECTING THIS BUILDING? IF SO
 THREE (3) SET OF ALL DOCUMENTS WILL NEED
 TO BE SUBMITTED AS IF FOR ATHRESHOLD
 BUILDING.WILL THIS INSPECTOR BE THE SAME
 PERSON AS THE THRESHOLD INSPECTOR? OR
 WILL THERE BE TWO INDIVIDUALS?
 FORMS WILL NEED TO BE FILLED OUT FOR THE
 SPECIAL INSPECTOR, CONTACT HAROLD
 PISKURA, INSPECTION SERVICES MANAGER @
 (561)805-6711 TO SEET UP AN APPOINTMENT.
  
 4) 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5) SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL JOHN HIGGINS FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. JOHN HIGGINS
 CONTACT NUMBER IS (561)822-1239.
  
 6A) THERE IS A DISCREPANCY IN THE PLANS
 SINCE THE BOUNDRY SURVEY FOR PARCEL# 7,
 ONLY INDICATES 2 LOTS PARCEL 1&2.NOTE:
 FOR TOWNHOUSES EACH UNIT WILL REQUIRE
 INDIVIDUAL PROPERTY CONTROL NUMBERS
 WITH ASSOCIATED PROPERTY LINE.
 6B) THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
  
 7) ENERGY COMPLIANCE FORMS:
 7A) UPDATE FORM TO FORM 400A-04
  
 8) GEOTECHNICAL REPORT THAT WORK WAS
 PREFORMED BY ARDAMAN NEEDS TO BE AN
 ORIGINAL WITH SIGNATURE AND RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 9A) SHEET A3.2.1 WALL SECTIONS DO NOT
 INDICATE WHAT TYPE OF TERMITE TREATMENT
 FOR SOILS WILL BE USED, SEE 1816.1.
 9B) THIS SAME SHEET INDICATES THE USE OF
 A VAPOR BARRIER, MUST BE A MINIMUM OF 6
 MIL TO BE USED WITH CHEMICALLY TREATED
 TERMITE TREATMENT FOR SOILS BENEATH
 SLAB.1806.1.4.
 9C) 1816.1.6 IF SOIL TREATMENT IS USED
 FOR SUBTERRANEAN TERMITE PREVENTION,
 CHEMICAL SOIL TREATMENT SHALL BE APPLIED
 UNDER ALL EXTERIOR CONCRETE OR GRADE
 WITHIN 1 FT OF THE PRIMARY STRUCTURE
 SIDEWALLS.
  
 10) SHEET A6.1.1:
 10A) THE WALL SECTION# 8 DOESN'T
 INDICATE COMPLIANCE WITH ATTIC
 VENTILATION REQUIREMENTS FOUND IN
 1203.2. PLEASE INDICATE COMPLIANCE
 WITH BOTH THE EAVE REQUIREMENTS AS
 WELL AS 1/150 OF THE AREA OF THE
 SPACE TO BE VENTILATED AND 50% OF
 THE REQUIRED VENTILATION BE IN THE
 UPPER PORTION OF THE SPACE TO BE
 VENTILATED.
 10B) THE DETAIL#8 DOESN'T MATCH SHEET
 A3.2.1VARIOUS CUT SECTIONS
 THROUGH THE ROOF SHEATHING, IN THE
 PLANS REVEAL 2 THICKNESSES AND THE
 USE OF 1/2" THICK HIGH DENSITY
 SUBSTATE, CLARIFY.PLEASE CORRECT
 ALL DETAILS TO THE SAME THICKNESS.
 10C) TABLE 2304.7(5) FOOTNOTE (D) LIMITS
  
 THE USE OF ROOF SHEATHING TO
 19/32" WOOD STRUCTURAL PANELS IN
 WIND REGIONS OF 110 - 140MPH,
 EXPOSURE B.
 10D) DETAIL# 8 INDICATES THE USE OF BOTH
  
 WOOD AND METAL TRUSSES?
 10E) BOTH THIS SHEET AND A2.1.1 ARE
 MISSING THE ATTIC ACCESS
  
 10F) THE FLOOR PLAN NOR WALL SECTIONS
 INDICATE ATTIC ACCESS?
  
 11) PLANS SUBMITTED ALSO INDICATE A BUS
 SHELTER (A6.13)THIS WILL BE STRUCK SINCE
 THE BUS SHELTER SHOULD BE PART OF A SITE
 AMENITIES PACKAGE THAT WOULD BE
 PERMITTED SEPARATELY.
  
 12A) PRODUCT APPROVALS REQUIRE;
 RULE 9B-72- PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE WITH THE ASSOCIATED REPORT. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL ON THE CITY FORM
 PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 12B) CONTRACTOR SUBMITTED PRODUCT
 APPROVALS WHICH WILL NOT BE USED ON THIS
 PROJECT, PLEASE REMOVE FROM PACKAGE.
  
 12C)FL BLD CODE 1602/COMPONENTS &
 CLADDING, 1609.6 : COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) GLAZED FRONT ENTRY DOORS
 B) SOLID SWING DOOR
 C) TRUSS ANCHORS
 D) ROOF ASSEMBLIES TILE ROOF
 E) DENSEGLASS SHEATHING
  
 13) SHEET S-3 :
 13A)WIND LOAD SCHEDULE INDICATES
 COMPLIANCE WITH THE 2001 FL BLDG CODE,
 PLEASE CORRECT.
 13B) TRUSS TIE DOWN SCHEDULE, SIMPSON
 HETAL-12 THE VALUE SHOWN IS FOR A TWO
 PLY MEMBER NOT INDICATED AS SUCH, THE
 VALUE FOR A SINGLE MEMBER IS 1265.
  
 14) 1503.6 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-27 Cont ID  
Sent By dpalmer Date 2006-04-27 Time 18:53 Rev Time 0.00
Received By dpalmer Date 2006-04-27 Time 16:56 Sent To  
Notes
2006-04-27 00:00:00IN ELEC FOR REVIEW.
 ***** UNSAT2ND REVIEW *****
  
 PLEASE SEE NOTES FROM PREVIOUSREVIEW
 WHICH REMAIN AND NEW NOTES.
  
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW. PLEASE
 ALSO SEE NOTES PERTAINING TO THE REMOVAL
 OF ALL OLD/VOIDED SHEETS AS REQUESTED
 ON PREVIOUS REVIEW.
  
  
  
 SAIL CLUB
 CLUBHOUSE BUILDING.
  
 1)NOTE:NOTE #1 NO, PLEASE SEE NOW THE
 PLANS ARE CHANGED SHOWING ALL EM/ EXT
 LTS CIRCUITED TO THE SAME CIRCUIT WHERE
 ORIGINAL COMMENT WAS TO SEE 700.12 E
 WHICH REQUIRED ALL EM/ EXT LTS CIRCUITED
 TO THE LOCAL LIGHTING IN ANY ONE AREA.
 PLEASE KNOW THE CIRCUITING ON PLANS WAS
 CORRECT AND IT WAS THE PANEL SCHEDULE
 THAT NEEDED TO BE ADJUSTED TO CORRELATE
 WITH THE PLANS WHICH SHOWED THE
 CIRCUITING CORRECT.
  
 ** PREVIOUS NOTE **
 PLEASE SEE EM/ EXT LTS ARE SHOWN
 CIRCUITED TO THE LOCAL BRANCH CIRCUIT
 FOR LIGHITNG IN THAT AREA, HOWEVER
 EM/EXT LTS ARE SHOWN ON A SEPARATE
 CIRCUIT ON PANEL SCHEDULE.
 700.12E.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE PLANS
 SHOULD REFERENCE THE FOLLOWING, 2002
 NFPA-70, 2002 NFPA-72, 2003 NFPA-101.
  
  
 ** PREVIOUS NOTE **
 PLEASE SEE PLANS REFERENCE THE 1999 NEC.
 PLEASE SEE AS OF JULY 7TH,2003 THE STATE
 ADOPTED THE 2002 NEC.
 PLEASE SEE COVER SHEETS FOR PROJECT.
  
  
 3)NOTE: NOTE#3, NO, PLEASE SEE WATER
 HEATER IS STILL BEING SHOWN IN STORAGE
 CLOSET?? PLEASE SEE RESPONSE MENTIONS ,
 PLUMBING DESIGNIS CORRECT"?
 PLEASE CLARIFY TYPE OF FIXTURE UNIT
 BEING INSTALLED AND ALL MIN CLEARENCES
 PER SPECS. IS THIS UNIT A OINT OF USE
 UNIT OF SOME KIND?
  
 ** PREVIOUS NOTE **
 PLEASE SEE WATER HEATER MAY NOT
 BE LOCATED IN "STORAGE" AREA/CLOSET.
 PLEASE SEE THIS LOCATION WILL BE PRONE
 TO STORAGE OF COMBUSTIBLES AND CREATE A
 FIRE HAZARD.
 PLEASE SEE 422.17 AND ANY COMMENTS FROM
 FIRE PLAN REVIEW.
  
 4)NOTE: NOTE #4 NO, SEE CIRCUIT FOR
 FRIG.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 210.8B3 IN KITCHENS
 IN OTHER THAN DWELLING UNITS, WHICH
 REQUIRES ALL 15/20A 125V RECEPTS TO BE
 GFI PROTECTED WHEATHER OR NOT SERVICE
 KITCHEN AREA COUNTERSPACES.
  
 5)NOTE: OK.
  
 6)NOTE: OK.
  
 7)NOTE:NOTE #7 NO, RESPONSE MENTIONS
 TO SEE REVISED PANEL SCHEDULE, HOWEVER
 PANEL SCHEDULE STILL SHOWS "A" AND "C"
 PHASE. PLEASE EXPLAIN.
  
 ** PREVIOUS NOTE **
 PLEASE ALSO SEE SERVICE IS SHOWN
 AS SINGLE PHASE, HOWEVER PANEL SCHEDULE
 INDICATES "A" AND "C" PHASE?
 A& B.
  
 **********************************
 NEW NOTE:
  
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONAL AND
 REPEAT COMMENTS FOR ANY OF THE SAME CODE
 COMPLIANT COMMENTS .
 THIS IS ONLY NOTICE GIVEN AT THIS TIME.
  
  
  
 ****************************************
 PLEASE COMPLETELY REMOVE ALL OLD/ VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD
 BE ATTACHED TO EACH OTHER TO COMPOSE OF
 ONE SET OF VOIDED SHEETS ONLY AND WILL
 BE SUBMITTED ALONG WITH NEW SETS FOR
 REFERENCE.
 **************************************
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-11 Cont ID  
Sent By dpalmer Date 2005-09-11 Time 13:12 Rev Time 0.50
Received By dpalmer Date 2005-09-11 Time 11:26 Sent To  
Notes
2005-09-11 00:00:00IN ELECTRIC FOR REVIEW.
 REVIEWS IN PROGRESS .
 ********* UNSAT ************
  
 SAIL CLUB
 CLUBHOUSE BUILDING.
  
 1)NOTE:PLEASE SEE EM/ EXT LTS ARE
 SHOWN CIRCUITED TO THE LOCAL BRANCH
 CIRCUIT FOR LIGHITNG IN THAT AREA,
 HOWEVER EM/EXT LTS ARE SHOWN ON A
 SEPARATE CIRCUIT ON PANEL SCHEDULE.
 700.12E.
  
 2)NOTE: PLEASE SEE PLANS REFERENCE THE
 1999 NEC. PLEASE SEE AS OF JULY 7TH,2003
 THE STATE ADOPTED THE 2002 NEC.
 PLEASE SEE COVER SHEETS FOR PROJECT.
  
  
 3)NOTE: PLEASE SEE WATER HEATER MAY NOT
 BE LOCATE DIN "STORAGE" AREA/CLOSET.
 PLEASE SEE THIS LOCATION WILL BE PRONE
 TO STORAGE OF COMBUSTIBLES AND CREATE A
 FIRE HAZARD.
 PLEASE SEE 422.17 AND ANY COMMENTS FROM
 FIRE PLAN REVIEW.
  
 4)NOTE: PLEASE SEE 210.8B3 IN KITCHENS
 IN OTHER THAN DWELLING UNITS, WHICH
 REQUIRES ALL 15/20A 125V RECEPTS TO BE
 GFI PROTECTED WHEATHER OR NOT SERVICE
 KITCHEN AREA COUNTERSPACES.
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 IT IS NOTED THE AIC RATING IS INDICATED
 FOR CH PANEL, HOWEVER PLEASE INDICATE
 FOR MAIN AS SHOWN ON RISER.
  
 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. IF LOADS ON PANEL
 SCHEDULE/LOADS CALCS ARE ALREADY FIG AT
 125%, PLEASE NOTE:
 215.3,230.42 ETC.
  
 7)NOTE: PLEASE ALSO SEE SERVICE IS SHOWN
 AS SINGLE PHASE, HOWEVER PANEL SCHEDULE
 INDICATES "A" AND "C" PHASE?
 A& B.
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ****************************************
 PLEASE COMPLETELY REMOVE ALL OLD/ VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD
 BE ATTACHED TO EACH OTHER TO COMPOSE OF
 ONE SET OF VOIDED SHEETS ONLY AND WILL
 BE SUBMITTED ALONG WITH NEW SETS FOR
 REFERENCE.
 **************************************
  
 PLEASE SEE BLDG REVIEW COMMENTS WITH
 RESPECT TO PRODUCT NOA'S ATTACHED TO
 PLANS.
 PLEASE ALSO SEE COMMENTS WITH REPECT TO
 PRODUCT APPROVALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By mamini Date 2005-08-23 Time 10:48 Rev Time 0.50
Received By mamini Date 2005-08-23 Time 10:48 Sent To  
Notes
2005-08-23 00:00:00FAILED:
  
 1. PLEASE SEE REVIEW NOTES UNDER PERMIT
 # 05080676.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-06-13 Cont ID  
Sent By mwennerg Date 2006-06-13 Time 10:19 Rev Time 0.00
Received By mwennerg Date 2006-06-13 Time 10:19 Sent To  
Notes
2006-06-13 00:00:00***DENIED***
  
 1) RESONSE DOES NOT ADDRESS COMMENT.
 PLEASE ADD NOTE REGARDING THIS
 REQUIREMENT.
  
 2) RESPONSE NOT FOUND.
  
 3) OK
  
 4) PLANS INDICATE FAN SHUT DOWN, HOWEVER
 NO MENTION OF AUDIBLE/VISUAL DEVICE
 REQUIREMENT.
  
 5) OK
  
 6) RESPONSE NOT FOUND.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-10-14 Cont ID  
Sent By mwennerg Date 2005-10-14 Time 10:27 Rev Time 0.00
Received By mwennerg Date 2005-10-14 Time 10:26 Sent To  
Notes
2005-10-14 00:00:00******DENIED******
  
 CLUBHOUSE
  
 1) APPROVED PANIC HARDWARE IS REQUIRED
 ON EXIT DOORS SERVING AREAS WITH
 OCCUPANT LOAD OF GREATER THAN 100
 PERSONS.
  
 2) PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILING IN TERMS OF CLASS A, B OR C.
  
 3) IN ADDITION TO THE HEIGHT REQUIREMENT
 ADDRESS NUMBER SHALL CONTRAST WITH
 BACKGROUND.
  
 4) AUDIBLE/VISUAL DEVICES TO BE
 INSTALLED IN AREAS OF SMOKE DUCT
 DETECTORS.
  
 5) PLEASE CONTACT THE BUREAU OF FIRE
 PREVENTION PRIOR TO FINAL FIRE
 INSPECTION TO OBTAIN AN OCCUPANT LOAD
 SIGN TO BE DISPLAYED.
  
 6) FIRE HYDRANTS TO BE WET PRIOR TO,
 DURING AND AFTER CONSTRUCTION. PROPER
 CLEARANCES TO BE MAINTAINED AT ALL
 TIMES.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-07 Cont ID  
Sent By adarroug Date 2006-03-07 Time 09:31 Rev Time 0.00
Received By adarroug Date 2006-03-07 Time 09:31 Sent To  
Notes
2006-03-30 00:00:00TO "COMM" BD#7
2006-03-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-21 Cont ID  
Sent By adarroug Date 2005-11-10 Time 08:36 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 08:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-07 Cont ID  
Sent By pkrauss Date 2006-06-07 Time 07:21 Rev Time 0.00
Received By pkrauss Date 2006-06-07 Time 07:13 Sent To  
Notes
2006-06-07 00:00:00PROVISO:
 PLAN SHEET M2.1, SEQUENCE OF OPERATION
 NOTES STATES "EF-3,4 SHALL BE
 INTERLOCKED WITH AHU-1,2".THIS SHOULD
 READ SF-3,4.PLEASE REVISE PLAN &
 SUBMIT WITH RESUBMITTAL.PLANS ARE
 OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-04 Cont ID  
Sent By pkrauss Date 2005-10-04 Time 13:31 Rev Time 0.55
Received By pkrauss Date 2005-10-04 Time 13:31 Sent To  
Notes
2005-10-04 00:00:00DENIED:2004 FBC - CLUBHOUSE
 1.PLAN SHEET M0.1 MECHANICAL NOTE 1
 REFERENCES ASHRAE STANDARDS THAT ARE NOT
 CURRENT WITH WHAT IS ACCECPTED UNDER THE
 2004 CODE.SHOULD READ ASRAE 15-01,
 34-01, 62-01 NFPA AS FOLLOWS; 90A-02,
 90B-02, 91-99, 96-01.MECHANICAL NOTES
 ALSO REFERENCE THE 2001 FBC.
  
 2.PLAN SHEET M2.1 DETAIL A-A,
 INDICATES AHU-1 & 2 IN A 'MECHANICAL
 ROOM' WILL SERVE AS A PLENUM.PER 2001
 FBC(M)602.2.1, NO COMBUSTIBLES ALLOWED.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 IS REQUIRED PER 2001 FBC(M)606.2.2.
  
 4.FRESH AIR INTAKE IS LOCATED ABOVE
 THE DOOR WITH THE CONDENSING UNITS
 LOCATED BELOW.PLEASE NOTE, HEAT FROM
 CONDENSING UNIT EXHAUST SHALL NOT BE
 RECIRCULATED OR DRAWN IN BY THE FRESH
 AIR INTAKE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-05-11 Cont ID  
Sent By kstevens Date 2006-05-11 Time 09:37 Rev Time 0.00
Received By kstevens Date 2006-05-10 Time 18:38 Sent To  
Notes
2006-05-11 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 11
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 3. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED, & DATED AS
 REQUIRED BY FLORIDA STATUTES. SECTION
 106.1.
 ***RESPONSE NOTED, BUT THE BOUNDARY
 SURVEY, PP1 OF 9 THRU PP9 OF 9, LA-POOL
 -1 THRU LA-POOL-4, LA-FW-1 THRU LA-FW-5
 SHEETS HAVE NOT BEEN SIGNED, SEALED,
 DATED. RESPONSE INDICATING THE GENERAL
 CONTRACTOR SHALL PROVIDE IS NOT PER FS
 AND FAC REQUIREMENTS.
  
 4. SHT CH A2.1.1 KITCHEN SINK SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. CLEAR FLOOR SPACE FOR SINK
 SHALL BE FORWARD APPROACH.
 ***RESPONSE NOTED, BUT A DETAIL FOR THE
 SINK HAS NOT BEEN FOUND AND NO RESPONSE
 FROM THE ARCHITECT HAS BEEN SUBMITTED.
 CLEAR FLOOR SPACE SHOWN ON SHT A2.1.1 IS
 NOT APPROVED AS IT IS A PARALLEL
 APPROACH.
  
 6. SHT P3.1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ***RESPONSE NOTED, BUT THE CORRESPONDING
 LENGTHS ARE NOT SHOWN, AND THE ISOMETRIC
 DOES NOT REFLECT THE OFFSETS SHOWN ON
 THE FLOOR PLAN FLAT LAYOUT.
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ***RESPONSE NOTED, BUT NO DELIVERY
 PRESSURE IS SHOWN ON THE ISOMETRIC.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 506.
 *** RESPONSE NOTED, BUT NO VENTING
 INFORMATION IS SHOWN ON SHT P3.1.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT NO MANUF.
 SPECIFICATION SHEETS WERE SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 SHEETS AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ***************NEW COMMENT**************
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL & FS 533.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-10 Cont ID  
Sent By kstevens Date 2005-11-10 Time 16:07 Rev Time 2.75
Received By kstevens Date 2005-11-10 Time 16:07 Sent To  
Notes
2005-11-10 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 11
 FBC-2001 CHAPTER 1
  
  
 1. TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED.
 2. SHTS LA-POOL-3 & LA-POOL-4 SEPARATE
 POOL PLANS & PERMIT ARE REQUIRED FOR
 EACH POOL. PLANS SHALL BE ROUTED TO THE
 PALM BEACH COUNTY HEALTH DEPT FOR REVIEW
 AND SHALL BE STAMPED PRIOR TO SUBMITTING
 TO CITY WPB FOR REVIEW. (MIN. 2 SETS OF
 PLANS).
 3. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED, & DATED AS
 REQUIRED BY FLORIDA STATUTES. SECTION
 106.1.
 4. SHT CH A2.1.1 KITCHEN SINK SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. CLEAR FLOOR SPACE FOR SINK
 SHALL BE FORWARD APPROACH.
 5. SHT P3.1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. (SEE
 NOTE 13 SHT P0.1).
 6. SHT P3.1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 506.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-02 Cont ID  
Sent By jroach Date 2006-07-02 Time 17:40 Rev Time 0.00
Received By jroach Date 2006-07-02 Time 17:40 Sent To  
Notes
2006-07-02 00:00:007/2/06 ***FAILED***
  
 1) INDICATE ON THE PHASING PLAN THAT THE
 TURQUOISE NECKLACE WILL BE DESIGNED,
 PERMITTED AND CONSTRUCTED AS PART OF
 PHASE 2.
  
 2) THE TURQUOISE NECKLACE SHALL BE
 PROVIDED ON THE CIVIL DRAWINGS.A NOTE
 MAY BE PROVIDED INDICATING THAT IT WILL
 BE DESIGNED, PERMITTED AND CONSTRUCTED
 AS PART OF PHASE 2.
  
 3) UNITY OF TITLE SHALL BE RECORDED IN
 THE PUBLIC RECORD OF PALM BEACH COUNTY.
 A COPY SHALL BE INCLUDED WITH ALL PERMIT
 PACKAGES.
  
 4) PARKING STALL DETAIL SHALL CONFORM TO
 THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.A WHEEL STOP SHALL BE
 SHOWN 2 FEET FROM THE HEAD OF THE STALL.
 IF NO WHEEL STOP IS PROVIDED, SIDEWALKS
 LOCATED AT THE HEAD OF THE STALL NEED TO
 BE 7 FEET IN WIDTH TO ALLOW FOR 2 FEET
 OF VEHICLE OVERHANG.IF THE OVERHANG
 OCCURS OVER LANDSCAPING, THE LANDSCAPING
 SHALL NOT EXCEED 6 INCHES ABOVE THE
 HEIGHT OF THE CURB.DETAIL OF DOUBLE
 STRIPING NEEDS TO SHOW 12 INCHES FROM
 INSIDE OF STRIP TO INSIDE OF STRIPE.
  
 5) ALL LANDSCAPE SHEETS NEED TO BE
 SIGNED AND SEALED BY A REGISTERED
 LANDSCAPE ARCHITECT, NOT JUST THE COVER
 SHEET.
  
 6) LANDSCAPE PLANS NEED TO BE ADJUSTED
 TO INDICATE THAT TOWNHOUSE #7 IS PART OF
 PHASE 1.
  
 7) THE LIFT STATION SHOWN ON THE CIVIL
 PLANS DOES NOT MATCH THAT SHOWN ON THE
 LANDSCAPE PLAN.LANDSCAPING NEEDS TO BE
 ADJUSTED ACCORDINGLY.
  
 8) AS A RESULT OF EACH BUILDING BEING
 CO'D SEPARATELY, AN INSPECTION PLAN
 SHALL BE PROVIDED INDICATING WHICH AREAS
 OF LANDSCAPING WILL BE INSPECTED WITH
 EACH BUILDING CO.
  
 9) THE AREAS BETWEEN THE TOWERS ARE
 SHOWN AS FA GRASS.THIS SHALL BE
 MODIFIED AS THE BOARDWALKS ARE NO LONGER
 BEING PROPOSED.
  
 10) THE SIDEWALK CONFIGURATION ON THE
 LANDSCAPE PLANS AND THE CIVIL PLANS
 SHALL CORRESPOND WITH THE SITE PLAN.
  
 11) THE LANDSCAPE PLANS SHWO THE BUS
 SHELTER AND ENTRANCE WALL/LANDSCAPING AS
 PART OF PHASE 1.THE PHASING PLAN
 INDICATES OTHERWISE.
  
 12) FYI...IN DEVELOPING THE SIGNAGE FOR
 THE FRONT ENTRY WALL, THE AREA SHALL NOT
 EXCEED 48 SQUARE FEET.
  
 13) A PHOTOMETRIC PLAN SHALL BE PROVIDED
 FOR SITE LIGHTING ON THE ENTIRE
 PROPERTY.THE PHOTOMETRIC LEVELS SHALL
 BE SHOWN AT THE PROPERTY LINES AND SHALL
 NOT EXCEED 0.5 FOOTCANDLES AT PROPERTY
 LINES ADJACENT TO RESIDENTIAL PROPERTY.
  
 THE FOLLOWING COMMENTS HAVE BEEN
 PROVIDED BY ALAN BARATTA, LANDSCAPE
 PLANNER:
  
 1) PLANTING DIAGRAMS SHALL BE MODIFIED
 TO REFLECT WHAT WAS AGREED TO IN THE
 TREE REMOVAL/RELOCATION LICENSE.
  
 2) IN ORDER TO PREVENT DESTRUCTION TO
 CURBING, PAVING AND PARKED VEHICLES,
 REPLACE THE MOHOGANY TREES IN THE
 LANDSCAPE ISLANDS IN FRONT OF THE
 TOWNHOMES WITH A SMALLER/ALTERNATE
 SPECIES.MINOR PD AMENDMENT (PB CASE
 NO. 1242E) APPROVED ON JULY 2, 2006,
 INDICATED GREEN BUTTONWOODS.
  
 3) ADDITIONAL LANGUAGE SHALL BE PROVIDED
 INDICATING REMOVAL OF SUPPORT MATERIAL
 FROM TREES/PALMS SHALL OCCUR AFTER
 ESTABLISHMENT OR HURRICANE SEASON,
 WHICHEVER COMES LATER.
  
 4) LANDSCAPING IN THE EXECUTIVE CENTER
 DRIVE CUL-DE-SAC SHALL BE COORDINATED
 WITH THE PUBLIC UTILITIES/ENGINEERING
 DEPARTMENT.
  
 MISCELLANEOUS COMMENTS:
  
 1) WORKFORCE HOUSING RESTRICTION ON THE
 LOFTS AND TOWNHOMES, FOLLOWING APPROVAL
 BY THE CITY OF WEST PALM BEACH, SHALL BE
 IN PLACE PRIOR TO THE ISSUANCE OF A CO
 FOR SUCH STRUCTURES.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-20 Cont ID  
Sent By jroach Date 2005-09-20 Time 14:13 Rev Time 0.00
Received By jroach Date 2005-09-20 Time 14:13 Sent To  
Notes
2005-09-20 00:00:009/20/2005 ***FAILED***
  
 IN ADDITION TO THE COMMENTS BELOW, REFER
 TO ALL ZONING COMMENTS ON PERMIT
 #05080675, LISTED UNDER "ALL PERMITS"
 AND "MISCELLANEOUS COMMENTS."
  
 CLUBHOUSE
  
 1. NO ADDITIONAL COMMENTS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.