Plan Review Details - Permit 05080675
| Plan Review Stops For Permit 05080675 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2007-11-30 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2007-11-30 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2008-05-05 15:41:30 | PERMIT IS EXTENDED TO 5/31/08 HHP | | | NOTE DATE WAS ADJUSTED TO COINCIDE WITH 6 MONTH | | | EXPIRATION FROM LAST ACTIVITY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-06-01 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-06-01 |
Time |
18:43 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-06-01 |
Time |
18:43 |
Sent To |
|
|
| Notes |
| 2007-06-01 18:44:06 | REQUEST GRANTED FOR EXTENSION OF PERMIT APPLICATION. | | | SEE LETTER DATED 5/31/07.UPDATED EXPIRATION DATE IS | | | 9/2/07. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-04-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-04-24 |
Time |
08:12 |
Rev Time |
5.55 |
| Received By |
jwitmer |
Date |
2006-04-24 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2006-04-24 00:00:00 | | | | PERMIT: 05080675 | | | ADD: 719 EXECUTIVE CENTER DR | | | (TOWER# 4) | | | CONT: THE WEITZ CO. | | | TEL: (561)686-5511 | | | CELL:(954)675-4302 | | | | | | ARCHITECT: ACI ARCHITECRTURALGROUP | | | PAUL M. TWITTY | | | TEL:(561)832-5599 | | | STRUC ENGINEER: ONM&J | | | PHILLIP RIZZO | | | TEL:(561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE | | | ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 2) 105.8* PROVIDE NOC RECORDED WITH THE | | | CLERK OF COURT BEFORE A PERMIT CAN BE | | | ISSUED. | | | | | | 3A)109.3.7*THIS PARTICUAL TYPE OF | | | BUILDING WILL REQUIRE A THRESHOLD | | | INSPECTOR.FORMS WILL NEED TO BE FILED | | | OUT FOR THE THRESHOLD INSPECTOR, CONTACT | | | HAROLD PISKURA, INSPECTION SERVICES | | | MANAGER @ (561)805-6711 TO SEET UP AN | | | APPOINTMENT. | | | | | | 3B) 109.3.6.1* THE ENFORCING AGENCY | | | SHALL REQUIRE A SPECIAL INSPECTOR TO | | | PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A | | | STRUCTURAL INSPECTION PLAN PREPARED BY | | | THE ENGINEER OR ARCHITECT OF RECORD. | | | THE STRUCTURAL INSPECTION PLAN MUST BE | | | SUBMITTED TO THE ENFORCINGAGENCY PRIOR | | | TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD | | | BUILDING.THE PURPOSE OF THE STRUCTURAL | | | INSPECTION PLANS IS TO PROVIDE SPECIFIC | | | INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY | | | INSPECTED FOR COMPLIANCE WITH THE | | | PERMITTED DOCUMENTS. | | | | | | 3C) 109.3.6.4.4.105.13.4.4 ALL PLANS FOR | | | THE BUILDING WHICH ARE REQUIRED TO BE | | | SIGNED AND SEALED BY THE ARCHITECT OR | | | ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR | | | ENGINEER'S KNOWLEDGE, THE PLANS AND | | | SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE MINIMUM BUILDING CODES AND | | | THE APPLICABLE FIRE-SAFETY STANDARDS AS | | | DETERMINED BY THE LOCAL AUTHORITY IN | | | ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTES. | | | | | | 3D) NOTE: SINCE THIS BUILDING WILL BE A | | | THRESHOLD STRUCTURE SUBMIT (3) OF ALL | | | DOCUMENTS FOR REVIEW. | | | | | | 4) 106.3.3* PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY DCA RULE | | | 9B-72 SHALL BE REVIEWED AND APPROVED IN | | | WRITTING BY THE DESIGNER OF RECORD PRIOR | | | TO SUBMITTAL FOR " JURISDICTIONAL | | | APPROVAL", (LOCAL PRODUCT APPROVAL). | | | | | | 5) SITE PLAN NEEDS TO BE SUBMITTED TO | | | ADDRESSING PERSONEL JOHN HIGGINS FOR | | | ADDRESSING AS WELL AS NEW PLAT MAP FOR | | | THE COMBINATION OF LOTS. JOHN HIGGINS | | | CONTACT NUMBER IS (561)822-1239. | | | | | | 6) THE SURVEY DOES SHOW 2 SEPERATE LOTS | | | WHICH APPEAR TO CUT THROUGH BULDING "B" | | | AND BUILDING "C". A UNITY OF TITLE SHALL | | | BE REQUIRED, TABLE 601 AND 602. | | | | | | 7) COMPLIED. | | | | | | 8) COMPLIED. | | | | | | 9) PROVISO. | | | | | | 10) PROVISO. | | | | | | 11) COMPLIED. | | | | | | 11B) COMPLIED. | | | | | | 12A) COMPLIED | | | | | | 12B) COMPLIED. | | | | | | 12C) 2ND REQUEST | | | PORTE COCHERE: THE PLANS DO NOT INDICATE | | | THERE IS AN ACCESSIBLE LOADING ZONE | | | UNDER THE PORTE COCHERE. FAIR HOUSING | | | ANSI 4.6. | | | | | | 12D) 2ND REQUEST, | | | PROVIDE SIGNAGE FOR HANDICAPPED PARKING | | | AND VAN ACCESSIBLE PARKING. FAIR HOUSING | | | | | | RESPONCE: SEE CIVIL, WHERE? SHEET# 9 | | | DOES HAVE HANDICAPPED ELEMENTS ON THIS | | | SHEET BUT FOR SIGNAGE ONLY A STOP SIGN. | | | | | | 12E) 2ND REQUEST REACH RANGES FOR THE | | | COMMON USE MAILBOXES. PROVIDE FRONT AND | | | SIDE RANGES. | | | | | | 12F) COMPLIED. | | | | | | 12G) COMPLIED. | | | | | | 12H) COMPLIED. | | | | | | 13) COMPLIED. | | | | | | 14) COMPLIED. | | | | | | 15A) COMPLIED. | | | | | | 15B) COMPLIED. | | | | | | 15C) COMPLIED. | | | | | | 15D)2ND REQUEST, NOTE: IF WINDOWS | | | REQUIRES FIRE RATED | | | GLASS, AS FAR AS I'M AWARE NO | | | MANUFACTURER MAKES FIRE RATED AND LARGE | | | MISSLE IMPACT RATED GLAZING!!!! SEE | | | THE BUILDING OFFICIALS INTERPRETATION ON | | | LARGE OR HIGH RISE BUILDINGS AS FAR AS | | | SHUTTERS VS LARGE OR SMALL MISSLE RATED | | | GLASS. | | | ************************* | | | QUESTION# 13) RECOGNIZING SUCH CONCERNS | | | AS ABSENTEE OWNERS, OR CASES WHERE | | | LONGER TIME AND EFFORT IS NECESSARY TO | | | SECURE SHUTTERS ON LARGE OR MULTI-STORY | | | BUILDINGS, WHAT MEASURES ARE BEING | | | RECOMMENDED OR IMPLEMENTED TO ENSURE | | | THAT COMPLETE INSTALLATION OR SECURING | | | IS DONE SUFFICIENTLY IN ADVANCE OF THE | | | HURRICANE EVENT? | | | | | | IN MATTERS FLORIDA BUILDING CODE, 2004 | | | EDITION, PROVIDES THE ABILITY FOR THE | | | BUILDING OFFICIAL TO IMPLEMENT | | | REQUIREMENTS FOR ENSURING STABILITY, | | | STRENGTH, AND PROPER OPERATION OF | | | EXISTING BUILDINGS. | | | | | | IN ORDER TO ASSURE THE SECURING OF | | | SHUTTERS ON LARGE OR MULTI-STORY | | | BUILDING, OR MULTIPLE BUILDINGS ON THE | | | SAME PROPERTY, | | | | | | SUBMIT: PRE-STORM PREPARATION: | | | | | | PLANS MUST BE SUBMITTED BY THE PROPERTY | | | OWNERS OR MANAGING AGENTS FOR REVIEW BY | | | THE CONSTRUCTION SERVICES DEPARTMENT. | | | ANY SUCH PLAN SHALL INCLUDE, AT A | | | MINIMUM, ON-SITE LOCATION OF SHUTTERS, | | | PARTY RESPONSIBLE FOR SECURING THE | | | SHUTTERS (SAID PARTIES MUST BE LOCATED | | | WITHIN PALM BEACH COUNTY), TOTAL NUMBER | | | OF OPENINGS TO BE PROTECTED AND TOTAL | | | TIME REQUIRED TO SECURE ALL OPENINGS. | | | PROTECTION OF OPENINGS SHALL BE | | | ACCOMPLISHED WITHIN TWELVE (12) HOURS OR | | | LESS OF THE OFFICIAL NOTIFICATION BY THE | | | NATIONAL WEATHER SERVICE OF A HURRICANE | | | WATCH. | | | | | | PROVISIONS IN THE BUILDING CODES (AND | | | THIS STANDARD) ARE NOT INTENDED TO | | | PROHIBIT THE USE OF ALTERNATIVE | | | MATERIALS AND METHODS, AND ALLOW THE | | | BUILDING OFFICIAL TO REVIEW AND APPROVE | | | ANY ALTERNATE DEEMED EQUIVALENT IN | | | QUALITY, STRENGTH, EFFECTIVENESS, FIRE | | | RESISTANCE, DURABILITY AND SAFETY | | | PRESCRIBED BY CODE. BASED UPON THIS CODE | | | PROVISION, ACCEPTANCE OF ALTERNATE | | | MATERIALS AND METHODS MAY BE APPROVED ON | | | A CASE-BY-CASE BASIS AND SHALL REQUIRE | | | SUFFICIENT EVIDENCE OR PROOF TO | | | SUBSTANTIATE ANY CLAIM MADE REGARDING | | | THE ALTERNATE. | | | | | | QUESTION# 14) ARE REMOVABLE STORM PANELS | | | APPROPRIATE FOR USE ON VERY LARGE, MID | | | OR HIGH-RISE STRUCTURES? | | | | | | NO, EXCEPT ON THE GROUND FLOOR. ON | | | COMMERCIAL AND MULTI-UNIT RESIDENTIAL | | | STRUCTURES, ABOVE THE FIRST LEVEL, | | | IMPACT RESISTANT GLAZING OR PERMANENTLY | | | AFFIXED PROTECTIVE DEVICES SHALL BE | | | INSTALLED. PERMANENTLY AFFIXED | | | PROTECTIVE DEVICES SHALL REQUIRE THE | | | WRITTEN APPROVAL OF THE BUILDING | | | OFFICIAL. | | | | | | 16) COMPLIED. | | | | | | 17A) COMPLIED. | | | | | | 17B) COMPLIED. | | | | | | 17C) 2ND REQUEST, | | | ROOF TOP MECHANICAL UNITS AS SHOWN ON | | | A6.1.3 DETAIL# 7 INDICATES A MINIMUM OF | | | 18" FROM ROOF, SEE TABLE 1509.7 FOR THE | | | MINIMUM VERTICAL DISTANCE. | | | | | | 18) 2ND REQUEST REWORD PHRASE | | | "PEDESTRIAN BRIDGE TO GARAGE (UNDER | | | SEPERATE PERMIT)" THIS APPEARS ON T-4 | | | A3.1.3. | | | | | | 18B) PEDESTRIAN BRIDGE INTERFACE WILL | | | REQUIRE A 1 1/2 HR RATED PROTECTIVE | | | (706.7) SEE FIGURE 3104.5 CODE | | | COMMENTARY. | | | 3104.5 FIRE BARRIERS BETWEEN PEDESTRIAN | | | WALKWAYS AND BUILDINGS. | | | WALKWAYS SHALL BE SEPARATED FROM THE | | | INTERIOR OF THE BUILDING BY FIRE BARRIER | | | WALLS WITH A FIRE-RESISTANCE RATING OF | | | NOT LESS THAN 2 HOURS. THIS PROTECTION | | | SHALL EXTEND VERTICALLY FROM A POINT 10 | | | FEET (3048 MM) ABOVE THE WALKWAY ROOF | | | SURFACE OR THE CONNECTED BUILDING ROOF | | | LINE, WHICHEVER IS LOWER, DOWN TO A | | | POINT 10 FEET (3048 MM) BELOW THE | | | WALKWAY AND HORIZONTALLY 10 FEET (3048 | | | MM) FROM EACH SIDE OF THE PEDESTRIAN | | | WALKWAY. OPENINGS WITHIN THE L0-FOOT | | | (3048 MM) HORIZONTAL EXTENSION OF THE | | | PROTECTED WALLS BEYOND THE WALKWAY SHALL | | | BE EQUIPPED WITH DEVICES PROVIDING A | | | 3/4-HOUR FIRE PROTECTION RATING IN | | | ACCORDANCE WITH SECTION 715 . | | | | | | 19) COMPLIED. | | | | | | 20) 2ND REQUEST, | | | 20) THE ELEVATION SHEETS AND A6.1.1 | | | DEPICT DETAILS WITH CAST RESIN CORNICE | | | AND BANDS ON THE EXTERIOR OF THE | | | BUILDING. 1406.2.2 ARCHITECTURAL TRIM | | | THAT EXCEEDS 40FT IN HEIGHT ABOVE GRADE | | | PLANE SHALL BE CONSTRUCTED OF APPROVED | | | NONCOMBUSTIBLE MATERIALS AND SHALL BE | | | SECURED TO THE WALL WITH METAL OR OTHER | | | APPROVED NONCOMBUSTIBLE BRACKETS. | | | | | | 21)COMPLIED. | | | | | | 22) 2ND REQUEST, T-4 A6.1.3 DETAIL# 11 | | | ALSO INDICATES THE USE OF INTEGRAL ROOF | | | DECK PROVIDE ADDITIONAL INFORMATION. | | | RESPONCE: SEE STRUCTURAL SHEETS, WHERE? | | | | | | | | | 23) 2ND REQUEST, RESPONCE ,SEE | | | STRUCTURAL WHERE? | | | SAME DETAIL AS ABOVE WHAT SPANS CAN | | | THE GALVANIZED METAL FURRING SPAN @ 12" | | | O. C. PROVIDE THE PSF APPLIED LOAD, AND | | | THICKNESS OF HI HAT IN MIL. SPANS TO BE | | | TAKEN AS MULTIPLE SPANS? | | | | | | 24A) COMPLIED. | | | | | | 24B) COMPLIED. | | | | | | 24C) COMPLIED. | | | | | | 24D) COMPLIED. | | | | | | 25: T-3 A5.1.5 | | | 25A) 2ND REQUEST, | | | DETAILS SHOW A DROPPED CEILING OVER THE | | | WALKWAYS WITH METAL FRAMING NO | | | INDICATION AS TO ATTACHMENT TO THE DECK | | | ABOVE, SPACING OF ATTACHMENT, GAUGE OR | | | SIZE OF FRAMING, OR SPACING OF FRAMING. | | | | | | 26) SHEET M2.5 HAS NO INDICATION OF A | | | SMOKEPROOF EXIT ENCLOSURE, SEE 403.13 | | | ALSO SEE 1019.1.3 FOR REQUIRED | | | VENTILATION, AND 909.20 FOR PRESSURIZED | | | STAIRS. | | | KAMM RESPONE: SMOKE PROOF ENCLOSURE NOT | | | REQUIRED. PLEASE REFER TO ARCHITECTURAL | | | DRAWINGS AND OR ARCHITECTS RESPONCE | | | LETTER. NO ARCHITECTURAL RESPONCE. | | | HIGH-RISE 403 | | | 403.13 SMOKEPROOF EXIT ENCLOSURES. | | | EVERY REQUIRED STAIRWAY SERVING FLOORS | | | MORE THAN 75 FEET (22 860 MM) ABOVE THE | | | LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE | | | ACCESS SHALL COMPLY WITH SECTIONS 909.20 | | | AND 1019.1.8 . | | | 1019.1.8 SMOKEPROOF ENCLOSURES. | | | IN BUILDINGS REQUIRED TO COMPLY WITH | | | SECTION 403 OR 405, EACH OF THE EXITS OF | | | A BUILDING THAT SERVES STORIES WHERE THE | | | FLOOR SURFACE IS LOCATED MORE THAN 75 | | | FEET (22 860 MM) ABOVE THE LOWEST LEVEL | | | OF FIRE DEPARTMENT VEHICLE ACCESS OR | | | MORE THAN 30 FEET (9144 MM) BELOW THE | | | LEVEL OF EXIT DISCHARGE SERVING SUCH | | | FLOOR LEVELS SHALL BE A SMOKEPROOF | | | ENCLOSURE OR PRESSURIZED STAIRWAY IN | | | ACCORDANCE WITH SECTION 909.20 . | | | | | | 27) PRODUCT APPROVALS: | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 28) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) EXT LOUVER DOORS | | | B) EXT SOLID DOORS | | | C) EXT GLAZED DOORS SWING | | | D) EXT GLAZED DOORS W/ TRANSOMS, SWING | | | E) CASEMENT WINDOWS | | | F) MULLIONS HORIZONTAL | | | G) EXT RAILINGS | | | H) LOUVERS | | | I) TRUSS ANCHORS | | | J) ROOFING ASSEMBLIES | | | 1) FLAT ROOF | | | 2) CEMENT TILE & TYPE OF INSTALATION | | | NOTE THE FLAT ROOF INFORMATION SUBMITTED | | | IS REDUCED TO 1/2 SHEET, NOT READABLE TO | | | COPY FOR RECORD RETENTION. | | | THE CONTRACTOR DID NOT HIGHLIGHT WHICH | | | SUBSYSTEM TO BE USED NOR DID THEY | | | HIGHLIGHT WHICH FASTENING OPTIONS TO BE | | | USED. | | | | | | 29) NEW COMMENT, | | | 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING | | | UNIT AND A PUBLIC OR SERVICE AREA WITHIN | | | THE STRUCTURE SHALL HAVE AN IMPACT | | | INSULATION CLASS (IIC) RATING OF NOT | | | LESS THAN 50 (45 IF FIELD TESTED) WHEN | | | TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 30)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-10-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-10-27 |
Time |
10:01 |
Rev Time |
33.00 |
| Received By |
jwitmer |
Date |
2005-10-17 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2005-10-17 00:00:00 | PERMIT: 05080675 | | | ADD: 719 EXECUTIVE CENTER DR | | | (TOWER# 4) | | | CONT: THE WEITZ CO. | | | TEL: (561)686-5511 | | | CELL:(954)675-4302 | | | | | | ARCHITECT: ACI ARCHITECRTURALGROUP | | | PAUL M. TWITTY | | | TEL:(561)832-5599 | | | STRUC ENGINEER: ONM&J | | | PHILLIP RIZZO | | | TEL:(561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE | | | ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 2) 105.8* PROVIDE NOC RECORDED WITH THE | | | CLERK OF COURT BEFORE A PERMIT CAN BE | | | ISSUED. | | | | | | 3A)109.3.7*THIS PARTICUAL TYPE OF | | | BUILDING WILL REQUIRE A THRESHOLD | | | INSPECTOR.FORMS WILL NEED TO BE FILED | | | OUT FOR THE THRESHOLD INSPECTOR, CONTACT | | | HAROLD PISKURA, INSPECTION SERVICES | | | MANAGER @ (561)805-6711 TO SEET UP AN | | | APPOINTMENT. | | | | | | 3B) 109.3.6.1* THE ENFORCING AGENCY | | | SHALL REQUIRE A SPECIAL INSPECTOR TO | | | PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A | | | STRUCTURAL INSPECTION PLAN PREPARED BY | | | THE ENGINEER OR ARCHITECT OF RECORD. | | | THE STRUCTURAL INSPECTION PLAN MUST BE | | | SUBMITTED TO THE ENFORCINGAGENCY PRIOR | | | TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD | | | BUILDING.THE PURPOSE OF THE STRUCTURAL | | | INSPECTION PLANS IS TO PROVIDE SPECIFIC | | | INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY | | | INSPECTED FOR COMPLIANCE WITH THE | | | PERMITTED DOCUMENTS. | | | | | | 3C) 109.3.6.4.4.105.13.4.4 ALL PLANS FOR | | | THE BUILDING WHICH ARE REQUIRED TO BE | | | SIGNED AND SEALED BY THE ARCHITECT OR | | | ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR | | | ENGINEER'S KNOWLEDGE, THE PLANS AND | | | SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE MINIMUM BUILDING CODES AND | | | THE APPLICABLE FIRE-SAFETY STANDARDS AS | | | DETERMINED BY THE LOCAL AUTHORITY IN | | | ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTES. | | | | | | 3D) NOTE: SINCE THIS BUILDING WILL BE A | | | THRESHOLD STRUCTURE SUBMIT (3) OF ALL | | | DOCUMENTS FOR REVIEW. | | | | | | 4) 106.3.3* PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY DCA RULE | | | 9B-72 SHALL BE REVIEWED AND APPROVED IN | | | WRITTING BY THE DESIGNER OF RECORD PRIOR | | | TO SUBMITTAL FOR " JURISDICTIONAL | | | APPROVAL", (LOCAL PRODUCT APPROVAL). | | | | | | 5) SITE PLAN NEEDS TO BE SUBMITTED TO | | | ADDRESSING PERSONEL JOHN HIGGINS FOR | | | ADDRESSING AS WELL AS NEW PLAT MAP FOR | | | THE COMBINATION OF LOTS. JOHN HIGGINS | | | CONTACT NUMBER IS (561)822-1239. | | | | | | 6) THE SURVEY DOES SHOW 2 SEPERATE LOTS | | | WHICH APPEAR TO CUT THROUGH BULDING "B" | | | AND BUILDING "C". A UNITY OF TITLE SHALL | | | BE REQUIRED, TABLE 601 AND 602. | | | | | | 7) SHEET A-1.1.2 BUILDING DATA FOR | | | TOWER#4 INDICATES 107 UNITS WHERE AS THE | | | SAME SHEET THE SITE PLAN INDICATES 108, | | | CORRECT DESCRIPANCY. | | | | | | 8) GEOTECHNICAL REPORT THAT WORK WAS | | | PREFORMED BY ARDAMAN NEEDS TO BE AN | | | ORIGINAL WITH SIGNATURE AND RAISED SEAL. | | | PLANS, SPECIFICATIONS,REPORTS OR OTHER | | | DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL | | | CONSTRUCTION ACTIVITY REGULATED BY THIS | | | CODE SHALL BE PERMORMED IN A MANNER SO | | | AS NOT TO ADVERSLY IMPACT THE CONDITION | | | OF ADJACENT PROPERTY, UNLESS SUCH | | | ACTIVITY IS PERMITTED TO AFFECT SAID | | | PROPERTY PURSUANT TO A CONSENT BY THE | | | APPLICABLE PROPERTY OWNER, UNDER TERMS & | | | CONDITIONS AGREEABLE TO THE APPLICABLE | | | PROPERTY OWNER.THIS INCLUDES BUT IS NOT | | | LIMITED TO THE CONTROL OF DUST, NOISE, | | | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND | | | THE STORAGE OF CONSTRUCTION MATERIALS. | | | NEW CONSTRUCTION ACTIVITY SHALL NOT | | | ADVERSELY IMPACT HISTORICSURFACE WATER | | | DRAINAGE FLOWS SERVING ADJACENT | | | PROPERTIES, & MAY REQUIRE SPECIAL | | | DRAINAGE DESIGNCOMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED | | | SITES.ACCORDINGLY, DEVELOPERS, | | | CONTRACTORS, AND OWNERS OF ALL NEW | | | RESIDENTIAL DEVELOPMENET, INCLUDING | | | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, | | | DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING IN A DECREASE IN | | | EXCESS OF 800SQ FT OF PERMEABLE LAND | | | AREA ON ANY PARCELL SHALL AS A PERMIT | | | CONDITION, PROVIDE A PROFESSIONALY | | | PREPARED DRAINAGE PLAN CLEARLY | | | INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE | | | IMPROVEMENT, A CERTIFICATE FROM A | | | LICENSED ENGINEER SHALL BE SUBMITTED TO | | | THE INSPECTOR IN ORDER TO RECEIVE | | | APPROVAL OF THE FINAL INSPECTION. | | | | | | 10)109.3.10.1 HURICANE PROTECTION. | | | IT SHALL BE UNLAWFUL FOR ANY PERSON TO | | | ALLOW CONSTRUCTION RELATED MATERIALS | | | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION | | | SITE FROM 24 HRS. AFTER A HURRICANE | | | WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN | | | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, | | | EQUIPMENT AND DEBRIS SHALL BE EITHER | | | REMOVED FROM THE CONSTRUCTION SITE OR | | | SECURED IN SUCH A MANNER AS TO MINIMIZE | | | THE DANGER OF SUCH CONSTRUCTION | | | MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | | DAMAGE TO PERSONS OR PROPERTY FROM | | | HIGHWINDS. | | | ANY PERSONS WHO FAILS TO COMPLY TO | | | REMOVE OR SECURE THE CONSTRUCTION | | | MATERIALS EQUIPMENT AND DEBRIS WITHIN | | | 24 HRS AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED SHALL BE SUBJECT TO A FINE NOT TO | | | EXCEED $500.00. | | | IN ADDITION TO THE ABOVE, A LICENSED | | | CONTRACTOR WHO VIOLATES THIS SECTION | | | SHALL BE SUBJECT TO DISCIPLINE PURSUANT | | | TO SECTION 113 OF THIS CHAPTER. | | | | | | 11) SHEET T-4 A2.1.1 | | | 11A) STAIR TOWER # 2, DOOR A/130 SWINGS | | | THE WRONG WAY,SEE 1008.1.2. | | | | | | 11B) ELEVATORS, PLEASE INDICATE THAT THE | | | ELEVATORS CAN ACCOMODATE AMBULANCE | | | STRETCHERS. 3002.4. | | | | | | 12)SHEET T-4 A2.1.1 FAIR HOUSING/ | | | ACCESIBLITY | | | 12A)PLANS DO NOT PROVIDE AN ACCESSIBLE | | | PATH TO THE BUS STOP. THE SIDEWALK STOPS | | | SHORT OF BUS STOP BENCH. THERE IS NO | | | PEDESTRIAN CROSSWALK CONNECTING THE | | | SIDEWALKS TO PUBLIC TRANS PORTATION. | | | | | | 12B) PROVIDE HOW THE HANDICAPPED | | | ACCESSIBLE PATH (SIDEWALKS) WILL BE | | | MAINTAINED DURING THE PHASING, PROVIDE A | | | SITE PLAN INDICATING ACCESSIBLITY TO THE | | | | | | PUBLIC WAY. | | | | | | 12C) PORTE COCHERE: THE PLANS DO NOT | | | INDICATE THERE IS A ACCESSIBLE LOADING | | | ZONE UNDER THE PORTE COCHERE. FAIR | | | HOUSING ANSI 4.6 | | | | | | 12D) PROVIDE SIGNAGE FOR HANDICAPPED | | | PARKING, AND VAN ACCESSIBLE PARKING. | | | | | | 12E) PLANS DO NOT INDICATE REACH RANGES | | | FOR THE COMMON USE MAIL BOXES. | | | | | | 12F) THERE IS NO KITCHEN DETAILS | | | INDICATING AN ACCESSIBLE SINK WITH | | | FORWARD APPOARCH. | | | | | | 12G) THE INDIVIDUAL UNITS WITH ENTRYS | | | WITH 45 DEGREE WALLS MISSING THE | | | REQUIRED 18" ON THE PULL SIDE OF DOOR. | | | SEE ANSI 4.13.6, ONLY REQUIED ON THE | | | EXTERIOR SIDE. | | | THE UNIT ENTRY DOORS WITH 45 DEGREE | | | WALLS ADJACENT TO THE FFRONT ENTRY DOOR | | | DO NOT MEET THE FAIR HOUSING GUIDELINE | | | FOR AN ACCESSIBLE FRONT ENTRY, SEE | | | ANSI 4.13FOR THE EXTERIOR SIDE LATCH | | | SIDE OF DOOR ONLY. | | | | | | 12H) IN BOTH STAIR TOWER 1 & 2 THE ARROW | | | INDICATING DIRECTION OF TRAVEL IS | | | BACKWARDS. WHEN CORRECTED THE PROBLEM | | | WITH REDUCED VERTICAL CLEARENCE UNDER | | | THE STAIRS WILL BE APPEARENT. ANSI 117.1 | | | SECTION 307.4 REQUIRING EITHER A | | | GUARDRAIL OR OTHER BARRIER WHERE THE | | | VERTICAL HEIGHT IS REDUCED LESS THAN | | | 80". | | | | | | 13) STAIR TOWER# 2 DOOR A/130 IS | | | SWINGING THE WRONG WAY, SEE 1008.1.2 | | | | | | 14) SHEET A2.1.1/ A2.1.3 | | | STAIR TOWER# 1& STAIR TOWER# 2 IN BOTH | | | CASES ONCE THE STAIR TOWER DOOR OPENS | | | LEAVES THE OCCUPANTS WITHIN THE CONFINES | | | OF THE BUILDING. THE DOORS AND WINDOWS | | | ON THE OPPOSITE WALL ARE NOT RATED. THE | | | LIFE SAFETY PLAN INDICATES IN BOTH CASES | | | A SINGLE MEANS OF EGRESS. | | | SEE 1013.5.1. THIS SECTION IS FOR | | | BALCONIES, THE SAME CONCERNS ABOUT | | | EGRESS APPLIES THAT THE OPENINGS WOULD | | | REQUIRE OPENING PROTECTIVES. | | | | | | 15) SHEET T-4 A2.2.1. | | | 15A) THE 2ND FLOOR AND HIGHER FLOORS | | | HAVE THE SAME PROBLEM WITH NOT HAVING AN | | | ELEVATOR LOBBY. THE AREA THAT SURROUNDS | | | THE ELEVATORS AND IS ENCLOSED NOT | | | MEETING THE DIFINITION OF AN OPEN | | | BALCONY (SEE 1013.5.2) AND WILL BE | | | CONSIDERED AS A CORRIDOR REQUIRING | | | A 1HR RATING SEE TABLE 1016.1. | | | | | | 15B) ELEVATOR LOBBIES SHALL MEET THE | | | REQUIREMENTS OF 707.1.14.1.THE LOBBY | | | SHALL SEPERATE THE ELEVATOR FROM THE | | | CORRIDOR BY FIRE PARTITIONS AND THE | | | REQUIRED OPENING PPROTECTION. | | | | | | 15C) UNIT A, UNIT B, UNIT C, UNIT E, | | | UNIT I, UNIT B AND UNIT A ARE EITHER | | | TOTALLY WITHIN A CORRIDOR OR PARTIALLY | | | WITHIN A CORRIDOR REQUIRING RATED | | | OPENING PROTECTIVES SEE TABLE 1016.1. | | | | | | 15D) NOTE IF WINDOWS REQUIRES FIRE RATED | | | GLASS, AS FAR AS I'M AWARE NO | | | MANUFACTURER MAKES FIRE RATED AND LARGE | | | MISSLE IMPACT RATED GLAZING!!!! SEE | | | THE BUILDING OFFICIALS INTERPRETATION ON | | | | | | LARGE OR HIGH RISE BUILDINGS AS FAR AS | | | SHUTTERS VS LARGE OR SMALL MISSLE RATED | | | GLASS. | | | ************************* | | | QUESTION# 13) RECOGNIZING SUCH CONCERNS | | | AS ABSENTEE OWNERS, OR CASES WHERE | | | LONGER TIME AND EFFORT IS NECESSARY TO | | | SECURE SHUTTERS ON LARGE OR MULTI-STORY | | | BUILDINGS, WHAT MEASURES ARE BEING | | | RECOMMENDED OR IMPLEMENTED TO ENSURE | | | THAT COMPLETE INSTALLATION OR SECURING | | | IS DONE SUFFICIENTLY IN ADVANCE OF THE | | | HURRICANE EVENT? | | | | | | IN MATTERS FLORIDA BUILDING CODE, 2004 | | | EDITION, PROVIDES THE ABILITY FOR THE | | | BUILDING OFFICIAL TO IMPLEMENT | | | REQUIREMENTS FOR ENSURING STABILITY, | | | STRENGTH, AND PROPER OPERATION OF | | | EXISTING BUILDINGS. | | | | | | IN ORDER TO ASSURE THE SECURING OF | | | SHUTTERS ON LARGE OR MULTI-STORY | | | BUILDING, OR MULTIPLE BUILDINGS ON THE | | | SAME PROPERTY, PRE-STORM PREPARATION | | | PLANS MUST BE SUBMITTED BY THE PROPERTY | | | OWNERS OR MANAGING AGENTS FOR REVIEW BY | | | THE CONSTRUCTION SERVICES DEPARTMENT. | | | ANY SUCH PLAN SHALL INCLUDE, AT A | | | MINIMUM, ON-SITE LOCATION OF SHUTTERS, | | | PARTY RESPONSIBLE FOR SECURING THE | | | SHUTTERS (SAID PARTIES MUST BE LOCATED | | | WITHIN PALM BEACH COUNTY), TOTAL NUMBER | | | OF OPENINGS TO BE PROTECTED AND TOTAL | | | TIME REQUIRED TO SECURE ALL OPENINGS. | | | PROTECTION OF OPENINGS SHALL BE | | | ACCOMPLISHED WITHIN TWELVE (12) HOURS OR | | | LESS OF THE OFFICIAL NOTIFICATION BY THE | | | NATIONAL WEATHER SERVICE OF A HURRICANE | | | WATCH. | | | | | | PROVISIONS IN THE BUILDING CODES (AND | | | THIS STANDARD) ARE NOT INTENDED TO | | | PROHIBIT THE USE OF ALTERNATIVE | | | MATERIALS AND METHODS, AND ALLOW THE | | | BUILDING OFFICIAL TO REVIEW AND APPROVE | | | ANY ALTERNATE DEEMED EQUIVALENT IN | | | QUALITY, STRENGTH, EFFECTIVENESS, FIRE | | | RESISTANCE, DURABILITY AND SAFETY | | | PRESCRIBED BY CODE. BASED UPON THIS CODE | | | PROVISION, ACCEPTANCE OF ALTERNATE | | | MATERIALS AND METHODS MAY BE APPROVED ON | | | A CASE-BY-CASE BASIS AND SHALL REQUIRE | | | SUFFICIENT EVIDENCE OR PROOF TO | | | SUBSTANTIATE ANY CLAIM MADE REGARDING | | | THE ALTERNATE. | | | | | | QUESTION# 14) ARE REMOVABLE STORM PANELS | | | APPROPRIATE FOR USE ON VERY LARGE, MID | | | OR HIGH-RISE STRUCTURES? | | | | | | NO, EXCEPT ON THE GROUND FLOOR. ON | | | COMMERCIAL AND MULTI-UNIT RESIDENTIAL | | | STRUCTURES, ABOVE THE FIRST LEVEL, | | | IMPACT RESISTANT GLAZING OR PERMANENTLY | | | AFFIXED PROTECTIVE DEVICES SHALL BE | | | INSTALLED. PERMANENTLY AFFIXED | | | PROTECTIVE DEVICES SHALL REQUIRE THE | | | WRITTEN APPROVAL OF THE BUILDING | | | OFFICIAL. | | | | | | 16)T-4 A.2.2.3 CODE REVIEW FOR HIGH RISE | | | BLDG DOES NOT INDICATE AS TO WHICH CODE | | | THIS BUILDING WAS DESIGNED TO. | | | | | | 17)SHEET T4-A2.4.1: | | | 17A) THIS PLAN HAS THE TERM "WALL | | | ANCHOR" PLEASE EXPLAIN? | | | | | | 17B) TERM E.O.S. EMERGENCY OVERFLOW | | | SCUPPER DOES NOT INDICATE ANY SECTIONS | | | THROUGH NOR GIVE SIZES, ADDITIONAL | | | INFORMATION REQUIRED. | | | | | | 17C) ROOF TOP MECHANICAL UNITS AS SHOWN | | | ON A6.1.3 DETAIL 8 INDICATES A MINIMUM | | | OF 18" FROM ROOF, SEE TABLE 1509.7 FOR | | | MINIMUM VERTICAL HEIGHTS. | | | | | | 18) T-4 A.2.5.1-A2.5.3 ARE FOR AN AREAL | | | COVERED WALKWAY . SHEET T-4 A.3.1.3, | | | NOTE, THAT A SEPERATE PERMIT WILL BE | | | SUBMITTED FOR CONSTRUCTION OF AREAL | | | COVED WALKWAY. THESE PAGES WILL BE | | | STRUCK "VOID" AND THE ASSOCIATED | | | STRUCTURAL PAGES. | | | | | | 19) SHEET T-4 A2.4.2 INDICATES 3 ATTIC | | | AREAS NO USEAGE INDICATED. 1509.2 A | | | PENTHOUSE, BULKHEAD OR ANY OTHER SIMILAR | | | PROJECTION ABOVE THE ROOF SHALL NOT BE | | | USSED FOR PURPOSES OTHER THAN SHELTERING | | | OF MECHANICAL EQUIPMENT OR SHELTEROF | | | VERTICAL SHAFT OPENINGS IN THE ROOF. | | | PENT HOUSES USSED FOR PURPOSES OTHER | | | THAN PERMITTED BY THIS SECTION SHALL | | | CONFORM TO THE REQUIREMENTS OFTHIS CODE | | | FOR AN ADDITIONAL STORY. | | | | | | 20) THE ELEVATION SHEETS AND A6.1.1 | | | DEPICT DETAILS WITH CAST RESIN CORNICE | | | AND BANDS ON THE EXTERIOR OF THE | | | BUILDING. 1406.2.2 ARCHITECTURAL TRIM | | | THAT EXCEEDS 40FT IN HEIGHT ABOVE GRADE | | | PLANE SHALL BE CONSTRUCTED OF APPROVED | | | NONCOMBUSTIBLE MATERIALS AND SHALL BE | | | SECURED TO THE WALL WITH METAL OR OTHER | | | APPROVED NONCOMBUSTIBLE BRACKETS. | | | | | | 21)T-4A6.1.3 DETAIL# 11/ A5.1.3 BOTH SEC | | | TIONS INDICATE USE OF R-30 INSULATION. | | | THE INSULATION IS DEPICTED TO BE IN THE | | | TOP CHORD OF THE METAL TRUSS. THE | | | TRUSSES ARE CENTERED @ 48" O. C. HOW | | | WILL THE INSULATION BE ATTACHEDAND TO | | | WHAT? | | | | | | 22) T-4 A6.1.3 DETAIL# 11 ALSO INDICATES | | | THE USE OF INTEGRAL ROOF DECK PROVIDE | | | ADDITIONAL INFORMATION. | | | | | | 23) SAME DETAIL AS ABOVE WHAT SPANS CAN | | | THE GALVANIZED METAL FURRING SPAN @ 12" | | | O. C. PROVIDE THE PSF APPLIED LOAD, AND | | | THICKNESS OF HI HAT IN MIL. SPANS TO BE | | | TAKEN AS MULTIPLE SPANS? | | | | | | 24) T-4 A7.2.1 THE DOOR SCHEDULE UNDER | | | REMARKS HAS NO NOTATIONS, AS TO REQUIRED | | | HARDWARE, SELF-CLOSING DOORS AND DROP | | | SEALS PLEASE PROVIDE THIS ADDITIONAL | | | INFORMATION. | | | | | | 24A) 709.3 FIRE-RESISTANCE RATING. A1 | | | HOUR FIRE-RESISTANCE RATING IS REQUIRED | | | FOR SMOKE BARRIERS. | | | | | | 24B) 710.5.2 SMOKE AND DRAFT-CONTROL | | | DOORS. WHERE REQUIRED ELSEWHERE IN THE | | | CODE, DOORS IN SMOKE PARTITIONS SHALL BE | | | TESTED IN ACCORDANCE WITH UL 1784 WITH | | | AN ARTIFICIAL BOTTOM SEAL INSTALLED | | | ACROSS THE FULL WIDTH OF THE BOTTOM OF | | | THE DOOR ASSEMBLY. | | | | | | 24C) DOOR A-129 STYLE"K" IS LOUVER THIS | | | CORRIDOR TO BE 1HR RATED, CORRECT | | | | | | 24D) DOOR 104,107, 110 & 112 FOR 2ND | | | FLOOR & ABOVE WILL ALL REQUIRE RATED | | | DOORS IN CORRIDOR. | | | | | | 25) 1406.2.2 ARCHITECTURAL TRIM THAT | | | EXCEEDS 40 FT IN HEIGHTABOVE GRADE | | | SHALL BE CONSTRUCTED OF APPROVED | | | NONCOMBUSTIBLE MATERIALS. SEE DEFINITION | | | OF NON-COMBUSTIBLE MATERIAL. | | | | | | 26) T-3 A5.1.5: | | | 26A) DETAILS SHOW A DROPPED CEILING OVER | | | WALKWAYS WITH METAL FRAMING NO | | | INDICATION AS TO THE ATTACHMENT TO THE | | | DECK ABOVE, SPACING OF ATTACHMENET, | | | GAUGE OR SIZE OF FRAMING OR SPACING OF | | | FRAMING. | | | 26B) PLANS INDICATE THAT THE FINISH WILL | | | BE A CEMENT PLASTER FINISH THIS MEANS A | | | TRUE CEMENT PLASTER FINISH AND NOT EFIS? | | | EFIS SYSTEMS INDICATE NOT TO BE USED ON | | | HORIZONTAL SURFACES. | | | | | | 27)FIRE SPRINKLER PLANS: | | | 27A)FS1.1 INDICATES THAT THERE IS NO | | | FIRE PUMP LOCATED IN HIGHRISE TOWER# 3. | | | | | | 403.8 & 911 BOTH DEAL WITH THE FIRE | | | COMMAND CENTER WHICH REQUIRES BOTH A | | | FIRE PUMP AND GENERATOR. FS.1 INDICATES | | | A SHARED FIRE PUMP FOR THREE BUILDINGS, | | | THE CODE ISN'T CLEAR AS TO IF THE FIRE | | | PUMP CAN BE SHARED OF NOT. IN SPEAKING | | | WITH THE FIRE REVIEWERS THIS MAY NOT BE | | | AN ACCEPTABLE METHOD OR APPLICATION. | | | THE PRESENT LOCATION OF THE FIRE PUMP IS | | | IN A PARKING GARAGE THAT HASN'T EVEN | | | APPLIED FOR A PERMIT. THE SECOND ISSUE | | | WILL BE THE SIZE OF THE FIRE PUMP IF THE | | | LOCATION IS ACCEPTED, PROVIDE THE | | | DOCUMENTATION FOR THE SIZE OF THE FIRE | | | PUMP REQUIRED FOR THE 3 BUILDINGS IT | | | WILL SERVICE. | | | | | | 28) T3 A2.1.1 DOESN'T INDICATE THE | | | LOCATION OF THE EMERGENCY GENERATOR, | | | 403.10 A STANDBY POWER SYSTEM COMPLYING | | | WITH 2702 SHALL BE PROVIDED FOR STANDBY | | | POWER LOADS SPECIFIED IN SECTION | | | 403.10.2 AND ALSO NFPA 110 & 111. | | | | | | 29) FS2.1 IS MISSING THE FIRE SPRINKLERS | | | IN THE CORRIDORS THAT FRONT EACH UNIT. | | | ALSO REMOVE THE LIGHTING SYMBLES THAT | | | ARE LOCATED IN THE SAME CORRIDOR. | | | | | | 30) SECTION 911.1 OF THE CODE DEALS WITH | | | THE FIRE COMMAND CENTER AND THE | | | ASSOCIATED SYSTEMS (15) THAT ARE | | | REQUIRED FOR A HIGH RISE BUILDING. | | | SUBMIT A LAYOUT OF THE FIRE COMMAND | | | CENTER AND ALL FEATURES REQUIRED BY THE | | | SECTION TO BE CONTAINED THEREIN SHALL BE | | | SUBMITTED FOR APPROVAL PRIOR TO | | | INSTALLATION. | | | | | | 31)SHEET M2.5 HAS NO INDICATION OF A | | | SMOKEPROOF EXIT ENCLOSURE, SEE 403.13 | | | ALSO SEE 1019.1.3 FOR REQUIRED | | | VENTILATION, AND 909.20 FOR PRESSURIZED | | | STAIRS. | | | | | | 32)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-05-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-05-01 |
Time |
18:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-27 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2006-05-01 00:00:00 | ************ UNSAT 2ND REVIEW ********* | | | | | | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW | | | WHICH NEED TO BE ADDRESSED AND SOME NEW | | | NOTES DUE TO CHANGES IN PLANS. | | | | | | ** PLEASE SEE NOTE BELOW ARE TAKEN | | | DIRECTLY FROMPREVIOUS REVIEW AND ARE | | | SO NOTED. | | | | | | ************************************** | | | PLEASE SEE NOTES AT THE END OF COMMENTS | | | WITH RESPECT TO REMOVAL OF ALL | | | OLD/VOIDED SHEETS. | | | ************************************** | | | | | | | | | SAIL CLUB TOWER #4 | | | | | | | | | | | | | | | 1)NOTE:NOTE #1 NO, PLEASE SEE PLANS | | | STILL REFLECT AND NOTE THE 1999 NEC. | | | PLEASE ALSO SEE REVISED ELECTRICAL PLANS | | | ARE REQUIRED TO REFLECT THE CODES AND | | | YEARS IN EFFECT FOR DESIGN. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE CODE REFERENCED ON PLANS LIST | | | THE 1999 NEC. PLEASE KNOW, AS OF JULY | | | 1ST 2003, THE STATE ADOPTED THE 2002 | | | NEC. | | | PLEASE ALSO SEE WE ARE UNDER THE 2003 | | | NFPA-101 AND 2002 NFPA-72 | | | PLEASE ADJUST. | | | | | | 2)NOTE: NOTE #2, OK, HOWEVER PLEASE SEE | | | ANYBLDG, FIRE REVIEW COMMENTS AS THEY | | | MAY AFFECT DESIGN. PLEASE SEE NEW | | | COMMENTS DUE TO CHNAGES AT FPL VAULT | | | LOCATION. | | | | | | 3)NOTE: NOTE #3 NO, PLEASE SEE AREAS | | | WHERE SOME CIRCUTING IS STILL MISSING. | | | | | | ** PREVIOUS NOTE** | | | PLEASE SHOW ALL CIRCUITING ON PLANS AND | | | CORRELATE WITH THE SUBMITTED PANEL | | | SCHEDULES. | | | PLEASE SEE SOME AREAS WHICH ELECTRICAL | | | FIXTURES SEEM TO BE MISSINGTHIS. | | | PLEASE ALSO SEE CIRCUITING FOR UNITS. | | | PLEASE KNOW, A "TYPICAL" UNIT LAYOUT MAY | | | BE PROVIDED, HOWEVER A LAYOUT WOULD BE | | | REQUIRED FOR EACH UNIT TYPE, INCLUDING | | | STUDIO UNIT. | | | CIRCUITING FOR SOME UNITS/ITEMS CAN NOT | | | BE VERIFIED AT THIS TIME. | | | | | | 4)NOTE: NOTE #4 NO, PLEASE SEE REPSONSE | | | LETTER MENTIOSN TO SEE E 3.1, HOWEVER | | | PLEASE SEETHIS SHEET ONLY SHOWS ONE | | | AREA OF FIRST FLR COMMON AREA. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE PROVIDE PHOTO-METRICS FOR | | | STAIR TOWERS ON NORMAL PWR AND STAND-BY. | | | ALONG WITH WALK AREAS. | | | PLEASE SEE STAIR TOWERS UNDER NORMAL PWR | | | SHALL MEET A MIN OF 10FT CANDLES. PLEASE | | | SEE ARES FOR HALLS ETC ARE PERMITTED TO | | | BE LESS. . | | | PLEASE SEE NFPA-101 7.8.1.3,7.9.2.1 | | | | | | 5)NOTE: NOTE #5 NO, PLEASE KNOW, A | | | BATTERY BACK UP FIXTURE OF SOME SORT | | | WILL BE REQUIRED IN STAIR TOWERS AT A | | | MIN OF EVERY OTHER LEVEL. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE KNOW, BATTERY BACK FIXTURES WILL | | | BE REQUIRED AT EVERY OTHER LEVEL(MIN). | | | PLEASE SEE LS 101 WHICH MENTIONS THE | | | TRIPPING/THROW OF A SINGLE BRKR SAHLL | | | NOT LEAVE ANY EGRESS AREA IN TOTAL | | | DARKNESS. PLEASE CALL ELECTRICAL PLAN | | | REVIEW AND FIRE MARSHALS OFFICE TO GO | | | OVER OPTIONS PERMITTED. | | | A BATTERY BACK-UP FIXTURE AT EVERY OTHER | | | LEVEL WILL SATISFY FIRE MARSHAL'S OFFICE | | | AND AHJ. | | | PLEASE BE SURE TO MEET THE MIN OF 1 | | | FT/CANDLE UNDER EM. | | | PLEASE BE SURE TO SEE PREVIOUS NOTE #4 | | | FOR LIGHTING LEVELS.(MIN) | | | | | | 6)NOTE: NOTE#6 NO, PLEASE SEE MOST | | | FIXTURES WERE ADDED TO THESE ROOMS, | | | HOWEVER PLEASE SEE ELEVATOR MACHINE ROOM | | | WHICH WILL REQUIRE ARE BATTERY BACK | | | FIXTURE OF SOME SORT. | | | IT WAS NOTED, THAT LTS ARE ON EM | | | CIRCUIT, HOWEVER A BATTERY BACK UP | | | FIXTURE WILL BE REQUIRED. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE PROVIDE BATTERY BACK-UP | | | FIXTURES IN MAIN ELECTRICAL RMS AND | | | ELEVATOR ROOM(S), GENERATOR AND FIRE | | | PUMP ROOM. PLEASE ALSO PROVIDE | | | CIRCUITING FOR THESE | | | RMS. | | | | | | 7)NOTE: NOTE #7 NO, RESPONSE MENITONS TO | | | SEE E 5.1, HOWEVER NO DETAIL WAS SHOWN | | | ON PLANS. | | | PLEASE ALSO KNOW DETAILSHALL INCLUDE | | | CURBING ALL FOUR SIDES. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE PROVIDE CURB DETAIL FOR | | | BUS-DUCT RISER AND FLOOR PENATRATIONS. | | | 368.6 | | | | | | 8)NOTE: NOTE #8, OK, HOWEVER PLEASE | | | CONTINUE WITH NOTE FOR ALL MIN | | | CLEARENCES PER 110.26 SHALL BE MET. | | | NOTE FOR PANIC HARDWARE WAS ADDED WHICH | | | WAS OK. | | | NOTE WAS NOT ADDED FOR ALL. | | | | | | ** PREVIOUS NOTE ** | | | PLEASSE PROVIDE NOTE ON RISER AND | | | ELECTRICAL ROOM SHEETS FOR REQUIREMENTS | | | FOR 110.26 FOR PANIC HARDWARE AND DOOR | | | SWINGS. PLEASE SEE MIN CLEARENCE PER | | | 110.26 | | | PLEASE ALSO SEE MIN DOOR OPENING 6' WITH | | | SINGLE ACCESS FOR EQUIPMENT MORE THAN | | | 1200A'S AND OVER 6' WIDE. | | | | | | | | | 9)NOTE:NOTE # 9, OK, CHANGED TO | | | FEEDERS FROM BUS-DUCT, HOWEVER PLEASE | | | SEE NEW COMMENTS FOR VAULT AND FOR | | | SIZING OF SEC'S. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE RISER INDICATES ALL | | | BUS-DUCT FROM FPL VAULT TO MAIN | | | ELECTRICAL ROOM AS OVER-HEAD. PLEASE SEE | | | 230.70, 230.6, NO MORE THAN 8' OF | | | UNPROTECTED CONDUCTORS/ OR BUS DUCT | | | PERMITTED "INSIDE THE BLDG. | | | PLEASE SEE ROUTING OF BUS-DUCT APPEARS | | | TO SHOW INSTALLATION INSIDE CONDO | | | UNITS?? | | | PLEASE PROVIDE LAYOUT, REVISE TO | | | UNDER-GROUND FEEDERS OR OTHER ACCEPTABLE | | | MEANS. | | | | | | 10)NOTE: NOTE #10, NO, ?? PLEASE SEE | | | PLANS INDICATE THIS AS HAVING A 3-POLE | | | MAIN, HOWEVER THERE IS NO INDICATION OF | | | THE MANUAL MENAS OF DISCONNECT, LOCATED | | | ON THE OUTSIDE. RESPONSE MENTIONS THIS | | | WAS ADDRESSED IN A PREVIOUS REVISION, | | | HOWEVER WE HAVE NOT SEEN ANY OTHER | | | REVSIONS BEFORE THIS SUBMITTIAL. PLEASE | | | SEE NEW NOTES FOR MAIN AS NOTED ON RISER | | | "KEY NOTES"". | | | | | | ** PREVIOUS NOTES ** | | | PLEASE PROVIDE INFORMATION ON | | | BUS -DUCT RISER MAINS. APPEARS TO SHOW | | | THESE AS "SHUNT-TRIP" AND NOT CONTAINING | | | A MANUAL MEANS OF DISCONNECT LOCATED ON | | | THE OUTSIDE OF THE EQUIPMENT. PLEASE SEE | | | MAIN PANEL SCHEDULE(S), THESE DO NOT | | | SEEM TO INDICATE A MCB. | | | 230.76,230.79 | | | | | | 11)NOTE: NOTE #11, OK, HOWEVER SEE NOTES | | | UNDER GARAGE PERMIT FOR ROOMS. | | | PLEASE ALSO PROVIDE MIN LAYUOUT , AS | | | THESE CAN BE REFERENCED UNDER A SEPARATE | | | PERMIT. PLEASE SEE RESPONSE MENTIONS TO | | | SEE REVISED 4.1, HOWEVER ONLY THE GEN RM | | | SHOWS SOME SORT OF ELECTRICAL. PLEASE | | | SEE MIN FT CNADLE FOR GEN RM SHAL BE 30 | | | FT CANDLES, WHICH IS NOTED UNDER GARAGE | | | PERMIT. | | | PLEASE ALSO KNOW, THESE AREAS WHERE THE | | | GARAGE IS LOCATED SHALL BE 100% COMPLETE | | | AND A CO MUST BE OBTAINED BEFORE | | | ISSUANCE OF ANY TCO OR CO FOR TOWER | | | BUILDINGS. THIS IS ONLY ANOTE AT THIS | | | TIME TO HELP WITH THE PHASING OF THE | | | PROJECT. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE GARAGE PLANS FOR FIRE PUMP | | | RM AND GEN RM ARE SHOWN BLANK? | | | | | | 12)NOTE: NOTE #12 NO, PLEASE SEE | | | REPSONSE MENTIONS TO SEE E5.2, HOWEVER | | | E5.2 DOES NOT REVISE INFORMATION ON | | | BUS-DUCT? PLEASE CORRELATE WITH NOTES ON | | | E0.1 AS NOTES SEEM TO CHNAGE ALL | | | BUS-DUCT TO COPPER. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE PROVIDE SPECIFIC INFORMATION ON | | | BUS-DUCT, PLEASE SEE AN ALUM EQUIPMENT | | | GROUNDING CONDUCTOR/ MATERIAL IS NOT | | | PERMITED. | | | 310.2. LOCAL AMENDMENTS. | | | | | | 13)NOTE: NOTE #13 NO, RESPONSE MENTIONS | | | FOR CONTRACTOR TO SUBMIT, HOWEVER THIS | | | WAS NOT DONE. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SUBMIT ALL MANUFACTURE SPECS AND | | | CUT SHEETS FOR GENERATOR, ATS, | | | FIRE PUMP AND FIRE PUMP CONTROLLER. | | | PLEASE ALSO SUBMIT THE SAME FOR ANYSUB | | | BASE FUEL TANK. | | | PLEASE KNOW, DUE TO THE INFORMATION NOT | | | BEING SUBMITTED AT THIS TIME, REVIEW FOR | | | SOME ITEMS FOR CODE COMPLIANCE CAN NOT | | | BE DONE. | | | UNABLE TO VERIFY CODE COMPLIANCE FOR | | | MANY ITEMS UNDER NFPA, 20,70,101,110 | | | ETC. | | | SOME INFORMATION IS "APECIFIED" ON PLANS | | | FOR TOWER #4, HOWEVER, TOWER #3 SHOULD | | | REFLECT THE SAME INFORMATION. ALL | | | MANUFACTURE CUTS/SPECS ARE STILL | | | REQUIRED. | | | | | | 14)NOTE:NOTE # 14 NO, SAME NOTE. | | | RESPONSE MENTIONS TO SEE REVISED, | | | HOWEVER COULD NOT LOCATE INFORMATION | | | NEEDED. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE ELECTRICAL RISER DIAGRAM DOES | | | CONTAININFORMATION FOR FIRE PUMP, YET | | | NOT FIRE PUMP CONTROLLER, | | | SERVICE, SIZING, LOCKED ROTOR SETTINGS | | | ETC. | | | PLEASE COMPLETE. | | | ENCASEMENT IN CONCRETE, OUTSIDE THE | | | BLDGS, ETC | | | | | | 15)NOTE: NOTE #15 OK,SEE NOTE MENTIONED | | | ABOVE. | | | | | | 16)NOTE: NOTE #16, OK, HOWEVER PLEASE | | | SEE NEW COMMENT FOR H12A. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE A PANEL SCHEDULE FOR A PANEL | | | H12B IS SUBMITTED, HOWEVER THIS PANEL | | | COULD NOT BE LOCATED ON RISER | | | DIAGRAM?? | | | PLEASE CORRELATE. | | | | | | 17)NOTE: NOTE #17 YES AND NO, PLEASE SEE | | | THE FIRST PART OF THE NOTE REQUESTED A | | | TYPICAL DISCONNECT DETAIL WHICH WAS | | | DONE, HOWEVER PLEASE SEE HEAT FOR AHU'S | | | FOR UNITS STILL DO NOT COORELATE. PLEASE | | | ALSO SEE NOTE #41 | | | | | | ** PREVIOUS NOTE ** | | | PART 2) | | | PLEASE CORRELATE ALL A/C KW RATINGS AND | | | LOADS WITH MECHANICAL PLANS. (KW RATINGS | | | ETC. ) | | | | | | | | | 18)NOTE:NOTE #18 NO, PLEASE RESPONSE | | | MENTIONS TO SEEE5.1 FOR REVISED PLANS, | | | HOWEVER 5.1DID NOT SHOW THIS? PLEASE | | | SEE A ROOM LAYOUT ON3.1 WAS LOCATED, | | | HOWEVER DID NOT SEEM TO CONTAIN ALL | | | REQUIRED EQUIPMENT, PANELS ETC. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE FIRE REVIEW NOTES | | | ALSO: PLEASE PROVIDE A LAYOUT FOR | | | CENTRAL STATION RM(FIRE COMMAND RM) | | | SHOWING ALL DEVICES/ PANELS/ STATUS | | | PANELS ETC. | | | PLEASE LIST ALL ITEMS AS SPECIFIED IN | | | NFPA- 101 11.8.5, | | | | | | 19)NOTE: PLEASE SEE MOST WERE CORRECTED, | | | ONLY ONE OR TWO WERE MISSING OR LOCATED | | | NOT TO SPACING, THESE CAN BE REDLINED , | | | HOWEVER IF REDLINES ARE VIEWED, PLEASE | | | SEE POSSIBLE AREAS. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE RECEPTS MISSING PER | | | 210.52 | | | SEE REDLINED PLANS. | | | | | | 20)NOTE:NOTE #20 OK. | | | | | | 21)NOTE:NOTE #21 OK. | | | | | | 22)NOTE: NOTE #22 NO, COULD NOT LOCATE | | | NOTE. RESPONSE MENTIONS E0.1 | | | | | | ** PREVIOUS NOTE ** | | | PLEASE PROVIDE NOTE ON PLANS FOR SMOKE | | | DETECTOR PLACEMENT PER REQUIREMENTS NFPA | | | -72 11.8.3.5. | | | | | | 23) NOTE: NOTE #23 OK.: | | | | | | 24) NOTE: NOTE #24 OK. | | | | | | 25)NOTE: NOTE #25 OK, HOWEVER PLEASE SEE | | | NEW NOTE. (MINOR CHANGE NEED FOR PANEL | | | SCHEDULE. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE A 70A BRKR IS BEING SHOWN FOR | | | RANGE?? PLEASE SEE 210.23,422.11B | | | 50A RANGE RECEPT, 50A BRKR MAX. | | | | | | 26)NOTE: PLEASE SEE PANEL SCHEDULES SEEM | | | TO SHOW "A" AND "C" PHASE FOR SINLGLE | | | PHASE SERVICE AND UNITS?? | | | PLEASE CLARIFY / ADJSUT. | | | 215.5 | | | | | | 27)NOTE: NOTE #27 NO, PLEASE SEE MANY | | | AREAS SHWON AS LIVING RM AND CIRCUITED | | | FOR SMALL APPLIANCE. PLEASE SEE AREAS | | | SEEM TO HAVE IDENTIFICATION SWITCHED. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE LABEL AND /OR CLARIFY "DINING" | | | AREAS IN ALL UNITS. | | | UNABLE TO VERIFY CIRCUITING AS DINING | | | /LIVING ARE SEEMED TO BE COMBINED.' | | | PLEASE SEE 210.52B1 | | | | | | 28)NOTE:OK. | | | | | | 29)NOTE: NOTE #29, NO, PLEASE SEE | | | REDLINED PLANS AS SOME AREAS FOR HALLWAY | | | WALLS. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE MISSING RECEPTS IN HALLWAY | | | AREAS, 10' OR MORE OF CONTINUOUS | | | WALL. 210.52H. | | | | | | 30)NOTE: NOTE #30 NO, ? PLEASE SEE | | | REPSONSE MENTIONS TO SEE REVISED 5.1, | | | HOWEVER NO CHANGES COULD BE LOCATED TO | | | PLANS. | | | PLEASE ALSO SEE NO PANEL SCHEDULE ETC | | | WAS SUBMITTED.? | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE RISER SEEMS TO INDICATE A | | | POOL PANEL, HOWEVER NO OTHER | | | INFORMATION WAS SUBMITTED AND PANEL | | | COULD NOT LOCATED ON PLANS. | | | LOADS ETC. | | | 215.5, 220 | | | | | | 31)NOTE: OK, AS NOTED. | | | | | | 32)NOTE: NOTE #32 NO, AS IT SEEMS NOTE | | | WAS NOT COMPLETE. PLEASE SEE RESPONSE | | | MENTIONS "LIGHTNING PROTECTION NOT | | | REQUIRED", THIS IS TRUE AND NOTE WAS NOT | | | TO REQUEST A LPS. | | | PLEASE PLACE A NOTE ON "ROOF PLANS" | | | WHICH STATES "ANY LIGHTNING PROTECTION | | | SYSTEM INSTALLE SHALL MEET NFPA-780 AND | | | SHALL BE UNDER A SEPARATE PERMIT." | | | OR WORDS TO THAT AFFECT. | | | SOMEHOW THE NOTE WAS NOT PRINTED AS | | | TYPED? | | | | | | ** PREVIOUS NOTE ** | | | PLEASE PLACE NOTE ON "ROOF PLANS" WHICH | | | WILL REQUIRE ALL LIGHTNING PROTECTION | | | | | | | | | 33)NOTE:OK. | | | | | | 34)NOTE: OK. | | | | | | 35)NOTE: OK. | | | | | | 36) NOTE:OK | | | | | | 37)NOTE: OK, HOWEVER SEE NEW NOTE. | | | | | | 38)NOTE: OK. | | | | | | 39)NOTE: NOTE: NO, PLEASE SEE RESPONSE | | | MENTIONS TO SEE RISER E5.1? THIS COMMENT | | | IS FOR JOBSITE SPEC BOOKS. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SUBMIT "SPEC BOOKS' FOR REVIEW OF | | | PROJECT. | | | THESE WOULD CONTAIN JOBSITE SPECS. | | | | | | 40)NOTE:OK. | | | | | | 41)NOTE:NOTE #41 NO, PLEASE SEE | | | MECHNICAL PLANS AS NOTED ABOVE FOR KW | | | RATINGS INDICATED. | | | PLEASE SEE THIS COMMENT WAS FOR UNITS | | | AND SOME IN HOUSE AREAS. | | | YES, THE OCP WAS SHOWN CORRECT AT 125% | | | ON ELECTRICAL PANEL SCHEDULE FOR THE KW | | | HEAT WHICH WAS SHOWN. PLEASE KNOW, THE | | | COMMENT WAS BASED ON KW AS INDICATED ON | | | MECHANICAL PLANS AND NOTE #17. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE MIN OCP FOR AHU HEAT | | | TO BE 125%. 424.3B | | | SHOWS 50A OCP. | | | | | | 42)NOTE: OK. | | | | | | | | | *************************************** | | | *************** NEW NOTES ************* | | | | | | 1) NOTE: PLEASE SEE "KEY NOTE" #8 WHICH | | | NOW MENTIONS A 3000A MCB FOR BUS RISER | | | "ML", HOWEVER SEC'S ARE ONLY RATED FOR | | | 2520A'S. PLEASE SEE 240.4C FOR DEVICES | | | RATED OVER 800A'S. | | | PLEASE ALSO CORRELATE AS BUS-DUCT RISER | | | IS ONLY RATED @ 2500A'S. | | | 240.4,310.16 ETC. | | | 215.5 | | | | | | 2) NOTE: PLEASE SEE H12A, PLANS NOW SHOW | | | H12B BEING FED FROM THIS, PLEASE | | | INDICATE IF "FEED THRU LUGS" OR IF OCP | | | AND FEEDERS ARE BEING INSTALLED. | | | 215.5 | | | | | | 3) NOTE: PLEASE INDICATE ON PANEL | | | SCHEDULE ALL APPLIANCES AS GAS WHERE | | | APPLICABLE. "GAS RNAGE", GAS WH" ETC. | | | | | | 4) NOTE: PLEASE SEE A GORUNDING NOTE #19 | | | ON RISER AT GENERATOR MENTIONS TO SEE | | | KEY NOTE FOR THIS, HOWEVER #19 ON KEY | | | NOTES IS BLANK? | | | | | | 5) NOTE: PLEASE SEE 7.1 AS THIS SEEM TO | | | CONTAIN A "MISPRINT" FOR THE ATS IN THE | | | MAIN ELECTRICAL ROOM. THIS IS SHOWN AS | | | ATS-3, HOWEVER THIS IS TOWER #4. | | | | | | 6) NOTE: PLEASE OBTAIN A LETTER OF | | | APPROVAL FROM FPL ( MR. BILL HARTIGAN | | | FOR APPROVAL AND CHANGE OF FPL VAULT AS | | | SHOWN. | | | PLEASE ALSO SEE NOTES FOR TOWER #3 FOR A | | | SIMILAR COMMENT. | | | | | | | | | | | | ** PLEASE KNOW, MANY OF THE ABOVE ITEMS | | | ARE "REDLINED" AT LOCATIONS ON PLANS FOR | | | NOTES. | | | | | | ** PLEASE KNOW, A RESPONSE LETTER IN | | | TYPE WRITTEN FORM WILL HELP IN RESPONSES | | | TO ELECTRICAL COMMENTS. | | | | | | ** PLEASE BE SURE TO SEE ANY POSSIBLE | | | COMMENTS FROM OTHER TRADES WHICH MAY | | | AFFECT ELECTRICAL PLANS. | | | | | | ************************************ | | | | | | ** PLEASE KNOW IT WAS REQUESTED ON | | | PREVIOUS REVIEW BEFORE RESUBMITTING | | | PLANS FOR ALL OLD/VOIDED SHEETS TO BE | | | COMPLETELY REMOVED FROM SETS. PLEASE SEE | | | THIS WAS NOT DONE AND ALL NEW SHEETS | | | WERE INSERTED INTO NEW SETS. PLEASE | | | KNOW, WE ONLY REQUIRE "ONE" COPY OF THE | | | OLD REMOVED SHEETS. THESE SHOULD BE | | | BUNDLED INTOONE SET AND SUBMITTED | | | ALONG WITH THE THREE NEW REVISED SETS. | | | PLEASE KNOW, THIS WILL EFFECT THE PLAN | | | REVIEW PROCESS AND HELP TO EXPEDITE | | | PROJECT. | | | | | | *********************************** | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | 2006-04-28 00:00:00 | REVIEW IN PROGRESS. | | 2006-04-27 00:00:00 | IN ELEC FOR REVIEW. | | | REVIEW TO CONTINUE ON 4/28 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-28 |
Time |
19:20 |
Rev Time |
12.00 |
| Received By |
dpalmer |
Date |
2005-09-11 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2005-09-29 00:00:00 | SAIL CLUB TOWER #4 | | | | | | **** UNSAT **** | | | | | | | | | 1)NOTE: PLEASE SEE CODE REFERENCED ON | | | PLANS LIST THE 1999 NEC. PLEASE KNOW, AS | | | OF JULY 1ST 2003, THE STATE ADOPTE DTHE | | | 2002 NEC. | | | PLEASE ALSO SEE WE ARE UNDER THE 2003 | | | NFPA-101 AND 2002 NFPA-72 | | | PLEASE ADJUST. | | | | | | 2)NOTE: PLEASE SEE BLDG /FIRE REVIEW | | | COMMENTS FOR STAIR TOWER EXITING WHICH | | | WILL AFFECT ELECTRICAL LAYOUT. | | | EXITS BACK INTO HALL WAY AREAS IN FRONT | | | OF UNITS. | | | PLEASE ALSO SEE POSSIBLE NOTES FOR | | | EXITING OUTSIDE TRASH ROOM. | | | PLEASE SEE BLDG REVIEW FOR STAIR TOWER | | | #2 AND SWING OF DOOR AND PATH OF EGREES | | | TRAVEL. | | | | | | 3)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULES. | | | PLEASE SEE SOME AREAS WHICH ELECTRICAL | | | FIXTURES SEEM TO BE MISSINGTHIS. | | | PLEASE ALSO SEE CIRCUITING FOR UNITS. | | | PLEASE KNOW, A "TYPICAL" UNIT LAYOUT MAY | | | BE PROVIDED, HOWEVER A LAYOUT WOULD BE | | | REQUIRED FOR EACH UNIT TYPE, INCLUDING | | | STUDIO UNIT. | | | CIRCUITING FOR SOME UNITS/ITEMS CAN NOT | | | BE VERIFIED AT THIS TIME. | | | | | | 4)NOTE: PLEASE PROVIDE PHOTO-METRICS FOR | | | STAIR TOWERS ON NORMAL PWR AND STAND-BY. | | | ALONG WITH WALK AREAS. | | | PLEASE SEE STAIR TOWERS UNDER NORMAL PWR | | | SHALL MEET A MIN OF 10FT CANDLES. PLEASE | | | SEE ARES FOR HALLS ETC ARE PERMITTED TO | | | BE LESS. . | | | PLEASE SEE NFPA-101 7.8.1.3,7.9.2.1 | | | | | | 5)NOTE: | | | PLEASE KNOW, BATTERY BACK FIXTURES WILL | | | BE REQUIRED AT EVERY OTHER LEVEL(MIN). | | | PLEASE SEE LS 101 WHICH MENTIONS THE | | | TRIPPING/THROW OF A SINGLE BRKR SAHLL | | | NOT LEAVE ANY EGRESS AREA IN TOTAL | | | DARKNESS. PLEASE CALL ELECTRICAL PLAN | | | REVIEW AND FIRE MARSHALS OFFICE TO GO | | | OVER OPTIONS PERMITTED. | | | A BATTERY BACK-UP FIXTURE AT EVERY OTHER | | | LEVEL WILL SATISFY FIRE MARSHAL'S OFFICE | | | AND AHJ. | | | PLEASE BE SURE TO MEET THE MIN OF 1 | | | FT/CANDLE UNDER EM. | | | PLEASE BE SURE TO SEE PREVIOUS NOTE #4 | | | FOR LIGHTING LEVELS.(MIN) | | | | | | 6)NOTE: PLEASE PROVIDE BATTERY BACK-UP | | | FIXTURES IN MAIN ELECTRICAL RMS AND | | | ELEVATOR ROOM(S), GENERATOR AND FIRE | | | PUMP ROOM. PLEASE ALSO PROVIDE | | | CIRCUITING FOR THESE | | | RMS. | | | | | | 7)NOTE: PLEASE PROVIDE CURB DETAIL FOR | | | BUS-DUCT RISER AND FLOOR PENATRATIONS. | | | 368.6 | | | | | | 8)NOTE: PLEASE PROVIDE NOTES ON RISER | | | AND ELECTRICAL ROOM SHEETS FOR | | | REQUIREMENTS OF 110.26 FOR PANIC | | | HARDWARE AND DOOR SWINGS. | | | PLEASE SEE MIN CLEARENCE PER 110.26 | | | PLEASE ALSO SEE MIN DOOR OPENING 6' WITH | | | SINGLE ACCESS FOR EWUIPMENT MORE THAN | | | 1200 A'S AND OVER 6' WIDE. | | | | | | 9)NOTE: PLEASE SEE RISER INDICATES ALL | | | BUS-DUCT FROM FPL VAULT TO MAIN | | | ELECTRICAL ROOM AS OVER-HEAD. PLEASE SEE | | | 230.70, 230.6, NO MORE THAN 8' OF | | | UNPROTECTED CONDUCTORS/ OR BUS DUCT | | | PERMITTED "INSIDE THE BLDG. | | | PLEASE SEE ROUTING OF BUS-DUCT APPEARS | | | TO SHOW INSTALLATION INSIDE CONDO | | | UNITS?? | | | PLEASE PROVIDE LAYOUT, REVISE TO | | | UNDER-GROUND FEEDERS OR OTHER ACCEPTABLE | | | MEANS. | | | | | | 10)NOTE: PLEASE PROVIDE INFORMATION ON | | | BUS -DUCT RISER MAINS. APPEARS TO SHOW | | | THESE AS "SHUNT-TRIP" AND NOT CONTAINING | | | A MANUAL MEANS OF DISCONNECT LOCATED ON | | | THE OUTSIDE OF THE EQUIPMENT. PLEASE SEE | | | MAIN PANEL SCHEDULE(S), THESE DO NOT | | | SEEM TO INDICATE A MCB. | | | 230.76,230.79 | | | | | | 11)NOTE: PLEASE SEE GARAGE PLANS FOR | | | FIRE PUMP RM AND GEN RM ARE SHOWN BLANK? | | | | | | 12)NOTE: PLEASE PROVIDE SPECIFIC | | | INFORMATION ON BUS-DUCT, PLEASE SEE AN | | | ALUM EQUIPMENT GROUNDING CONDUCTOR/ | | | MATERIAL IS NOT PERMITED. | | | 310.2. LOCAL AMENDMENTS. | | | | | | 13)NOTE: PLEASE SUBMIT ALL MANUFACTURE | | | SPECS AND CUT SHEETS FOR GENERATOR, ATS, | | | FIRE PUMP AND FIRE PUMP CONTROLLER. | | | PLEASE ALSO SUBMIT THE SAME FOR ANYSUB | | | BASE FUEL TANK. | | | PLEASE KNOW, DUE TO THE INFORMATION NOT | | | BEING SUBMITTED AT THIS TIME, REVIEW FOR | | | SOME ITEMS FOR CODE COMPLIANCE CAN NOT | | | BE DONE. | | | UNABLE TO VERIFY CODE COMPLIANCE FOR | | | MANY ITEMS UNDER NFPA, 20,70,101,110 | | | ETC. | | | SOME INFORMATION IS "APECIFIED" ON PLANS | | | FOR TOWER #4, HOWEVER, TOWER #3 SHOULD | | | REFLECT THE SAME INFORMATION. ALL | | | MANUFACTURE CUTS/SPECS ARE STILL | | | REQUIRED. | | | | | | 14)NOTE: PLEASE SEE ELECTRICAL RISER | | | DIAGRAM DOES CONTAININFORMATION | | | FOR FIRE PUMP, YET NOT FIRE PUMP | | | CONTROLLER, | | | SERVICE, SIZING, LOCKED ROTOR SETTINGS | | | ETC. | | | PLEASE COMPLETE. | | | ENCASEMENT IN CONCRETE, OUTSIDE THE | | | BLDGS, ETC | | | | | | 15)NOTE: PLEASE SEE AREA FOR GARAGE | | | CONTAINING THE LOCATION OF FIRE PUMP AND | | | GENERATOR WILL BE REQUIRED TO BE | | | SUBITTED FOR PERMIT AND REVIEW. | | | PLEASE SEE LOCATIONS FOR FIRE | | | SEPARATIONS, ACCESS, LIGHTING, ETC CAN | | | NOT BE REVIEWED AT THIS TIME. | | | | | | 16)NOTE: PLEASE SEE A PANEL SCHEDULE FOR | | | A PANELH12B IS SUBMITTED, HOWEVER THIS | | | PANEL COULD NTO BELOCATED ON RISER | | | DIAGRAM?? | | | PLEASE CORRELATE. | | | | | | 17)NOTE: PLEASE PROVIDE DISCONNECTING | | | MEANS FOR ALL A/C EQUIPMENT AT ROOF TOP | | | LEVEL. A"TYPICAL" DETAIL MAY BE GIVEN | | | FOR THESE.440.11 | | | PLEASE SHOW A "TYPICAL DETAIL SHOWING | | | MOUNTING ETC. | | | | | | PLEASE CORRELATE ALL A/ KW RATINGS AND | | | LOADS WITH MECHANICNAL PLANS . (KW | | | RATINGS ETC). | | | | | | 18)NOTE: PLEASE SEE FIRE REVIEW NOTES | | | ALSO: PLEASE PROVIDE A LAYOUT FOR | | | CENTRAL STATION RM(FIRE COMMAND RM) | | | SHOWING ALL DEVICES/ PANELS/ STATUS | | | PANELS ETC. | | | PLEASE LIST ALL ITEMS AS SPECIFIED IN | | | NFPA- 101 11.8.5, | | | | | | 19)NOTE: PLEASE SEE RECEPTS MISSING PER | | | 210.52 | | | SEE REDLINED PLANS. | | | | | | 20)NOTE: PLEASE CALRIFY THE "P" LOCATED | | | NEXT TO SMOKE DETECTORS? | | | THIS CORRELATING SYMBOL COULD NOT BE | | | LOCATED ON PLANS. | | | | | | 21)NOTE: PLEASE VERIFY CIRCUITING OF | | | LAUNDRY RM/ WASHER CIRCUIT. | | | PLEASE SEE 210.11C2,210.52F,220.16 | | | PLEASE ALSO SEE MIN 1500VA. | | | PLEASE VERIFY LOAD FOR WASHER. | | | | | | 22)NOTE:PLEASE PROVIDE NOTE ON PLANS | | | FOR SMOKE DETECTOR PLACEMENT PER | | | REQUIREMENTS NFPA -72 11.8.3.5. | | | | | | 23): PLEASE PROVIDE NOTE FOR ALL | | | ELECTRICAL DEVICES TO BE INSTALLED PER | | | FAIR HOUSING ACT REGULATIONS, (FHAR) 24 | | | CFR 100.205 | | | | | | 24)NOTE: PLEASE SEE 210.52C1 FOR SOME | | | MISSING KITCHEN COUNTERSPACE RECEPTS. | | | PLEASE ALSO SEE COUNTERSPACE APPEARS TO | | | SHOW A DEDICATED CIRCUIT (19) FOR | | | MICROWAVE WHICH ALSO APPEARS TO BE THE | | | RECEPT FOR KITCHEN COUNTERSPACE? | | | IF THE MICROWAVE IS A DEDICATED RECEPT, | | | THEN AN ADDTIONAL GFI WOULD BE REQUIRED. | | | 210.8A16. | | | | | | 25)NOTE: PLEASE SEE A 70A BRKR IS BEING | | | SHOWN FOR RANGE?? | | | PLEASE SEE 210.23,422.11B | | | 50A RANGE RECEPT, 50A BRKR MAX. | | | | | | 26)NOTE: PLEASE SEE PANEL SCHEDULES SEEM | | | TO SHOW "A" AND "C" PHASE FOR SINLGLE | | | PHASE SERVICE AND UNITS?? | | | PLEASE CLARIFY / ADJSUT. | | | 215.5 | | | | | | 27)NOTE: PLEASE LABEL AND /OR CLARIFY | | | "DINING" AREAS IN ALL UNITS. | | | UNABLE TO VERIFY CIRCUITING AS DINING | | | /LIVING ARE SEEMED TO BE COMBINED.' | | | PLEASE SEE 210.52B1 | | | | | | 28)NOTE: PLEASE SEE 210.52D FOR SOME | | | UNITS MISSING GFI'S WITH IN 3' OF LAV'S. | | | PLEASE ALSO SEE A GFI MAY NOT PERMITTED | | | ON THE OTHER SIDE OF A LAV TO MEET | | | 210.52D (3'). | | | GFI 'S MAY BE MOVED IN BETWEEN BOTH | | | LAV'S OR AN ADDITIONALRECEPT MAY BE | | | ADDED. | | | | | | 29)NOTE: PLEASE SEE MISSING RECEPTS IN | | | HALLWAY AREAS, 10' OR MORE OF CONTINUOUS | | | WALL. | | | 210.52H. | | | | | | 30)NOTE: PLEASE SEE RISER SEEMS TO | | | INDICATE A POOL PANEL, HOWEVER NO OTHER | | | INFORMATION WAS SUBMITTED AND PANEL | | | COULD NOT LOCATED ON PLANS. | | | LOADS ETC. | | | 215.5, 220 | | | | | | 31)NOTE: PLEASE VERIFY BATH CIRCUITS | | | BEING SHOWN WITH ARC FAULT PROTECTION?? | | | 210.8 REQUIRES GFI PROTECTION FOR BATHS | | | AND 210.12 ARC FAULT PROTECTION FOR | | | BEDROOM CIRCUITS? | | | THIS IS ONLY A NOTE: | | | | | | 32)NOTE: PLEASE PLACE NOTE ON "ROOF | | | PLANS" WHICH WILL REQUIRE ALL LIGHTNING | | | PROTECTION | | | | | | | | | 33)NOTE: PLEASE IDICATE ON PLANS/RISER | | | IF GENERATOR WILL BE A "SEPARATELY | | | DERIVED SYSTEM" OR A " NON SEPARATELY | | | DERIVEDSYSTEM. | | | IF SD, PLEASE INCLUDE GROUNDING | | | ELECTRODE SYSTEM PER 250.30 | | | | | | 34)NOTE: PLEASE INDICATE IF PANELS EH2A- | | | EH9A ARE FEED THRU LUGS OR DOES EACH | | | PANEL CONTAIN OCP FOR EACH.? | | | PLEASE ALSO SEE PANELS H5A-9, ETC. | | | 215.5 | | | | | | 35)NOTE: PLEASESEE PANELS EH2-EH9 ARE | | | SHOWN ON RISER AND ESBA BEING FED W/ | | | 225A OVER CURRENT PROTECTION, HOWEVER | | | EACH OF THESE ARE SHOWN AS 125A ON PANEL | | | SCHEDULE(S). PLEASE CORRELATE. | | | 215.5 | | | | | | 36) NOTE:PLEASE INDICATE IF EH2A- 9 ARE | | | PANELS CONTAING "FEED-THRU" LUGS OR IS | | | THERE OCP IN EACH OF THESE PANELS | | | FEEDING THRU TO OTHER PANELS? | | | 215.5 | | | | | | 37)NOTE: PLEASE CLARIFY NOTES # 5 AND #6 | | | ON GROUNDING RISER? | | | 250.50 | | | | | | 38)NOTE: PLEASE SEE RISER INDICATES | | | PANEL H12A FEEDING "ELEV PANEL" WITH | | | CIRCUITS 20,22,24, HOWEVER PLEASE SEE | | | PANEL H12A, DOES NOT SHOW ANY FEED TO | | | "ELEVATOR PANEL". | | | PLEASE CORRELATE.215.5 | | | PLEASE ALSO ADJUST LOAD CALCULATIONS FOR | | | ADDITIONAL PANEL WHEN ADDED. | | | | | | 39)NOTE: PLEASE SUBMIT "SPEC BOOKS' FOR | | | REVIEW OF PROJECT. | | | THESE WOULD CONTAIN JOBSITE SPECS. | | | | | | 40)NOTE: PLEASE BE SURE ALL CONTINUOUS | | | LOADS ARE SHOWN AT 125%. | | | 215.3,230.42 ETC. | | | | | | 41)NOTE: PLEASE SEE MIN OCP FOR AHU HEAT | | | TO BE 125%. 424.3B | | | SHOWS 50A OCP. | | | | | | 42)NOTE: PLEASE HAVE PANEL H2A INDICATE | | | ALSO IF "FEED-THRU" LUGS. | | | | | | ** PLEASE SEE THAT NO PLANS, PERMIT | | | APPLICATION ETC WAS SUBMITTED FOR GARAGE | | | BLDGS. | | | | | | ** PLEASE KNOW, MANY OF THE ABOVE ITEMS | | | ARE "REDLINED" AT LOCATIONS ON PLANS FOR | | | NOTES. | | | | | | ** PLEASE KNOW, A RESPONSE LETTER IN | | | TYPE WRITTEN FORM WILL HELP IN RESPONSES | | | TO ELECTRICAL COMMENTS. | | | | | | ** PLEASE BE SURE TO SEE ANY POSSIBLE | | | COMMENTS FROM OTHER TRADES WHICH MAY | | | AFFECT ELECTRICAL PLANS. | | | | | | ** PLEASE BE SURE TO "REMOVE" ALL OLD | | | VOIDED SHEETS AND ONLY INSERT NEW | | | REVISED SHEETS INTO THE COMPLETED SETS | | | FOR REVIEW AND STAMPING. | | | | | | ** PLEASE SEE BLDG REVIEW COMMENTS WHICH | | | WILL REQUIRE ALL PRODUCT APPROVALS, | | | SUBMITTALS ETC TO BE DETACHED FROM | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2005-09-28 00:00:00 | PLANS IN "F" STATUS, NOTES TO FOLLOW. | | 2005-09-11 00:00:00 | ONE ROLL IN ELECTRIC FOR REVIEW. | | | REVIEWS IN PROGRESS . |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2005-08-23 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-08-23 |
Time |
10:55 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2005-08-23 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2005-08-23 00:00:00 | FAILED: | | | | | | 1. PLEASE SEE REVIEW NOTES UNDER PERMIT | | | # 05080676. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-06-13 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-06-13 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-06-13 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2006-06-13 00:00:00 | ***DENIED*** | | | | | | PLEASE NOTE THAT ARCHITECTUAL RESPONSE | | | LETTER WAS NOT FOUND WITH THIS | | | SUBMITTAL. THE FOLLOWING ADDRESSES | | | RESPONSE LETTER FROM KAMM CONSULTING. | | | | | | 1) OK | | | | | | 2) NOTE IS STILL ON PLANS. PLEASE | | | CORRECT OR REMOVE. | | | | | | 3) PLEASE INDICATE THE TOTAL BUILDING | | | COVEREAGE THAT IS EXPECTED BY A 1000 GPM | | | FIRE PUMP. | | | | | | 4) OK | | | | | | 5-15) NO ARCHITECT'S RESPONSE LETTER | | | FOUND. | | | | | | 16) OK | | | | | | 17) OK | | | | | | 18) OK | | | | | | 19) OK | | | | | | 20) NO MENTION OF LOCK AND CHAIN IN | | | ADDITION TO TAMPER SWITCHES. | | | | | | 21) HYDRAULIC CALCULATIONS WILL BE | | | REQUIRED AT THE TIME OF FIRE SPRINKLER | | | PERMITTING. | | | | | | 22) OK | | | | | | 23) OK | | | | | | 24) OK | | | | | | 25) OK | | | | | | 26) NO MENTION REGARDING SURVIVABILITY | | | REQUIREMENT ON FA0.1. | | | | | | 27) PLEASE NOTE THAT A HIGHRISE BUILDING | | | WITH ENCLOSED STAIRWELLS IS REQUIRED TO | | | HAVE STAIRWELL PRESSURIZATION. | | | | | | 28) NO RESPONSE LETTER. | | | | | | 31-36) NO RESPONSE LETTER FOUND. | | | | | | PLEASE NOTE THAT IT WOULD HELP EXPEDITE | | | THIS PROCESS IF RESPONSE LETTERS | | | INDICATING SHEET #'S ARE INCLUDED WITH | | | SUBMITTALS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-12-01 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-12-01 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-12-01 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2005-12-01 00:00:00 | ******DENIED****** | | | | | | TOWER #4 | | | | | | 1) FIRE HYDRANTS TO BE WET AND | | | OPERATIONAL PRIOR TO, DURING AND AFTER | | | CONSTRUCTION | | | | | | 2) FOR REFERENCE, HIGHRISE IS DEFINED AS | | | A BUILDING GREATER THAN 75' IN HEIGHT. | | | SHT A-1.1.2 | | | | | | 3) PLEASE NOTE THAT THE FIRE PUMP IS | | | SHOWN IN THE PARKING GARAGE THAT ISN'T | | | PART OF THIS PHASE. ADDITIONAL | | | INFORMATION REGARDING WHAT ARRANGEMENT | | | BY THIS OFFICE HAS BEEN ACCEPTED IS | | | REQUIRED. THE FIRE PUMP SHALL BE A | | | MINIMUM OF 1250 GPM FOR A HIGHRISE | | | BUILDING. PLEASE CONTACT THE BUREAU OF | | | FIRE PREVENTION AT (561) 804-4724. | | | | | | 4) BUILDING TO MEET APPLICABLE BUILDING | | | CODES AND NFPA CHAPTER 11 REQUIREMENTS | | | FOR HIGHRISE BUILDINGS. | | | | | | 5) PLEASE VERIFY THAT NO COOKING WILL | | | OCCUR IN THE CATERING KITCHEN. | | | | | | 6) EXIT STAIRS ARE TO BE KEPT UP WITH | | | CONSTRUCTION. | | | | | | 7) NOTE REGARDING THE ADDRESS NUMBER IS | | | ACKNOWLEDGED. PLEASE ILLUSTRATE ON | | | ELEVATION SHEETS FOR FUTURE REFERENCE | | | AND FURTHER PLAN REVIEW. | | | | | | 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENT FOR HANDRAILS AND GUARDS | | | | | | 9) KNOX BOXES WILL BE REQUIRED. | | | | | | 10) PLEASE INDICATE THE OCCUPANT LOAD | | | CALCULATIONS FOR THE HOME THEATER AND | | | FITTNESS CENTER. | | | | | | 11) PLEASE PROVIDE THE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS IE | | | CLASS A,B OR C. | | | | | | 12) TACTILE SIGNAGE IS REQUIRED AT EXIT | | | DOORS. | | | | | | 13) PLEASE INDICATE IF ELEVATORS ARE | | | STRETCHER ACCESSIBLE. | | | | | | 14) SIGNS ARE REQUIRED IN STAIRWELLS | | | INDICATING TOP, BOTTOM, FLOOR NUMBER AND | | | ROOF ACCESS. | | | | | | 15) WARNING SIGNS ARE REQUIRED IN | | | ELEVATOR LOBBIES. | | | | | | 16) IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM WHEN | | | ACTIVATED. | | | | | | 17) FIRE ALARM SYSTEM TO BE CLASS A, | | | STYLE D OR FULLY ADDRESSABLE. | | | | | | 18) AS INDICATED ON PLANS, SEPARATE SHOP | | | DRAWINGS AND PERMITS ARE REQUIRED FOR | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS. | | | | | | 19) UL CERTIFICATION TO BE PROVIDED AT | | | THE TIME OF THE FIRE ALARM ACCEPTANCE | | | TEST. | | | | | | 20) IN ADDITION TO ELECTRONIC SWITCHES, | | | DOUBLE CHECK DETECTOR ASSEMBLY TO BE | | | SECURED WITH LOCK AND CHAIN. | | | | | | 21) HYDRAULIC CALCULATIONS WILL BE | | | REQUIRED WHEN APPLYING FOR THE FIRE | | | SPRINKLER PERMIT. | | | | | | 22) FDV ON STANDPIPE SHALL BE 2 1/2" TO | | | 1 1/2" REDUCER WITH CHAIN. | | | | | | 23) TEMPORARY STANDPIPES ARE REQUIRED | | | WHEN THE BUILDING REACHED 3 STORIES OR | | | 30" IN HEIGHT. | | | | | | 24) NO FIRE SPRINKLER COVERAGE NOTED TO | | | COVERED WALKWAYS AND PORTE COCHERE. | | | | | | 25) PLANS DON'T SHOW ANY EXIT SIGNS OR | | | EMERGENCY LIGHTING FACILITIES IN COMMON | | | AREA MEANS OF EGRESS. PLEASE SHOW ON | | | ELECRICAL AND LIFE SAFETY SHTS. | | | | | | 26) FIRE ALARM SYSTEM TO MEET THE | | | SURVIVABILITY REQUIREMENTS IN ACCORDANCE | | | WITH NFPA 72. | | | | | | 27) THE ANTICIPATED STACK EFFECT NOTE | | | WORDING SHALL BE ADDED TO THE MECHANICAL | | | SHTS. | | | | | | 28) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 29) ELEVATORS TO COMPLY WITH BUILDING | | | AND FIRE CODES AND ASME/ANSI A 17.1. | | | | | | 30) FIRE SPRINKLER COVERAGE DOESN'T | | | EXTEND TO ELEC/PHONE ROOMS. | | | | | | 31) NO CUTTING OR WELDING TO OCCUR | | | WITHOUT APPROVAL OF FIRE PREVENTION | | | BUREAU AND COMPLIANCE WITH NFPA 51B. | | | | | | 32) EMERGENCY LIGHTING IS NOT SHOWN IN | | | ELEC/PHONE ROOMS ON UPPER FLOORS. | | | | | | 33) A MINIMUM OF (2) FIRE DEPARTMENT | | | CONNECTIONS ARE REQUIRED ON HIGHRISE | | | BUILDINGS. | | | | | | | | | 34) FIRE PUMP SHALL MEET THE | | | REQUIREMENTS OF NFPA 20 AND MANUFACTURER | | | SPEC SHEETS REQUIRED. | | | | | | 35) ALL SHAFTS LARGE ENOUGH FOR PERSONS | | | TO FALL INTO MUST BE MARKED SHAFTWAY IN | | | 6" LETTERS. | | | | | | 36) LOCKING KNOX BOX CAPS ARE REQUIRED | | | ON THE FIRE DEPARTMENT CONNECTIONS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-05-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-05-12 |
Time |
18:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-05-11 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2006-05-12 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | FROM PLUMBING REVIEW: | | | | | | 27. THE FOLLOWING INFORMATION REQUIRED | | | FOR THE GAS PERMIT: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. CUT SECTIONS NOT SHOWN | | | AND MOST RISERS NOT SHOWN. | | | ***RESPONSE NOTED, BUT LENGTHS OF CUT | | | SECTIONS NOT SHOWN. | | | | | | C. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | ***RESPONSE NOTED, BUT CALCULATIONS FOR | | | CLOTHES DRYER ROOMS NOT SUBMITTED. | | | | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ***RESPONSE NOTED, BUT NO MANUF. SHEETS | | | SUBMITTED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | ***RESPONSE NOTED, BUT VOIDED SHEETS NOT | | | REMOVED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-03-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-07 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-07 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2006-03-30 00:00:00 | TO "COMM" BD#7 | | 2006-03-07 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-17 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-23 |
Time |
08:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-04-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-04-13 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-04-13 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2006-04-13 00:00:00 | DENIED:TOWER #4 | | | REPSONSE TO COMMENTS DATED 11/17/05. | | | COMMENT #8 | | | PLEASE PROVIDE COMBUSTION AIR | | | CALCULATIONS (IF A CONFINED SPACE) FOR | | | THE GAS DRYERS LOCATED IN THE LAUNDRY | | | ROOM/CLOSET.2004 FMC CHAPTER 7. | | | | | | RESPONSE INDICATES THE ARCHITECTURAL | | | DRAWINGS WERE REVISED TO REFLECT LOUVER | | | ON DOOR.PLEASE INDICATE THE SPECIFIC | | | PLAN SHEET.PLAN SHEET T-4 A7.2.1(DOOR | | | SCHEDULE) DOES NOT REFLECT THIS CHANGE. | | | | | | COMMENT #12 | | | PLUMBING PLAN SHEET P6.4 INDICATES | | | GAS APPLICANCES, SPECIFICALLY THE WATER | | | HEATER.PLEASE CLARIFY VENTING A GAS | | | WATER HEATER LOCATED IN AN AHU CLOSET. | | | | | | REPONSE REFERS TO PLAN SHEET P0.1, | | | DETAIL FOR THE GAS WATER HEATER IN THE | | | AHU CLOSET IS NOT SHOWN.PER 2004 FMC | | | 602.1, FUEL FIRED APPLIANCES SHALL NOT | | | BE INSTALLED WITHIN A PLENUM. | | | | | | | | | | | | NEW COMMENT: | | | 1.PLAN SHEET M7.1 INDICATES RETURN AIR | | | TO AHU WILL BE THROUGH A LOUVERED GRILLE | | | IN THE WALL.THE AHU CLOSET WILL BE A | | | PLENUM.THE A/C CLOSET DOOR SHALL BE | | | NONCOMBUSTIBLE PER 2004 FMC 602.2.1. | | | PLEASE PROVIDE SUBMITTAL. | | | | | | 2.PLEASE NOTE, SHOULD DRYER EXHAUST | | | GREATER THAN 200 CFM, MAKEUP AIR | | | SHALL BE PROVIDED. | | | | | | 3.PROVIDE ADDITIONAL INFORMATION FOR | | | THE VENTILATION/PRESSURIZATION OF THE | | | EXIT STAIRWAY.SHOW COMPLIANCE WITH | | | 2004 FMC 909.20 & 1019.1.8. | | | | | | 4.PLEASE NOTE, SPRINKLER SYSTEMS | | | REQUIRED FOR TRASH CHUTES & DRYER | | | EXHAUST (SUB-DUCT) PER 2004 FBC | | | 903.2.10.2 & 903.2.12.1. | | | | | | 5.PLAN SHEET M2.1, RESPONSE INDICATES | | | THE INTAKE DUCT FOR THE TOILET & DRYER | | | EXHAUST CHASE IS FOR THE MAKE-UP AIR. | | | PLEASE CLARIFY THE FOLLOWING: | | | 1) SIZE OF THE BRANCH DUCT. | | | 2) PLEASE CLARIFY THE PENETRATION | | | BETWEEN THE RESIDENCE AND THE WALKWAY. | | | DOES THIS HAVE THE PENETRATION HAVE A | | | FIRE, SMOKE OR BOTH RATING? SHOW | | | COMPLIANCE WITH 2004 FBC 716. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-11-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-11-17 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-11-10 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2005-11-17 00:00:00 | DENIED:2004 FBC / TOWER 4 | | | 1.PLANS SHEET M0.1, MECHANICAL NOTES | | | REFERENCE 2001 FBC & STANDARDS THAT ARE | | | APPLICABLE TO THIS SUBMITTAL.PLEASE | | | REVISE. | | | | | | 2.PLAN SHEET M2.1 DETAIL SECTION A-A, | | | PLEASE ANNOTATE SUFFICIENT CLEARANCE FOR | | | MAINTENANCE, SERVICE, & REPLACEMENT TO | | | ALL EQUIPMENT INDCLUDING FIRE DAMPERS IS | | | REQUIRED PER 2004 FMC 306.1. | | | | | | 3.PLAN SHEET M2.1 KEY NOTE 11 'PROVIDE | | | ACCESS PANELD FOR AHU.SEE ARCH PANELS | | | FOR DETAILS.'THIS IS INDICATED IN THE | | | MASTER BEDRM IN UNIT J104.PLEASE | | | CLARIFY AHU LOCATION & WHAT AREA IT | | | SERVES.PLEASE NOTE, ACCESS TO | | | EQUIPMENT FOR THE COMMON AREAS SHALL NOT | | | BE OBTAINED BY ENETERING A PRIVATE | | | RESIDENCE. | | | | | | 4.PLAN SHEET M2.1 EXHAUST DUCT FROM | | | UNIT J THAT PENETRATES THE TENENANT | | | SEPARATION WALL TO THE FITNESS CENTER & | | | HOME THEATER AREAS SHALL COMPLY WITH | | | 2004 FMC 501.4, 504.2 & 603.3, FOR | | | REQUIRED GAUGE OF GALVANIZED DUCT | | | PENTETRATING RATED WALL/PARTITION. | | | | | | 5.PLAN SHEET M2.2 DETAIL 1 DOES NOT | | | INDICATE AUXILIARY DRAIN PAN.EQUIPMENT | | | SCHEDULE (M6.1) INDICATES AUXILIARY | | | DRAIN PAN W/FLOAT SWITCH. | | | | | | 6.PLEASE NOTE THE AHU DETAIL 1 ON PLAN | | | SHEET M2.2 INDICATES NO CEILING IN THE | | | AHU CLOSET & THE DOOR IS TO HAVE | | | 'GASKET, SEALED'.PLAN SHEET M7.1 | | | DETAIL #2 (AHU) INDICATES R/A THROUGH | | | LOUVERED DOOR, & NO DRAIN PAN.PLEASE | | | CORRELATE PLANS. | | | | | | 7.PLAN SHEET M2.2 DETAIL 2 SHOWS | | | LAYOUT ABOVE THE CEILING.PLEASE NOTE | | | DUCT SHALL HAVE ENOUGH CLEARANCE FOR | | | ASSEMBLY, INSPECTION , CLEANING & | | | MAINTENANCE PER 2004 FMC 603.1 & | | | 603.1.3. | | | | | | 8.PLEASE PROVIDE COMBUSTION AIR | | | CALCULATIONS (IF A CONFINED SPACE) FOR | | | THE GAS DRYERS LOCATED IN THE LAUNDRY | | | ROOM/CLOSET.2004 FMC CHAPTER 7. | | | | | | 9.PLAN SHEET M2.5 KEY NOTE #4 'SEE | | | ARCHITECTURAL PLANS FOR ACCESS TO UNDER | | | FLOOR AREA.PLEASE CLARIFY THE | | | ARCHITECTURAL PLAN SHEET THAT DETAILS | | | THE ACCESS. | | | | | | 10.PLAN SHEET M6.2 REFERENCES ASHRAE | | | 62-89, THIS SHOULD READ 62-01. | | | | | | 11.PLAN SHEET M6.2 OUTSIDE AIR | | | CALCULATIONS ARE GIVEN FOR COMMON AREAS | | | ONLY.PLEASE PROVIDE CALCULATIONS FOR | | | THE RESIDENT UNITS PER TABLE 403.3 AS | | | REQUIRED FOR R-2 OCCUPANCIES. | | | | | | 12.PLUMBING PLAN SHEET P6.4 INDICATES | | | GAS APPLICANCES, SPECIFICALLY THE WATER | | | HEATER.PLEASE CLARIFY VENTING A GAS | | | WATER HEATER LOCATED IN AN AHU CLOSET. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-05-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-05-12 |
Time |
17:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-05-11 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2006-05-12 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | FROM PREVIOUS REVIEW: | | | | | | 1. ALL PLANS DESIGNED BY A PROFESSIONAL | | | ARCHITECT OR ENGINEER, THEN ALL SHEETS | | | SHALL BE SIGNED, SEALED & DATED AS | | | REQUIRED BY FS. SECTION 106.1. | | | ***RESPONSE NOTED, BUT SEE BOUNDRY | | | SURVEY, SHTS PP1 OF 9 THRU PP9 OF 9, | | | SHTS LA-POOL-1 THRU LA-POOL-4, AND SHTS | | | LA-FW-1 THRU LA-FW-6. | | | | | | 2. INFORMATIONAL ONLY. | | | | | | 3. SHT T-4 A2.4.1 SUBMIT CALCULATIONS | | | FOR PRIMARY AND SECONDARY ROOF DRAINS. | | | SHOW THE SQUARE FOOTAGE FOR EACH AREA & | | | SHOW 1/2 AREA OF ALL VERTICAL WALLS | | | INCLUDING PARAPETS ALONG WITH THE AREA | | | OF ROOF THAT DRAINS ONTO THE ROOF FROM | | | ABOVE FOR EACH AREA IN CALCLATIONS. | | | SECTIONS 1106 & 1107 WITH ALL | | | SUBSECTIONS. | | | ***RESPONSE NOTED, BUT THE AREAS FROM | | | ROOFS ABOVE HAVE NOT BEEN ADDRESSED FOR | | | THE MECHANICAL RM ROOF, THE HIP ROOFS, | | | THE OCTAGON ROOF, OR THE STAIRWELL ROOF. | | | | | | 4. SHTS T-4 A4.1.1 THRU T-4 A4.1.10 | | | UNITS A, B, C, D, E, H, F, G & K SHALL | | | COMPLY WITH REQUIREMENTS 1 THRU 7 OF THE | | | FHA-98 DESIGN MANUAL. INDICATE | | | SPECIFICATION "A" OR "B" FOR EACH UNIT. | | | SHOW THE W/C OPENING, (MINIMUM 33"), | | | SHOW THE W/C AT 18" OFF THE WALL TO THE | | | CENTER OF THE FIXTURE WHERE APPLICABLE, | | | AND 18" MINIMUM OFF AN ADJACENT FIXTURE. | | | SEE PAGES 6.7 7.43 & 7.44. - SHOW CLEAR | | | FLOOR SPACE FOR ALL USABLE FIXTURES. - | | | SUBMIT A DETAIL FOR BACKING FOR W/C'S, | | | TUBS, SHOWERS ECT. PER REQUIREMENT 6. - | | | CLEAR FLOOR SPACE FOR SHOWERS SHALL BE | | | PARALLEL TO SHOWER & FLUSH WITH CONTROL | | | WALL. INDICATE CONTROL WALL ON UNIT | | | FLOOR PLAN. (SEE PAGE 7.56). | | | ***NO RESPONSE FROM ARCHITECT, NOT | | | ADDRESSED. | | | | | | 5. SHT T-4 A4.1.11 MEN'S & WOMEN'S | | | TOILET ROOMS SHALL COMPLY WITH SECTIONS | | | 11-4.16, 11-4.19 & 11-4.22 WITH ALL | | | SUBSECTIONS. SUBMIT A DETAIL SHOWING | | | COMPLIANCE. | | | ***NO RESPONSE FROM THE ARCHITECT, NOT | | | ADDRESSED. | | | | | | 6. SUBMIT CALCULATIONS FOR ALL | | | AMENITITES AREAS FOR MINIMUM FACILITIES | | | PER TABLES 1004.2 (BLDG) AND 403.1 | | | (PLMG). SHOW THE SQUARE FOOTAGE FOR ALL | | | COMMON USE AREAS ALONG WITH THE | | | OCCUPANCY LOAD OF EACH AREA. INDICATE | | | THE LOCATION OF THE SANITARY FACILITIES | | | FOR THE POOL AREA. | | | ***NO RESPONSE FROM THE ARCHITECT, NOT | | | ADDRESSED. | | | | | | 7. SHT T-4 A7.1.1 FLOORS AND WALLS IN | | | TOILET ROOM SHALL BE NONABSORBENT PER | | | SECTIONS 1210.1 & 1210.2. PLEASE | | | INDICATE HOW THIS WILL BE ACCOMPLISHED | | | WITH EXPOSED CONCRETE, GYP. BOARD AND NO | | | BASE AS SHOWN IN GROUND LEVEL ROOM | | | FINISH SCHEDULE. | | | ***NO RESPONSE FROM THE ARCHITECT, NOT | | | ADDRESSED. | | | | | | 8. SHT T-4 A4.11 SINK IN CATERING | | | KITCHEN SHALL COMPLY WITH SECTION | | | 11-4.24 AND ALL SUBSECTIONS. PROVIDE A | | | DETAIL. | | | ***NO RESPONSE FROM THE ARCHITECT, NOT | | | ADDRESSED. | | | | | | 9. SHT T-4 A6.1.1 DETAIL #4 TRASH CHUTE | | | WATER SUPPLY SHALL HAVE BACKFLOW | | | PROTECTION. INDICATE THE METHOD OF | | | BACKFLOW PROTECTION REQUIRED IN SECTION | | | 608 AND TABLE 608.1. | | | ***RESPONSE NOTED, BUT NO BACKFLOW | | | SHOWN. | | | | | | 10. SHT T-4 A6.1.3 DETAIL #10 ROOF DRAIN | | | DETAIL, INDICATE MEASUREMENT FROM THE | | | ROOF TO THE TOP OF THE SECONDARY ROOF | | | DRAIN PIPI, (EMERGENCY OVERFLOW PIPE). | | | ***NO RESPONSE FROM THE ARCHITECT, NOT | | | ADDRESSED. | | | | | | 11. SHT T-4 A8.1.1 SHOW THE BACKING FOR | | | THE W/C'S PER FHA DESIGN MANUAL PAGES | | | 6.3 & 6.4. SHOW BACKING FOR THE TUBS PER | | | PAGE 6.9. | | | ***NO RESPONSE FROM THE ARCHITECT, NOT | | | ADDRESSED. | | | | | | 12. SHT P0.1 PLUMBING NOTES #1 & #24 | | | REFER TO FBC-2001, CODE ADOPTED FOR THIS | | | JOB IS FBC-2004. PLEASE CHANGE REFERENCE | | | ***RESPONSED NOTED, BUT PLUMBING NOTE | | | #24 HAS NOT BEEN CHANGED. | | | | | | 14. SHT P2.1 MANY FITTINGS CONNECTING | | | BRANCH LINES TO BLDG. SANT. DRAIN ARE | | | NOT SHOWN TO GUIDE SEWAGE AND WASTE IN | | | THE DIRECTION OF FLOW. SECTION 706.3. - | | | IDENTIFY THE RISER BETWEEN ROOMS B110 & | | | B110. | | | ***RESPONSE NOTED, BUT THIS HAS NOT BEEN | | | ADDRESSED. | | | | | | 16. SHT P2.4 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS. (SEE | | | COMMENT #3). | | | ***RESPONSE NOTED, BUT SEE COMMENT #3 | | | FOR REQUIREMENTS FOR ROOFS THAT DRAIN | | | ONTO ROOF FROM ABOVE. | | | | | | 18. SHT P3.3 2ND SHEET WITH 2ND, 4TH - | | | 12TH FLOORS. NO 3RD FLOOR SUBMITTED. | | | PLEASE CLARIFY. | | | ***RESPONSE NOTED, BUT NO CHANGE SEEN. | | | | | | 21. SHTS P5.1 & P5.2 SUBMIT SOVENT | | | DESIGN MANUAL FOR THE SOVENT SYSTEM. THE | | | SOVENT SYSTEM SHALL BE APPROVED. SECTION | | | 106.1.1. | | | ***RESPONSE NOTED, BUT THIS SYSTEM IS | | | NOT APPROVED. NO TESTING AND APPROVAL OF | | | FITTINGS. | | | | | | 22. SHT P5.3 BLDG DRAIN ISOMETRIC RISER | | | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. | | | THE ISOMETRIC IS REVERSE FROM THE FLOOR | | | PLAN. THE BLDG. DRAIN IS SHOWN AS | | | EXITING THE BLDG. BETWEEN S/1 & S/2 ON | | | THE FLOOR PLAN. SHOW ALL GROUND FLOOR | | | FIXTURE PIPING ON THE ISOMETRIC WITH ALL | | | PIPE SIZES AND VENTING. SECTION | | | 104.3.1.1. | | | ***RESPONSE NOTED, BUT THE RISER DIAGRAM | | | STILL DOES NOT REFLECT THE FLOOR PLAN IN | | | MANY AREAS. CHECK ALL PIPE SIZES AGAINST | | | TABLE 710.1(1). - FLOOR DRAINS MISSING, | | | UNIDENTIFIED FIXTURE DOWNSTREAM OF RISER | | | S/63 NOT SHOWN. (SEE RED LINE | | | CORRECTIONS ON ONE SET OF PLUMBING | | | SHEETS). | | | | | | 23. SHT P5.3 SHOW DFU'S AS THEY | | | ACCUMULATE IN THE SYSTEM. TABLE 710.1(1) | | | ***RESPONSE NOTED, BUT SOME FIXTURES | | | MISSING AND ADDITION DOWNSTREAM OF RISER | | | S/49 NEEDS TO BE RECHECKED. FLOOR DRAINS | | | PER TABLE 709.2. | | | | | | 27. THE FOLLOWING INFORMATION REQUIRED | | | FOR THE GAS PERMIT: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. CUT SECTIONS NOT SHOWN | | | AND MOST RISERS NOT SHOWN. | | | ***RESPONSE NOTED, BUT LENGTHS OF CUT | | | SECTIONS NOT SHOWN. | | | | | | C. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | ***RESPONSE NOTED, BUT CALCULATIONS FOR | | | CLOTHES DRYER ROOMS NOT SUBMITTED. | | | | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ***RESPONSE NOTED, BUT NO MANUF. SHEETS | | | SUBMITTED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | ***RESPONSE NOTED, BUT VOIDED SHEETS NOT | | | REMOVED. | | | | | | **************NEW COMMENTS************** | | | | | | 1B. SHTS T-4 A8.1.2 THRU T-4 A8.1.8 | | | SHOWN ON THE INDEX OF DRAWINGS HAVE NOT | | | BEEN SUBMITTED. PLEASE CLARIFY. SECTION | | | 106.1.1. | | | | | | 2B. SHTS P2.4 & P7.1 STORM RISERS 6 & 10 | | | SF DOES NOT REFLECT SF ON ROOF PLAN NOR | | | ON BLDG. STORM DRAIN ISOMETRIC. PLEASE | | | CORRELATE RISERS WITH ROOF PLANS AND | | | STORM DRAIN ISOMETRIC. SECTION 106.1.1. | | | | | | 3B. SHTS P5.1 & P5.2 BASE OF STACKS DO | | | NOT REFLECT REQUIREMENTS OF SOVENT | | | DESIGN MANUAL. FIRST FLOOR FIXTURES DO | | | NOT CONNECT TO VERTICLE STACK UNDER THE | | | DEAERATOR REQUIREMENT FOR THE PRL LINE | | | IS NOT CORRECT. | | | | | | 4B. SEE ATTACHED SHEET CONCERNING THE | | | DESIGN PROFESSIONAL & FS 553.80(2)(B). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-12-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-12-01 |
Time |
07:26 |
Rev Time |
5.50 |
| Received By |
kstevens |
Date |
2005-11-30 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2005-11-30 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL PLANS DESIGNED BY A PROFESSIONAL | | | ARCHITECT OR ENGINEER, THEN ALL SHEETS | | | SHALL BE SIGNED, SEALED & DATED AS | | | REQUIRED BY FS. SECTION 106.1 | | | 2. SHTS LA-POOL 3 & LA-POOL 4 PLANS & | | | PERMIT ARE REQUIRED. PLANS SHALL BE | | | REVIEWED & STAMPED BY THE PALM BEACH | | | COUNTY HEALTH DEPT. PRIOR TO SUBMITTING | | | FOR REVIEW. | | | 3. SHT T-4 A2.4.1 SUBMIT CALCULATIONS | | | FOR PRIMARY AND SECONDARY ROOF DRAINS. | | | SHOW THE SQUARE FOOTAGE FOR EACH AREA & | | | SHOW 1/2 AREA OF ALL VERTICAL WALLS | | | INCLUDING PARAPETS ALONG WITH THE AREA | | | OF ROOF THAT DRAINS ONTO THE ROOF FROM | | | ABOVE FOR EACH AREA IN CALCLATIONS. | | | SECTIONS 1106 & 1107 WITH ALL | | | SUBSECTIONS. | | | 4. SHTS T-4 A4.1.1 THRU T-4 A4.1.10 | | | UNITS A, B, C, D, E, H, F, G & K SHALL | | | COMPLY WITH REQUIREMENTS 1 THRU 7 OF THE | | | FHA-98 DESIGN MANUAL. INDICATE | | | SPECIFICATION "A" OR "B" FOR EACH UNIT. | | | SHOW THE W/C OPENING, (MINIMUM 33"), | | | SHOW THE W/C AT 18" OFF THE WALL TO THE | | | CENTER OF THE FIXTURE WHERE APPLICABLE, | | | AND 18" MINIMUM OFF AN ADJACENT FIXTURE. | | | SEE PAGES 6.7 7.43 & 7.44. - SHOW CLEAR | | | FLOOR SPACE FOR ALL USABLE FIXTURES. - | | | SUBMIT A DETAIL FOR BACKING FOR W/C'S, | | | TUBS, SHOWERS ECT. PER REQUIREMENT 6. - | | | CLEAR FLOOR SPACE FOR SHOWERS SHALL BE | | | PARALLEL TO SHOWER & FLUSH WITH CONTROL | | | WALL. INDICATE CONTROL WALL ON UNIT | | | FLOOR PLAN. (SEE PAGE 7.56). | | | 5. SHT T-4 A4.1.11 MEN'S & WOMEN'S | | | TOILET ROOMS SHALL COMPLY WITH SECTIONS | | | 11-4.16, 11-4.19 & 11-4.22 WITH ALL | | | SUBSECTIONS. SUBMIT A DETAIL SHOWING | | | COMPLIANCE. | | | 6. SUBMIT CALCULATIONS FOR ALL | | | AMENITITES AREAS FOR MINIMUM FACILITIES | | | PER TABLES 1004.2 (BLDG) AND 403.1 | | | (PLMG). SHOW THE SQUARE FOOTAGE FOR ALL | | | COMMON USE AREAS ALONG WITH THE | | | OCCUPANCY LOAD OF EACH AREA. INDICATE | | | THE LOCATION OF THE SANITARY FACILITIES | | | FOR THE POOL AREA. | | | 7. SHT T-4 A7.1.1 FLOORS AND WALLS IN | | | TOILET ROOM SHALL BE NONABSORBENT PER | | | SECTIONS 1210.1 & 1210.2. PLEASE | | | INDICATE HOW THIS WILL BE ACCOMPLISHED | | | WITH EXPOSED CONCRETE, GYP. BOARD AND NO | | | BASE AS SHOWN IN GROUND LEVEL ROOM | | | FINISH SCHEDULE. | | | 8. SHT T-4 A4.11 SINK IN CATERING | | | KITCHEN SHALL COMPLY WITH SECTION | | | 11-4.24 AND ALL SUBSECTIONS. PROVIDE A | | | DETAIL. | | | 9. SHT T-4 A6.1.1 DETAIL #4 TRASH CHUTE | | | WATER SUPPLY SHALL HAVE BACKFLOW | | | PROTECTION. INDICATE THE METHOD OF | | | BACKFLOW PROTECTION REQUIRED IN SECTION | | | 608 AND TABLE 608.1. | | | 10. SHT T-4 A6.1.3 DETAIL #10 ROOF DRAIN | | | DETAIL, INDICATE MEASUREMENT FROM THE | | | ROOF TO THE TOP OF THE SECONDARY ROOF | | | DRAIN PIPI, (EMERGENCY OVERFLOW PIPE). | | | 11. SHT T-4 A8.1.1 SHOW THE BACKING FOR | | | THE W/C'S PER FHA DESIGN MANUAL PAGES | | | 6.3 & 6.4. SHOW BACKING FOR THE TUBS PER | | | PAGE 6.9. | | | 12. SHT P0.1 PLUMBING NOTES #1 & #24 | | | REFER TO FBC-2001, CODE ADOPTED FOR THIS | | | JOB IS FBC-2004. PLEASE CHANGE REFERENCE | | | 13. SUBMIT A STORM BUILDING DRAIN | | | ISOMETRIC RISER DIAGRAM. SHOW ALL SQUARE | | | FOOTAGE AS IT ACCUMULATES. INDICATE THE | | | RISER NUMBER CONNECTING TO STORM DRAIN. | | | INDICATE ALL PIPE SIZES AND SLOPE OF | | | PIPE. | | | 14. SHT P2.1 NO SANITARY BRANCH LINE | | | SHOWN TO RISERS S/9,S/37, S/41 OR S/46 | | | FROM THE BUILDING SANT. DRAIN. PLEASE | | | SHOW ALL PIPING ON FLOOR PLAN. SECTION | | | 106.1.1. - MANY FITTINGS CONNECTING | | | BRANCH LINES TO BLDG. SANT. DRAIN ARE | | | NOT SHOWN TO GUIDE SEWAGE AND WASTE IN | | | THE DIRECTION OF FLOW. SECTION 706.3. - | | | IDENTIFY RISER BETWEEN ROOMS B110 & | | | B110. SECTION 104.2.1. - NO PIPING SHOWN | | | TO RWL IN FITNESS CENTER. ALSO RWL DOES | | | NOT APPEAR TO BE IN THE WALL. SECTION | | | 104.2.1. | | | 15. SHT P2.3 6" RWL (2200SF) SHOWN IN | | | THE HALLWAY. PLEASE CLARIFY. SECTION | | | 106.1.1. | | | 16. SHT P2.4 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS. (SEE | | | COMMENT #3). | | | 17. SHT P3.1 NO PIPING SHOWN TO CD/8. | | | SECTION 104.2.1. | | | 18. SHT P3.3 2ND SHEET WITH 2ND, 4TH - | | | 12TH FLOORS. NO 3RD FLOOR SUBMITTED. | | | PLEASE CLARIFY. | | | 19. SHT P4.1 AN RPZV BACKFLOW IS | | | REQUIRED ON THE WATER SERVICE TO EACH | | | BUILDING. | | | 20. SHT P4.1 SHOWS 3" WATER SERVICE TO | | | EACH TOWER, BUT CIVIL PLANS, SHTS P3.1, | | | AND P6.4 SHOW 4" WATER SERVICE. PLEASE | | | CORRELATE PLANS. SECTION 106.1.1. | | | 21. SHTS P5.1 & P5.2 SUBMIT SOVENT | | | DESIGN MANUAL FOR THE SOVENT SYSTEM. THE | | | SOVENT SYSTEM SHALL BE APPROVED. SECTION | | | 106.1.1. | | | 22. SHT P5.3 BLDG DRAIN ISOMETRIC RISER | | | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. | | | THE ISOMETRIC IS REVERSE FROM THE FLOOR | | | PLAN. THE BLDG. DRAIN IS SHOWN AS | | | EXITING THE BLDG. BETWEEN S/1 & S/2 ON | | | THE FLOOR PLAN. SHOW ALL GROUND FLOOR | | | FIXTURE PIPING ON THE ISOMETRIC WITH ALL | | | PIPE SIZES AND VENTING. SECTION | | | 104.3.1.1. | | | 23. SHT P5.3 SHOW DFU'S AS THEY | | | ACCUMULATE IN THE SYSTEM. TABLE 710.1(1) | | | 24. SHTS P6.1, P6.2, & P6.3 WATER HAMMER | | | ARRESTORS SHALL BE LOCATED NEAR THE | | | FIXTURES IN AN 'EFFECTIVE RANGE" NOT IN | | | THE CEILING AS SHOWN. PDI-WH 201 AND | | | MANUF. INSTALLATION INSTRUCTIONS. - FULL | | | OPEN VALVES ARE REQUIRED ON THE TOP OF | | | ALL WATER DOWN-FEED LINES. SECTION | | | 606.1(4) | | | 25. SUBMIT A CONDENSATE BUILDING DRAIN | | | ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE | | | SIZES, TERMINATION POINTS FOR THE | | | CONDENSATE DRAIN AND VENT. SECTION | | | 106.3.5.1.3. - SUBMIT CONDENSATE RISER | | | DIAGRAMS. SHOW ALL PIPE SIZES. | | | 26. SUBMIT STORM RISER DIAGRAMS AND A | | | BUILDING DRAIN ISOMETRIC RISER DIAGRAM. | | | SHOW ALL PIPE SIZES, LOCATION OF ALL | | | RISER CONNECTIONS, SQUARE FOOTAGE AS IT | | | ACCUMULATES IN THE SYSTEM, TERMINATION | | | POINT OF STORM WATER ECT. SECTION | | | 106.3.5.1.3. | | | 27. THE FOLLOWING INFORMATION REQUIRED | | | FOR THE GAS PERMIT: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. CUT SECTIONS NOT SHOWN | | | AND MOST RISERS NOT SHOWN. | | | B. TYPE OF GAS, (LP OR NATURAL) | | | C. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2 | | | E. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | F. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-07-02 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-07-02 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-07-02 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2006-07-02 00:00:00 | 7/2/06 ***FAILED*** | | | | | | 1) INDICATE ON THE PHASING PLAN THAT THE | | | TURQUOISE NECKLACE WILL BE DESIGNED, | | | PERMITTED AND CONSTRUCTED AS PART OF | | | PHASE 2. | | | | | | 2) THE TURQUOISE NECKLACE SHALL BE | | | PROVIDED ON THE CIVIL DRAWINGS.A NOTE | | | MAY BE PROVIDED INDICATING THAT IT WILL | | | BE DESIGNED, PERMITTED AND CONSTRUCTED | | | AS PART OF PHASE 2. | | | | | | 3) UNITY OF TITLE SHALL BE RECORDED IN | | | THE PUBLIC RECORD OF PALM BEACH COUNTY. | | | A COPY SHALL BE INCLUDED WITH ALL PERMIT | | | PACKAGES. | | | | | | 4) PARKING STALL DETAIL SHALL CONFORM TO | | | THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS.A WHEEL STOP SHALL BE | | | SHOWN 2 FEET FROM THE HEAD OF THE STALL. | | | IF NO WHEEL STOP IS PROVIDED, SIDEWALKS | | | LOCATED AT THE HEAD OF THE STALL NEED TO | | | BE 7 FEET IN WIDTH TO ALLOW FOR 2 FEET | | | OF VEHICLE OVERHANG.IF THE OVERHANG | | | OCCURS OVER LANDSCAPING, THE LANDSCAPING | | | SHALL NOT EXCEED 6 INCHES ABOVE THE | | | HEIGHT OF THE CURB.DETAIL OF DOUBLE | | | STRIPING NEEDS TO SHOW 12 INCHES FROM | | | INSIDE OF STRIP TO INSIDE OF STRIPE. | | | | | | 5) ALL LANDSCAPE SHEETS NEED TO BE | | | SIGNED AND SEALED BY A REGISTERED | | | LANDSCAPE ARCHITECT, NOT JUST THE COVER | | | SHEET. | | | | | | 6) LANDSCAPE PLANS NEED TO BE ADJUSTED | | | TO INDICATE THAT TOWNHOUSE #7 IS PART OF | | | PHASE 1. | | | | | | 7) THE LIFT STATION SHOWN ON THE CIVIL | | | PLANS DOES NOT MATCH THAT SHOWN ON THE | | | LANDSCAPE PLAN.LANDSCAPING NEEDS TO BE | | | ADJUSTED ACCORDINGLY. | | | | | | 8) AS A RESULT OF EACH BUILDING BEING | | | CO'D SEPARATELY, AN INSPECTION PLAN | | | SHALL BE PROVIDED INDICATING WHICH AREAS | | | OF LANDSCAPING WILL BE INSPECTED WITH | | | EACH BUILDING CO. | | | | | | 9) THE AREAS BETWEEN THE TOWERS ARE | | | SHOWN AS FA GRASS.THIS SHALL BE | | | MODIFIED AS THE BOARDWALKS ARE NO LONGER | | | BEING PROPOSED. | | | | | | 10) THE SIDEWALK CONFIGURATION ON THE | | | LANDSCAPE PLANS AND THE CIVIL PLANS | | | SHALL CORRESPOND WITH THE SITE PLAN. | | | | | | 11) THE LANDSCAPE PLANS SHWO THE BUS | | | SHELTER AND ENTRANCE WALL/LANDSCAPING AS | | | PART OF PHASE 1.THE PHASING PLAN | | | INDICATES OTHERWISE. | | | | | | 12) FYI...IN DEVELOPING THE SIGNAGE FOR | | | THE FRONT ENTRY WALL, THE AREA SHALL NOT | | | EXCEED 48 SQUARE FEET. | | | | | | 13) A PHOTOMETRIC PLAN SHALL BE PROVIDED | | | FOR SITE LIGHTING ON THE ENTIRE | | | PROPERTY.THE PHOTOMETRIC LEVELS SHALL | | | BE SHOWN AT THE PROPERTY LINES AND SHALL | | | NOT EXCEED 0.5 FOOTCANDLES AT PROPERTY | | | LINES ADJACENT TO RESIDENTIAL PROPERTY. | | | | | | THE FOLLOWING COMMENTS HAVE BEEN | | | PROVIDED BY ALAN BARATTA, LANDSCAPE | | | PLANNER: | | | | | | 1) PLANTING DIAGRAMS SHALL BE MODIFIED | | | TO REFLECT WHAT WAS AGREED TO IN THE | | | TREE REMOVAL/RELOCATION LICENSE. | | | | | | 2) IN ORDER TO PREVENT DESTRUCTION TO | | | CURBING, PAVING AND PARKED VEHICLES, | | | REPLACE THE MOHOGANY TREES IN THE | | | LANDSCAPE ISLANDS IN FRONT OF THE | | | TOWNHOMES WITH A SMALLER/ALTERNATE | | | SPECIES.MINOR PD AMENDMENT (PB CASE | | | NO. 1242E) APPROVED ON JULY 2, 2006, | | | INDICATED GREEN BUTTONWOODS. | | | | | | 3) ADDITIONAL LANGUAGE SHALL BE PROVIDED | | | INDICATING REMOVAL OF SUPPORT MATERIAL | | | FROM TREES/PALMS SHALL OCCUR AFTER | | | ESTABLISHMENT OR HURRICANE SEASON, | | | WHICHEVER COMES LATER. | | | | | | 4) LANDSCAPING IN THE EXECUTIVE CENTER | | | DRIVE CUL-DE-SAC SHALL BE COORDINATED | | | WITH THE PUBLIC UTILITIES/ENGINEERING | | | DEPARTMENT. | | | | | | MISCELLANEOUS COMMENTS: | | | | | | 1) WORKFORCE HOUSING RESTRICTION ON THE | | | LOFTS AND TOWNHOMES, FOLLOWING APPROVAL | | | BY THE CITY OF WEST PALM BEACH, SHALL BE | | | IN PLACE PRIOR TO THE ISSUANCE OF A CO | | | FOR SUCH STRUCTURES. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, | | | SENIOR PLANNER, AT (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2005-09-20 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2005-09-20 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2005-09-20 00:00:00 | 9/20/2005 ***FAILED*** | | | | | | ALL PERMITS | | | | | | 1. INDICATE ON THE PHASING PLAN THAT THE | | | TURQUOISE NECKLACE WILL BE DESIGNED, | | | PERMITTED AND CONSTRUCTED AS PART OF | | | PHASE 2. | | | | | | 2. THE TURQUOISE NECKLACE SHALL BE | | | PROVIDED ON THE CIVIL DRAWINGS?A NOTE | | | MAY BE PROVIDED THAT IT WILL BE | | | DESIGNED, PERMITTED AND CONSTRUCTED AS | | | PART OF PHASE 2. | | | | | | 3. PHASING PLAN DOES NOT ACCURATELY | | | REFLECT WHAT IS BEING PROPOSED | | | (TOWNHOUSE #7 IS SHOWN AS PART OF PHASE | | | 3, NOT PHASE 1 AS PROPOSED). | | | | | | 4. UNITY OF TITLE SHALL BE RECORD INTO | | | THE PUBLIC RECORDS OF PALM BEACH COUNTY | | | WITH THE CLERK OF THE CIRCUIT COURT.A | | | COPY SHALL BE INCLUDED WITH ALL PERMIT | | | PACKAGES. | | | | | | 5. IN RESPONSE TO ELECTRICAL PLAN REVIEW | | | COMMENT #1 (PERMIT #05080676)?THE | | | PROPERTY MAY NOT BE REPLATTED TO PROVIDE | | | FEE-SIMPLE TOWNHOMES. | | | | | | 6. PARKING STALL DETAIL SHALL BE | | | MODIFIED TO PROVIDE A WHEEL STOP 2? FROM | | | THE HEAD OF THE STALL.IF NO WHEEL STOP | | | IS PROVIDED AND THE VEHICLE OVERHANGS A | | | SIDEWALK, THE SIDEWALK SHALL BE 7? IN | | | WIDTH MINIMUM.IF THE VEHICLE OVERHANGS | | | LANDSCAPING, THE LANDSCAPING SHALL NOT | | | BE HIGHER THAN 6? ABOVE THE HEIGHT OF | | | THE CURB. | | | | | | 7. ALL LANDSCAPE SHEETS SHALL BE SIGNED | | | AND SEALED, NOT JUST THE COVER SHEET. | | | | | | 8. LANDSCAPE PLANS SHALL BE ADJUSTED TO | | | INDICATE THAT TOWNHOUSE #7 IS PART OF | | | PHASE 1. | | | | | | 9. AS A RESULT OF EACH BUILDING BEING | | | CO?D SEPARATELY, AN INSPECTION PLAN | | | SHOULD BE PROVIDED FOR THE LANDSCAPING, | | | INDICATING WHICH AREAS WILL BE SUBJECT | | | TO INSPECTION WITH EACH BUILDING. | | | | | | 10. AREAS BETWEEN THE TOWERS ARE SHOWN | | | AS FA GRASS.THIS SHOULD BE MODIFIED AS | | | THE BOARDWALKS NO LONGER EXIST. | | | | | | 11. THE SIDEWALK CONFIGURATION ON THE | | | LANDSCAPE PLANS SHALL CORRESPOND WITH | | | THE SITE PLAN AND CIVIL DRAWINGS (REFER | | | TO AREA BETWEEN THE TOWERS). | | | | | | 12. THE LANDSCAPE PLANS SHOW THE BUS | | | SHELTER INCLUDED IN PHASE 1.THE | | | PHASING PLAN INDICATES OTHERWISE.IF IT | | | IS TO BE CONSTRUCTED WITH PHASE 1, NO | | | ARCHITECTURAL DRAWINGS HAVE BEEN | | | PROVIDED. | | | | | | 13. FENCES/WALLS/COLUMNS SHALL NOT | | | EXCEED 48? IN HEIGHT WITHIN THE FRONT | | | SETBACK (25? FROM EXECUTIVE CENTER | | | DRIVE).REFER TO ENTRY GATE WALL LAYOUT | | | AND ELEVATIONS.IN ORDER TO EXCEED THE | | | MAXIMUM HEIGHT, A MINOR PD AMENDMENT MAY | | | BE SUBMITTED TO THE PLANNING DEPARTMENT | | | FOR REVIEW. | | | | | | 14. THE ENTRY GATE WALL LAYOUT, | | | ELEVATIONS AND SIGNAGE WALL DO NOT | | | CORRESPOND WITH EACH OTHER IN REGARD TO | | | HEIGHT, ETC. | | | | | | 15. IN DEVELOPING THE SIGNAGE FOR THE | | | MAIN ENTRY, THE SIGNS AREA SHALL NOT | | | EXCEED 48 SQUARE FEET. | | | | | | 16. FENCES/WALL/COLUMNS SHALL NOT EXCEED | | | 72? IN HEIGHT WITHIN THE REQUIRED SIDE | | | AND REAR SETBACK (15? FROM THE PROPERTY | | | LINES).REFER TO THE WALL ELEVATIONS | | | ASSOCIATED WITH THE SOUTH LAP POOL.THE | | | HEIGHT OF THE FENCE/WALL/COLUMNS SHALL | | | BE REDUCED IN HEIGHT OR MOVE THE | | | LOCATION OUTSIDE OF THE SETBACK. | | | | | | 17. FOUNTAINS WERE NOT SHOWN IN THE | | | INTERIOR TRAFFIC CIRCLES.PLEASE | | | CLARIFY IF THIS WILL BE INCLUDED UNDER A | | | SEPARATE PERMIT.IF UNDER THIS PERMIT, | | | ADJUST ALL PLANS NECESSARY AND PROVIDE | | | DETAILS FOR REVIEW BY OTHER DISCIPLINES. | | | | | | 18. A PHOTOMETRIC PLAN SHALL BE PROVIDED | | | INDICATING SITE LIGHTING AND | | | CORRESPONDING LEVELS.PHOTOMETRIC | | | LEVELS SHALL BE PROVIDED AT THE PROPERTY | | | LINE AND SHALL NOT EXCEED 0.5 | | | FOOTCANDLES AT PROPERTY LINES THAT ABUT | | | ADJACENT RESIDENTIAL PROPERTY. | | | | | | THE FOLLOWING COMMENTS HAVE BEEN | | | PROVIDED BY ALAN BARATTA, LANDSCAPE | | | PLANNER: | | | | | | 1. PLANTING DIAGRAMS SHALL BE MODIFIED | | | TO REFLECT WHAT WAS AGREED TO IN THE | | | TREE REMOVAL/RELOCATION LICENSE. | | | | | | 2. IN ORDER TO PREVENT DESTRUCTION TO | | | CURBING, PAVEMENT AND PARKED VEHICLES, | | | REPLACE THE MAHOGANY TREES IN THE | | | LANDSCAPE ISLANDS LOCATED IN FRONT OF | | | THE TOWNHOMES WITH A SMALLER/ALTERNATE | | | SPECIES. | | | | | | 3. ADDITIONAL LANGUAGE SHALL BE PROVIDED | | | INDICATING THE REMOVAL OF SUPPORT | | | MATERIAL FROM TREES/PALMS AFTER | | | ESTABLISHMENT OR HURRICANE SEASON, | | | WHICHEVER COMES LATER. | | | | | | 4. LANDSCAPING IN THE EXECUTIVE CENTER | | | DRIVE CUL-DE-SAC SHALL BE COORDINATED | | | WITH JONATHON BRAMLEY (CITY OF WEST PALM | | | BEACH PUBLIC UTILITIES ? (561) | | | 494-1040). | | | | | | MISCELLANEOUS COMMENTS: | | | | | | 1. WORKFORCE HOUSING RESTRICTIONS ON THE | | | LOFTS AND TOWNHOMES, FOLLOWING APPROVAL | | | BY THE CITY OF WEST PALM BEACH, SHALL BE | | | IN PLACE PRIOR TO THE ISSUANCE OF A | | | CERTIFICATE OF OCCUPANCY (CO) FOR SUCH | | | STRUCTURES. | | | | | | TOWER #4 | | | | | | 1. NO ADDITIONAL COMMENTS. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, | | | PLANNER AT (561) 822-1435. |
|
|
|