Plan Review Details - Permit 05080560
Plan Review Stops For Permit 05080560
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-18 Cont ID  
Sent By shill Date 2006-04-18 Time 14:58 Rev Time 0.00
Received By shill Date 2006-04-18 Time 14:54 Sent To  
Notes
2006-04-18 00:00:00****PROVISO***
 ACCESSIBLE ROUTE > 44"
 ACCESSIBLE PARKING TO COMPLY WITH CITY
 OF WPB STANDARD, SEE DETAIL
  
  
  
 NOTE - REMOVED LANDSCAPE PLANS PER
 CONTRACTOR REQUEST, NO DATE ON SEAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-03-14 Cont ID  
Sent By shill Date 2006-03-14 Time 09:19 Rev Time 0.00
Received By shill Date 2006-03-14 Time 08:52 Sent To  
Notes
2006-03-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS FROM PREVIOUS TWO REVIEWS:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 THE NOC PROVIDED IS EXPIRED (OVER A YEAR
 OLD WITH NO OTHER EXPIRATION DATE
 SPECIFIED).THIS COMMENT DOES NOT
 PREVENT THE PERMIT FROM BEING ISSUED,
 BUT A CURRENT VALID NOC MUST BE PROVIDED
 PRIOR TO PERMIT PICKUP.FS713.13
  
 2.)(FIRST REVIEW COMMENT) PROVIDE A
 SITE PLAN SO THAT CODE COMPLIANCE CAN BE
 DETERMINED, FBC TABLE 600, FBC CHAPTER
 11 (ACCESSIBLE ROUTE).
  
 (SECOND REVIEW COMMENT) THE LETTER
 STATING THAT THE SITE PLAN IS
 ON FILE WITH THE CITY IS ACKNOWLEDGED.
 HOWEVER, THIS PERMIT APPLICATION IS TO
 SHOW CODE COMPLIANCE.PROVIDE A SITE
 PLAN AS REQUESTED.SHOW DISTANCE TO
 ADJACENT BUILDINGS (IF ANY), ACCESSIBLE
 ROUTE (WIDTH AND SLOPE) SO THAT CODE
 COMPLIANCE CAN BE DETERMINED.
  
 THIRD REVIEW COMMENT - NOT PROPERLY
 ADDRESSED.TWO SITE PLANS WERE
 SUBMITTED.ONE IS AN REDUCED COPY OF A
 SITE PLAN PREPARED BY URBAN STUDIO
 DESIGN.THE OTHER FULL SIZE SHEET DOES
 NOT HAVE A TITLE BLOCK, AND IS NOT
 SIGNED AND SEALED.THE SITE PLAN MUST
 MUST BE A SIGNED, SEALED ORIGINAL
 FS481.306, FAC61G10-11.010 (LANDSCAPE
 ARCHITECT, SUBMITTED FOR PUBLIC RECORD).
 ALSO THE SITE PLAN DOES NOT SHOW THE
 REQUESTED INFORMATION TO DETERMINE CODE
 COMPLIANCE - SLOPE, SIDEWALK WIDTH,
 DISTANCE OF THIS STRUCTURE FROM OTHER
 STRUCTURES.FBC TABLE 600, FBC CHAPTER
 11, FBC*104.3.1.1.THE NOTE THAT THE
 PLANS ARE ON FILE WITH THE CITY ARE
 AGAIN ACKNOWLEDGED, BUT THIS PERMIT
 PACKAGE IS TO SHOW CODE COMPLIANCE.
  
 A 4X PLAN REVIEW FEE HAS BEEN CHARGED,
 AND WILL BE CHARGED EVERY TIME THAT THIS
 PLAN IS RESUBMITTED WITHOUT ADDRESSING
 THE ABOVE CODE ISSUES RELATED TO
 ACCESSIBILITY AND FIRE RESISTANCE
 REQUIREMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-23 Cont ID  
Sent By shill Date 2005-12-23 Time 09:30 Rev Time 1.00
Received By shill Date 2005-12-23 Time 07:56 Sent To  
Notes
2005-12-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS FROM PREVIOUS REVIEW:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PROVIDE A SITE PLAN SO THAT CODE
 COMPLIANCE CAN BE DETERMINED, FBC TABLE
 600, FBC CHAPTER 11 (ACCESSIBLE ROUTE).
  
 THE LETTER STATING THAT THE SITE PLAN IS
 ON FILE WITH THE CITY IS ACKNOWLEDGED.
 HOWEVER, THIS PERMIT APPLICATION IS TO
 SHOW CODE COMPLIANCE.PROVIDE A SITE
 PLAN AS REQUESTED.SHOW DISTANCE TO
 ADJACENT BUILDINGS (IF ANY), ACCESSIBLE
 ROUTE (WIDTH AND SLOPE) SO THAT CODE
 COMPLIANCE CAN BE DETERMINED.
  
 5.)THE CHIMNEY LINING IS TO COMPLY
 WITH FBC2113.3.8.PROVIDE PRODUCT
 SPECIFICATION SHEETS.
  
 SPECS FROM HOOD DEPOT WERE PROVIDED.IT
 APPEARS THAT YOU ARE USING AN EXHAUST
 DUCT.THE EXHAUST DUCT DOES NOT SHOW
 COMPLIANCE WITH THE REQUIREMENT OF
 FBC2113.3.8.PLEASE ADDRESS.
  
 6.)PROVIDE PRODUCT APPROVALS FOR THE
 SHINGLE ROOF.IF PRODUCT APPROVALS ARE
 NOT REVIEWED PRIOR TO PERMIT ISSUANCE A
 SEPARATE PERMIT WILL BE REQUIRED.
  
 SEVERAL DIFFERENT PRODUCTS WERE
 SUBMITTED.ONE NOA HAD ONLY ONE SHEET.
 PLEASE INDICATE WHICH PRODUCT YOU ARE
 INSTALLING AND SUBMIT ONLY THE NOA FOR
 THAT SHINGLE, BOTH THE NOA AND FLORIDA
 STATE PRODUCT APPROVAL WHICH CORRELATES
 WITH THE NOA.
  
  
 NEW COMMENTS -
  
 SHEET S3 IS NOT SEALED ON ONE OF THE
 SETS.PLEASE SEAL THIS PAGE IF YOU
 REQUIRE TWOSTAMPED SETS.
  
 SEE ATTACHED FS 553.80(2)(B).A 4X PLAN
 REVIEW FEE WILL BE CHARGED ITEMS ARE NOT
 ADDRESSED ON THIRD REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-06 Cont ID  
Sent By shill Date 2005-09-06 Time 15:55 Rev Time 2.00
Received By shill Date 2005-09-06 Time 15:55 Sent To  
Notes
2005-09-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PROVIDE A SITE PLAN SO THAT CODE
 COMPLIANCE CAN BE DETERMINED, FBC TABLE
 600, FBC CHAPTER 11 (ACCESSIBLE ROUTE).
  
 3.)NAILING FOR THE USP CONNECTORS
 CONFLICTS WITH THE CATALOG.IF THE
 CONNECTORS ARE INSTALLED IN A MANNER NOT
 CONSISTENT WITH THE STATE PRODUCT
 APPROVAL, A LOCAL PRODUCT APPROVAL IS
 REQUIRED FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 4.)PROVIDE ALL INFORMATION REQUIRED BY
 FBC1606.1.7.
  
 5.)THE CHIMNEY LINING IS TO COMPLY
 WITH FBC211.3.8.PROVIDE PRODUCT
 SPECIFICATION SHEETS.
  
 6.)PROVIDE PRODUCT APPROVALS FOR THE
 SHINGLE ROOF.IF PRODUCT APPROVALS ARE
 NOT REVIEWED PRIOR TO PERMIT ISSUANCE A
 SEPARATE PERMIT WILL BE REQUIRED.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-06-07 Cont ID  
Sent By dpalmer Date 2006-06-07 Time 18:33 Rev Time 0.00
Received By dpalmer Date 2006-06-07 Time 17:45 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-04-24 Cont ID  
Sent By dpalmer Date 2006-04-24 Time 20:54 Rev Time 0.00
Received By dpalmer Date 2006-04-24 Time 20:44 Sent To  
Notes
2006-04-24 00:00:00********* UNSAT *************
  
 1) NOTE: PLEASE CORRELATE SERVICE PANELS
 FEEDERS ETC.
 PLEASE SEE MDP IS NOW SHOWN AS 1-PHASE,
 HOWEVER MCB IS SHOWN AS 3-POLE?
 PLEASE SEE BRKRS FEEDING PANEL "PP" IS
 SHOWN AS 2 POLE FROM MDP , YET PANEL
 "PP" IS SHOWN AS CONTAINING A 3-POLE
 MCB?
 PLEASE SEE FEEDERS FROM MDP ARE SHOWN AS
 3-PHASE ON MDP AND SINGLE PHASE ON
 RISER?
 PLEASE CORRELATE ALL OF THE ABOVE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-03-01 Cont ID  
Sent By dpalmer Date 2006-03-01 Time 20:53 Rev Time 0.00
Received By dpalmer Date 2006-03-01 Time 20:32 Sent To  
Notes
2006-03-01 00:00:00************UNSAT ****************
  
 *** PLEASE SEE NEW ELECTRICAL PLANS ARE
 NOW BEING SUBMITTED WITH CHANGES TO
 PREVIOUS PLANS SUBMITTED.
 PLEASE SEE NOTES BELOW AS THERE HAVE
 BEEN MANY CHANGES.
  
 **************************************
  
 1)NOTE: PLEASE ONLY SUBMIT PLANS
 RELEVANT TO THE PERMIT APPLICATIONS
 SCOPE OF WORK. PLEASE SEE PERMIT
 APPLICATION IS FOR THE POOL PAVILION
 ONLY.
 PLEASE SEE PLANS NOW INDICATE A COMPLETE
 CHANGE IN THE "CLUBHOUSE" RISER DIAGRAM
 ETC.
 PLEASE SEE LOAD SUMMARY MENTIONS NEW
 PANEL "PP" TO BE LOCATED AT POOL
 PAVILION, HOWEVER PLANS DO NOT CORRELATE
 WITH THIS??
 PLEASE SEE THIS LOAD SUMMARY NOW
 INDICATES MORE THAN ONE MAIN AND NONE OF
 THESE ARE GROUPED.230.72 ETC
 PLEASE SEE THAT ANY REVISIONS TO
 "CLUBHOUSE" NEED TO BE SUBMITTED UNDER
 THAT PERMIT.
  
 2)NOTE: PLEASE SEE PLANS ARE STILL
 MISSING THE DISCONNECTING MEANS AT THE
 POOL PAVILION PER REQUIRED PER 225.31.
 ** PLEASE KNOW, THESE MAY BE SNAP
 SWITCHES IF SO
 DESIRED).
  
 3)NOTE: PLEASE SEE GROUNDING AT POOL
 PAVILION (WHICH IS A DETACHED STRUCTURE)
 TO BE PER 250.32.
  
 4)NOTE: PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS FROM THESE SETS WHICH
 DO NOT HAVE TO DO WITH THIS PERMTI SCOPE
 OF WORK. PLEASE KNOW, THIS WILL HELP TO
 ALLEAVIATE ANY CONFUSION IN THE SCOPE OF
 WORK, PAPER, AND TO HELP IN EXPEDITING
 THIS PERMIT.
  
 5)NOTE: PLEASE SEE NOTICE OF COMMENCMENT
 SUBMITTED HAS EXPIRED PER FS 713.13
 PLEASE KNOW, A NEW RECORDED UPDATED NOC
 WILL BE REQUIRED BEFORE PICKING UP
 PERMIT.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-21 Cont ID  
Sent By dpalmer Date 2005-12-21 Time 16:13 Rev Time 0.00
Received By dpalmer Date 2005-12-21 Time 15:35 Sent To  
Notes
2005-12-21 00:00:00REDLINED TWO ITEMS NOT ADDRESSED ON
 PREVIOUS REVIEW.
  
 PLEASE SEE 225.31 FOR MEANS OF
 DISCONNECT REQUIRED.
  
 PLEASE SEE 250.32 FOR GROUNDING AT
 DETACHED BLDG.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-15 Cont ID  
Sent By dpalmer Date 2005-08-15 Time 19:27 Rev Time 0.30
Received By dpalmer Date 2005-08-15 Time 19:27 Sent To  
Notes
2005-08-15 00:00:00***** UNSAT ******
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION IS
 FOR BLDG OF "POOL PAVILION" ONLY,
 HOWEVER PLANS SUBMITTED SHOWS , POOL
 EQUIPMENT, POOL PANEL ETC.
 PLEASE ONLY SUBMIT ELECTRICAL PERTAINING
 TO POOL PAVILION. PLEASE SEE "POOL "
 WILL BE UNDER SEPARATE PERMIT.
  
 2)NOTE: PLEASE SEE 225.31, A MEANS OF
 DISCONNECT WILL BE REQUIRED FOR CIRCUITS
 TO DETACHED STRUCTURE.
 **PLEASE SEE THIS MAY BE DONE BY MEANS
 OF SP/DP ETC SWITCHES.
  
 3)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 AT DETACHED STRUCTURE.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE .
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-08-31 Cont ID  
Sent By mwennerg Date 2005-08-31 Time 13:29 Rev Time 0.00
Received By mwennerg Date 2005-08-31 Time 13:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-23 Cont ID  
Sent By adarroug Date 2006-05-23 Time 16:03 Rev Time 0.00
Received By adarroug Date 2006-05-23 Time 16:03 Sent To E
Notes
2006-05-23 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-29 Cont ID  
Sent By adarroug Date 2006-03-29 Time 11:22 Rev Time 0.00
Received By adarroug Date 2006-03-29 Time 11:22 Sent To  
Notes
2006-04-18 00:00:00TO "COMM" BD#59
2006-03-29 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-30 Cont ID  
Sent By adarroug Date 2006-01-30 Time 11:28 Rev Time 0.00
Received By adarroug Date 2006-01-30 Time 11:28 Sent To  
Notes
2006-03-01 00:00:00TO "COMM" BD#27
2006-01-30 00:00:00WAITING FOR "COMM" BD-(NEW ELECTRICAL
 SHEETS)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-30 Cont ID  
Sent By adarroug Date 2005-11-30 Time 09:46 Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 09:46 Sent To  
Notes
2005-12-16 00:00:00TO "COMM" BD#32
2005-11-30 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-10 Cont ID  
Sent By kstevens Date 2005-09-10 Time 22:51 Rev Time 0.00
Received By kstevens Date 2005-08-10 Time 18:37 Sent To  
Notes
2005-08-10 00:00:00WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-09-10 Cont ID  
Sent By kstevens Date 2005-09-10 Time 22:38 Rev Time 0.25
Received By kstevens Date 2005-09-10 Time 22:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-23 Cont ID  
Sent By eschneid Date 2005-08-23 Time 12:58 Rev Time 0.00
Received By eschneid Date 2005-08-23 Time 12:58 Sent To  
Notes
***NONE***