| 2005-09-13 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- ENERGY CALCS ARE GETTING THE CEILING |
| | FAN CREDIT. NEED TO SPECIFY CEILING |
| | SIZES IN THE ELECTRICAL PLAN, INCLUDING |
| | FANS REQUIRED AT GREAT ROOM. SEE TABLE |
| | 6-6 CHAPTER 13 FBC 2001. |
| | |
| | 3- ROOF FRAMING PLAN NEEDS TO BE REVISED |
| | AT ENTRY PORCH AREA TO MATCH FOUNDATION |
| | AND FLOOR PLAN. CONCRETE BEAM DOESN'T |
| | EXTEND ALL THE WAY BACK TO THE FOYER. |
| | CONCRETE BEAM IS ONLY AT ENTRY PORCH |
| | AREA. REVISE ROOF FRAMING PLAN AS |
| | REQUIRED AND SPECIFY CORRESPONDING |
| | CONNECTORS. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 4- TRUSS ANCHOR SCHEDULE: REVISE NUMBER |
| | OF NAILS SPECIFIED FOR CONNECTOR HUS26. |
| | SEE 2005 CATALOGUE. |
| | |
| | 5- ONE HR FIRE RATED DOOR AT ATRIUM |
| | PRODUCT APPROVAL SUBMITTED IS FOR |
| | OUTSWING DOOR. PLANS SHOW INSWING DOORS. |
| | REVISE AS REQUIRED. |
| | |
| | 6- SPECIFY MULLION SIZE AND ANCHORS FOR |
| | FIXED WINDOWS AT GREAT ROOM. SIZE OF |
| | MULLION SPECIFIED ON WINDOW SCHEDULE |
| | DOESN'T RESIST THE CALCULATED DESIGN |
| | PRESSURES. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL FOR WINDOW |
| | MULLION SIZE AS SPECIFIED ABOVE. |
| | |
| | 8- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL (FLORIDA APPROVAL WAS NOT |
| | SUBMITTED) FOR: |
| | A) ROOF TILE. |
| | B) SINGLE HUNG WINDOWS. |
| | C) FIXED WINDOWS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |