Plan Review Details - Permit 05080656
Plan Review Stops For Permit 05080656
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-09-19 Cont ID  
Sent By alange Date 2005-09-19 Time 13:26 Rev Time 0.50
Received By alange Date 2005-09-19 Time 13:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-09 Cont ID  
Sent By btrobaug Date 2005-11-09 Time 12:41 Rev Time 0.50
Received By btrobaug Date 2005-11-09 Time 12:36 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-10-14 Cont ID  
Sent By btrobaug Date 2005-10-14 Time 18:44 Rev Time 0.50
Received By btrobaug Date 2005-10-14 Time 07:45 Sent To M
Notes
2005-10-14 00:00:00.PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE CALCULATED LOAD EXCEEDS THE
 GENERATOR OUTPUT.
  
 2} THE MAINS ARE NOT GROUPED.
  
 3} THERE IS NO GENERATOR DISCONNECT PER
 225.31. THE TOGGLE SWITCH IS NOT SERVICE
 RATED.
  
 4} THE FEEDER WIRE MUST COMPLY WITH
 445.13. 115% OF NAMEPLATE.
  
 I WILL BE OUT UNTILL 10/24, I HAVE
 DISCUSSED THIS WITH DEWEY, IF YOU HAVE
 QUESTIONS BEFORE I RETURN PLEASE CALL
 HIM AT 805-6717.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By btrobaug Date 2005-08-23 Time 09:28 Rev Time 0.33
Received By btrobaug Date 2005-08-23 Time 09:28 Sent To M
Notes
2005-08-23 00:00:00 
 PLEASE NOTE THAT LOAD CALCS INDICATE A
 2000VA WATER HEATER,SEE 220.18 AND THE
 RANGE MUSTBE IN COMPLIANCE WITH 220.19.
  
 SEE 700.5 FOR LOADS @ 100%. THE GENERAL
 LIGHTING LOAD MAY USE THE DEMAND FROM
 TABLE 220.11.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 09:54 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 09:54 Sent To E
Notes
2005-10-11 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-22 Cont ID  
Sent By adarroug Date 2005-08-22 Time 09:02 Rev Time 0.00
Received By adarroug Date 2005-08-22 Time 09:02 Sent To E
Notes
2005-08-22 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-19 Cont ID  
Sent By alange Date 2005-09-19 Time 13:28 Rev Time 0.00
Received By alange Date 2005-08-11 Time 19:02 Sent To  
Notes
2005-08-11 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-10-17 Cont ID  
Sent By tgordon Date 2005-10-17 Time 08:06 Rev Time 0.20
Received By tgordon Date 2005-10-17 Time 08:06 Sent To P
Notes
2005-10-17 00:00:00*** PROVISO ***
 1) GENERATOR EXHUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENINGS. PER 2001 FBC/M 804.3.3 .
 2) MANUFACTURE'S INSTALLATION
 INSTRUCTIONS MUST BE ON JOB SITE FOR
 INSPECTOR.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-30 Cont ID  
Sent By prafter Date 2005-08-30 Time 07:48 Rev Time 0.75
Received By prafter Date 2005-08-30 Time 07:48 Sent To P
Notes
2005-08-30 00:00:00MECH. PLAN REVIEW:
  
 1. PLAN MUST INDICATE ANY BUILDING
 OPENING, WINDOWS/DOOR/ROOF VENTS.
 GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS, AND TEN
 FEET AWAY FROM ADJACENT BUILDING
 OPENINGS.
 2001 FBC/M 804.3.3 TERMINATION.
 2001 FBC SECTION 915 REQUIREMENT OF
 NFPA 37 8.2.3.2 EXHAUST SYSTEM
 TERMINATION.
  
 2. LP GAS REQUIRE LICENSE
 GAS CONTRACTOR AND MUST SUBMIT GAS
 PIPING DRAWING WITH GAS PERMIT APP.
  
 3. GENERATOR MANF. RECOMATIONS FOR
 SERVICE CLEARANCE/VENELATION IN
 FEET/INCHES IN ALL DIRECTIONS MUST ACCM.
 GENERATOR PERMIT APP. NEC 70 110.3 B .
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-10-17 Cont ID  
Sent By jleech Date 2005-10-17 Time 09:18 Rev Time 0.25
Received By jleech Date 2005-10-17 Time 09:16 Sent To  
Notes
2005-09-13 00:00:00PERMIT REQUIRED FOR FUEL INSTALLATION
 BEFORE FINAL INSPECTION.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-18 Cont ID  
Sent By mmclean Date 2005-08-18 Time 17:17 Rev Time 0.00
Received By mmclean Date 2005-08-18 Time 17:17 Sent To I
Notes
***NONE***