Plan Review Details - Permit 05080675
Plan Review Stops For Permit 05080675
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-11-30 Cont ID  
Sent By hpiskura Date 2007-11-30 Time 15:38 Rev Time 0.00
Received By hpiskura Date 2007-11-30 Time 15:37 Sent To  
Notes
2008-05-05 15:41:30PERMIT IS EXTENDED TO 5/31/08 HHP
 NOTE DATE WAS ADJUSTED TO COINCIDE WITH 6 MONTH
 EXPIRATION FROM LAST ACTIVITY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-01 Cont ID  
Sent By rbrown Date 2007-06-01 Time 18:43 Rev Time 0.00
Received By rbrown Date 2007-06-01 Time 18:43 Sent To  
Notes
2007-06-01 18:44:06REQUEST GRANTED FOR EXTENSION OF PERMIT APPLICATION.
 SEE LETTER DATED 5/31/07.UPDATED EXPIRATION DATE IS
 9/2/07.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-24 Cont ID  
Sent By jwitmer Date 2006-04-24 Time 08:12 Rev Time 5.55
Received By jwitmer Date 2006-04-24 Time 07:03 Sent To  
Notes
2006-04-24 00:00:00 
 PERMIT: 05080675
 ADD: 719 EXECUTIVE CENTER DR
 (TOWER# 4)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 105.8* PROVIDE NOC RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3A)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING WILL REQUIRE A THRESHOLD
 INSPECTOR.FORMS WILL NEED TO BE FILED
 OUT FOR THE THRESHOLD INSPECTOR, CONTACT
 HAROLD PISKURA, INSPECTION SERVICES
 MANAGER @ (561)805-6711 TO SEET UP AN
 APPOINTMENT.
  
 3B) 109.3.6.1* THE ENFORCING AGENCY
 SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCINGAGENCY PRIOR
 TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD
 BUILDING.THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLANS IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 3C) 109.3.6.4.4.105.13.4.4 ALL PLANS FOR
 THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTES.
  
 3D) NOTE: SINCE THIS BUILDING WILL BE A
 THRESHOLD STRUCTURE SUBMIT (3) OF ALL
 DOCUMENTS FOR REVIEW.
  
 4) 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5) SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL JOHN HIGGINS FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. JOHN HIGGINS
 CONTACT NUMBER IS (561)822-1239.
  
 6) THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) PROVISO.
  
 10) PROVISO.
  
 11) COMPLIED.
  
 11B) COMPLIED.
  
 12A) COMPLIED
  
 12B) COMPLIED.
  
 12C) 2ND REQUEST
 PORTE COCHERE: THE PLANS DO NOT INDICATE
 THERE IS AN ACCESSIBLE LOADING ZONE
 UNDER THE PORTE COCHERE. FAIR HOUSING
 ANSI 4.6.
  
 12D) 2ND REQUEST,
 PROVIDE SIGNAGE FOR HANDICAPPED PARKING
 AND VAN ACCESSIBLE PARKING. FAIR HOUSING
  
 RESPONCE: SEE CIVIL, WHERE? SHEET# 9
 DOES HAVE HANDICAPPED ELEMENTS ON THIS
 SHEET BUT FOR SIGNAGE ONLY A STOP SIGN.
  
 12E) 2ND REQUEST REACH RANGES FOR THE
 COMMON USE MAILBOXES. PROVIDE FRONT AND
 SIDE RANGES.
  
 12F) COMPLIED.
  
 12G) COMPLIED.
  
 12H) COMPLIED.
  
 13) COMPLIED.
  
 14) COMPLIED.
  
 15A) COMPLIED.
  
 15B) COMPLIED.
  
 15C) COMPLIED.
  
 15D)2ND REQUEST, NOTE: IF WINDOWS
 REQUIRES FIRE RATED
 GLASS, AS FAR AS I'M AWARE NO
 MANUFACTURER MAKES FIRE RATED AND LARGE
 MISSLE IMPACT RATED GLAZING!!!! SEE
 THE BUILDING OFFICIALS INTERPRETATION ON
 LARGE OR HIGH RISE BUILDINGS AS FAR AS
 SHUTTERS VS LARGE OR SMALL MISSLE RATED
 GLASS.
 *************************
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY,
  
 SUBMIT: PRE-STORM PREPARATION:
  
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE
 PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS
 APPROPRIATE FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 16) COMPLIED.
  
 17A) COMPLIED.
  
 17B) COMPLIED.
  
 17C) 2ND REQUEST,
 ROOF TOP MECHANICAL UNITS AS SHOWN ON
 A6.1.3 DETAIL# 7 INDICATES A MINIMUM OF
 18" FROM ROOF, SEE TABLE 1509.7 FOR THE
 MINIMUM VERTICAL DISTANCE.
  
 18) 2ND REQUEST REWORD PHRASE
 "PEDESTRIAN BRIDGE TO GARAGE (UNDER
 SEPERATE PERMIT)" THIS APPEARS ON T-4
 A3.1.3.
  
 18B) PEDESTRIAN BRIDGE INTERFACE WILL
 REQUIRE A 1 1/2 HR RATED PROTECTIVE
 (706.7) SEE FIGURE 3104.5 CODE
 COMMENTARY.
 3104.5 FIRE BARRIERS BETWEEN PEDESTRIAN
 WALKWAYS AND BUILDINGS.
 WALKWAYS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING BY FIRE BARRIER
 WALLS WITH A FIRE-RESISTANCE RATING OF
 NOT LESS THAN 2 HOURS. THIS PROTECTION
 SHALL EXTEND VERTICALLY FROM A POINT 10
 FEET (3048 MM) ABOVE THE WALKWAY ROOF
 SURFACE OR THE CONNECTED BUILDING ROOF
 LINE, WHICHEVER IS LOWER, DOWN TO A
 POINT 10 FEET (3048 MM) BELOW THE
 WALKWAY AND HORIZONTALLY 10 FEET (3048
 MM) FROM EACH SIDE OF THE PEDESTRIAN
 WALKWAY. OPENINGS WITHIN THE L0-FOOT
 (3048 MM) HORIZONTAL EXTENSION OF THE
 PROTECTED WALLS BEYOND THE WALKWAY SHALL
 BE EQUIPPED WITH DEVICES PROVIDING A
 3/4-HOUR FIRE PROTECTION RATING IN
 ACCORDANCE WITH SECTION 715 .
  
 19) COMPLIED.
  
 20) 2ND REQUEST,
 20) THE ELEVATION SHEETS AND A6.1.1
 DEPICT DETAILS WITH CAST RESIN CORNICE
 AND BANDS ON THE EXTERIOR OF THE
 BUILDING. 1406.2.2 ARCHITECTURAL TRIM
 THAT EXCEEDS 40FT IN HEIGHT ABOVE GRADE
 PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE
 SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.
  
 21)COMPLIED.
  
 22) 2ND REQUEST, T-4 A6.1.3 DETAIL# 11
 ALSO INDICATES THE USE OF INTEGRAL ROOF
 DECK PROVIDE ADDITIONAL INFORMATION.
 RESPONCE: SEE STRUCTURAL SHEETS, WHERE?
  
  
 23) 2ND REQUEST, RESPONCE ,SEE
 STRUCTURAL WHERE?
 SAME DETAIL AS ABOVE WHAT SPANS CAN
 THE GALVANIZED METAL FURRING SPAN @ 12"
 O. C. PROVIDE THE PSF APPLIED LOAD, AND
 THICKNESS OF HI HAT IN MIL. SPANS TO BE
 TAKEN AS MULTIPLE SPANS?
  
 24A) COMPLIED.
  
 24B) COMPLIED.
  
 24C) COMPLIED.
  
 24D) COMPLIED.
  
 25: T-3 A5.1.5
 25A) 2ND REQUEST,
 DETAILS SHOW A DROPPED CEILING OVER THE
 WALKWAYS WITH METAL FRAMING NO
 INDICATION AS TO ATTACHMENT TO THE DECK
 ABOVE, SPACING OF ATTACHMENT, GAUGE OR
 SIZE OF FRAMING, OR SPACING OF FRAMING.
  
 26) SHEET M2.5 HAS NO INDICATION OF A
 SMOKEPROOF EXIT ENCLOSURE, SEE 403.13
 ALSO SEE 1019.1.3 FOR REQUIRED
 VENTILATION, AND 909.20 FOR PRESSURIZED
 STAIRS.
 KAMM RESPONE: SMOKE PROOF ENCLOSURE NOT
 REQUIRED. PLEASE REFER TO ARCHITECTURAL
 DRAWINGS AND OR ARCHITECTS RESPONCE
 LETTER. NO ARCHITECTURAL RESPONCE.
 HIGH-RISE 403
 403.13 SMOKEPROOF EXIT ENCLOSURES.
 EVERY REQUIRED STAIRWAY SERVING FLOORS
 MORE THAN 75 FEET (22 860 MM) ABOVE THE
 LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE
 ACCESS SHALL COMPLY WITH SECTIONS 909.20
 AND 1019.1.8 .
 1019.1.8 SMOKEPROOF ENCLOSURES.
 IN BUILDINGS REQUIRED TO COMPLY WITH
 SECTION 403 OR 405, EACH OF THE EXITS OF
 A BUILDING THAT SERVES STORIES WHERE THE
 FLOOR SURFACE IS LOCATED MORE THAN 75
 FEET (22 860 MM) ABOVE THE LOWEST LEVEL
 OF FIRE DEPARTMENT VEHICLE ACCESS OR
 MORE THAN 30 FEET (9144 MM) BELOW THE
 LEVEL OF EXIT DISCHARGE SERVING SUCH
 FLOOR LEVELS SHALL BE A SMOKEPROOF
 ENCLOSURE OR PRESSURIZED STAIRWAY IN
 ACCORDANCE WITH SECTION 909.20 .
  
 27) PRODUCT APPROVALS:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 28) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXT LOUVER DOORS
 B) EXT SOLID DOORS
 C) EXT GLAZED DOORS SWING
 D) EXT GLAZED DOORS W/ TRANSOMS, SWING
 E) CASEMENT WINDOWS
 F) MULLIONS HORIZONTAL
 G) EXT RAILINGS
 H) LOUVERS
 I) TRUSS ANCHORS
 J) ROOFING ASSEMBLIES
 1) FLAT ROOF
 2) CEMENT TILE & TYPE OF INSTALATION
 NOTE THE FLAT ROOF INFORMATION SUBMITTED
 IS REDUCED TO 1/2 SHEET, NOT READABLE TO
 COPY FOR RECORD RETENTION.
 THE CONTRACTOR DID NOT HIGHLIGHT WHICH
 SUBSYSTEM TO BE USED NOR DID THEY
 HIGHLIGHT WHICH FASTENING OPTIONS TO BE
 USED.
  
 29) NEW COMMENT,
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT
 LESS THAN 50 (45 IF FIELD TESTED) WHEN
 TESTED IN ACCORDANCE WITH ASTM E 492.
  
 30)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-27 Cont ID  
Sent By jwitmer Date 2005-10-27 Time 10:01 Rev Time 33.00
Received By jwitmer Date 2005-10-17 Time 08:02 Sent To  
Notes
2005-10-17 00:00:00PERMIT: 05080675
 ADD: 719 EXECUTIVE CENTER DR
 (TOWER# 4)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 105.8* PROVIDE NOC RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3A)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING WILL REQUIRE A THRESHOLD
 INSPECTOR.FORMS WILL NEED TO BE FILED
 OUT FOR THE THRESHOLD INSPECTOR, CONTACT
 HAROLD PISKURA, INSPECTION SERVICES
 MANAGER @ (561)805-6711 TO SEET UP AN
 APPOINTMENT.
  
 3B) 109.3.6.1* THE ENFORCING AGENCY
 SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCINGAGENCY PRIOR
 TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD
 BUILDING.THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLANS IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 3C) 109.3.6.4.4.105.13.4.4 ALL PLANS FOR
 THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTES.
  
 3D) NOTE: SINCE THIS BUILDING WILL BE A
 THRESHOLD STRUCTURE SUBMIT (3) OF ALL
 DOCUMENTS FOR REVIEW.
  
 4) 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5) SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL JOHN HIGGINS FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. JOHN HIGGINS
 CONTACT NUMBER IS (561)822-1239.
  
 6) THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
 7) SHEET A-1.1.2 BUILDING DATA FOR
 TOWER#4 INDICATES 107 UNITS WHERE AS THE
 SAME SHEET THE SITE PLAN INDICATES 108,
 CORRECT DESCRIPANCY.
  
 8) GEOTECHNICAL REPORT THAT WORK WAS
 PREFORMED BY ARDAMAN NEEDS TO BE AN
 ORIGINAL WITH SIGNATURE AND RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10)109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 11) SHEET T-4 A2.1.1
 11A) STAIR TOWER # 2, DOOR A/130 SWINGS
 THE WRONG WAY,SEE 1008.1.2.
  
 11B) ELEVATORS, PLEASE INDICATE THAT THE
 ELEVATORS CAN ACCOMODATE AMBULANCE
 STRETCHERS. 3002.4.
  
 12)SHEET T-4 A2.1.1 FAIR HOUSING/
 ACCESIBLITY
 12A)PLANS DO NOT PROVIDE AN ACCESSIBLE
 PATH TO THE BUS STOP. THE SIDEWALK STOPS
 SHORT OF BUS STOP BENCH. THERE IS NO
 PEDESTRIAN CROSSWALK CONNECTING THE
 SIDEWALKS TO PUBLIC TRANS PORTATION.
  
 12B) PROVIDE HOW THE HANDICAPPED
 ACCESSIBLE PATH (SIDEWALKS) WILL BE
 MAINTAINED DURING THE PHASING, PROVIDE A
 SITE PLAN INDICATING ACCESSIBLITY TO THE
  
 PUBLIC WAY.
  
 12C) PORTE COCHERE: THE PLANS DO NOT
 INDICATE THERE IS A ACCESSIBLE LOADING
 ZONE UNDER THE PORTE COCHERE. FAIR
 HOUSING ANSI 4.6
  
 12D) PROVIDE SIGNAGE FOR HANDICAPPED
 PARKING, AND VAN ACCESSIBLE PARKING.
  
 12E) PLANS DO NOT INDICATE REACH RANGES
 FOR THE COMMON USE MAIL BOXES.
  
 12F) THERE IS NO KITCHEN DETAILS
 INDICATING AN ACCESSIBLE SINK WITH
 FORWARD APPOARCH.
  
 12G) THE INDIVIDUAL UNITS WITH ENTRYS
 WITH 45 DEGREE WALLS MISSING THE
 REQUIRED 18" ON THE PULL SIDE OF DOOR.
 SEE ANSI 4.13.6, ONLY REQUIED ON THE
 EXTERIOR SIDE.
 THE UNIT ENTRY DOORS WITH 45 DEGREE
 WALLS ADJACENT TO THE FFRONT ENTRY DOOR
 DO NOT MEET THE FAIR HOUSING GUIDELINE
 FOR AN ACCESSIBLE FRONT ENTRY, SEE
 ANSI 4.13FOR THE EXTERIOR SIDE LATCH
 SIDE OF DOOR ONLY.
  
 12H) IN BOTH STAIR TOWER 1 & 2 THE ARROW
 INDICATING DIRECTION OF TRAVEL IS
 BACKWARDS. WHEN CORRECTED THE PROBLEM
 WITH REDUCED VERTICAL CLEARENCE UNDER
 THE STAIRS WILL BE APPEARENT. ANSI 117.1
 SECTION 307.4 REQUIRING EITHER A
 GUARDRAIL OR OTHER BARRIER WHERE THE
 VERTICAL HEIGHT IS REDUCED LESS THAN
 80".
  
 13) STAIR TOWER# 2 DOOR A/130 IS
 SWINGING THE WRONG WAY, SEE 1008.1.2
  
 14) SHEET A2.1.1/ A2.1.3
 STAIR TOWER# 1& STAIR TOWER# 2 IN BOTH
 CASES ONCE THE STAIR TOWER DOOR OPENS
 LEAVES THE OCCUPANTS WITHIN THE CONFINES
 OF THE BUILDING. THE DOORS AND WINDOWS
 ON THE OPPOSITE WALL ARE NOT RATED. THE
 LIFE SAFETY PLAN INDICATES IN BOTH CASES
 A SINGLE MEANS OF EGRESS.
 SEE 1013.5.1. THIS SECTION IS FOR
 BALCONIES, THE SAME CONCERNS ABOUT
 EGRESS APPLIES THAT THE OPENINGS WOULD
 REQUIRE OPENING PROTECTIVES.
  
 15) SHEET T-4 A2.2.1.
 15A) THE 2ND FLOOR AND HIGHER FLOORS
 HAVE THE SAME PROBLEM WITH NOT HAVING AN
 ELEVATOR LOBBY. THE AREA THAT SURROUNDS
 THE ELEVATORS AND IS ENCLOSED NOT
 MEETING THE DIFINITION OF AN OPEN
 BALCONY (SEE 1013.5.2) AND WILL BE
 CONSIDERED AS A CORRIDOR REQUIRING
 A 1HR RATING SEE TABLE 1016.1.
  
 15B) ELEVATOR LOBBIES SHALL MEET THE
 REQUIREMENTS OF 707.1.14.1.THE LOBBY
 SHALL SEPERATE THE ELEVATOR FROM THE
 CORRIDOR BY FIRE PARTITIONS AND THE
 REQUIRED OPENING PPROTECTION.
  
 15C) UNIT A, UNIT B, UNIT C, UNIT E,
 UNIT I, UNIT B AND UNIT A ARE EITHER
 TOTALLY WITHIN A CORRIDOR OR PARTIALLY
 WITHIN A CORRIDOR REQUIRING RATED
 OPENING PROTECTIVES SEE TABLE 1016.1.
  
 15D) NOTE IF WINDOWS REQUIRES FIRE RATED
 GLASS, AS FAR AS I'M AWARE NO
 MANUFACTURER MAKES FIRE RATED AND LARGE
 MISSLE IMPACT RATED GLAZING!!!! SEE
 THE BUILDING OFFICIALS INTERPRETATION ON
  
 LARGE OR HIGH RISE BUILDINGS AS FAR AS
 SHUTTERS VS LARGE OR SMALL MISSLE RATED
 GLASS.
 *************************
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE
 PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS
 APPROPRIATE FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 16)T-4 A.2.2.3 CODE REVIEW FOR HIGH RISE
 BLDG DOES NOT INDICATE AS TO WHICH CODE
 THIS BUILDING WAS DESIGNED TO.
  
 17)SHEET T4-A2.4.1:
 17A) THIS PLAN HAS THE TERM "WALL
 ANCHOR" PLEASE EXPLAIN?
  
 17B) TERM E.O.S. EMERGENCY OVERFLOW
 SCUPPER DOES NOT INDICATE ANY SECTIONS
 THROUGH NOR GIVE SIZES, ADDITIONAL
 INFORMATION REQUIRED.
  
 17C) ROOF TOP MECHANICAL UNITS AS SHOWN
 ON A6.1.3 DETAIL 8 INDICATES A MINIMUM
 OF 18" FROM ROOF, SEE TABLE 1509.7 FOR
 MINIMUM VERTICAL HEIGHTS.
  
 18) T-4 A.2.5.1-A2.5.3 ARE FOR AN AREAL
 COVERED WALKWAY . SHEET T-4 A.3.1.3,
 NOTE, THAT A SEPERATE PERMIT WILL BE
 SUBMITTED FOR CONSTRUCTION OF AREAL
 COVED WALKWAY. THESE PAGES WILL BE
 STRUCK "VOID" AND THE ASSOCIATED
 STRUCTURAL PAGES.
  
 19) SHEET T-4 A2.4.2 INDICATES 3 ATTIC
 AREAS NO USEAGE INDICATED. 1509.2 A
 PENTHOUSE, BULKHEAD OR ANY OTHER SIMILAR
 PROJECTION ABOVE THE ROOF SHALL NOT BE
 USSED FOR PURPOSES OTHER THAN SHELTERING
 OF MECHANICAL EQUIPMENT OR SHELTEROF
 VERTICAL SHAFT OPENINGS IN THE ROOF.
 PENT HOUSES USSED FOR PURPOSES OTHER
 THAN PERMITTED BY THIS SECTION SHALL
 CONFORM TO THE REQUIREMENTS OFTHIS CODE
 FOR AN ADDITIONAL STORY.
  
 20) THE ELEVATION SHEETS AND A6.1.1
 DEPICT DETAILS WITH CAST RESIN CORNICE
 AND BANDS ON THE EXTERIOR OF THE
 BUILDING. 1406.2.2 ARCHITECTURAL TRIM
 THAT EXCEEDS 40FT IN HEIGHT ABOVE GRADE
 PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE
 SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.
  
 21)T-4A6.1.3 DETAIL# 11/ A5.1.3 BOTH SEC
 TIONS INDICATE USE OF R-30 INSULATION.
 THE INSULATION IS DEPICTED TO BE IN THE
 TOP CHORD OF THE METAL TRUSS. THE
 TRUSSES ARE CENTERED @ 48" O. C. HOW
 WILL THE INSULATION BE ATTACHEDAND TO
 WHAT?
  
 22) T-4 A6.1.3 DETAIL# 11 ALSO INDICATES
 THE USE OF INTEGRAL ROOF DECK PROVIDE
 ADDITIONAL INFORMATION.
  
 23) SAME DETAIL AS ABOVE WHAT SPANS CAN
 THE GALVANIZED METAL FURRING SPAN @ 12"
 O. C. PROVIDE THE PSF APPLIED LOAD, AND
 THICKNESS OF HI HAT IN MIL. SPANS TO BE
 TAKEN AS MULTIPLE SPANS?
  
 24) T-4 A7.2.1 THE DOOR SCHEDULE UNDER
 REMARKS HAS NO NOTATIONS, AS TO REQUIRED
 HARDWARE, SELF-CLOSING DOORS AND DROP
 SEALS PLEASE PROVIDE THIS ADDITIONAL
 INFORMATION.
  
 24A) 709.3 FIRE-RESISTANCE RATING. A1
 HOUR FIRE-RESISTANCE RATING IS REQUIRED
 FOR SMOKE BARRIERS.
  
 24B) 710.5.2 SMOKE AND DRAFT-CONTROL
 DOORS. WHERE REQUIRED ELSEWHERE IN THE
 CODE, DOORS IN SMOKE PARTITIONS SHALL BE
 TESTED IN ACCORDANCE WITH UL 1784 WITH
 AN ARTIFICIAL BOTTOM SEAL INSTALLED
 ACROSS THE FULL WIDTH OF THE BOTTOM OF
 THE DOOR ASSEMBLY.
  
 24C) DOOR A-129 STYLE"K" IS LOUVER THIS
 CORRIDOR TO BE 1HR RATED, CORRECT
  
 24D) DOOR 104,107, 110 & 112 FOR 2ND
 FLOOR & ABOVE WILL ALL REQUIRE RATED
 DOORS IN CORRIDOR.
  
 25) 1406.2.2 ARCHITECTURAL TRIM THAT
 EXCEEDS 40 FT IN HEIGHTABOVE GRADE
 SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS. SEE DEFINITION
 OF NON-COMBUSTIBLE MATERIAL.
  
 26) T-3 A5.1.5:
 26A) DETAILS SHOW A DROPPED CEILING OVER
 WALKWAYS WITH METAL FRAMING NO
 INDICATION AS TO THE ATTACHMENT TO THE
 DECK ABOVE, SPACING OF ATTACHMENET,
 GAUGE OR SIZE OF FRAMING OR SPACING OF
 FRAMING.
 26B) PLANS INDICATE THAT THE FINISH WILL
 BE A CEMENT PLASTER FINISH THIS MEANS A
 TRUE CEMENT PLASTER FINISH AND NOT EFIS?
 EFIS SYSTEMS INDICATE NOT TO BE USED ON
 HORIZONTAL SURFACES.
  
 27)FIRE SPRINKLER PLANS:
 27A)FS1.1 INDICATES THAT THERE IS NO
 FIRE PUMP LOCATED IN HIGHRISE TOWER# 3.
  
 403.8 & 911 BOTH DEAL WITH THE FIRE
 COMMAND CENTER WHICH REQUIRES BOTH A
 FIRE PUMP AND GENERATOR. FS.1 INDICATES
 A SHARED FIRE PUMP FOR THREE BUILDINGS,
 THE CODE ISN'T CLEAR AS TO IF THE FIRE
 PUMP CAN BE SHARED OF NOT. IN SPEAKING
 WITH THE FIRE REVIEWERS THIS MAY NOT BE
 AN ACCEPTABLE METHOD OR APPLICATION.
 THE PRESENT LOCATION OF THE FIRE PUMP IS
 IN A PARKING GARAGE THAT HASN'T EVEN
 APPLIED FOR A PERMIT. THE SECOND ISSUE
 WILL BE THE SIZE OF THE FIRE PUMP IF THE
 LOCATION IS ACCEPTED, PROVIDE THE
 DOCUMENTATION FOR THE SIZE OF THE FIRE
 PUMP REQUIRED FOR THE 3 BUILDINGS IT
 WILL SERVICE.
  
 28) T3 A2.1.1 DOESN'T INDICATE THE
 LOCATION OF THE EMERGENCY GENERATOR,
 403.10 A STANDBY POWER SYSTEM COMPLYING
 WITH 2702 SHALL BE PROVIDED FOR STANDBY
 POWER LOADS SPECIFIED IN SECTION
 403.10.2 AND ALSO NFPA 110 & 111.
  
 29) FS2.1 IS MISSING THE FIRE SPRINKLERS
 IN THE CORRIDORS THAT FRONT EACH UNIT.
 ALSO REMOVE THE LIGHTING SYMBLES THAT
 ARE LOCATED IN THE SAME CORRIDOR.
  
 30) SECTION 911.1 OF THE CODE DEALS WITH
 THE FIRE COMMAND CENTER AND THE
 ASSOCIATED SYSTEMS (15) THAT ARE
 REQUIRED FOR A HIGH RISE BUILDING.
 SUBMIT A LAYOUT OF THE FIRE COMMAND
 CENTER AND ALL FEATURES REQUIRED BY THE
 SECTION TO BE CONTAINED THEREIN SHALL BE
 SUBMITTED FOR APPROVAL PRIOR TO
 INSTALLATION.
  
 31)SHEET M2.5 HAS NO INDICATION OF A
 SMOKEPROOF EXIT ENCLOSURE, SEE 403.13
 ALSO SEE 1019.1.3 FOR REQUIRED
 VENTILATION, AND 909.20 FOR PRESSURIZED
 STAIRS.
  
 32)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-01 Cont ID  
Sent By dpalmer Date 2006-05-01 Time 18:44 Rev Time 0.00
Received By dpalmer Date 2006-04-27 Time 16:57 Sent To  
Notes
2006-05-01 00:00:00************ UNSAT 2ND REVIEW *********
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW
 WHICH NEED TO BE ADDRESSED AND SOME NEW
 NOTES DUE TO CHANGES IN PLANS.
  
 ** PLEASE SEE NOTE BELOW ARE TAKEN
 DIRECTLY FROMPREVIOUS REVIEW AND ARE
 SO NOTED.
  
 **************************************
 PLEASE SEE NOTES AT THE END OF COMMENTS
 WITH RESPECT TO REMOVAL OF ALL
 OLD/VOIDED SHEETS.
 **************************************
  
  
 SAIL CLUB TOWER #4
  
  
  
  
 1)NOTE:NOTE #1 NO, PLEASE SEE PLANS
 STILL REFLECT AND NOTE THE 1999 NEC.
 PLEASE ALSO SEE REVISED ELECTRICAL PLANS
 ARE REQUIRED TO REFLECT THE CODES AND
 YEARS IN EFFECT FOR DESIGN.
  
 ** PREVIOUS NOTE **
 PLEASE SEE CODE REFERENCED ON PLANS LIST
 THE 1999 NEC. PLEASE KNOW, AS OF JULY
 1ST 2003, THE STATE ADOPTED THE 2002
 NEC.
 PLEASE ALSO SEE WE ARE UNDER THE 2003
 NFPA-101 AND 2002 NFPA-72
 PLEASE ADJUST.
  
 2)NOTE: NOTE #2, OK, HOWEVER PLEASE SEE
 ANYBLDG, FIRE REVIEW COMMENTS AS THEY
 MAY AFFECT DESIGN. PLEASE SEE NEW
 COMMENTS DUE TO CHNAGES AT FPL VAULT
 LOCATION.
  
 3)NOTE: NOTE #3 NO, PLEASE SEE AREAS
 WHERE SOME CIRCUTING IS STILL MISSING.
  
 ** PREVIOUS NOTE**
 PLEASE SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE SOME AREAS WHICH ELECTRICAL
 FIXTURES SEEM TO BE MISSINGTHIS.
 PLEASE ALSO SEE CIRCUITING FOR UNITS.
 PLEASE KNOW, A "TYPICAL" UNIT LAYOUT MAY
 BE PROVIDED, HOWEVER A LAYOUT WOULD BE
 REQUIRED FOR EACH UNIT TYPE, INCLUDING
 STUDIO UNIT.
 CIRCUITING FOR SOME UNITS/ITEMS CAN NOT
 BE VERIFIED AT THIS TIME.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE REPSONSE
 LETTER MENTIOSN TO SEE E 3.1, HOWEVER
 PLEASE SEETHIS SHEET ONLY SHOWS ONE
 AREA OF FIRST FLR COMMON AREA.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE PHOTO-METRICS FOR
 STAIR TOWERS ON NORMAL PWR AND STAND-BY.
 ALONG WITH WALK AREAS.
 PLEASE SEE STAIR TOWERS UNDER NORMAL PWR
 SHALL MEET A MIN OF 10FT CANDLES. PLEASE
 SEE ARES FOR HALLS ETC ARE PERMITTED TO
 BE LESS. .
 PLEASE SEE NFPA-101 7.8.1.3,7.9.2.1
  
 5)NOTE: NOTE #5 NO, PLEASE KNOW, A
 BATTERY BACK UP FIXTURE OF SOME SORT
 WILL BE REQUIRED IN STAIR TOWERS AT A
 MIN OF EVERY OTHER LEVEL.
  
 ** PREVIOUS NOTE **
 PLEASE KNOW, BATTERY BACK FIXTURES WILL
 BE REQUIRED AT EVERY OTHER LEVEL(MIN).
 PLEASE SEE LS 101 WHICH MENTIONS THE
 TRIPPING/THROW OF A SINGLE BRKR SAHLL
 NOT LEAVE ANY EGRESS AREA IN TOTAL
 DARKNESS. PLEASE CALL ELECTRICAL PLAN
 REVIEW AND FIRE MARSHALS OFFICE TO GO
 OVER OPTIONS PERMITTED.
 A BATTERY BACK-UP FIXTURE AT EVERY OTHER
 LEVEL WILL SATISFY FIRE MARSHAL'S OFFICE
 AND AHJ.
 PLEASE BE SURE TO MEET THE MIN OF 1
 FT/CANDLE UNDER EM.
 PLEASE BE SURE TO SEE PREVIOUS NOTE #4
 FOR LIGHTING LEVELS.(MIN)
  
 6)NOTE: NOTE#6 NO, PLEASE SEE MOST
 FIXTURES WERE ADDED TO THESE ROOMS,
 HOWEVER PLEASE SEE ELEVATOR MACHINE ROOM
 WHICH WILL REQUIRE ARE BATTERY BACK
 FIXTURE OF SOME SORT.
 IT WAS NOTED, THAT LTS ARE ON EM
 CIRCUIT, HOWEVER A BATTERY BACK UP
 FIXTURE WILL BE REQUIRED.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE BATTERY BACK-UP
 FIXTURES IN MAIN ELECTRICAL RMS AND
 ELEVATOR ROOM(S), GENERATOR AND FIRE
 PUMP ROOM. PLEASE ALSO PROVIDE
 CIRCUITING FOR THESE
 RMS.
  
 7)NOTE: NOTE #7 NO, RESPONSE MENITONS TO
 SEE E 5.1, HOWEVER NO DETAIL WAS SHOWN
 ON PLANS.
 PLEASE ALSO KNOW DETAILSHALL INCLUDE
 CURBING ALL FOUR SIDES.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE CURB DETAIL FOR
 BUS-DUCT RISER AND FLOOR PENATRATIONS.
 368.6
  
 8)NOTE: NOTE #8, OK, HOWEVER PLEASE
 CONTINUE WITH NOTE FOR ALL MIN
 CLEARENCES PER 110.26 SHALL BE MET.
 NOTE FOR PANIC HARDWARE WAS ADDED WHICH
 WAS OK.
 NOTE WAS NOT ADDED FOR ALL.
  
 ** PREVIOUS NOTE **
 PLEASSE PROVIDE NOTE ON RISER AND
 ELECTRICAL ROOM SHEETS FOR REQUIREMENTS
 FOR 110.26 FOR PANIC HARDWARE AND DOOR
 SWINGS. PLEASE SEE MIN CLEARENCE PER
 110.26
 PLEASE ALSO SEE MIN DOOR OPENING 6' WITH
 SINGLE ACCESS FOR EQUIPMENT MORE THAN
 1200A'S AND OVER 6' WIDE.
  
  
 9)NOTE:NOTE # 9, OK, CHANGED TO
 FEEDERS FROM BUS-DUCT, HOWEVER PLEASE
 SEE NEW COMMENTS FOR VAULT AND FOR
 SIZING OF SEC'S.
  
 ** PREVIOUS NOTE **
 PLEASE SEE RISER INDICATES ALL
 BUS-DUCT FROM FPL VAULT TO MAIN
 ELECTRICAL ROOM AS OVER-HEAD. PLEASE SEE
 230.70, 230.6, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTORS/ OR BUS DUCT
 PERMITTED "INSIDE THE BLDG.
 PLEASE SEE ROUTING OF BUS-DUCT APPEARS
 TO SHOW INSTALLATION INSIDE CONDO
 UNITS??
 PLEASE PROVIDE LAYOUT, REVISE TO
 UNDER-GROUND FEEDERS OR OTHER ACCEPTABLE
 MEANS.
  
 10)NOTE: NOTE #10, NO, ?? PLEASE SEE
 PLANS INDICATE THIS AS HAVING A 3-POLE
 MAIN, HOWEVER THERE IS NO INDICATION OF
 THE MANUAL MENAS OF DISCONNECT, LOCATED
 ON THE OUTSIDE. RESPONSE MENTIONS THIS
 WAS ADDRESSED IN A PREVIOUS REVISION,
 HOWEVER WE HAVE NOT SEEN ANY OTHER
 REVSIONS BEFORE THIS SUBMITTIAL. PLEASE
 SEE NEW NOTES FOR MAIN AS NOTED ON RISER
 "KEY NOTES"".
  
 ** PREVIOUS NOTES **
 PLEASE PROVIDE INFORMATION ON
 BUS -DUCT RISER MAINS. APPEARS TO SHOW
 THESE AS "SHUNT-TRIP" AND NOT CONTAINING
 A MANUAL MEANS OF DISCONNECT LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT. PLEASE SEE
 MAIN PANEL SCHEDULE(S), THESE DO NOT
 SEEM TO INDICATE A MCB.
 230.76,230.79
  
 11)NOTE: NOTE #11, OK, HOWEVER SEE NOTES
 UNDER GARAGE PERMIT FOR ROOMS.
 PLEASE ALSO PROVIDE MIN LAYUOUT , AS
 THESE CAN BE REFERENCED UNDER A SEPARATE
 PERMIT. PLEASE SEE RESPONSE MENTIONS TO
 SEE REVISED 4.1, HOWEVER ONLY THE GEN RM
 SHOWS SOME SORT OF ELECTRICAL. PLEASE
 SEE MIN FT CNADLE FOR GEN RM SHAL BE 30
 FT CANDLES, WHICH IS NOTED UNDER GARAGE
 PERMIT.
 PLEASE ALSO KNOW, THESE AREAS WHERE THE
 GARAGE IS LOCATED SHALL BE 100% COMPLETE
 AND A CO MUST BE OBTAINED BEFORE
 ISSUANCE OF ANY TCO OR CO FOR TOWER
 BUILDINGS. THIS IS ONLY ANOTE AT THIS
 TIME TO HELP WITH THE PHASING OF THE
 PROJECT.
  
 ** PREVIOUS NOTE **
 PLEASE SEE GARAGE PLANS FOR FIRE PUMP
 RM AND GEN RM ARE SHOWN BLANK?
  
 12)NOTE: NOTE #12 NO, PLEASE SEE
 REPSONSE MENTIONS TO SEE E5.2, HOWEVER
 E5.2 DOES NOT REVISE INFORMATION ON
 BUS-DUCT? PLEASE CORRELATE WITH NOTES ON
 E0.1 AS NOTES SEEM TO CHNAGE ALL
 BUS-DUCT TO COPPER.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE SPECIFIC INFORMATION ON
 BUS-DUCT, PLEASE SEE AN ALUM EQUIPMENT
 GROUNDING CONDUCTOR/ MATERIAL IS NOT
 PERMITED.
 310.2. LOCAL AMENDMENTS.
  
 13)NOTE: NOTE #13 NO, RESPONSE MENTIONS
 FOR CONTRACTOR TO SUBMIT, HOWEVER THIS
 WAS NOT DONE.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT ALL MANUFACTURE SPECS AND
 CUT SHEETS FOR GENERATOR, ATS,
 FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE ALSO SUBMIT THE SAME FOR ANYSUB
 BASE FUEL TANK.
 PLEASE KNOW, DUE TO THE INFORMATION NOT
 BEING SUBMITTED AT THIS TIME, REVIEW FOR
 SOME ITEMS FOR CODE COMPLIANCE CAN NOT
 BE DONE.
 UNABLE TO VERIFY CODE COMPLIANCE FOR
 MANY ITEMS UNDER NFPA, 20,70,101,110
 ETC.
 SOME INFORMATION IS "APECIFIED" ON PLANS
 FOR TOWER #4, HOWEVER, TOWER #3 SHOULD
 REFLECT THE SAME INFORMATION. ALL
 MANUFACTURE CUTS/SPECS ARE STILL
 REQUIRED.
  
 14)NOTE:NOTE # 14 NO, SAME NOTE.
 RESPONSE MENTIONS TO SEE REVISED,
 HOWEVER COULD NOT LOCATE INFORMATION
 NEEDED.
  
 ** PREVIOUS NOTE **
 PLEASE SEE ELECTRICAL RISER DIAGRAM DOES
 CONTAININFORMATION FOR FIRE PUMP, YET
 NOT FIRE PUMP CONTROLLER,
 SERVICE, SIZING, LOCKED ROTOR SETTINGS
 ETC.
 PLEASE COMPLETE.
 ENCASEMENT IN CONCRETE, OUTSIDE THE
 BLDGS, ETC
  
 15)NOTE: NOTE #15 OK,SEE NOTE MENTIONED
 ABOVE.
  
 16)NOTE: NOTE #16, OK, HOWEVER PLEASE
 SEE NEW COMMENT FOR H12A.
  
 ** PREVIOUS NOTE **
 PLEASE SEE A PANEL SCHEDULE FOR A PANEL
 H12B IS SUBMITTED, HOWEVER THIS PANEL
 COULD NOT BE LOCATED ON RISER
 DIAGRAM??
 PLEASE CORRELATE.
  
 17)NOTE: NOTE #17 YES AND NO, PLEASE SEE
 THE FIRST PART OF THE NOTE REQUESTED A
 TYPICAL DISCONNECT DETAIL WHICH WAS
 DONE, HOWEVER PLEASE SEE HEAT FOR AHU'S
 FOR UNITS STILL DO NOT COORELATE. PLEASE
 ALSO SEE NOTE #41
  
 ** PREVIOUS NOTE **
 PART 2)
 PLEASE CORRELATE ALL A/C KW RATINGS AND
 LOADS WITH MECHANICAL PLANS. (KW RATINGS
 ETC. )
  
  
 18)NOTE:NOTE #18 NO, PLEASE RESPONSE
 MENTIONS TO SEEE5.1 FOR REVISED PLANS,
 HOWEVER 5.1DID NOT SHOW THIS? PLEASE
 SEE A ROOM LAYOUT ON3.1 WAS LOCATED,
 HOWEVER DID NOT SEEM TO CONTAIN ALL
 REQUIRED EQUIPMENT, PANELS ETC.
  
 ** PREVIOUS NOTE **
 PLEASE SEE FIRE REVIEW NOTES
 ALSO: PLEASE PROVIDE A LAYOUT FOR
 CENTRAL STATION RM(FIRE COMMAND RM)
 SHOWING ALL DEVICES/ PANELS/ STATUS
 PANELS ETC.
 PLEASE LIST ALL ITEMS AS SPECIFIED IN
 NFPA- 101 11.8.5,
  
 19)NOTE: PLEASE SEE MOST WERE CORRECTED,
 ONLY ONE OR TWO WERE MISSING OR LOCATED
 NOT TO SPACING, THESE CAN BE REDLINED ,
 HOWEVER IF REDLINES ARE VIEWED, PLEASE
 SEE POSSIBLE AREAS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE RECEPTS MISSING PER
 210.52
 SEE REDLINED PLANS.
  
 20)NOTE:NOTE #20 OK.
  
 21)NOTE:NOTE #21 OK.
  
 22)NOTE: NOTE #22 NO, COULD NOT LOCATE
 NOTE. RESPONSE MENTIONS E0.1
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE NOTE ON PLANS FOR SMOKE
 DETECTOR PLACEMENT PER REQUIREMENTS NFPA
 -72 11.8.3.5.
  
 23) NOTE: NOTE #23 OK.:
  
 24) NOTE: NOTE #24 OK.
  
 25)NOTE: NOTE #25 OK, HOWEVER PLEASE SEE
 NEW NOTE. (MINOR CHANGE NEED FOR PANEL
 SCHEDULE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE A 70A BRKR IS BEING SHOWN FOR
 RANGE?? PLEASE SEE 210.23,422.11B
 50A RANGE RECEPT, 50A BRKR MAX.
  
 26)NOTE: PLEASE SEE PANEL SCHEDULES SEEM
 TO SHOW "A" AND "C" PHASE FOR SINLGLE
 PHASE SERVICE AND UNITS??
 PLEASE CLARIFY / ADJSUT.
 215.5
  
 27)NOTE: NOTE #27 NO, PLEASE SEE MANY
 AREAS SHWON AS LIVING RM AND CIRCUITED
 FOR SMALL APPLIANCE. PLEASE SEE AREAS
 SEEM TO HAVE IDENTIFICATION SWITCHED.
  
 ** PREVIOUS NOTE **
 PLEASE LABEL AND /OR CLARIFY "DINING"
 AREAS IN ALL UNITS.
 UNABLE TO VERIFY CIRCUITING AS DINING
 /LIVING ARE SEEMED TO BE COMBINED.'
 PLEASE SEE 210.52B1
  
 28)NOTE:OK.
  
 29)NOTE: NOTE #29, NO, PLEASE SEE
 REDLINED PLANS AS SOME AREAS FOR HALLWAY
 WALLS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE MISSING RECEPTS IN HALLWAY
 AREAS, 10' OR MORE OF CONTINUOUS
 WALL. 210.52H.
  
 30)NOTE: NOTE #30 NO, ? PLEASE SEE
 REPSONSE MENTIONS TO SEE REVISED 5.1,
 HOWEVER NO CHANGES COULD BE LOCATED TO
 PLANS.
 PLEASE ALSO SEE NO PANEL SCHEDULE ETC
 WAS SUBMITTED.?
  
 ** PREVIOUS NOTE **
 PLEASE SEE RISER SEEMS TO INDICATE A
 POOL PANEL, HOWEVER NO OTHER
 INFORMATION WAS SUBMITTED AND PANEL
 COULD NOT LOCATED ON PLANS.
 LOADS ETC.
 215.5, 220
  
 31)NOTE: OK, AS NOTED.
  
 32)NOTE: NOTE #32 NO, AS IT SEEMS NOTE
 WAS NOT COMPLETE. PLEASE SEE RESPONSE
 MENTIONS "LIGHTNING PROTECTION NOT
 REQUIRED", THIS IS TRUE AND NOTE WAS NOT
 TO REQUEST A LPS.
 PLEASE PLACE A NOTE ON "ROOF PLANS"
 WHICH STATES "ANY LIGHTNING PROTECTION
 SYSTEM INSTALLE SHALL MEET NFPA-780 AND
 SHALL BE UNDER A SEPARATE PERMIT."
 OR WORDS TO THAT AFFECT.
 SOMEHOW THE NOTE WAS NOT PRINTED AS
 TYPED?
  
 ** PREVIOUS NOTE **
 PLEASE PLACE NOTE ON "ROOF PLANS" WHICH
 WILL REQUIRE ALL LIGHTNING PROTECTION
  
  
 33)NOTE:OK.
  
 34)NOTE: OK.
  
 35)NOTE: OK.
  
 36) NOTE:OK
  
 37)NOTE: OK, HOWEVER SEE NEW NOTE.
  
 38)NOTE: OK.
  
 39)NOTE: NOTE: NO, PLEASE SEE RESPONSE
 MENTIONS TO SEE RISER E5.1? THIS COMMENT
 IS FOR JOBSITE SPEC BOOKS.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT "SPEC BOOKS' FOR REVIEW OF
 PROJECT.
 THESE WOULD CONTAIN JOBSITE SPECS.
  
 40)NOTE:OK.
  
 41)NOTE:NOTE #41 NO, PLEASE SEE
 MECHNICAL PLANS AS NOTED ABOVE FOR KW
 RATINGS INDICATED.
 PLEASE SEE THIS COMMENT WAS FOR UNITS
 AND SOME IN HOUSE AREAS.
 YES, THE OCP WAS SHOWN CORRECT AT 125%
 ON ELECTRICAL PANEL SCHEDULE FOR THE KW
 HEAT WHICH WAS SHOWN. PLEASE KNOW, THE
 COMMENT WAS BASED ON KW AS INDICATED ON
 MECHANICAL PLANS AND NOTE #17.
  
 ** PREVIOUS NOTE **
 PLEASE SEE MIN OCP FOR AHU HEAT
 TO BE 125%. 424.3B
 SHOWS 50A OCP.
  
 42)NOTE: OK.
  
  
 ***************************************
 *************** NEW NOTES *************
  
 1) NOTE: PLEASE SEE "KEY NOTE" #8 WHICH
 NOW MENTIONS A 3000A MCB FOR BUS RISER
 "ML", HOWEVER SEC'S ARE ONLY RATED FOR
 2520A'S. PLEASE SEE 240.4C FOR DEVICES
 RATED OVER 800A'S.
 PLEASE ALSO CORRELATE AS BUS-DUCT RISER
 IS ONLY RATED @ 2500A'S.
 240.4,310.16 ETC.
 215.5
  
 2) NOTE: PLEASE SEE H12A, PLANS NOW SHOW
 H12B BEING FED FROM THIS, PLEASE
 INDICATE IF "FEED THRU LUGS" OR IF OCP
 AND FEEDERS ARE BEING INSTALLED.
 215.5
  
 3) NOTE: PLEASE INDICATE ON PANEL
 SCHEDULE ALL APPLIANCES AS GAS WHERE
 APPLICABLE. "GAS RNAGE", GAS WH" ETC.
  
 4) NOTE: PLEASE SEE A GORUNDING NOTE #19
 ON RISER AT GENERATOR MENTIONS TO SEE
 KEY NOTE FOR THIS, HOWEVER #19 ON KEY
 NOTES IS BLANK?
  
 5) NOTE: PLEASE SEE 7.1 AS THIS SEEM TO
 CONTAIN A "MISPRINT" FOR THE ATS IN THE
 MAIN ELECTRICAL ROOM. THIS IS SHOWN AS
 ATS-3, HOWEVER THIS IS TOWER #4.
  
 6) NOTE: PLEASE OBTAIN A LETTER OF
 APPROVAL FROM FPL ( MR. BILL HARTIGAN
 FOR APPROVAL AND CHANGE OF FPL VAULT AS
 SHOWN.
 PLEASE ALSO SEE NOTES FOR TOWER #3 FOR A
 SIMILAR COMMENT.
  
  
  
 ** PLEASE KNOW, MANY OF THE ABOVE ITEMS
 ARE "REDLINED" AT LOCATIONS ON PLANS FOR
 NOTES.
  
 ** PLEASE KNOW, A RESPONSE LETTER IN
 TYPE WRITTEN FORM WILL HELP IN RESPONSES
 TO ELECTRICAL COMMENTS.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ************************************
  
 ** PLEASE KNOW IT WAS REQUESTED ON
 PREVIOUS REVIEW BEFORE RESUBMITTING
 PLANS FOR ALL OLD/VOIDED SHEETS TO BE
 COMPLETELY REMOVED FROM SETS. PLEASE SEE
 THIS WAS NOT DONE AND ALL NEW SHEETS
 WERE INSERTED INTO NEW SETS. PLEASE
 KNOW, WE ONLY REQUIRE "ONE" COPY OF THE
 OLD REMOVED SHEETS. THESE SHOULD BE
 BUNDLED INTOONE SET AND SUBMITTED
 ALONG WITH THE THREE NEW REVISED SETS.
 PLEASE KNOW, THIS WILL EFFECT THE PLAN
 REVIEW PROCESS AND HELP TO EXPEDITE
 PROJECT.
  
 ***********************************
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
2006-04-28 00:00:00REVIEW IN PROGRESS.
2006-04-27 00:00:00IN ELEC FOR REVIEW.
 REVIEW TO CONTINUE ON 4/28

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-28 Cont ID  
Sent By dpalmer Date 2005-09-28 Time 19:20 Rev Time 12.00
Received By dpalmer Date 2005-09-11 Time 11:25 Sent To  
Notes
2005-09-29 00:00:00SAIL CLUB TOWER #4
  
 **** UNSAT ****
  
  
 1)NOTE: PLEASE SEE CODE REFERENCED ON
 PLANS LIST THE 1999 NEC. PLEASE KNOW, AS
 OF JULY 1ST 2003, THE STATE ADOPTE DTHE
 2002 NEC.
 PLEASE ALSO SEE WE ARE UNDER THE 2003
 NFPA-101 AND 2002 NFPA-72
 PLEASE ADJUST.
  
 2)NOTE: PLEASE SEE BLDG /FIRE REVIEW
 COMMENTS FOR STAIR TOWER EXITING WHICH
 WILL AFFECT ELECTRICAL LAYOUT.
 EXITS BACK INTO HALL WAY AREAS IN FRONT
 OF UNITS.
 PLEASE ALSO SEE POSSIBLE NOTES FOR
 EXITING OUTSIDE TRASH ROOM.
 PLEASE SEE BLDG REVIEW FOR STAIR TOWER
 #2 AND SWING OF DOOR AND PATH OF EGREES
 TRAVEL.
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE SOME AREAS WHICH ELECTRICAL
 FIXTURES SEEM TO BE MISSINGTHIS.
 PLEASE ALSO SEE CIRCUITING FOR UNITS.
 PLEASE KNOW, A "TYPICAL" UNIT LAYOUT MAY
 BE PROVIDED, HOWEVER A LAYOUT WOULD BE
 REQUIRED FOR EACH UNIT TYPE, INCLUDING
 STUDIO UNIT.
 CIRCUITING FOR SOME UNITS/ITEMS CAN NOT
 BE VERIFIED AT THIS TIME.
  
 4)NOTE: PLEASE PROVIDE PHOTO-METRICS FOR
 STAIR TOWERS ON NORMAL PWR AND STAND-BY.
 ALONG WITH WALK AREAS.
 PLEASE SEE STAIR TOWERS UNDER NORMAL PWR
 SHALL MEET A MIN OF 10FT CANDLES. PLEASE
 SEE ARES FOR HALLS ETC ARE PERMITTED TO
 BE LESS. .
 PLEASE SEE NFPA-101 7.8.1.3,7.9.2.1
  
 5)NOTE:
 PLEASE KNOW, BATTERY BACK FIXTURES WILL
 BE REQUIRED AT EVERY OTHER LEVEL(MIN).
 PLEASE SEE LS 101 WHICH MENTIONS THE
 TRIPPING/THROW OF A SINGLE BRKR SAHLL
 NOT LEAVE ANY EGRESS AREA IN TOTAL
 DARKNESS. PLEASE CALL ELECTRICAL PLAN
 REVIEW AND FIRE MARSHALS OFFICE TO GO
 OVER OPTIONS PERMITTED.
 A BATTERY BACK-UP FIXTURE AT EVERY OTHER
 LEVEL WILL SATISFY FIRE MARSHAL'S OFFICE
 AND AHJ.
 PLEASE BE SURE TO MEET THE MIN OF 1
 FT/CANDLE UNDER EM.
 PLEASE BE SURE TO SEE PREVIOUS NOTE #4
 FOR LIGHTING LEVELS.(MIN)
  
 6)NOTE: PLEASE PROVIDE BATTERY BACK-UP
 FIXTURES IN MAIN ELECTRICAL RMS AND
 ELEVATOR ROOM(S), GENERATOR AND FIRE
 PUMP ROOM. PLEASE ALSO PROVIDE
 CIRCUITING FOR THESE
 RMS.
  
 7)NOTE: PLEASE PROVIDE CURB DETAIL FOR
 BUS-DUCT RISER AND FLOOR PENATRATIONS.
 368.6
  
 8)NOTE: PLEASE PROVIDE NOTES ON RISER
 AND ELECTRICAL ROOM SHEETS FOR
 REQUIREMENTS OF 110.26 FOR PANIC
 HARDWARE AND DOOR SWINGS.
 PLEASE SEE MIN CLEARENCE PER 110.26
 PLEASE ALSO SEE MIN DOOR OPENING 6' WITH
 SINGLE ACCESS FOR EWUIPMENT MORE THAN
 1200 A'S AND OVER 6' WIDE.
  
 9)NOTE: PLEASE SEE RISER INDICATES ALL
 BUS-DUCT FROM FPL VAULT TO MAIN
 ELECTRICAL ROOM AS OVER-HEAD. PLEASE SEE
 230.70, 230.6, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTORS/ OR BUS DUCT
 PERMITTED "INSIDE THE BLDG.
 PLEASE SEE ROUTING OF BUS-DUCT APPEARS
 TO SHOW INSTALLATION INSIDE CONDO
 UNITS??
 PLEASE PROVIDE LAYOUT, REVISE TO
 UNDER-GROUND FEEDERS OR OTHER ACCEPTABLE
 MEANS.
  
 10)NOTE: PLEASE PROVIDE INFORMATION ON
 BUS -DUCT RISER MAINS. APPEARS TO SHOW
 THESE AS "SHUNT-TRIP" AND NOT CONTAINING
 A MANUAL MEANS OF DISCONNECT LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT. PLEASE SEE
 MAIN PANEL SCHEDULE(S), THESE DO NOT
 SEEM TO INDICATE A MCB.
 230.76,230.79
  
 11)NOTE: PLEASE SEE GARAGE PLANS FOR
 FIRE PUMP RM AND GEN RM ARE SHOWN BLANK?
  
 12)NOTE: PLEASE PROVIDE SPECIFIC
 INFORMATION ON BUS-DUCT, PLEASE SEE AN
 ALUM EQUIPMENT GROUNDING CONDUCTOR/
 MATERIAL IS NOT PERMITED.
 310.2. LOCAL AMENDMENTS.
  
 13)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS AND CUT SHEETS FOR GENERATOR, ATS,
 FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE ALSO SUBMIT THE SAME FOR ANYSUB
 BASE FUEL TANK.
 PLEASE KNOW, DUE TO THE INFORMATION NOT
 BEING SUBMITTED AT THIS TIME, REVIEW FOR
 SOME ITEMS FOR CODE COMPLIANCE CAN NOT
 BE DONE.
 UNABLE TO VERIFY CODE COMPLIANCE FOR
 MANY ITEMS UNDER NFPA, 20,70,101,110
 ETC.
 SOME INFORMATION IS "APECIFIED" ON PLANS
 FOR TOWER #4, HOWEVER, TOWER #3 SHOULD
 REFLECT THE SAME INFORMATION. ALL
 MANUFACTURE CUTS/SPECS ARE STILL
 REQUIRED.
  
 14)NOTE: PLEASE SEE ELECTRICAL RISER
 DIAGRAM DOES CONTAININFORMATION
 FOR FIRE PUMP, YET NOT FIRE PUMP
 CONTROLLER,
 SERVICE, SIZING, LOCKED ROTOR SETTINGS
 ETC.
 PLEASE COMPLETE.
 ENCASEMENT IN CONCRETE, OUTSIDE THE
 BLDGS, ETC
  
 15)NOTE: PLEASE SEE AREA FOR GARAGE
 CONTAINING THE LOCATION OF FIRE PUMP AND
 GENERATOR WILL BE REQUIRED TO BE
 SUBITTED FOR PERMIT AND REVIEW.
 PLEASE SEE LOCATIONS FOR FIRE
 SEPARATIONS, ACCESS, LIGHTING, ETC CAN
 NOT BE REVIEWED AT THIS TIME.
  
 16)NOTE: PLEASE SEE A PANEL SCHEDULE FOR
 A PANELH12B IS SUBMITTED, HOWEVER THIS
 PANEL COULD NTO BELOCATED ON RISER
 DIAGRAM??
 PLEASE CORRELATE.
  
 17)NOTE: PLEASE PROVIDE DISCONNECTING
 MEANS FOR ALL A/C EQUIPMENT AT ROOF TOP
 LEVEL. A"TYPICAL" DETAIL MAY BE GIVEN
 FOR THESE.440.11
 PLEASE SHOW A "TYPICAL DETAIL SHOWING
 MOUNTING ETC.
  
 PLEASE CORRELATE ALL A/ KW RATINGS AND
 LOADS WITH MECHANICNAL PLANS . (KW
 RATINGS ETC).
  
 18)NOTE: PLEASE SEE FIRE REVIEW NOTES
 ALSO: PLEASE PROVIDE A LAYOUT FOR
 CENTRAL STATION RM(FIRE COMMAND RM)
 SHOWING ALL DEVICES/ PANELS/ STATUS
 PANELS ETC.
 PLEASE LIST ALL ITEMS AS SPECIFIED IN
 NFPA- 101 11.8.5,
  
 19)NOTE: PLEASE SEE RECEPTS MISSING PER
 210.52
 SEE REDLINED PLANS.
  
 20)NOTE: PLEASE CALRIFY THE "P" LOCATED
 NEXT TO SMOKE DETECTORS?
 THIS CORRELATING SYMBOL COULD NOT BE
 LOCATED ON PLANS.
  
 21)NOTE: PLEASE VERIFY CIRCUITING OF
 LAUNDRY RM/ WASHER CIRCUIT.
 PLEASE SEE 210.11C2,210.52F,220.16
 PLEASE ALSO SEE MIN 1500VA.
 PLEASE VERIFY LOAD FOR WASHER.
  
 22)NOTE:PLEASE PROVIDE NOTE ON PLANS
 FOR SMOKE DETECTOR PLACEMENT PER
 REQUIREMENTS NFPA -72 11.8.3.5.
  
 23): PLEASE PROVIDE NOTE FOR ALL
 ELECTRICAL DEVICES TO BE INSTALLED PER
 FAIR HOUSING ACT REGULATIONS, (FHAR) 24
 CFR 100.205
  
 24)NOTE: PLEASE SEE 210.52C1 FOR SOME
 MISSING KITCHEN COUNTERSPACE RECEPTS.
 PLEASE ALSO SEE COUNTERSPACE APPEARS TO
 SHOW A DEDICATED CIRCUIT (19) FOR
 MICROWAVE WHICH ALSO APPEARS TO BE THE
 RECEPT FOR KITCHEN COUNTERSPACE?
 IF THE MICROWAVE IS A DEDICATED RECEPT,
 THEN AN ADDTIONAL GFI WOULD BE REQUIRED.
 210.8A16.
  
 25)NOTE: PLEASE SEE A 70A BRKR IS BEING
 SHOWN FOR RANGE??
 PLEASE SEE 210.23,422.11B
 50A RANGE RECEPT, 50A BRKR MAX.
  
 26)NOTE: PLEASE SEE PANEL SCHEDULES SEEM
 TO SHOW "A" AND "C" PHASE FOR SINLGLE
 PHASE SERVICE AND UNITS??
 PLEASE CLARIFY / ADJSUT.
 215.5
  
 27)NOTE: PLEASE LABEL AND /OR CLARIFY
 "DINING" AREAS IN ALL UNITS.
 UNABLE TO VERIFY CIRCUITING AS DINING
 /LIVING ARE SEEMED TO BE COMBINED.'
 PLEASE SEE 210.52B1
  
 28)NOTE: PLEASE SEE 210.52D FOR SOME
 UNITS MISSING GFI'S WITH IN 3' OF LAV'S.
 PLEASE ALSO SEE A GFI MAY NOT PERMITTED
 ON THE OTHER SIDE OF A LAV TO MEET
 210.52D (3').
 GFI 'S MAY BE MOVED IN BETWEEN BOTH
 LAV'S OR AN ADDITIONALRECEPT MAY BE
 ADDED.
  
 29)NOTE: PLEASE SEE MISSING RECEPTS IN
 HALLWAY AREAS, 10' OR MORE OF CONTINUOUS
 WALL.
 210.52H.
  
 30)NOTE: PLEASE SEE RISER SEEMS TO
 INDICATE A POOL PANEL, HOWEVER NO OTHER
 INFORMATION WAS SUBMITTED AND PANEL
 COULD NOT LOCATED ON PLANS.
 LOADS ETC.
 215.5, 220
  
 31)NOTE: PLEASE VERIFY BATH CIRCUITS
 BEING SHOWN WITH ARC FAULT PROTECTION??
 210.8 REQUIRES GFI PROTECTION FOR BATHS
 AND 210.12 ARC FAULT PROTECTION FOR
 BEDROOM CIRCUITS?
 THIS IS ONLY A NOTE:
  
 32)NOTE: PLEASE PLACE NOTE ON "ROOF
 PLANS" WHICH WILL REQUIRE ALL LIGHTNING
 PROTECTION
  
  
 33)NOTE: PLEASE IDICATE ON PLANS/RISER
 IF GENERATOR WILL BE A "SEPARATELY
 DERIVED SYSTEM" OR A " NON SEPARATELY
 DERIVEDSYSTEM.
 IF SD, PLEASE INCLUDE GROUNDING
 ELECTRODE SYSTEM PER 250.30
  
 34)NOTE: PLEASE INDICATE IF PANELS EH2A-
 EH9A ARE FEED THRU LUGS OR DOES EACH
 PANEL CONTAIN OCP FOR EACH.?
 PLEASE ALSO SEE PANELS H5A-9, ETC.
 215.5
  
 35)NOTE: PLEASESEE PANELS EH2-EH9 ARE
 SHOWN ON RISER AND ESBA BEING FED W/
 225A OVER CURRENT PROTECTION, HOWEVER
 EACH OF THESE ARE SHOWN AS 125A ON PANEL
 SCHEDULE(S). PLEASE CORRELATE.
 215.5
  
 36) NOTE:PLEASE INDICATE IF EH2A- 9 ARE
 PANELS CONTAING "FEED-THRU" LUGS OR IS
 THERE OCP IN EACH OF THESE PANELS
 FEEDING THRU TO OTHER PANELS?
 215.5
  
 37)NOTE: PLEASE CLARIFY NOTES # 5 AND #6
 ON GROUNDING RISER?
 250.50
  
 38)NOTE: PLEASE SEE RISER INDICATES
 PANEL H12A FEEDING "ELEV PANEL" WITH
 CIRCUITS 20,22,24, HOWEVER PLEASE SEE
 PANEL H12A, DOES NOT SHOW ANY FEED TO
 "ELEVATOR PANEL".
 PLEASE CORRELATE.215.5
 PLEASE ALSO ADJUST LOAD CALCULATIONS FOR
 ADDITIONAL PANEL WHEN ADDED.
  
 39)NOTE: PLEASE SUBMIT "SPEC BOOKS' FOR
 REVIEW OF PROJECT.
 THESE WOULD CONTAIN JOBSITE SPECS.
  
 40)NOTE: PLEASE BE SURE ALL CONTINUOUS
 LOADS ARE SHOWN AT 125%.
 215.3,230.42 ETC.
  
 41)NOTE: PLEASE SEE MIN OCP FOR AHU HEAT
 TO BE 125%. 424.3B
 SHOWS 50A OCP.
  
 42)NOTE: PLEASE HAVE PANEL H2A INDICATE
 ALSO IF "FEED-THRU" LUGS.
  
 ** PLEASE SEE THAT NO PLANS, PERMIT
 APPLICATION ETC WAS SUBMITTED FOR GARAGE
 BLDGS.
  
 ** PLEASE KNOW, MANY OF THE ABOVE ITEMS
 ARE "REDLINED" AT LOCATIONS ON PLANS FOR
 NOTES.
  
 ** PLEASE KNOW, A RESPONSE LETTER IN
 TYPE WRITTEN FORM WILL HELP IN RESPONSES
 TO ELECTRICAL COMMENTS.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO "REMOVE" ALL OLD
 VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO THE COMPLETED SETS
 FOR REVIEW AND STAMPING.
  
 ** PLEASE SEE BLDG REVIEW COMMENTS WHICH
 WILL REQUIRE ALL PRODUCT APPROVALS,
 SUBMITTALS ETC TO BE DETACHED FROM
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-09-28 00:00:00PLANS IN "F" STATUS, NOTES TO FOLLOW.
2005-09-11 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW.
 REVIEWS IN PROGRESS .

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By mamini Date 2005-08-23 Time 10:55 Rev Time 0.50
Received By mamini Date 2005-08-23 Time 10:55 Sent To  
Notes
2005-08-23 00:00:00FAILED:
  
 1. PLEASE SEE REVIEW NOTES UNDER PERMIT
 # 05080676.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-06-13 Cont ID  
Sent By mwennerg Date 2006-06-13 Time 14:12 Rev Time 0.00
Received By mwennerg Date 2006-06-13 Time 14:12 Sent To  
Notes
2006-06-13 00:00:00***DENIED***
  
 PLEASE NOTE THAT ARCHITECTUAL RESPONSE
 LETTER WAS NOT FOUND WITH THIS
 SUBMITTAL. THE FOLLOWING ADDRESSES
 RESPONSE LETTER FROM KAMM CONSULTING.
  
 1) OK
  
 2) NOTE IS STILL ON PLANS. PLEASE
 CORRECT OR REMOVE.
  
 3) PLEASE INDICATE THE TOTAL BUILDING
 COVEREAGE THAT IS EXPECTED BY A 1000 GPM
 FIRE PUMP.
  
 4) OK
  
 5-15) NO ARCHITECT'S RESPONSE LETTER
 FOUND.
  
 16) OK
  
 17) OK
  
 18) OK
  
 19) OK
  
 20) NO MENTION OF LOCK AND CHAIN IN
 ADDITION TO TAMPER SWITCHES.
  
 21) HYDRAULIC CALCULATIONS WILL BE
 REQUIRED AT THE TIME OF FIRE SPRINKLER
 PERMITTING.
  
 22) OK
  
 23) OK
  
 24) OK
  
 25) OK
  
 26) NO MENTION REGARDING SURVIVABILITY
 REQUIREMENT ON FA0.1.
  
 27) PLEASE NOTE THAT A HIGHRISE BUILDING
 WITH ENCLOSED STAIRWELLS IS REQUIRED TO
 HAVE STAIRWELL PRESSURIZATION.
  
 28) NO RESPONSE LETTER.
  
 31-36) NO RESPONSE LETTER FOUND.
  
 PLEASE NOTE THAT IT WOULD HELP EXPEDITE
 THIS PROCESS IF RESPONSE LETTERS
 INDICATING SHEET #'S ARE INCLUDED WITH
 SUBMITTALS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-01 Cont ID  
Sent By mwennerg Date 2005-12-01 Time 15:15 Rev Time 0.00
Received By mwennerg Date 2005-12-01 Time 15:15 Sent To  
Notes
2005-12-01 00:00:00******DENIED******
  
 TOWER #4
  
 1) FIRE HYDRANTS TO BE WET AND
 OPERATIONAL PRIOR TO, DURING AND AFTER
 CONSTRUCTION
  
 2) FOR REFERENCE, HIGHRISE IS DEFINED AS
 A BUILDING GREATER THAN 75' IN HEIGHT.
 SHT A-1.1.2
  
 3) PLEASE NOTE THAT THE FIRE PUMP IS
 SHOWN IN THE PARKING GARAGE THAT ISN'T
 PART OF THIS PHASE. ADDITIONAL
 INFORMATION REGARDING WHAT ARRANGEMENT
 BY THIS OFFICE HAS BEEN ACCEPTED IS
 REQUIRED. THE FIRE PUMP SHALL BE A
 MINIMUM OF 1250 GPM FOR A HIGHRISE
 BUILDING. PLEASE CONTACT THE BUREAU OF
 FIRE PREVENTION AT (561) 804-4724.
  
 4) BUILDING TO MEET APPLICABLE BUILDING
 CODES AND NFPA CHAPTER 11 REQUIREMENTS
 FOR HIGHRISE BUILDINGS.
  
 5) PLEASE VERIFY THAT NO COOKING WILL
 OCCUR IN THE CATERING KITCHEN.
  
 6) EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 7) NOTE REGARDING THE ADDRESS NUMBER IS
 ACKNOWLEDGED. PLEASE ILLUSTRATE ON
 ELEVATION SHEETS FOR FUTURE REFERENCE
 AND FURTHER PLAN REVIEW.
  
 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS
  
 9) KNOX BOXES WILL BE REQUIRED.
  
 10) PLEASE INDICATE THE OCCUPANT LOAD
 CALCULATIONS FOR THE HOME THEATER AND
 FITTNESS CENTER.
  
 11) PLEASE PROVIDE THE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IE
 CLASS A,B OR C.
  
 12) TACTILE SIGNAGE IS REQUIRED AT EXIT
 DOORS.
  
 13) PLEASE INDICATE IF ELEVATORS ARE
 STRETCHER ACCESSIBLE.
  
 14) SIGNS ARE REQUIRED IN STAIRWELLS
 INDICATING TOP, BOTTOM, FLOOR NUMBER AND
 ROOF ACCESS.
  
 15) WARNING SIGNS ARE REQUIRED IN
 ELEVATOR LOBBIES.
  
 16) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM WHEN
 ACTIVATED.
  
 17) FIRE ALARM SYSTEM TO BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 18) AS INDICATED ON PLANS, SEPARATE SHOP
 DRAWINGS AND PERMITS ARE REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 19) UL CERTIFICATION TO BE PROVIDED AT
 THE TIME OF THE FIRE ALARM ACCEPTANCE
 TEST.
  
 20) IN ADDITION TO ELECTRONIC SWITCHES,
 DOUBLE CHECK DETECTOR ASSEMBLY TO BE
 SECURED WITH LOCK AND CHAIN.
  
 21) HYDRAULIC CALCULATIONS WILL BE
 REQUIRED WHEN APPLYING FOR THE FIRE
 SPRINKLER PERMIT.
  
 22) FDV ON STANDPIPE SHALL BE 2 1/2" TO
 1 1/2" REDUCER WITH CHAIN.
  
 23) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHED 3 STORIES OR
 30" IN HEIGHT.
  
 24) NO FIRE SPRINKLER COVERAGE NOTED TO
 COVERED WALKWAYS AND PORTE COCHERE.
  
 25) PLANS DON'T SHOW ANY EXIT SIGNS OR
 EMERGENCY LIGHTING FACILITIES IN COMMON
 AREA MEANS OF EGRESS. PLEASE SHOW ON
 ELECRICAL AND LIFE SAFETY SHTS.
  
 26) FIRE ALARM SYSTEM TO MEET THE
 SURVIVABILITY REQUIREMENTS IN ACCORDANCE
 WITH NFPA 72.
  
 27) THE ANTICIPATED STACK EFFECT NOTE
 WORDING SHALL BE ADDED TO THE MECHANICAL
 SHTS.
  
 28) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 29) ELEVATORS TO COMPLY WITH BUILDING
 AND FIRE CODES AND ASME/ANSI A 17.1.
  
 30) FIRE SPRINKLER COVERAGE DOESN'T
 EXTEND TO ELEC/PHONE ROOMS.
  
 31) NO CUTTING OR WELDING TO OCCUR
 WITHOUT APPROVAL OF FIRE PREVENTION
 BUREAU AND COMPLIANCE WITH NFPA 51B.
  
 32) EMERGENCY LIGHTING IS NOT SHOWN IN
 ELEC/PHONE ROOMS ON UPPER FLOORS.
  
 33) A MINIMUM OF (2) FIRE DEPARTMENT
 CONNECTIONS ARE REQUIRED ON HIGHRISE
 BUILDINGS.
  
  
 34) FIRE PUMP SHALL MEET THE
 REQUIREMENTS OF NFPA 20 AND MANUFACTURER
 SPEC SHEETS REQUIRED.
  
 35) ALL SHAFTS LARGE ENOUGH FOR PERSONS
 TO FALL INTO MUST BE MARKED SHAFTWAY IN
 6" LETTERS.
  
 36) LOCKING KNOX BOX CAPS ARE REQUIRED
 ON THE FIRE DEPARTMENT CONNECTIONS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-05-12 Cont ID  
Sent By kstevens Date 2006-05-12 Time 18:52 Rev Time 0.00
Received By kstevens Date 2006-05-11 Time 14:31 Sent To  
Notes
2006-05-12 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PLUMBING REVIEW:
  
 27. THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CUT SECTIONS NOT SHOWN
 AND MOST RISERS NOT SHOWN.
 ***RESPONSE NOTED, BUT LENGTHS OF CUT
 SECTIONS NOT SHOWN.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ***RESPONSE NOTED, BUT CALCULATIONS FOR
 CLOTHES DRYER ROOMS NOT SUBMITTED.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT NO MANUF. SHEETS
 SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ***RESPONSE NOTED, BUT VOIDED SHEETS NOT
 REMOVED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-07 Cont ID  
Sent By adarroug Date 2006-03-07 Time 09:30 Rev Time 0.00
Received By adarroug Date 2006-03-07 Time 09:30 Sent To  
Notes
2006-03-30 00:00:00TO "COMM" BD#7
2006-03-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-21 Cont ID  
Sent By adarroug Date 2005-11-17 Time 08:39 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 08:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-04-13 Cont ID  
Sent By pkrauss Date 2006-04-13 Time 12:11 Rev Time 0.00
Received By pkrauss Date 2006-04-13 Time 11:30 Sent To  
Notes
2006-04-13 00:00:00DENIED:TOWER #4
 REPSONSE TO COMMENTS DATED 11/17/05.
 COMMENT #8
 PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS (IF A CONFINED SPACE) FOR
 THE GAS DRYERS LOCATED IN THE LAUNDRY
 ROOM/CLOSET.2004 FMC CHAPTER 7.
  
 RESPONSE INDICATES THE ARCHITECTURAL
 DRAWINGS WERE REVISED TO REFLECT LOUVER
 ON DOOR.PLEASE INDICATE THE SPECIFIC
 PLAN SHEET.PLAN SHEET T-4 A7.2.1(DOOR
 SCHEDULE) DOES NOT REFLECT THIS CHANGE.
  
 COMMENT #12
 PLUMBING PLAN SHEET P6.4 INDICATES
 GAS APPLICANCES, SPECIFICALLY THE WATER
 HEATER.PLEASE CLARIFY VENTING A GAS
 WATER HEATER LOCATED IN AN AHU CLOSET.
  
 REPONSE REFERS TO PLAN SHEET P0.1,
 DETAIL FOR THE GAS WATER HEATER IN THE
 AHU CLOSET IS NOT SHOWN.PER 2004 FMC
 602.1, FUEL FIRED APPLIANCES SHALL NOT
 BE INSTALLED WITHIN A PLENUM.
  
  
  
 NEW COMMENT:
 1.PLAN SHEET M7.1 INDICATES RETURN AIR
 TO AHU WILL BE THROUGH A LOUVERED GRILLE
 IN THE WALL.THE AHU CLOSET WILL BE A
 PLENUM.THE A/C CLOSET DOOR SHALL BE
 NONCOMBUSTIBLE PER 2004 FMC 602.2.1.
 PLEASE PROVIDE SUBMITTAL.
  
 2.PLEASE NOTE, SHOULD DRYER EXHAUST
 GREATER THAN 200 CFM, MAKEUP AIR
 SHALL BE PROVIDED.
  
 3.PROVIDE ADDITIONAL INFORMATION FOR
 THE VENTILATION/PRESSURIZATION OF THE
 EXIT STAIRWAY.SHOW COMPLIANCE WITH
 2004 FMC 909.20 & 1019.1.8.
  
 4.PLEASE NOTE, SPRINKLER SYSTEMS
 REQUIRED FOR TRASH CHUTES & DRYER
 EXHAUST (SUB-DUCT) PER 2004 FBC
 903.2.10.2 & 903.2.12.1.
  
 5.PLAN SHEET M2.1, RESPONSE INDICATES
 THE INTAKE DUCT FOR THE TOILET & DRYER
 EXHAUST CHASE IS FOR THE MAKE-UP AIR.
 PLEASE CLARIFY THE FOLLOWING:
 1) SIZE OF THE BRANCH DUCT.
 2) PLEASE CLARIFY THE PENETRATION
 BETWEEN THE RESIDENCE AND THE WALKWAY.
 DOES THIS HAVE THE PENETRATION HAVE A
 FIRE, SMOKE OR BOTH RATING? SHOW
 COMPLIANCE WITH 2004 FBC 716.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-17 Cont ID  
Sent By pkrauss Date 2005-11-17 Time 16:28 Rev Time 0.00
Received By pkrauss Date 2005-11-10 Time 13:46 Sent To  
Notes
2005-11-17 00:00:00DENIED:2004 FBC / TOWER 4
 1.PLANS SHEET M0.1, MECHANICAL NOTES
 REFERENCE 2001 FBC & STANDARDS THAT ARE
 APPLICABLE TO THIS SUBMITTAL.PLEASE
 REVISE.
  
 2.PLAN SHEET M2.1 DETAIL SECTION A-A,
 PLEASE ANNOTATE SUFFICIENT CLEARANCE FOR
 MAINTENANCE, SERVICE, & REPLACEMENT TO
 ALL EQUIPMENT INDCLUDING FIRE DAMPERS IS
 REQUIRED PER 2004 FMC 306.1.
  
 3.PLAN SHEET M2.1 KEY NOTE 11 'PROVIDE
 ACCESS PANELD FOR AHU.SEE ARCH PANELS
 FOR DETAILS.'THIS IS INDICATED IN THE
 MASTER BEDRM IN UNIT J104.PLEASE
 CLARIFY AHU LOCATION & WHAT AREA IT
 SERVES.PLEASE NOTE, ACCESS TO
 EQUIPMENT FOR THE COMMON AREAS SHALL NOT
 BE OBTAINED BY ENETERING A PRIVATE
 RESIDENCE.
  
 4.PLAN SHEET M2.1 EXHAUST DUCT FROM
 UNIT J THAT PENETRATES THE TENENANT
 SEPARATION WALL TO THE FITNESS CENTER &
 HOME THEATER AREAS SHALL COMPLY WITH
 2004 FMC 501.4, 504.2 & 603.3, FOR
 REQUIRED GAUGE OF GALVANIZED DUCT
 PENTETRATING RATED WALL/PARTITION.
  
 5.PLAN SHEET M2.2 DETAIL 1 DOES NOT
 INDICATE AUXILIARY DRAIN PAN.EQUIPMENT
 SCHEDULE (M6.1) INDICATES AUXILIARY
 DRAIN PAN W/FLOAT SWITCH.
  
 6.PLEASE NOTE THE AHU DETAIL 1 ON PLAN
 SHEET M2.2 INDICATES NO CEILING IN THE
 AHU CLOSET & THE DOOR IS TO HAVE
 'GASKET, SEALED'.PLAN SHEET M7.1
 DETAIL #2 (AHU) INDICATES R/A THROUGH
 LOUVERED DOOR, & NO DRAIN PAN.PLEASE
 CORRELATE PLANS.
  
 7.PLAN SHEET M2.2 DETAIL 2 SHOWS
 LAYOUT ABOVE THE CEILING.PLEASE NOTE
 DUCT SHALL HAVE ENOUGH CLEARANCE FOR
 ASSEMBLY, INSPECTION , CLEANING &
 MAINTENANCE PER 2004 FMC 603.1 &
 603.1.3.
  
 8.PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS (IF A CONFINED SPACE) FOR
 THE GAS DRYERS LOCATED IN THE LAUNDRY
 ROOM/CLOSET.2004 FMC CHAPTER 7.
  
 9.PLAN SHEET M2.5 KEY NOTE #4 'SEE
 ARCHITECTURAL PLANS FOR ACCESS TO UNDER
 FLOOR AREA.PLEASE CLARIFY THE
 ARCHITECTURAL PLAN SHEET THAT DETAILS
 THE ACCESS.
  
 10.PLAN SHEET M6.2 REFERENCES ASHRAE
 62-89, THIS SHOULD READ 62-01.
  
 11.PLAN SHEET M6.2 OUTSIDE AIR
 CALCULATIONS ARE GIVEN FOR COMMON AREAS
 ONLY.PLEASE PROVIDE CALCULATIONS FOR
 THE RESIDENT UNITS PER TABLE 403.3 AS
 REQUIRED FOR R-2 OCCUPANCIES.
  
 12.PLUMBING PLAN SHEET P6.4 INDICATES
 GAS APPLICANCES, SPECIFICALLY THE WATER
 HEATER.PLEASE CLARIFY VENTING A GAS
 WATER HEATER LOCATED IN AN AHU CLOSET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-05-12 Cont ID  
Sent By kstevens Date 2006-05-12 Time 17:53 Rev Time 0.00
Received By kstevens Date 2006-05-11 Time 14:31 Sent To  
Notes
2006-05-12 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 1. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED & DATED AS
 REQUIRED BY FS. SECTION 106.1.
 ***RESPONSE NOTED, BUT SEE BOUNDRY
 SURVEY, SHTS PP1 OF 9 THRU PP9 OF 9,
 SHTS LA-POOL-1 THRU LA-POOL-4, AND SHTS
 LA-FW-1 THRU LA-FW-6.
  
 2. INFORMATIONAL ONLY.
  
 3. SHT T-4 A2.4.1 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SHOW THE SQUARE FOOTAGE FOR EACH AREA &
 SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ALONG WITH THE AREA
 OF ROOF THAT DRAINS ONTO THE ROOF FROM
 ABOVE FOR EACH AREA IN CALCLATIONS.
 SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS.
 ***RESPONSE NOTED, BUT THE AREAS FROM
 ROOFS ABOVE HAVE NOT BEEN ADDRESSED FOR
 THE MECHANICAL RM ROOF, THE HIP ROOFS,
 THE OCTAGON ROOF, OR THE STAIRWELL ROOF.
  
 4. SHTS T-4 A4.1.1 THRU T-4 A4.1.10
 UNITS A, B, C, D, E, H, F, G & K SHALL
 COMPLY WITH REQUIREMENTS 1 THRU 7 OF THE
 FHA-98 DESIGN MANUAL. INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT.
 SHOW THE W/C OPENING, (MINIMUM 33"),
 SHOW THE W/C AT 18" OFF THE WALL TO THE
 CENTER OF THE FIXTURE WHERE APPLICABLE,
 AND 18" MINIMUM OFF AN ADJACENT FIXTURE.
 SEE PAGES 6.7 7.43 & 7.44. - SHOW CLEAR
 FLOOR SPACE FOR ALL USABLE FIXTURES. -
 SUBMIT A DETAIL FOR BACKING FOR W/C'S,
 TUBS, SHOWERS ECT. PER REQUIREMENT 6. -
 CLEAR FLOOR SPACE FOR SHOWERS SHALL BE
 PARALLEL TO SHOWER & FLUSH WITH CONTROL
 WALL. INDICATE CONTROL WALL ON UNIT
 FLOOR PLAN. (SEE PAGE 7.56).
 ***NO RESPONSE FROM ARCHITECT, NOT
 ADDRESSED.
  
 5. SHT T-4 A4.1.11 MEN'S & WOMEN'S
 TOILET ROOMS SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.22 WITH ALL
 SUBSECTIONS. SUBMIT A DETAIL SHOWING
 COMPLIANCE.
 ***NO RESPONSE FROM THE ARCHITECT, NOT
 ADDRESSED.
  
 6. SUBMIT CALCULATIONS FOR ALL
 AMENITITES AREAS FOR MINIMUM FACILITIES
 PER TABLES 1004.2 (BLDG) AND 403.1
 (PLMG). SHOW THE SQUARE FOOTAGE FOR ALL
 COMMON USE AREAS ALONG WITH THE
 OCCUPANCY LOAD OF EACH AREA. INDICATE
 THE LOCATION OF THE SANITARY FACILITIES
 FOR THE POOL AREA.
 ***NO RESPONSE FROM THE ARCHITECT, NOT
 ADDRESSED.
  
 7. SHT T-4 A7.1.1 FLOORS AND WALLS IN
 TOILET ROOM SHALL BE NONABSORBENT PER
 SECTIONS 1210.1 & 1210.2. PLEASE
 INDICATE HOW THIS WILL BE ACCOMPLISHED
 WITH EXPOSED CONCRETE, GYP. BOARD AND NO
 BASE AS SHOWN IN GROUND LEVEL ROOM
 FINISH SCHEDULE.
 ***NO RESPONSE FROM THE ARCHITECT, NOT
 ADDRESSED.
  
 8. SHT T-4 A4.11 SINK IN CATERING
 KITCHEN SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. PROVIDE A
 DETAIL.
 ***NO RESPONSE FROM THE ARCHITECT, NOT
 ADDRESSED.
  
 9. SHT T-4 A6.1.1 DETAIL #4 TRASH CHUTE
 WATER SUPPLY SHALL HAVE BACKFLOW
 PROTECTION. INDICATE THE METHOD OF
 BACKFLOW PROTECTION REQUIRED IN SECTION
 608 AND TABLE 608.1.
 ***RESPONSE NOTED, BUT NO BACKFLOW
 SHOWN.
  
 10. SHT T-4 A6.1.3 DETAIL #10 ROOF DRAIN
 DETAIL, INDICATE MEASUREMENT FROM THE
 ROOF TO THE TOP OF THE SECONDARY ROOF
 DRAIN PIPI, (EMERGENCY OVERFLOW PIPE).
 ***NO RESPONSE FROM THE ARCHITECT, NOT
 ADDRESSED.
  
 11. SHT T-4 A8.1.1 SHOW THE BACKING FOR
 THE W/C'S PER FHA DESIGN MANUAL PAGES
 6.3 & 6.4. SHOW BACKING FOR THE TUBS PER
 PAGE 6.9.
 ***NO RESPONSE FROM THE ARCHITECT, NOT
 ADDRESSED.
  
 12. SHT P0.1 PLUMBING NOTES #1 & #24
 REFER TO FBC-2001, CODE ADOPTED FOR THIS
 JOB IS FBC-2004. PLEASE CHANGE REFERENCE
 ***RESPONSED NOTED, BUT PLUMBING NOTE
 #24 HAS NOT BEEN CHANGED.
  
 14. SHT P2.1 MANY FITTINGS CONNECTING
 BRANCH LINES TO BLDG. SANT. DRAIN ARE
 NOT SHOWN TO GUIDE SEWAGE AND WASTE IN
 THE DIRECTION OF FLOW. SECTION 706.3. -
 IDENTIFY THE RISER BETWEEN ROOMS B110 &
 B110.
 ***RESPONSE NOTED, BUT THIS HAS NOT BEEN
 ADDRESSED.
  
 16. SHT P2.4 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. (SEE
 COMMENT #3).
 ***RESPONSE NOTED, BUT SEE COMMENT #3
 FOR REQUIREMENTS FOR ROOFS THAT DRAIN
 ONTO ROOF FROM ABOVE.
  
 18. SHT P3.3 2ND SHEET WITH 2ND, 4TH -
 12TH FLOORS. NO 3RD FLOOR SUBMITTED.
 PLEASE CLARIFY.
 ***RESPONSE NOTED, BUT NO CHANGE SEEN.
  
 21. SHTS P5.1 & P5.2 SUBMIT SOVENT
 DESIGN MANUAL FOR THE SOVENT SYSTEM. THE
 SOVENT SYSTEM SHALL BE APPROVED. SECTION
 106.1.1.
 ***RESPONSE NOTED, BUT THIS SYSTEM IS
 NOT APPROVED. NO TESTING AND APPROVAL OF
 FITTINGS.
  
 22. SHT P5.3 BLDG DRAIN ISOMETRIC RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE ISOMETRIC IS REVERSE FROM THE FLOOR
 PLAN. THE BLDG. DRAIN IS SHOWN AS
 EXITING THE BLDG. BETWEEN S/1 & S/2 ON
 THE FLOOR PLAN. SHOW ALL GROUND FLOOR
 FIXTURE PIPING ON THE ISOMETRIC WITH ALL
 PIPE SIZES AND VENTING. SECTION
 104.3.1.1.
 ***RESPONSE NOTED, BUT THE RISER DIAGRAM
 STILL DOES NOT REFLECT THE FLOOR PLAN IN
 MANY AREAS. CHECK ALL PIPE SIZES AGAINST
 TABLE 710.1(1). - FLOOR DRAINS MISSING,
 UNIDENTIFIED FIXTURE DOWNSTREAM OF RISER
 S/63 NOT SHOWN. (SEE RED LINE
 CORRECTIONS ON ONE SET OF PLUMBING
 SHEETS).
  
 23. SHT P5.3 SHOW DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLE 710.1(1)
 ***RESPONSE NOTED, BUT SOME FIXTURES
 MISSING AND ADDITION DOWNSTREAM OF RISER
 S/49 NEEDS TO BE RECHECKED. FLOOR DRAINS
 PER TABLE 709.2.
  
 27. THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CUT SECTIONS NOT SHOWN
 AND MOST RISERS NOT SHOWN.
 ***RESPONSE NOTED, BUT LENGTHS OF CUT
 SECTIONS NOT SHOWN.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ***RESPONSE NOTED, BUT CALCULATIONS FOR
 CLOTHES DRYER ROOMS NOT SUBMITTED.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT NO MANUF. SHEETS
 SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ***RESPONSE NOTED, BUT VOIDED SHEETS NOT
 REMOVED.
  
 **************NEW COMMENTS**************
  
 1B. SHTS T-4 A8.1.2 THRU T-4 A8.1.8
 SHOWN ON THE INDEX OF DRAWINGS HAVE NOT
 BEEN SUBMITTED. PLEASE CLARIFY. SECTION
 106.1.1.
  
 2B. SHTS P2.4 & P7.1 STORM RISERS 6 & 10
 SF DOES NOT REFLECT SF ON ROOF PLAN NOR
 ON BLDG. STORM DRAIN ISOMETRIC. PLEASE
 CORRELATE RISERS WITH ROOF PLANS AND
 STORM DRAIN ISOMETRIC. SECTION 106.1.1.
  
 3B. SHTS P5.1 & P5.2 BASE OF STACKS DO
 NOT REFLECT REQUIREMENTS OF SOVENT
 DESIGN MANUAL. FIRST FLOOR FIXTURES DO
 NOT CONNECT TO VERTICLE STACK UNDER THE
 DEAERATOR REQUIREMENT FOR THE PRL LINE
 IS NOT CORRECT.
  
 4B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL & FS 553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-01 Cont ID  
Sent By kstevens Date 2005-12-01 Time 07:26 Rev Time 5.50
Received By kstevens Date 2005-11-30 Time 16:50 Sent To  
Notes
2005-11-30 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED & DATED AS
 REQUIRED BY FS. SECTION 106.1
 2. SHTS LA-POOL 3 & LA-POOL 4 PLANS &
 PERMIT ARE REQUIRED. PLANS SHALL BE
 REVIEWED & STAMPED BY THE PALM BEACH
 COUNTY HEALTH DEPT. PRIOR TO SUBMITTING
 FOR REVIEW.
 3. SHT T-4 A2.4.1 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SHOW THE SQUARE FOOTAGE FOR EACH AREA &
 SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ALONG WITH THE AREA
 OF ROOF THAT DRAINS ONTO THE ROOF FROM
 ABOVE FOR EACH AREA IN CALCLATIONS.
 SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS.
 4. SHTS T-4 A4.1.1 THRU T-4 A4.1.10
 UNITS A, B, C, D, E, H, F, G & K SHALL
 COMPLY WITH REQUIREMENTS 1 THRU 7 OF THE
 FHA-98 DESIGN MANUAL. INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT.
 SHOW THE W/C OPENING, (MINIMUM 33"),
 SHOW THE W/C AT 18" OFF THE WALL TO THE
 CENTER OF THE FIXTURE WHERE APPLICABLE,
 AND 18" MINIMUM OFF AN ADJACENT FIXTURE.
 SEE PAGES 6.7 7.43 & 7.44. - SHOW CLEAR
 FLOOR SPACE FOR ALL USABLE FIXTURES. -
 SUBMIT A DETAIL FOR BACKING FOR W/C'S,
 TUBS, SHOWERS ECT. PER REQUIREMENT 6. -
 CLEAR FLOOR SPACE FOR SHOWERS SHALL BE
 PARALLEL TO SHOWER & FLUSH WITH CONTROL
 WALL. INDICATE CONTROL WALL ON UNIT
 FLOOR PLAN. (SEE PAGE 7.56).
 5. SHT T-4 A4.1.11 MEN'S & WOMEN'S
 TOILET ROOMS SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.22 WITH ALL
 SUBSECTIONS. SUBMIT A DETAIL SHOWING
 COMPLIANCE.
 6. SUBMIT CALCULATIONS FOR ALL
 AMENITITES AREAS FOR MINIMUM FACILITIES
 PER TABLES 1004.2 (BLDG) AND 403.1
 (PLMG). SHOW THE SQUARE FOOTAGE FOR ALL
 COMMON USE AREAS ALONG WITH THE
 OCCUPANCY LOAD OF EACH AREA. INDICATE
 THE LOCATION OF THE SANITARY FACILITIES
 FOR THE POOL AREA.
 7. SHT T-4 A7.1.1 FLOORS AND WALLS IN
 TOILET ROOM SHALL BE NONABSORBENT PER
 SECTIONS 1210.1 & 1210.2. PLEASE
 INDICATE HOW THIS WILL BE ACCOMPLISHED
 WITH EXPOSED CONCRETE, GYP. BOARD AND NO
 BASE AS SHOWN IN GROUND LEVEL ROOM
 FINISH SCHEDULE.
 8. SHT T-4 A4.11 SINK IN CATERING
 KITCHEN SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. PROVIDE A
 DETAIL.
 9. SHT T-4 A6.1.1 DETAIL #4 TRASH CHUTE
 WATER SUPPLY SHALL HAVE BACKFLOW
 PROTECTION. INDICATE THE METHOD OF
 BACKFLOW PROTECTION REQUIRED IN SECTION
 608 AND TABLE 608.1.
 10. SHT T-4 A6.1.3 DETAIL #10 ROOF DRAIN
 DETAIL, INDICATE MEASUREMENT FROM THE
 ROOF TO THE TOP OF THE SECONDARY ROOF
 DRAIN PIPI, (EMERGENCY OVERFLOW PIPE).
 11. SHT T-4 A8.1.1 SHOW THE BACKING FOR
 THE W/C'S PER FHA DESIGN MANUAL PAGES
 6.3 & 6.4. SHOW BACKING FOR THE TUBS PER
 PAGE 6.9.
 12. SHT P0.1 PLUMBING NOTES #1 & #24
 REFER TO FBC-2001, CODE ADOPTED FOR THIS
 JOB IS FBC-2004. PLEASE CHANGE REFERENCE
 13. SUBMIT A STORM BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM. SHOW ALL SQUARE
 FOOTAGE AS IT ACCUMULATES. INDICATE THE
 RISER NUMBER CONNECTING TO STORM DRAIN.
 INDICATE ALL PIPE SIZES AND SLOPE OF
 PIPE.
 14. SHT P2.1 NO SANITARY BRANCH LINE
 SHOWN TO RISERS S/9,S/37, S/41 OR S/46
 FROM THE BUILDING SANT. DRAIN. PLEASE
 SHOW ALL PIPING ON FLOOR PLAN. SECTION
 106.1.1. - MANY FITTINGS CONNECTING
 BRANCH LINES TO BLDG. SANT. DRAIN ARE
 NOT SHOWN TO GUIDE SEWAGE AND WASTE IN
 THE DIRECTION OF FLOW. SECTION 706.3. -
 IDENTIFY RISER BETWEEN ROOMS B110 &
 B110. SECTION 104.2.1. - NO PIPING SHOWN
 TO RWL IN FITNESS CENTER. ALSO RWL DOES
 NOT APPEAR TO BE IN THE WALL. SECTION
 104.2.1.
 15. SHT P2.3 6" RWL (2200SF) SHOWN IN
 THE HALLWAY. PLEASE CLARIFY. SECTION
 106.1.1.
 16. SHT P2.4 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. (SEE
 COMMENT #3).
 17. SHT P3.1 NO PIPING SHOWN TO CD/8.
 SECTION 104.2.1.
 18. SHT P3.3 2ND SHEET WITH 2ND, 4TH -
 12TH FLOORS. NO 3RD FLOOR SUBMITTED.
 PLEASE CLARIFY.
 19. SHT P4.1 AN RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE TO EACH
 BUILDING.
 20. SHT P4.1 SHOWS 3" WATER SERVICE TO
 EACH TOWER, BUT CIVIL PLANS, SHTS P3.1,
 AND P6.4 SHOW 4" WATER SERVICE. PLEASE
 CORRELATE PLANS. SECTION 106.1.1.
 21. SHTS P5.1 & P5.2 SUBMIT SOVENT
 DESIGN MANUAL FOR THE SOVENT SYSTEM. THE
 SOVENT SYSTEM SHALL BE APPROVED. SECTION
 106.1.1.
 22. SHT P5.3 BLDG DRAIN ISOMETRIC RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE ISOMETRIC IS REVERSE FROM THE FLOOR
 PLAN. THE BLDG. DRAIN IS SHOWN AS
 EXITING THE BLDG. BETWEEN S/1 & S/2 ON
 THE FLOOR PLAN. SHOW ALL GROUND FLOOR
 FIXTURE PIPING ON THE ISOMETRIC WITH ALL
 PIPE SIZES AND VENTING. SECTION
 104.3.1.1.
 23. SHT P5.3 SHOW DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLE 710.1(1)
 24. SHTS P6.1, P6.2, & P6.3 WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN 'EFFECTIVE RANGE" NOT IN
 THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. - FULL
 OPEN VALVES ARE REQUIRED ON THE TOP OF
 ALL WATER DOWN-FEED LINES. SECTION
 606.1(4)
 25. SUBMIT A CONDENSATE BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TERMINATION POINTS FOR THE
 CONDENSATE DRAIN AND VENT. SECTION
 106.3.5.1.3. - SUBMIT CONDENSATE RISER
 DIAGRAMS. SHOW ALL PIPE SIZES.
 26. SUBMIT STORM RISER DIAGRAMS AND A
 BUILDING DRAIN ISOMETRIC RISER DIAGRAM.
 SHOW ALL PIPE SIZES, LOCATION OF ALL
 RISER CONNECTIONS, SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM, TERMINATION
 POINT OF STORM WATER ECT. SECTION
 106.3.5.1.3.
 27. THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CUT SECTIONS NOT SHOWN
 AND MOST RISERS NOT SHOWN.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 E. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-02 Cont ID  
Sent By jroach Date 2006-07-02 Time 16:35 Rev Time 0.00
Received By jroach Date 2006-07-02 Time 16:35 Sent To  
Notes
2006-07-02 00:00:007/2/06 ***FAILED***
  
 1) INDICATE ON THE PHASING PLAN THAT THE
 TURQUOISE NECKLACE WILL BE DESIGNED,
 PERMITTED AND CONSTRUCTED AS PART OF
 PHASE 2.
  
 2) THE TURQUOISE NECKLACE SHALL BE
 PROVIDED ON THE CIVIL DRAWINGS.A NOTE
 MAY BE PROVIDED INDICATING THAT IT WILL
 BE DESIGNED, PERMITTED AND CONSTRUCTED
 AS PART OF PHASE 2.
  
 3) UNITY OF TITLE SHALL BE RECORDED IN
 THE PUBLIC RECORD OF PALM BEACH COUNTY.
 A COPY SHALL BE INCLUDED WITH ALL PERMIT
 PACKAGES.
  
 4) PARKING STALL DETAIL SHALL CONFORM TO
 THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.A WHEEL STOP SHALL BE
 SHOWN 2 FEET FROM THE HEAD OF THE STALL.
 IF NO WHEEL STOP IS PROVIDED, SIDEWALKS
 LOCATED AT THE HEAD OF THE STALL NEED TO
 BE 7 FEET IN WIDTH TO ALLOW FOR 2 FEET
 OF VEHICLE OVERHANG.IF THE OVERHANG
 OCCURS OVER LANDSCAPING, THE LANDSCAPING
 SHALL NOT EXCEED 6 INCHES ABOVE THE
 HEIGHT OF THE CURB.DETAIL OF DOUBLE
 STRIPING NEEDS TO SHOW 12 INCHES FROM
 INSIDE OF STRIP TO INSIDE OF STRIPE.
  
 5) ALL LANDSCAPE SHEETS NEED TO BE
 SIGNED AND SEALED BY A REGISTERED
 LANDSCAPE ARCHITECT, NOT JUST THE COVER
 SHEET.
  
 6) LANDSCAPE PLANS NEED TO BE ADJUSTED
 TO INDICATE THAT TOWNHOUSE #7 IS PART OF
 PHASE 1.
  
 7) THE LIFT STATION SHOWN ON THE CIVIL
 PLANS DOES NOT MATCH THAT SHOWN ON THE
 LANDSCAPE PLAN.LANDSCAPING NEEDS TO BE
 ADJUSTED ACCORDINGLY.
  
 8) AS A RESULT OF EACH BUILDING BEING
 CO'D SEPARATELY, AN INSPECTION PLAN
 SHALL BE PROVIDED INDICATING WHICH AREAS
 OF LANDSCAPING WILL BE INSPECTED WITH
 EACH BUILDING CO.
  
 9) THE AREAS BETWEEN THE TOWERS ARE
 SHOWN AS FA GRASS.THIS SHALL BE
 MODIFIED AS THE BOARDWALKS ARE NO LONGER
 BEING PROPOSED.
  
 10) THE SIDEWALK CONFIGURATION ON THE
 LANDSCAPE PLANS AND THE CIVIL PLANS
 SHALL CORRESPOND WITH THE SITE PLAN.
  
 11) THE LANDSCAPE PLANS SHWO THE BUS
 SHELTER AND ENTRANCE WALL/LANDSCAPING AS
 PART OF PHASE 1.THE PHASING PLAN
 INDICATES OTHERWISE.
  
 12) FYI...IN DEVELOPING THE SIGNAGE FOR
 THE FRONT ENTRY WALL, THE AREA SHALL NOT
 EXCEED 48 SQUARE FEET.
  
 13) A PHOTOMETRIC PLAN SHALL BE PROVIDED
 FOR SITE LIGHTING ON THE ENTIRE
 PROPERTY.THE PHOTOMETRIC LEVELS SHALL
 BE SHOWN AT THE PROPERTY LINES AND SHALL
 NOT EXCEED 0.5 FOOTCANDLES AT PROPERTY
 LINES ADJACENT TO RESIDENTIAL PROPERTY.
  
 THE FOLLOWING COMMENTS HAVE BEEN
 PROVIDED BY ALAN BARATTA, LANDSCAPE
 PLANNER:
  
 1) PLANTING DIAGRAMS SHALL BE MODIFIED
 TO REFLECT WHAT WAS AGREED TO IN THE
 TREE REMOVAL/RELOCATION LICENSE.
  
 2) IN ORDER TO PREVENT DESTRUCTION TO
 CURBING, PAVING AND PARKED VEHICLES,
 REPLACE THE MOHOGANY TREES IN THE
 LANDSCAPE ISLANDS IN FRONT OF THE
 TOWNHOMES WITH A SMALLER/ALTERNATE
 SPECIES.MINOR PD AMENDMENT (PB CASE
 NO. 1242E) APPROVED ON JULY 2, 2006,
 INDICATED GREEN BUTTONWOODS.
  
 3) ADDITIONAL LANGUAGE SHALL BE PROVIDED
 INDICATING REMOVAL OF SUPPORT MATERIAL
 FROM TREES/PALMS SHALL OCCUR AFTER
 ESTABLISHMENT OR HURRICANE SEASON,
 WHICHEVER COMES LATER.
  
 4) LANDSCAPING IN THE EXECUTIVE CENTER
 DRIVE CUL-DE-SAC SHALL BE COORDINATED
 WITH THE PUBLIC UTILITIES/ENGINEERING
 DEPARTMENT.
  
 MISCELLANEOUS COMMENTS:
  
 1) WORKFORCE HOUSING RESTRICTION ON THE
 LOFTS AND TOWNHOMES, FOLLOWING APPROVAL
 BY THE CITY OF WEST PALM BEACH, SHALL BE
 IN PLACE PRIOR TO THE ISSUANCE OF A CO
 FOR SUCH STRUCTURES.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-20 Cont ID  
Sent By jroach Date 2005-09-20 Time 13:26 Rev Time 0.00
Received By jroach Date 2005-09-20 Time 13:26 Sent To  
Notes
2005-09-20 00:00:009/20/2005 ***FAILED***
  
 ALL PERMITS
  
 1. INDICATE ON THE PHASING PLAN THAT THE
 TURQUOISE NECKLACE WILL BE DESIGNED,
 PERMITTED AND CONSTRUCTED AS PART OF
 PHASE 2.
  
 2. THE TURQUOISE NECKLACE SHALL BE
 PROVIDED ON THE CIVIL DRAWINGS?A NOTE
 MAY BE PROVIDED THAT IT WILL BE
 DESIGNED, PERMITTED AND CONSTRUCTED AS
 PART OF PHASE 2.
  
 3. PHASING PLAN DOES NOT ACCURATELY
 REFLECT WHAT IS BEING PROPOSED
 (TOWNHOUSE #7 IS SHOWN AS PART OF PHASE
 3, NOT PHASE 1 AS PROPOSED).
  
 4. UNITY OF TITLE SHALL BE RECORD INTO
 THE PUBLIC RECORDS OF PALM BEACH COUNTY
 WITH THE CLERK OF THE CIRCUIT COURT.A
 COPY SHALL BE INCLUDED WITH ALL PERMIT
 PACKAGES.
  
 5. IN RESPONSE TO ELECTRICAL PLAN REVIEW
 COMMENT #1 (PERMIT #05080676)?THE
 PROPERTY MAY NOT BE REPLATTED TO PROVIDE
 FEE-SIMPLE TOWNHOMES.
  
 6. PARKING STALL DETAIL SHALL BE
 MODIFIED TO PROVIDE A WHEEL STOP 2? FROM
 THE HEAD OF THE STALL.IF NO WHEEL STOP
 IS PROVIDED AND THE VEHICLE OVERHANGS A
 SIDEWALK, THE SIDEWALK SHALL BE 7? IN
 WIDTH MINIMUM.IF THE VEHICLE OVERHANGS
 LANDSCAPING, THE LANDSCAPING SHALL NOT
 BE HIGHER THAN 6? ABOVE THE HEIGHT OF
 THE CURB.
  
 7. ALL LANDSCAPE SHEETS SHALL BE SIGNED
 AND SEALED, NOT JUST THE COVER SHEET.
  
 8. LANDSCAPE PLANS SHALL BE ADJUSTED TO
 INDICATE THAT TOWNHOUSE #7 IS PART OF
 PHASE 1.
  
 9. AS A RESULT OF EACH BUILDING BEING
 CO?D SEPARATELY, AN INSPECTION PLAN
 SHOULD BE PROVIDED FOR THE LANDSCAPING,
 INDICATING WHICH AREAS WILL BE SUBJECT
 TO INSPECTION WITH EACH BUILDING.
  
 10. AREAS BETWEEN THE TOWERS ARE SHOWN
 AS FA GRASS.THIS SHOULD BE MODIFIED AS
 THE BOARDWALKS NO LONGER EXIST.
  
 11. THE SIDEWALK CONFIGURATION ON THE
 LANDSCAPE PLANS SHALL CORRESPOND WITH
 THE SITE PLAN AND CIVIL DRAWINGS (REFER
 TO AREA BETWEEN THE TOWERS).
  
 12. THE LANDSCAPE PLANS SHOW THE BUS
 SHELTER INCLUDED IN PHASE 1.THE
 PHASING PLAN INDICATES OTHERWISE.IF IT
 IS TO BE CONSTRUCTED WITH PHASE 1, NO
 ARCHITECTURAL DRAWINGS HAVE BEEN
 PROVIDED.
  
 13. FENCES/WALLS/COLUMNS SHALL NOT
 EXCEED 48? IN HEIGHT WITHIN THE FRONT
 SETBACK (25? FROM EXECUTIVE CENTER
 DRIVE).REFER TO ENTRY GATE WALL LAYOUT
 AND ELEVATIONS.IN ORDER TO EXCEED THE
 MAXIMUM HEIGHT, A MINOR PD AMENDMENT MAY
 BE SUBMITTED TO THE PLANNING DEPARTMENT
 FOR REVIEW.
  
 14. THE ENTRY GATE WALL LAYOUT,
 ELEVATIONS AND SIGNAGE WALL DO NOT
 CORRESPOND WITH EACH OTHER IN REGARD TO
 HEIGHT, ETC.
  
 15. IN DEVELOPING THE SIGNAGE FOR THE
 MAIN ENTRY, THE SIGNS AREA SHALL NOT
 EXCEED 48 SQUARE FEET.
  
 16. FENCES/WALL/COLUMNS SHALL NOT EXCEED
 72? IN HEIGHT WITHIN THE REQUIRED SIDE
 AND REAR SETBACK (15? FROM THE PROPERTY
 LINES).REFER TO THE WALL ELEVATIONS
 ASSOCIATED WITH THE SOUTH LAP POOL.THE
 HEIGHT OF THE FENCE/WALL/COLUMNS SHALL
 BE REDUCED IN HEIGHT OR MOVE THE
 LOCATION OUTSIDE OF THE SETBACK.
  
 17. FOUNTAINS WERE NOT SHOWN IN THE
 INTERIOR TRAFFIC CIRCLES.PLEASE
 CLARIFY IF THIS WILL BE INCLUDED UNDER A
 SEPARATE PERMIT.IF UNDER THIS PERMIT,
 ADJUST ALL PLANS NECESSARY AND PROVIDE
 DETAILS FOR REVIEW BY OTHER DISCIPLINES.
  
 18. A PHOTOMETRIC PLAN SHALL BE PROVIDED
 INDICATING SITE LIGHTING AND
 CORRESPONDING LEVELS.PHOTOMETRIC
 LEVELS SHALL BE PROVIDED AT THE PROPERTY
 LINE AND SHALL NOT EXCEED 0.5
 FOOTCANDLES AT PROPERTY LINES THAT ABUT
 ADJACENT RESIDENTIAL PROPERTY.
  
 THE FOLLOWING COMMENTS HAVE BEEN
 PROVIDED BY ALAN BARATTA, LANDSCAPE
 PLANNER:
  
 1. PLANTING DIAGRAMS SHALL BE MODIFIED
 TO REFLECT WHAT WAS AGREED TO IN THE
 TREE REMOVAL/RELOCATION LICENSE.
  
 2. IN ORDER TO PREVENT DESTRUCTION TO
 CURBING, PAVEMENT AND PARKED VEHICLES,
 REPLACE THE MAHOGANY TREES IN THE
 LANDSCAPE ISLANDS LOCATED IN FRONT OF
 THE TOWNHOMES WITH A SMALLER/ALTERNATE
 SPECIES.
  
 3. ADDITIONAL LANGUAGE SHALL BE PROVIDED
 INDICATING THE REMOVAL OF SUPPORT
 MATERIAL FROM TREES/PALMS AFTER
 ESTABLISHMENT OR HURRICANE SEASON,
 WHICHEVER COMES LATER.
  
 4. LANDSCAPING IN THE EXECUTIVE CENTER
 DRIVE CUL-DE-SAC SHALL BE COORDINATED
 WITH JONATHON BRAMLEY (CITY OF WEST PALM
 BEACH PUBLIC UTILITIES ? (561)
 494-1040).
  
 MISCELLANEOUS COMMENTS:
  
 1. WORKFORCE HOUSING RESTRICTIONS ON THE
 LOFTS AND TOWNHOMES, FOLLOWING APPROVAL
 BY THE CITY OF WEST PALM BEACH, SHALL BE
 IN PLACE PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY (CO) FOR SUCH
 STRUCTURES.
  
 TOWER #4
  
 1. NO ADDITIONAL COMMENTS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.