| Plan Review Stops For Permit 05080524 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-09-20 |
Time |
12:36 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2005-09-20 |
Time |
12:36 |
Sent To |
PC |
|
| Notes |
| 2005-09-20 00:00:00 | PERMIT IS DESIGNED TO THE 2004FBC WITH A | | | | | | DESIGN OCCUPANT LOAD OF 99 OCCUPANTS | | | MAXIMUM. | | | | | | CONSTRUCTION BOARD OF ADJUSTMENT & | | | APPEAL CASE# 1284. BOARD APPROVES | | | VARIANCE FOR 44" CORRIDORS SUBJECT TO | | | THE FIRE SPRINKLER IN PLACE AND CONTINUE | | | TO BEACTIVE & MONITORED. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2005-09-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-09-15 |
Time |
11:05 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2005-09-15 |
Time |
11:05 |
Sent To |
E |
|
| Notes |
| 2005-09-15 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT:05080524 | | | ADD: 5800 CORPORATE WAY | | | CONT: LTL BUILDERS | | | TEL: (561)628-9753 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RD REVIEW | | | ACTION: BUILDING PROVISO: | | | | | | 1)BUILDING PLANS APPEAR TO BE CODE | | | COMPLIANT DEPENDING ON THE OUTCOME OF | | | THE FIRE VARIANCE APPLIED FOR. | | | | | | 2) FIRE SPRINKLER PERMIT 05080533 FEES | | | NOT PAID, ONLY (1) SET OF PLANS | | | SUBMITTED ORIGINALLY, NONE SUBMITTED | | | THIS REVIEW. | | | | | | 3) IMPACTFEES NOT PAID. | | | | | | STATIS WILL REMAIN (F) IN COMPUTER UNTIL | | | THE THREE ITEMS ABOVE ARE RESOLVED. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-09-01 |
Time |
14:07 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2005-09-01 |
Time |
14:05 |
Sent To |
E |
|
| Notes |
| 2005-09-01 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05080524 | | | ADD: 5800 CORPORATE WAY | | | CONT:LTL BUILDERS | | | TEL: (561)628-9753 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RD REVIEW | | | ACTION: DENIED | | | | | | 1)COMMENT 4B FROM THE PREVIOUS EVIEW | | | DEALS WITH THE "DESIGN OCCUPANT | | | LOAD".THIS IS DIFFERENT FORM THE | | | CALCULATED LOAD. THE DESIGN OCCUPANT | | | LOAD THE DESIGNER PUTS THIS RESTRICTION | | | ON THE BUILDING AND WILL PRINT OUT ON | | | THE C.O.THE PLANS STATE ACUALL | | | OCCUPANT LOAD TO BE 99. | | | | | | 2) COMMENT 4B ALSO INDICATES THE MINIMUM | | | | | | CORRIDOR WIDTH OF 44". THIS IS TAKING | | | THE EXEMPTION FOR EDUCATIONAL | | | OCCUPANCIES SERVICING LESS THAN 100. | | | WHERE YOU INDICATE THE EXEMPTION UNDER | | | 1016.2 EXCEPTION(2). YOU LOOK AT THE A | | | GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC REQUIREMEENT | | | SHALL BE APPLICABLE. THE GENERAL | | | REQUIREMENT IS 44" THE MORE STRICTIVE IS | | | | | | EDUCATIONAL WILL CORRIDORS OF 72" IF 100 | | | OR MORE PERSONS ARE UNDER THIS | | | EDUCATIONAL OCCUPANCY. | | | | | | 3) A FIRE SPRINKLER PERMIT IS DROPPED | | | OFF, NO FEES WERE PAID, NO PLANS | | | SUBMITTED INDICATING THE 19 HEADS THAT | | | WERE ADDED, ALSO NO CALCULATIONS | | | PROVIDED. | | | | | | 4) THE APPLICATION FOR THE FIRE VARIANCE | | | TO BE SUBMITTED BEFORE THIS COMMENT WILL | | | NOT REAPPEAR | | | | | | BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-08-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-08-20 |
Time |
07:09 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2005-08-20 |
Time |
07:09 |
Sent To |
|
|
| Notes |
| 2005-08-20 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05080524 | | | ADD: 5800 CORPORATE WAY | | | CONT:LTL BUILDERS | | | TEL: (561)628-9753 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) PLANS INDICATE DESIGN TO FL BLDG CODE | | | 2004 IT WAS AGREED ON THAT THE DESIGN | | | CRITERIA WOULD BE TO THE FL 2004 CODE. | | | THE 2004 CODE WILL PROVIDE THE DESIGNER | | | GREATER LATITUDES IN DESIGN. ALOT OF THE | | | GENERAL NOTES DO HAVE THE HEADING FROM | | | THE 2004 CODE BUT HAVE DATA FROM THE | | | 2001, NOTES ARE NOT UPDATED. | | | | | | 3) UNDER THE 2004 CODE REVISIT THE | | | MINIMUM BLDG TYPE FOR DESIGN.TABLE 503. | | | THERE IS NO TYPE VI. | | | | | | 4A) SEE 110.1.2* REQUIREMENTS FOR | | | CERTIFICATE OF OCCUPANCY SEE ITEMS 1-12. | | | NOTE# 11 IF A FIRE SPRINKLER IS PROVIDED | | | AND IF ONE IS REQUIRED. YOU HAVE TAKEN | | | THE EXCEPTION "C" TABLE 1016.1 THAT THE | | | CORRIDORS NEED NOT BE 1 HR PROTECTED BUT | | | SMOKE RATED. TO DO THIS THE FIRE | | | SPRINKLERS ADDED STILL NEED TO APPLY FOR | | | SEPERATE PERMIT BEFORE ISSUANCE OF THIS | | | PERMIT. | | | | | | | | | 4B) NOTE ITEM# 10 ON THE REQUIREMENTS | | | FOR C. O. "THE DESIGN OCCUPANT LOAD".!!! | | | THIS LIMITATION UNDER 1004.1.1 WILL | | | ALLOW THE DESIGNER TO "LIMIT THE DESIGN | | | LOAD". UNDER THIS EDITION OF THE CODE | | | SEE SECTION 1016.2 CORRIDOR WIDTHS, | | | MINIMUM CORRIDOR WIDTH SHALL BE AS | | | DETERMINED IN 1005.1 BUT NOT LESS THAN | | | 44" SEE EXCEPTIONS (4) 72" IN GROUP "E" | | | WITH A OCCUPANT LOAD GREATER THAN 100, | | | THE CORRIDOR WIDTHCAN BE 44" IF THE | | | DESIGNER LIMITS THE OCCUPANT LOAD UNDER | | | 100, EVEN THOUGH THE TOTAL SHOWN ON THE | | | PLAN IS GREATER THAN 100. CORRECT PLAN | | | TO REFLECT THE NEW "DESIGN OCCUPANT | | | LOAD". | | | | | | THE DESIGNER STILL INDICATES THAT THERE | | | ARE CORRIDORS WITH A WIDTH LESS THAN | | | 44". | | | | | | 4C) INDICATE COMPLIANCE WITH CORRIDORS | | | WITH TABLE 1016.1 WITH FIRE SPRINKLERS | | | FOR WALLS AND DOORS.SEE FOOTNOTE "C". | | | SMOKE RATING. | | | | | | | | | | | | 5)PLANS INDICATE A STORAGE AREA THAT | | | COMMUNICATES WITH THE EXIT ACCESS | | | CORRIDOR, NO SEPERATION?SMOKE RATING. | | | | | | | | | 6)BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-08-10 |
Time |
16:57 |
Rev Time |
4.44 |
| Received By |
jwitmer |
Date |
2005-08-10 |
Time |
16:57 |
Sent To |
M |
|
| Notes |
| 2005-08-10 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05080524 | | | ADD: 5800 CORPORATE WAY | | | CONT:LTL BUILDERS | | | TEL: (561)628-9753 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) PLANS INDICATE DESIGN TO FL BLDG CODE | | | 2001, IT WAS AGREED ON THAT THE DESIGN | | | CRITERIA WOULD BE TO THE FL 2004 CODE. | | | THE 2004 CODE WILL PROVIDE THE DESIGNER | | | GREATER LATITUDES IN SESIGN. | | | | | | 3) UNDER THE 2004 CODE REVISIT THE | | | MINIMUM BLDG TYPE FOR DESIGN.TABLE 503. | | | | | | 4A) SEE 110.1.2* REQUIREMENTS FOR | | | CERTIFICATE OF OCCUPANCY SEE ITEMS 1-12. | | | | | | 4B) NOTE ITEM# 10 ON THE REQUIREMENTS | | | FOR C. O. "THE DESIGN OCCUPANT LOAD".!!! | | | THIS LIMITATION UNDER 1004.1.1 WILL | | | ALLOW THE DESIGNER TO "LIMIT THE DESIGN | | | LOAD". UNDER THIS EDITION OF THE CODE | | | SEE SECTION 1016.2 CORRIDOR WIDTHS, | | | MINIMUM CORRIDOR WIDTH SHALL BE AS | | | DETERMINED IN 1005.1 BUT NOT LESS THAN | | | 44" SEE EXCEPTIONS (4) 72" IN GROUP "E" | | | WITH A OCCUPANT LOAD GREATER THAN 100, | | | THE CORRIDOR WIDTHCAN BE 44" IF THE | | | DESIGNER LIMITS THE OCCUPANT LOAD UNDER | | | 100, EVEN THOUGH THE TOTAL SHOWN ON THE | | | PLAN IS GREATER THAN 100. CORRECT PLAN | | | TO REFLECT THE NEW "DESIGN OCCUPANT | | | LOAD". | | | | | | 4C) INDICATE COMPLIANCE WITH CORRIDORS | | | WITH TABLE 1016.1 WITH FIRE SPRINKLERS | | | FOR WALLS AND DOORS.SEE FOOTNOTE "C". | | | | | | 5)THE COPY ROOM DOOR WILL NOT MAKE THE | | | ACCESSIBILITY REQUIREMENTS 11-4.13.6 | | | REQUIRING THE 18" ON THE PULL SIDE OF | | | LATCH. | | | | | | 6) PLANS INDICATE A STORAGE AREA THAT | | | COMMUNICATES WITH THE EXIT ACCESS | | | CORRIDOR, NO SEPERATION? | | | | | | 7) AIR MOVEMENT IN CORRIDORS 1016.4. | | | PROVIDE COMPLIANCE WITH EXIT ACCESS | | | CORRIDORS SHALL NOT SERVE AS SUPPLY, | | | RETURN, EXHAUST RELIEF OR VENTILATION | | | AIR DUCTS, SEE EXCEPTIONS. | | | | | | 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2005-09-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-16 |
Time |
09:44 |
Rev Time |
0.20 |
| Received By |
dpalmer |
Date |
2005-09-16 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2005-09-16 00:00:00 | ******* PROVISO ******* | | | | | | PLEASE CORRELATE SHEETS BEFORE FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2005-09-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-15 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-09-15 |
Time |
11:41 |
Sent To |
M |
|
| Notes |
| 2005-09-15 00:00:00 | ** NOTES ** | | | | | | PLEASE SEE LAYOUT ON SHEET A-1 AND A-2 | | | FOR RECEPTION ARE AND HALL(S) AREA(S). | | | PLEASE SEE A-1 HAS BEEN REVISED YET, A-2 | | | WAS NOT? | | | | | | PLEASE KNOW, ELECTRICAL PLANS ARE OK, | | | HOWEVER FLOOR LAYOUT NEEDS TO CORRELATE | | | WITH A-1 FOR CHNAGES MADE FROM PREVOUS | | | REVIEW. | | | ELECTRICAL PLANS CAN BE STAMPED, ONCE | | | OTHER TRADES ARE PASSED AND OUTCOME OF | | | VARIANCE WHICH MAY AFFECT ELECTRICAL | | | LAYOUT? | | | | | | PLANS TO REMAIN IN "F" STATUS PENDING. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-09-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-02 |
Time |
10:18 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-09-02 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2005-09-02 00:00:00 | ELECTRICAL PLANS OK, WAITING FOR OTHER | | | TRADES TO PASS IN ORDER TO STAMP PLANS. | | | ELECTRICAL SHOWN ON PLANS WITH OTHER | | | TRADES. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-08-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-22 |
Time |
07:29 |
Rev Time |
0.10 |
| Received By |
dpalmer |
Date |
2005-08-22 |
Time |
07:29 |
Sent To |
|
|
| Notes |
| 2005-08-22 00:00:00 | ***** UNSAT ****** | | | | | | 1)NOTE: PLEASE SEE NEW WATER FOUNTAINS | | | ARE NOW SHOWN ON PLANS, HOWEVER NEW | | | ELECTRICAL PLANS DO NOT INDICATE ANY NEW | | | RECEPTS OR CIRCUIT #'S AND WHICH PANELS | | | WILL FEED THESE. | | | | | | PLEASE SEE PLANS ARE COMING BACK FOR | | | OTHER COMMENTS, PLEASE MAKE CORRECTIONS | | | AT THIS TIME. | | | | | | ** ALL CIRCUITINGAND LIGHTING FOR | | | EGRESS AREAS ETC ARE SHOWN ** | | | | | | ** EXISTING MEANS OF EGRESS/DISCHARGE | | | LIGHTING TO BE VERIFIED IN FEILD.** | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-08-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-18 |
Time |
12:59 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-08-18 |
Time |
12:57 |
Sent To |
FIRE |
|
| Notes |
| 2005-08-18 00:00:00 | ***** UNSAT ****** | | | | | | 1)NOTE: PLEASE SEE NEW WATER FOUNTAINS | | | ARE NOW SHOWN ON PLANS, HOWEVER NEW | | | ELECTRICAL PLANS DO NOT INDICATE ANY NEW | | | RECEPTS OR CIRCUIT #'S AND WHICH PANELS | | | WILL FEED THESE. | | | | | | 2)NOTE: PLEASE SEE PLANS FOR TRAILER | | | SHOWING NEW OR EXSITING ELECTRICAL WHICH | | | IS REQUIRED TO MEET 2002 NEC AND OTHER | | | CURRENTS CODES, WERE NOT SUBMITTED FOR | | | REVIEW. | | | PLEASE ALSO SEE OTHER REVIEWER(S) | | | COMMENTS. | | | | | | 3)NOTE: PLEASE SEE OTHER PERMIT APPLIED | | | FOR INSTALLATION OF PORTABLE CLASSROOM | | | IS STILL OPEN AND NEEDS TO BE CLOSED | | | OUT, PLEASE SEE BLDG REVIEW COMMENTS FOR | | | THIS. | | | | | | | | | ** ALL CIRCUITINGAND LIGHTING FOR | | | EGRESS AREAS ETC ARE SHOWN ** | | | | | | ** EXISTING MEANS OF EGRESS/DISCHARGE | | | LIGHTING TO BE VERIFIED IN FEILD.** | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-10 |
Time |
09:11 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2005-08-10 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2005-08-10 00:00:00 | ******** UNSAT ********* | | | | | | 1)NOTE: PLEASE SHOW CIRCUITING FOR | | | EM/EXT LTS PER 700.12E THE BRANCH | | | CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL | | | BE THE SAME BRANCH CIRCUIT AS THAT | | | SERVING THE NORMAL LIGHTING IN THE AREA | | | AND CONNECTED AHEAD OF ANY LOCAL | | | SWITCHES. | | | | | | 2)NOTE: PLEASE SHOW LIGHTING LAYOUT FOR | | | MEANS OF EGRESS ON PLANS. | | | 215.5 | | | | | | 3)NOTE: PLEASE CORRRELATE ELECTRICAL | | | CONNECTIONS FOR NEW TRAILER/PORTABLE | | | CLASSROOM. | | | PLEASE SHOW WHICH LOCATION THIS WILL BE | | | FED FROM. TWO PLANS SHOWING TWO | | | DIFFERENT FEEDS WERE SUBMITTED. | | | PLEASE PROVIDE LOAD CALCUALTIONS FOR | | | EXISTING SERVICE. THIS SHALL INCLUDE ALL | | | NEW LOADS TO BE ADDED ALONG WITH | | | EXSITING | | | LOADS.220.3,220.10,220.11,220.13 ETC. | | | 215.5 | | | PLEASE BE SURE ALL CONTINUOUS LOADS ARE | | | SHOWN AT 125% ALONG WITH LARGEST MOTOR | | | LOADS. | | | 215.3,230.42 ETC | | | | | | 4)NOTE: PLEASE SHOW LOCATIONS OF ALL | | | ELECTRICAL PANELS ON PLANS. | | | PLEASE SEE THAT ANY ELECTRICAL PANELS ON | | | INTERIOR/BATH ROOM SHALL BE EQUIPED WITH | | | A LOCKING TYPE ELECTRICAL PANEL COVER. | | | | | | 5)NOTE: ALL LIGHTING FIXTURES AT EXIST | | | DISCHANGE AND MEANS OF EGREES TO THE | | | OUTSIDE OF BLDG SHALL BE IN WORKING | | | ORDER. | | | LS101 14.2.8, 7-8 | | | THIS IS ONLY A NOTE FOR ALL FIXTURES TO | | | COMPLY AT JOBSITE. | | | | | | 6)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR | | | KITCHENS IN OTHER THAN DWELLING UNITS | | | WHICH REQUIRES ALL 15- AND 20-AMPERE, | | | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE | | | KITCHENS TO BE GFCI PROTECTED. THIS | | | REQUIREMENT APPLIES TO EACH AND EVERY | | | 15- AND 20-AMPERE, 125-VOLT KITCHEN | | | RECEPTACLE, WHETHER OR NOT THE | | | RECEPTACLE SERVES COUNTERTOP APPLIANCES. | | | | | | PLEASE SEE OTHER POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2005-09-16 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-09-16 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-09-16 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2005-09-16 00:00:00 | ******PROVISO****** | | | | | | 1) CASE WAS HEARD BEFORE THE | | | CONSTRUCTION BOARD OF ADJUSTMENT AND | | | APPEALS REGARDING MINIMUM CORRIDOR WIDTH | | | FOR EDUCATIONAL OCCUPANCIES. THE BOARD | | | GRANTED A VARIANCE. PLEASE SEE BUILDING | | | AND FIRE PREVENTION FILES. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMIT IS | | | REQUIRED FOR FIRE SPRINKLER REMODEL. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2005-09-06 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-09-06 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-09-06 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2005-09-06 00:00:00 | ******DENIED****** | | | | | | PLEASE NOTE THAT ALTHOUGH A MEETING WAS | | | HELD, COMMENTS FROM THE LAST REVIEW HAVE | | | NOT BEEN ADDRESSED WITH THIS RESUBMITTAL | | | TO THIS WRITER. PLEASE SEE THAT COMMENT | | | #3 STILL STANDS IN ACCORDANCE WITH NFPA | | | 101, SECTION 14.2.3.2. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2005-08-18 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-08-18 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-08-18 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2005-08-18 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE NOTE THAT THE PREVIOUS FIRE | | | REVIEW INDICATED THAT SEPARATE SHOP | | | DRAWINGS AND PERMIT FOR THE FIRE | | | SPRINKLER SYSTEM IS REQUIRED. FIRE | | | SPRINKLER DRAWINGS HAVE BEEN SUBMITTED | | | UNDER THE MASTER PERMIT. PLEASE HAVE | | | CALCULATION SHEETS INCLUDED WHEN | | | SUBMITTING FOR FIRE SPRINKLER REVIEW. | | | | | | 2) PLEASE INCLUDE EXISTING LOCATION OF | | | FDC AND DOUBLE DETECTOR CHECK ASSEMBLY | | | WHEN FIRE SPRINKLER PACKAGE IS | | | SUBMITTED. | | | | | | 3) PLEASE NOTE THAT PLANS ARE STILL | | | SHOWING EXIT ACCESS CORRIDOR WIDTH TO BE | | | LESS THAN THE MINIMUM REQUIREMENT OF 72" | | | IN ACCORDANCE WITH NFPA 101, SECTION | | | 14.2.3.2. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-08-10 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-08-10 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-08-10 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2005-08-10 00:00:00 | ******DENIED****** | | | | | | 1) EXIT ACCESS CORRIDORS SHALL BE NOT | | | LESS THAN 72" IN CLEAR WIDTH. NFPA 101, | | | SECTION 14.2.3.2. | | | | | | 2) IN ADDITION TO THE FBC, LIFE SAFETY | | | TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 3) PLEASE NOTE THAT MAXIMUM TRAVEL | | | DISTANCE SHALL NOT EXCEED 200' IN | | | EDUCATIONAL OCCUPANCIES PROTECTED | | | THROUGHOUT WITH AN AUTOMATIC FIRE | | | SPRINKLER SYSTEM. | | | | | | 4) PANIC HARDWARE IS REQUIRED ON EXIT | | | DOORS SERVING AREAS OF GREATER THAN 100 | | | PERSONS. | | | | | | 5) PLEASE INDICATE THE SEPARATION | | | REQUIREMENTS FOR CORRIDORS AND STORAGE | | | ROOMS. | | | | | | 6) PLEASE ILLUSTRATE THE MINIMUM | | | INTERIOR FINISH CLASSIFICATION FOR WALLS | | | AND CEILINGS. | | | | | | 7) FIRE ALARM PERMIT HAS BEEN ISSUED. | | | MONITORING SHALL BE UL CERTIFIED FOR | | | CENTRAL STATION SERVICE. | | | | | | 8) AN ADDRESS IS REQUIRED ON THE BUIDING | | | TO BE AT LEAST 6" IN HEIGHT AND | | | CONTRASTING TO THE BACKGROUND. PLEASE | | | ADVISE IF EXISTING OR NEW. | | | | | | 9) SEPARATE SHOP DRAWINGS AND PERMIT | | | REQUIRED FOR FIRE SPRINKLER REMODEL. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-09-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-15 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
|
Time |
|
Sent To |
B |
|
| Notes |
| 2005-09-15 00:00:00 | TO "JWITMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-08-11 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2005-08-09 |
Time |
12:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2005-09-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-09-15 |
Time |
16:36 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-09-15 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2005-09-15 00:00:00 | PROVISO: | | | 1.PER 2004 FBC TABLE 1016.1; OCCUPANCY | | | EC INDICATES IN BUILDINGS PROTECTED | | | THROUGHOUT BY AN APPROVED, SUPERVISED | | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH SECTION 903, CORRIDORS ARE NOT | | | REQUIRED TO HAVE FIRE RATED SO LONG AS | | | SUCH WALLS FORM SMOKE PARTITIONS IN | | | ACCORDANCE WITH THE FBC.PLEASE | | | INDICATE SMOKE DAMPERS IN ACCORDANCE | | | WITH 2004 FMC 607.3.2, SHOULD DUCT | | | PENETRATE SMOKE CORRIDOR. | | | | | | 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | REQUIRED PER 2004 FMC 606.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-09-01 |
Time |
15:37 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2005-09-01 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2005-09-01 00:00:00 | DENIED: 2ND REQUEST | | | COMMENT #1:OUTSIDE AIR CALCULATIONS | | | WILL BE REQUIRED DUE TO THE CHANGE OF | | | OCCUPANCY.OUTSIDE AIR CALCULATIONS | | | SHALL BE BASED ON 2004 FBC(M) TABLE | | | 403.3. | | | | | | COMMENT #3:PROVIDE DUCT & GRILLE SIZE, | | | MATERIAL, AND LAYOUT. | | | | | | NEW COMMENT:INDICATE ANY AND ALL FIRE | | | DAMPERS.FIRE DAMPERS ARE REQUIRED ON | | | DUCTS PENETRATING FIRE RATED PARTITIONS | | | OR WALLS.INDICATE LOCATION OF FIRE | | | DAMPERS IN ACCORDANCE WITH 2004 | | | FBC(M)607. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-08-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-08-22 |
Time |
08:37 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-08-22 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2005-08-22 00:00:00 | DENIED: | | | PLEASE ADDRESS COMMENTS DATED 8-11-05, | | | ALSO PER OUR MEETING. | | | | | | 1.OUTSIDE AIR CALCULATIONS WILLBE | | | REQUIRED DUE TO THE CHANGE IN OCCUPANCY. | | | | | | 2.PLEASE ANNOTATE EXISTING EQUIPMENT | | | ON PLAN. | | | | | | 3.PLAN INDICATES "NEW CLASSROOMS", | | | PLEASE INDICATE ANY NEW DUCTWORK. | | | PLEASE ANNOTATE IF NO MODIFICATIONS TO | | | THE DUCT ARE REQUIRED.PLEASE NOTE, | | | RETURN AIR REQUIRED FROM ALL ROOMS | | | SEPARATED FROM THE CENTRAL RETURN BY A | | | DOOR (2004 FBC(M)601.4).SHOULD RETURN | | | BE A PLENUM, NO COMBUSTIBLES ALLOWED IN | | | A RETURN AIR PLENUM PER 2004 FBC(M) | | | 602.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-08-11 |
Time |
06:40 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-08-11 |
Time |
06:39 |
Sent To |
B |
|
| Notes |
| 2005-08-11 00:00:00 | DENIED:REVIEWED UNDER 2004 FBC | | | NO MECHANICAL PLANS OR ANALYSIS | | | SUBMITTED FOR REVIEW.PLEASE PROVIDE | | | THE FOLLOWING INFORMATION. | | | | | | 1.PLEASE INDICATE EXISTING HVAC & | | | EXHAUST SYSTEMS IN ACCORDANCE WITH 2004 | | | FBC(M)401.3.PLEASE NOTE, CORRIDORS | | | SHALL NOT BE USED AS RETURN AIR PLENUMS | | | PER 2004 FBC 423.15.2. | | | | | | 2.PROVIDE EQUIPMENT SCHEDULE (NEW OR | | | EXISTING). | | | | | | 3.INDICATE ANY NEW WORK OR | | | MODIFICATIONS TO DUCT & GRILLE LAYOUT. | | | | | | 4.PLANS DO NOT INDICATE FIRE RATING OF | | | WALLS, PARTITIONS OR SEPARATION | | | REQUIREMENTS.PLEASE PROVIDE DETAILS | | | FOR PENETRATIONS. | | | | | | 5.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2004 FBC(M) TABLE 403.3. | | | | | | 6.BATHROOM EXHAUST SHALL BE A MINIMUM | | | OF 50 CFM PER WATER CLOSET OR URINAL. | | | BATHROOMSSHALL BE CONTINUOUSLY | | | VENTILATED DURING OCCUPANCYOR COMPLY | | | WITH THE EXCEPTION UNDER 2004 FBC | | | 423.15.4. | | | | | | 7.PLEASE NOTE PLAN INDICATES THE | | | GENERAL BUILDING CODE ANALYSIS IS UNDER | | | THE 2001 FBC NOT THE 2004 FBC IN WHICH | | | THE PERMIT APPLICATION INDICATES. | | | PLEASE CLARIFY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2005-09-16 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-09-16 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-09-16 |
Time |
09:05 |
Sent To |
B |
|
| Notes |
| 2005-09-16 00:00:00 | PROVISO: | | | SEE COMENTS DATED 9-1-05 BY KEN STEVENS | | | ATTACHED TO SHT. A-1PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-09-01 |
Time |
16:56 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-09-01 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2005-09-01 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1. SHT A-1 DETAIL 1 SINK DETAIL KNEE | | | CLEARANCE TO BE 27" NOT 47". SECTION | | | 11-4.24.3.DETAIL 2 LAV CLEARANCE TO BE | | | 29" NOT 47". SECTION 11-4.19.2. DETAIL 2 | | | THE FLUSH CONTROLS SHALL BE LOCATED ON | | | THE WIDE SIDE OF THE TOILET, (AWAY FROM | | | THE WALL). SECTION 11-4.16.5 | | | 2. SHT A-2 ONLY THE FIXTURES WITHIN THE | | | BATHROOM GROUPS SHALL CONNECT TO THE | | | WET-VENTED HORIZONTAL BRANCH DRAIN. ANY | | | ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. SECTION | | | 909.1 THE MOP SINK, THE DRINKING | | | FOUNTAIN, AND THE BREAKROOM SINK SHALL | | | CONNECT DOWNSTREAM OF THE BATHROOM | | | FIXTURES, NOT ON THE STACK WITH THE LAVS | | | ON THE SANITARY RISER DIAGRAMS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-08-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-08-19 |
Time |
16:37 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2005-08-19 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2005-08-19 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | FROM PREVIOUS REVIEW: | | | 4. THE BREAK ROOM SINK SHALL BE | | | ACCESSIBLE. NEW SINK NOTED. PLEASE | | | SUBMIT A DETAIL SHOWING THE FOLLOWING: | | | B. 11-4.24.3 KNEE CLEARANCE | | | C. 11-4.24.4 SINK DEPTH | | | E. 11-4.24.6 EXPOSED PIPES & SURFACES | | | D. 11-4.24.7 FAUCETS | | | 5. FOR DRINKING FOUNTAINS: | | | C. 11-4.15.4 CONTROLS | | | 6. FOR W/C'S | | | D. 11-4.16.5 FLUSH CONTROLS | | | FOR LAVS | | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | | D. 11-4.19.5 FAUCETS | | | 8. SUBMIT A SANITARY RISER DIAGRAM | | | SHOWING ALL PIPE SIZES, VENTS, TRAPS, | | | AND POINTS OF CONNECTION. SECTION | | | 106.3.5.1.3. | | | 9. SUBMIT A WATER ISOMETRIC RISER | | | DIAGRAM SHOWING ALL PIPE SIZES, VALVES, | | | WATER HAMMER ARRESTORS IF REQUIRED BY | | | SECTION 604.9, AND POINTS OF CONNTECTION | | | . | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-08-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-08-11 |
Time |
18:54 |
Rev Time |
3.00 |
| Received By |
kstevens |
Date |
2005-08-11 |
Time |
18:54 |
Sent To |
|
|
| Notes |
| 2005-08-11 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME, ADDRESS, AND LICENSE NUMBER | | | ON EACH SHEET. (SEE SHEET A-1) | | | 2. SHT A-1 GENERAL BLDG CODE ANALSYS | | | READS FBC-2001, BUT PLANS WERE TO BE | | | DESIGNED TO FBC-2004. PLEASE CLARIFY. | | | 3. SHT A-1 KITCHEN SPACE INDICATED IN | | | MEANS OF EGRESS AND OCCUPANT LOAD | | | SECTIONS OF CODE ANALSYS, BUT KITCHEN | | | SPACE NOT FOUND ON PLANS. PLEASE | | | INDICATE IF THE BREAKROOM IS THE SAME | | | ROOM. SECTION 106.1.1. | | | 4. SHT A-1 BREAKROOM SINK BE ACCESSIBLE | | | AND SHALL COMPLY WITH SECTION 11-4.24 | | | AND ALL SUBSECTIONS. PLEASE SUBMIT A | | | DETAIL SHOWING THE FOLLOWING: | | | A. 11-4.24.2 HEIGHT | | | B. 11-4.24.3 KNEE CLEARANCE | | | C. 11-4.24.4 SINK DEPTH | | | D. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD | | | APPROACH IS REQUIRED AND SHALL EXTEND A | | | MAX. 19" UNDERNEATH THE SINK. CABINET | | | DOORS ARE NOT APPROVED IN THE CLEAR | | | FLOOR SPACE. | | | E. 11-4.24.6 EXPOSED PIPES & SURFACES | | | D. 11-4.24.7 FAUCETS | | | 5. SHT A-1 PER TABLE 403.1 2 DRINKING | | | FOUNTAINS ARE REQUIRED. - INDICATE | | | LOCATION OF FIXTURES AND SUBMIT A DETAIL | | | SHOWING THE FOLLOWING: | | | A. 11-4.15.2 SPOUT HEIGHT | | | B. 11-4.15.3 SPOUT LOCTION | | | C. 11-4.15.4 CONTROLS | | | D. 11-4.15.5 CLEARANCES/CLEAR FLOOR | | | SPACE. | | | E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE | | | WHO HAVE DIFFICULTY BENDING OR STOOPING. | | | 6. SHT A-1 ACCESSIBLE TOILET ROOM. | | | SUBMIT A DETAIL SHOWING THE FOLLOWING: | | | FOR W/C'S | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.3 HEIGHT | | | C. 11-4.16.4 GRAB BARS | | | D. 11-4.16.5 FLUSH CONTROLS | | | E. 11-4.16.6 DISPENSERS | | | FOR LAVS | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | B. 11-4.19.3 CLEAR FLOOR SPACE | | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | | D. 11-4.19.5 FAUCETS | | | E. 11-4.19.6 MIRRORS | | | FOR TOILET ROOMS - SECTION 11-4.22 AND | | | ALL SUBSECTIONS. | | | 7. AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE, AND SHALL BE THE SAME | | | SIZE AS THE WATER SERVICE. TABLE | | | 603.1(D) AND SECTION 606.8.13.2 | | | 8. SUBMIT A SANITARY RISER DIAGRAM | | | SHOWING ALL PIPE SIZES, VENTS, TRAPS AND | | | POINT OF CONNECTION. SECTION 106.3.5.1.3 | | | 9. SUBMIT A WATER ISOMETRIC RISER | | | DIAGRAM SHOWING ALL PIPE SIZES, VALVES, | | | WATER HAMMER ARRESTORS IF REQUIRED BY | | | SECTION 604.9, AND POINT OF CONNECTION. | | | 10. PER TABLE 403.1 A SERVICE SINK IS | | | REQUIRED. | | | 11. PLEASE INDICATE THE AGES OF THE | | | STUDENTS IN THE SCHOOL. REQUIREMENTS FOR | | | DIFFERENT AGE GROUPS SHALL BE PER THE | | | ACCESS BOARD RECOMMENDATIONS. (SEE | | | BUILDING ELEMENTS FOR CHILDREN: ADAAG | | | AMENDMENTS) | | | WWW.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX. | | | HTM | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|