Plan Review Details - Permit 05080658
Plan Review Stops For Permit 05080658
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2005-08-11 Cont ID  
Sent By ptjomsto Date 2005-08-11 Time 12:11 Rev Time 0.00
Received By pkrauss Date 2005-09-07 Time 07:38 Sent To  
Notes
2005-08-11 00:00:00EXT REQUIRED FOR STE #103

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-22 Cont ID  
Sent By mjacobs Date 2005-09-22 Time 10:03 Rev Time 1.25
Received By mjacobs Date 2005-09-22 Time 08:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-30 Cont ID  
Sent By mjacobs Date 2005-08-30 Time 09:30 Rev Time 0.75
Received By mjacobs Date 2005-08-30 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-12 Cont ID  
Sent By mjacobs Date 2005-08-12 Time 09:54 Rev Time 0.50
Received By mjacobs Date 2005-08-12 Time 09:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-21 Cont ID  
Sent By dpalmer Date 2005-09-21 Time 18:53 Rev Time 0.25
Received By dpalmer Date 2005-09-21 Time 18:53 Sent To  
Notes
2005-09-21 00:00:00NEW SHEETS.
  
 REDLINED 230.70A2

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-30 Cont ID  
Sent By dpalmer Date 2005-08-30 Time 12:53 Rev Time 0.25
Received By dpalmer Date 2005-08-30 Time 12:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-15 Cont ID  
Sent By dpalmer Date 2005-08-15 Time 06:32 Rev Time 0.25
Received By dpalmer Date 2005-08-15 Time 06:32 Sent To  
Notes
2005-08-15 00:00:00**** UNSAT ******
  
 PLEASE SEE PLANS ARE COMING BACK FOR
 PLUYMB COMMENTS, PLEASE MAKE THE BELOW
 CORRECTIONS AT THIS TIME.
  
 1)NOTE: PLEASE SEE 2002NEC 210.8B3,
 WHICHREQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 2)NOTE: PLEASE BE SURE ENIGINEER SIGNS
 PLANS WITH LEGAL SIGNATURE AS IS ON
 FILE.
 SIGNATURE DOES NOT CORRELATE WITH FILE.
 FS 471.025, FAC 61G15-16.002
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-09-22 Cont ID  
Sent By mwennerg Date 2005-09-22 Time 11:19 Rev Time 0.00
Received By mwennerg Date 2005-09-22 Time 11:19 Sent To  
Notes
2005-09-22 00:00:00******OK******
  
 ADDRESS ON RESUBMITTAL FORM INCORRECT?

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-31 Cont ID  
Sent By mwennerg Date 2005-08-31 Time 10:00 Rev Time 0.00
Received By mwennerg Date 2005-08-31 Time 10:00 Sent To  
Notes
2005-08-31 00:00:00PASSED ON 8/15/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-08-15 Cont ID  
Sent By mwennerg Date 2005-08-15 Time 10:41 Rev Time 0.00
Received By mwennerg Date 2005-08-15 Time 10:41 Sent To  
Notes
2005-08-15 00:00:00******PASSED******
  
 SEPARATE SHOP DRAWINGS AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-19 Cont ID  
Sent By adarroug Date 2005-09-19 Time 09:11 Rev Time 0.00
Received By adarroug Date 2005-09-19 Time 09:11 Sent To  
Notes
2005-09-19 00:00:00TO "BOB" #12/NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-29 Cont ID  
Sent By adarroug Date 2005-08-29 Time 14:54 Rev Time 0.00
Received By adarroug Date 2005-08-29 Time 14:54 Sent To  
Notes
2005-08-29 00:00:00TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-15 Cont ID  
Sent By mwennerg Date 2005-08-15 Time 10:42 Rev Time 0.00
Received By mwennerg Date 2005-08-11 Time 17:00 Sent To  
Notes
2005-08-11 00:00:00TO "BOB"#3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-07 Cont ID  
Sent By pkrauss Date 2005-09-07 Time 07:39 Rev Time 0.30
Received By pkrauss Date 2005-09-07 Time 07:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-08-12 Cont ID  
Sent By hmoser Date 2005-08-12 Time 09:13 Rev Time 0.50
Received By prafter Date 2005-09-28 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-09-26 Cont ID  
Sent By jleech Date 2005-09-26 Time 09:07 Rev Time 0.50
Received By jleech Date 2005-09-26 Time 09:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-09-07 Cont ID  
Sent By kstevens Date 2005-09-07 Time 17:13 Rev Time 1.00
Received By kstevens Date 2005-09-07 Time 17:13 Sent To  
Notes
2005-09-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
 3. INDICATE THE CLEAR FLOOR SPACE AT THE
 LAVATORY AND THE WATER CLOSET. FBC
 11-4.19.3 AND 11-4.16.2. - NOT ADDRESSED
 9. MIRRORS MUST COMPLY WITH FBC
 11-4.19.6. SHOWN AS 3'2" WHEN 3'4" IS
 REQUIRED.
 10. 11-4.24.4 DEPTH. EACH SINK SHALL BE
 A MAXIMUM OF 6-1/2" DEEP. - NO RESPONSE.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30"X48" SHALL BE
 PROVIDED IN FRONT OF THE SINK TO ALLOW
 FORWARD APPROACH AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK. SEE
 FIG. 11-32. - NO RESPONSE NOTED.
 11-4.24.6 EXPOSED PIPES & SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER
 SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER SINKS. - NO
 RESPONSE NOTED.
 11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH 11-4.27.4. LEVER-OPERATED,
 PUSH-TYPE, TOUCH-TYPE, OR ELECTRONICALLY
 CONTROLLED MENCHANISMS ARE ACCEPTABLE
 DESIGNS. - NO RESPONSE NOTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-13 Cont ID  
Sent By pschmitz Date 2005-08-13 Time 13:15 Rev Time 0.00
Received By pschmitz Date 2005-08-13 Time 13:15 Sent To E
Notes
2005-08-13 00:00:00PAUL SCHMITZ, PLUMBING PLANS EXAMINER
 [email protected]
  
 PLUMBING PLAN REVIEW FBC 2001
 DENIED
 (1) SEC 1012.1.4 REST ROOM DOOR SWING.
 SHT 1. PROVIDE FLOOR PLAN TO SHOW AREA
 NEW DOOR WILL BE OPENING INTO.
 (2) ?P310.4 WATER CLOSET COMPARTMENT.
 EACH WATER CLOSET UTILIZED BY THE
 PUBLIC OR EMPLOYEES SHALL OCCUPY A
 SEPARATE COMPARTMENT WITH A DOOR AND
 WALLS OR PARTITIONS BETWEEN FIXTURES TO
 ENSURE PRIVACY.
  
 (3) INDICATE THE CLEAR FLOOR SPACE AT
 LAVATORY AND WATER CLOSET. FBC 11-4.19.3
 AND 11-4.16.2
  
 (4) INDICATE THE UNOBSTRUCTED TURNING
 SPACE REQUIRED BY FBC 11-4.22.3.
  
 (5) PROVIDE BATHROOM ELEVATIONS ON THE
 PLANS. SHOW THE REQUIRED LOCATIONS
 CLEARANCES AND HEIGHTS OF ALL ACCESSIBLE
 FIXTURES. FBC CHAPTER 11.
  
 (7) THE DISTANCE FROM THE WALL TO THE
 CENTER OF THE WATER CLOSET IS 18". SEE
 FBC CHAP.11 FIGURE 28.
  
 (8) SIDE GRAB BAR IS REQUIRED TO BE 12"
 OFF THE REAR WALL. SEE FIGURE 29.
  
 (9) MIRRORS MUST COMPLY WITH FBC
 11-4.19.6.
  
 (10) BREAK ROOM SINK
 ?11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
  
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
  
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
  
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
  
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
  
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
  
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
  
 IF THERE ANY QUESTIONS, DO NOT
 HESITATE TO CALL.