Plan Review Details - Permit 05080524
Plan Review Stops For Permit 05080524
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-09-20 Cont ID  
Sent By jwitmer Date 2005-09-20 Time 12:36 Rev Time 0.77
Received By jwitmer Date 2005-09-20 Time 12:36 Sent To PC
Notes
2005-09-20 00:00:00PERMIT IS DESIGNED TO THE 2004FBC WITH A
  
 DESIGN OCCUPANT LOAD OF 99 OCCUPANTS
 MAXIMUM.
  
 CONSTRUCTION BOARD OF ADJUSTMENT &
 APPEAL CASE# 1284. BOARD APPROVES
 VARIANCE FOR 44" CORRIDORS SUBJECT TO
 THE FIRE SPRINKLER IN PLACE AND CONTINUE
 TO BEACTIVE & MONITORED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-09-15 Cont ID  
Sent By jwitmer Date 2005-09-15 Time 11:05 Rev Time 2.22
Received By jwitmer Date 2005-09-15 Time 11:05 Sent To E
Notes
2005-09-15 00:00:00BUILDING PLAN REVIEW
 PERMIT:05080524
 ADD: 5800 CORPORATE WAY
 CONT: LTL BUILDERS
 TEL: (561)628-9753
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: BUILDING PROVISO:
  
 1)BUILDING PLANS APPEAR TO BE CODE
 COMPLIANT DEPENDING ON THE OUTCOME OF
 THE FIRE VARIANCE APPLIED FOR.
  
 2) FIRE SPRINKLER PERMIT 05080533 FEES
 NOT PAID, ONLY (1) SET OF PLANS
 SUBMITTED ORIGINALLY, NONE SUBMITTED
 THIS REVIEW.
  
 3) IMPACTFEES NOT PAID.
  
 STATIS WILL REMAIN (F) IN COMPUTER UNTIL
 THE THREE ITEMS ABOVE ARE RESOLVED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-01 Cont ID  
Sent By jwitmer Date 2005-09-01 Time 14:07 Rev Time 1.33
Received By jwitmer Date 2005-09-01 Time 14:05 Sent To E
Notes
2005-09-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080524
 ADD: 5800 CORPORATE WAY
 CONT:LTL BUILDERS
 TEL: (561)628-9753
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1)COMMENT 4B FROM THE PREVIOUS EVIEW
 DEALS WITH THE "DESIGN OCCUPANT
 LOAD".THIS IS DIFFERENT FORM THE
 CALCULATED LOAD. THE DESIGN OCCUPANT
 LOAD THE DESIGNER PUTS THIS RESTRICTION
 ON THE BUILDING AND WILL PRINT OUT ON
 THE C.O.THE PLANS STATE ACUALL
 OCCUPANT LOAD TO BE 99.
  
 2) COMMENT 4B ALSO INDICATES THE MINIMUM
  
 CORRIDOR WIDTH OF 44". THIS IS TAKING
 THE EXEMPTION FOR EDUCATIONAL
 OCCUPANCIES SERVICING LESS THAN 100.
 WHERE YOU INDICATE THE EXEMPTION UNDER
 1016.2 EXCEPTION(2). YOU LOOK AT THE A
 GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMEENT
 SHALL BE APPLICABLE. THE GENERAL
 REQUIREMENT IS 44" THE MORE STRICTIVE IS
  
 EDUCATIONAL WILL CORRIDORS OF 72" IF 100
 OR MORE PERSONS ARE UNDER THIS
 EDUCATIONAL OCCUPANCY.
  
 3) A FIRE SPRINKLER PERMIT IS DROPPED
 OFF, NO FEES WERE PAID, NO PLANS
 SUBMITTED INDICATING THE 19 HEADS THAT
 WERE ADDED, ALSO NO CALCULATIONS
 PROVIDED.
  
 4) THE APPLICATION FOR THE FIRE VARIANCE
 TO BE SUBMITTED BEFORE THIS COMMENT WILL
 NOT REAPPEAR
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-20 Cont ID  
Sent By jwitmer Date 2005-08-20 Time 07:09 Rev Time 2.22
Received By jwitmer Date 2005-08-20 Time 07:09 Sent To  
Notes
2005-08-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080524
 ADD: 5800 CORPORATE WAY
 CONT:LTL BUILDERS
 TEL: (561)628-9753
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS INDICATE DESIGN TO FL BLDG CODE
 2004 IT WAS AGREED ON THAT THE DESIGN
 CRITERIA WOULD BE TO THE FL 2004 CODE.
 THE 2004 CODE WILL PROVIDE THE DESIGNER
 GREATER LATITUDES IN DESIGN. ALOT OF THE
 GENERAL NOTES DO HAVE THE HEADING FROM
 THE 2004 CODE BUT HAVE DATA FROM THE
 2001, NOTES ARE NOT UPDATED.
  
 3) UNDER THE 2004 CODE REVISIT THE
 MINIMUM BLDG TYPE FOR DESIGN.TABLE 503.
 THERE IS NO TYPE VI.
  
 4A) SEE 110.1.2* REQUIREMENTS FOR
 CERTIFICATE OF OCCUPANCY SEE ITEMS 1-12.
 NOTE# 11 IF A FIRE SPRINKLER IS PROVIDED
 AND IF ONE IS REQUIRED. YOU HAVE TAKEN
 THE EXCEPTION "C" TABLE 1016.1 THAT THE
 CORRIDORS NEED NOT BE 1 HR PROTECTED BUT
 SMOKE RATED. TO DO THIS THE FIRE
 SPRINKLERS ADDED STILL NEED TO APPLY FOR
 SEPERATE PERMIT BEFORE ISSUANCE OF THIS
 PERMIT.
  
  
 4B) NOTE ITEM# 10 ON THE REQUIREMENTS
 FOR C. O. "THE DESIGN OCCUPANT LOAD".!!!
 THIS LIMITATION UNDER 1004.1.1 WILL
 ALLOW THE DESIGNER TO "LIMIT THE DESIGN
 LOAD". UNDER THIS EDITION OF THE CODE
 SEE SECTION 1016.2 CORRIDOR WIDTHS,
 MINIMUM CORRIDOR WIDTH SHALL BE AS
 DETERMINED IN 1005.1 BUT NOT LESS THAN
 44" SEE EXCEPTIONS (4) 72" IN GROUP "E"
 WITH A OCCUPANT LOAD GREATER THAN 100,
 THE CORRIDOR WIDTHCAN BE 44" IF THE
 DESIGNER LIMITS THE OCCUPANT LOAD UNDER
 100, EVEN THOUGH THE TOTAL SHOWN ON THE
 PLAN IS GREATER THAN 100. CORRECT PLAN
 TO REFLECT THE NEW "DESIGN OCCUPANT
 LOAD".
  
 THE DESIGNER STILL INDICATES THAT THERE
 ARE CORRIDORS WITH A WIDTH LESS THAN
 44".
  
 4C) INDICATE COMPLIANCE WITH CORRIDORS
 WITH TABLE 1016.1 WITH FIRE SPRINKLERS
 FOR WALLS AND DOORS.SEE FOOTNOTE "C".
 SMOKE RATING.
  
  
  
 5)PLANS INDICATE A STORAGE AREA THAT
 COMMUNICATES WITH THE EXIT ACCESS
 CORRIDOR, NO SEPERATION?SMOKE RATING.
  
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-10 Cont ID  
Sent By jwitmer Date 2005-08-10 Time 16:57 Rev Time 4.44
Received By jwitmer Date 2005-08-10 Time 16:57 Sent To M
Notes
2005-08-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080524
 ADD: 5800 CORPORATE WAY
 CONT:LTL BUILDERS
 TEL: (561)628-9753
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS INDICATE DESIGN TO FL BLDG CODE
 2001, IT WAS AGREED ON THAT THE DESIGN
 CRITERIA WOULD BE TO THE FL 2004 CODE.
 THE 2004 CODE WILL PROVIDE THE DESIGNER
 GREATER LATITUDES IN SESIGN.
  
 3) UNDER THE 2004 CODE REVISIT THE
 MINIMUM BLDG TYPE FOR DESIGN.TABLE 503.
  
 4A) SEE 110.1.2* REQUIREMENTS FOR
 CERTIFICATE OF OCCUPANCY SEE ITEMS 1-12.
  
 4B) NOTE ITEM# 10 ON THE REQUIREMENTS
 FOR C. O. "THE DESIGN OCCUPANT LOAD".!!!
 THIS LIMITATION UNDER 1004.1.1 WILL
 ALLOW THE DESIGNER TO "LIMIT THE DESIGN
 LOAD". UNDER THIS EDITION OF THE CODE
 SEE SECTION 1016.2 CORRIDOR WIDTHS,
 MINIMUM CORRIDOR WIDTH SHALL BE AS
 DETERMINED IN 1005.1 BUT NOT LESS THAN
 44" SEE EXCEPTIONS (4) 72" IN GROUP "E"
 WITH A OCCUPANT LOAD GREATER THAN 100,
 THE CORRIDOR WIDTHCAN BE 44" IF THE
 DESIGNER LIMITS THE OCCUPANT LOAD UNDER
 100, EVEN THOUGH THE TOTAL SHOWN ON THE
 PLAN IS GREATER THAN 100. CORRECT PLAN
 TO REFLECT THE NEW "DESIGN OCCUPANT
 LOAD".
  
 4C) INDICATE COMPLIANCE WITH CORRIDORS
 WITH TABLE 1016.1 WITH FIRE SPRINKLERS
 FOR WALLS AND DOORS.SEE FOOTNOTE "C".
  
 5)THE COPY ROOM DOOR WILL NOT MAKE THE
 ACCESSIBILITY REQUIREMENTS 11-4.13.6
 REQUIRING THE 18" ON THE PULL SIDE OF
 LATCH.
  
 6) PLANS INDICATE A STORAGE AREA THAT
 COMMUNICATES WITH THE EXIT ACCESS
 CORRIDOR, NO SEPERATION?
  
 7) AIR MOVEMENT IN CORRIDORS 1016.4.
 PROVIDE COMPLIANCE WITH EXIT ACCESS
 CORRIDORS SHALL NOT SERVE AS SUPPLY,
 RETURN, EXHAUST RELIEF OR VENTILATION
 AIR DUCTS, SEE EXCEPTIONS.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-09-16 Cont ID  
Sent By dpalmer Date 2005-09-16 Time 09:44 Rev Time 0.20
Received By dpalmer Date 2005-09-16 Time 09:44 Sent To  
Notes
2005-09-16 00:00:00******* PROVISO *******
  
 PLEASE CORRELATE SHEETS BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-09-15 Cont ID  
Sent By dpalmer Date 2005-09-15 Time 11:41 Rev Time 0.00
Received By dpalmer Date 2005-09-15 Time 11:41 Sent To M
Notes
2005-09-15 00:00:00** NOTES **
  
 PLEASE SEE LAYOUT ON SHEET A-1 AND A-2
 FOR RECEPTION ARE AND HALL(S) AREA(S).
 PLEASE SEE A-1 HAS BEEN REVISED YET, A-2
 WAS NOT?
  
 PLEASE KNOW, ELECTRICAL PLANS ARE OK,
 HOWEVER FLOOR LAYOUT NEEDS TO CORRELATE
 WITH A-1 FOR CHNAGES MADE FROM PREVOUS
 REVIEW.
 ELECTRICAL PLANS CAN BE STAMPED, ONCE
 OTHER TRADES ARE PASSED AND OUTCOME OF
 VARIANCE WHICH MAY AFFECT ELECTRICAL
 LAYOUT?
  
 PLANS TO REMAIN IN "F" STATUS PENDING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-02 Cont ID  
Sent By dpalmer Date 2005-09-02 Time 10:18 Rev Time 0.25
Received By dpalmer Date 2005-09-02 Time 10:18 Sent To  
Notes
2005-09-02 00:00:00ELECTRICAL PLANS OK, WAITING FOR OTHER
 TRADES TO PASS IN ORDER TO STAMP PLANS.
 ELECTRICAL SHOWN ON PLANS WITH OTHER
 TRADES.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-08-22 Cont ID  
Sent By dpalmer Date 2005-08-22 Time 07:29 Rev Time 0.10
Received By dpalmer Date 2005-08-22 Time 07:29 Sent To  
Notes
2005-08-22 00:00:00***** UNSAT ******
  
 1)NOTE: PLEASE SEE NEW WATER FOUNTAINS
 ARE NOW SHOWN ON PLANS, HOWEVER NEW
 ELECTRICAL PLANS DO NOT INDICATE ANY NEW
 RECEPTS OR CIRCUIT #'S AND WHICH PANELS
 WILL FEED THESE.
  
 PLEASE SEE PLANS ARE COMING BACK FOR
 OTHER COMMENTS, PLEASE MAKE CORRECTIONS
 AT THIS TIME.
  
 ** ALL CIRCUITINGAND LIGHTING FOR
 EGRESS AREAS ETC ARE SHOWN **
  
 ** EXISTING MEANS OF EGRESS/DISCHARGE
 LIGHTING TO BE VERIFIED IN FEILD.**
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-18 Cont ID  
Sent By dpalmer Date 2005-08-18 Time 12:59 Rev Time 0.50
Received By dpalmer Date 2005-08-18 Time 12:57 Sent To FIRE
Notes
2005-08-18 00:00:00***** UNSAT ******
  
 1)NOTE: PLEASE SEE NEW WATER FOUNTAINS
 ARE NOW SHOWN ON PLANS, HOWEVER NEW
 ELECTRICAL PLANS DO NOT INDICATE ANY NEW
 RECEPTS OR CIRCUIT #'S AND WHICH PANELS
 WILL FEED THESE.
  
 2)NOTE: PLEASE SEE PLANS FOR TRAILER
 SHOWING NEW OR EXSITING ELECTRICAL WHICH
 IS REQUIRED TO MEET 2002 NEC AND OTHER
 CURRENTS CODES, WERE NOT SUBMITTED FOR
 REVIEW.
 PLEASE ALSO SEE OTHER REVIEWER(S)
 COMMENTS.
  
 3)NOTE: PLEASE SEE OTHER PERMIT APPLIED
 FOR INSTALLATION OF PORTABLE CLASSROOM
 IS STILL OPEN AND NEEDS TO BE CLOSED
 OUT, PLEASE SEE BLDG REVIEW COMMENTS FOR
 THIS.
  
  
 ** ALL CIRCUITINGAND LIGHTING FOR
 EGRESS AREAS ETC ARE SHOWN **
  
 ** EXISTING MEANS OF EGRESS/DISCHARGE
 LIGHTING TO BE VERIFIED IN FEILD.**
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-10 Cont ID  
Sent By dpalmer Date 2005-08-10 Time 09:11 Rev Time 0.75
Received By dpalmer Date 2005-08-10 Time 09:11 Sent To  
Notes
2005-08-10 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SHOW CIRCUITING FOR
 EM/EXT LTS PER 700.12E THE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 2)NOTE: PLEASE SHOW LIGHTING LAYOUT FOR
 MEANS OF EGRESS ON PLANS.
 215.5
  
 3)NOTE: PLEASE CORRRELATE ELECTRICAL
 CONNECTIONS FOR NEW TRAILER/PORTABLE
 CLASSROOM.
 PLEASE SHOW WHICH LOCATION THIS WILL BE
 FED FROM. TWO PLANS SHOWING TWO
 DIFFERENT FEEDS WERE SUBMITTED.
 PLEASE PROVIDE LOAD CALCUALTIONS FOR
 EXISTING SERVICE. THIS SHALL INCLUDE ALL
 NEW LOADS TO BE ADDED ALONG WITH
 EXSITING
 LOADS.220.3,220.10,220.11,220.13 ETC.
 215.5
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE
 SHOWN AT 125% ALONG WITH LARGEST MOTOR
 LOADS.
 215.3,230.42 ETC
  
 4)NOTE: PLEASE SHOW LOCATIONS OF ALL
 ELECTRICAL PANELS ON PLANS.
 PLEASE SEE THAT ANY ELECTRICAL PANELS ON
 INTERIOR/BATH ROOM SHALL BE EQUIPED WITH
 A LOCKING TYPE ELECTRICAL PANEL COVER.
  
 5)NOTE: ALL LIGHTING FIXTURES AT EXIST
 DISCHANGE AND MEANS OF EGREES TO THE
 OUTSIDE OF BLDG SHALL BE IN WORKING
 ORDER.
 LS101 14.2.8, 7-8
 THIS IS ONLY A NOTE FOR ALL FIXTURES TO
 COMPLY AT JOBSITE.
  
 6)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-09-16 Cont ID  
Sent By mwennerg Date 2005-09-16 Time 10:47 Rev Time 0.00
Received By mwennerg Date 2005-09-16 Time 10:47 Sent To  
Notes
2005-09-16 00:00:00******PROVISO******
  
 1) CASE WAS HEARD BEFORE THE
 CONSTRUCTION BOARD OF ADJUSTMENT AND
 APPEALS REGARDING MINIMUM CORRIDOR WIDTH
 FOR EDUCATIONAL OCCUPANCIES. THE BOARD
 GRANTED A VARIANCE. PLEASE SEE BUILDING
 AND FIRE PREVENTION FILES.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT IS
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-09-06 Cont ID  
Sent By mwennerg Date 2005-09-06 Time 10:34 Rev Time 0.00
Received By mwennerg Date 2005-09-06 Time 10:33 Sent To  
Notes
2005-09-06 00:00:00******DENIED******
  
 PLEASE NOTE THAT ALTHOUGH A MEETING WAS
 HELD, COMMENTS FROM THE LAST REVIEW HAVE
 NOT BEEN ADDRESSED WITH THIS RESUBMITTAL
 TO THIS WRITER. PLEASE SEE THAT COMMENT
 #3 STILL STANDS IN ACCORDANCE WITH NFPA
 101, SECTION 14.2.3.2.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-08-18 Cont ID  
Sent By mwennerg Date 2005-08-18 Time 15:30 Rev Time 0.00
Received By mwennerg Date 2005-08-18 Time 15:30 Sent To  
Notes
2005-08-18 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT THE PREVIOUS FIRE
 REVIEW INDICATED THAT SEPARATE SHOP
 DRAWINGS AND PERMIT FOR THE FIRE
 SPRINKLER SYSTEM IS REQUIRED. FIRE
 SPRINKLER DRAWINGS HAVE BEEN SUBMITTED
 UNDER THE MASTER PERMIT. PLEASE HAVE
 CALCULATION SHEETS INCLUDED WHEN
 SUBMITTING FOR FIRE SPRINKLER REVIEW.
  
 2) PLEASE INCLUDE EXISTING LOCATION OF
 FDC AND DOUBLE DETECTOR CHECK ASSEMBLY
 WHEN FIRE SPRINKLER PACKAGE IS
 SUBMITTED.
  
 3) PLEASE NOTE THAT PLANS ARE STILL
 SHOWING EXIT ACCESS CORRIDOR WIDTH TO BE
 LESS THAN THE MINIMUM REQUIREMENT OF 72"
 IN ACCORDANCE WITH NFPA 101, SECTION
 14.2.3.2.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-10 Cont ID  
Sent By mwennerg Date 2005-08-10 Time 13:58 Rev Time 0.00
Received By mwennerg Date 2005-08-10 Time 13:58 Sent To  
Notes
2005-08-10 00:00:00******DENIED******
  
 1) EXIT ACCESS CORRIDORS SHALL BE NOT
 LESS THAN 72" IN CLEAR WIDTH. NFPA 101,
 SECTION 14.2.3.2.
  
 2) IN ADDITION TO THE FBC, LIFE SAFETY
 TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 3) PLEASE NOTE THAT MAXIMUM TRAVEL
 DISTANCE SHALL NOT EXCEED 200' IN
 EDUCATIONAL OCCUPANCIES PROTECTED
 THROUGHOUT WITH AN AUTOMATIC FIRE
 SPRINKLER SYSTEM.
  
 4) PANIC HARDWARE IS REQUIRED ON EXIT
 DOORS SERVING AREAS OF GREATER THAN 100
 PERSONS.
  
 5) PLEASE INDICATE THE SEPARATION
 REQUIREMENTS FOR CORRIDORS AND STORAGE
 ROOMS.
  
 6) PLEASE ILLUSTRATE THE MINIMUM
 INTERIOR FINISH CLASSIFICATION FOR WALLS
 AND CEILINGS.
  
 7) FIRE ALARM PERMIT HAS BEEN ISSUED.
 MONITORING SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 8) AN ADDRESS IS REQUIRED ON THE BUIDING
 TO BE AT LEAST 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND. PLEASE
 ADVISE IF EXISTING OR NEW.
  
 9) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-15 Cont ID  
Sent By adarroug Date 2005-09-15 Time 08:25 Rev Time 0.00
Received By adarroug Date   Time   Sent To B
Notes
2005-09-15 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-20 Cont ID  
Sent By jwitmer Date 2005-08-11 Time 12:35 Rev Time 0.00
Received By jwitmer Date 2005-08-09 Time 12:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-09-15 Cont ID  
Sent By pkrauss Date 2005-09-15 Time 16:36 Rev Time 0.40
Received By pkrauss Date 2005-09-15 Time 16:36 Sent To  
Notes
2005-09-15 00:00:00PROVISO:
 1.PER 2004 FBC TABLE 1016.1; OCCUPANCY
 EC INDICATES IN BUILDINGS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION 903, CORRIDORS ARE NOT
 REQUIRED TO HAVE FIRE RATED SO LONG AS
 SUCH WALLS FORM SMOKE PARTITIONS IN
 ACCORDANCE WITH THE FBC.PLEASE
 INDICATE SMOKE DAMPERS IN ACCORDANCE
 WITH 2004 FMC 607.3.2, SHOULD DUCT
 PENETRATE SMOKE CORRIDOR.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 2004 FMC 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-09-01 Cont ID  
Sent By pkrauss Date 2005-09-01 Time 15:37 Rev Time 0.55
Received By pkrauss Date 2005-09-01 Time 15:37 Sent To  
Notes
2005-09-01 00:00:00DENIED: 2ND REQUEST
 COMMENT #1:OUTSIDE AIR CALCULATIONS
 WILL BE REQUIRED DUE TO THE CHANGE OF
 OCCUPANCY.OUTSIDE AIR CALCULATIONS
 SHALL BE BASED ON 2004 FBC(M) TABLE
 403.3.
  
 COMMENT #3:PROVIDE DUCT & GRILLE SIZE,
 MATERIAL, AND LAYOUT.
  
 NEW COMMENT:INDICATE ANY AND ALL FIRE
 DAMPERS.FIRE DAMPERS ARE REQUIRED ON
 DUCTS PENETRATING FIRE RATED PARTITIONS
 OR WALLS.INDICATE LOCATION OF FIRE
 DAMPERS IN ACCORDANCE WITH 2004
 FBC(M)607.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-22 Cont ID  
Sent By pkrauss Date 2005-08-22 Time 08:37 Rev Time 0.40
Received By pkrauss Date 2005-08-22 Time 08:24 Sent To  
Notes
2005-08-22 00:00:00DENIED:
 PLEASE ADDRESS COMMENTS DATED 8-11-05,
 ALSO PER OUR MEETING.
  
 1.OUTSIDE AIR CALCULATIONS WILLBE
 REQUIRED DUE TO THE CHANGE IN OCCUPANCY.
  
 2.PLEASE ANNOTATE EXISTING EQUIPMENT
 ON PLAN.
  
 3.PLAN INDICATES "NEW CLASSROOMS",
 PLEASE INDICATE ANY NEW DUCTWORK.
 PLEASE ANNOTATE IF NO MODIFICATIONS TO
 THE DUCT ARE REQUIRED.PLEASE NOTE,
 RETURN AIR REQUIRED FROM ALL ROOMS
 SEPARATED FROM THE CENTRAL RETURN BY A
 DOOR (2004 FBC(M)601.4).SHOULD RETURN
 BE A PLENUM, NO COMBUSTIBLES ALLOWED IN
 A RETURN AIR PLENUM PER 2004 FBC(M)
 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By pkrauss Date 2005-08-11 Time 06:40 Rev Time 0.40
Received By pkrauss Date 2005-08-11 Time 06:39 Sent To B
Notes
2005-08-11 00:00:00DENIED:REVIEWED UNDER 2004 FBC
 NO MECHANICAL PLANS OR ANALYSIS
 SUBMITTED FOR REVIEW.PLEASE PROVIDE
 THE FOLLOWING INFORMATION.
  
 1.PLEASE INDICATE EXISTING HVAC &
 EXHAUST SYSTEMS IN ACCORDANCE WITH 2004
 FBC(M)401.3.PLEASE NOTE, CORRIDORS
 SHALL NOT BE USED AS RETURN AIR PLENUMS
 PER 2004 FBC 423.15.2.
  
 2.PROVIDE EQUIPMENT SCHEDULE (NEW OR
 EXISTING).
  
 3.INDICATE ANY NEW WORK OR
 MODIFICATIONS TO DUCT & GRILLE LAYOUT.
  
 4.PLANS DO NOT INDICATE FIRE RATING OF
 WALLS, PARTITIONS OR SEPARATION
 REQUIREMENTS.PLEASE PROVIDE DETAILS
 FOR PENETRATIONS.
  
 5.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2004 FBC(M) TABLE 403.3.
  
 6.BATHROOM EXHAUST SHALL BE A MINIMUM
 OF 50 CFM PER WATER CLOSET OR URINAL.
 BATHROOMSSHALL BE CONTINUOUSLY
 VENTILATED DURING OCCUPANCYOR COMPLY
 WITH THE EXCEPTION UNDER 2004 FBC
 423.15.4.
  
 7.PLEASE NOTE PLAN INDICATES THE
 GENERAL BUILDING CODE ANALYSIS IS UNDER
 THE 2001 FBC NOT THE 2004 FBC IN WHICH
 THE PERMIT APPLICATION INDICATES.
 PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-09-16 Cont ID  
Sent By pschmitz Date 2005-09-16 Time 09:05 Rev Time 0.00
Received By pschmitz Date 2005-09-16 Time 09:05 Sent To B
Notes
2005-09-16 00:00:00PROVISO:
 SEE COMENTS DATED 9-1-05 BY KEN STEVENS
 ATTACHED TO SHT. A-1PES

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-09-01 Cont ID  
Sent By kstevens Date 2005-09-01 Time 16:56 Rev Time 0.50
Received By kstevens Date 2005-09-01 Time 16:55 Sent To  
Notes
2005-09-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT A-1 DETAIL 1 SINK DETAIL KNEE
 CLEARANCE TO BE 27" NOT 47". SECTION
 11-4.24.3.DETAIL 2 LAV CLEARANCE TO BE
 29" NOT 47". SECTION 11-4.19.2. DETAIL 2
 THE FLUSH CONTROLS SHALL BE LOCATED ON
 THE WIDE SIDE OF THE TOILET, (AWAY FROM
 THE WALL). SECTION 11-4.16.5
 2. SHT A-2 ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SECTION
 909.1 THE MOP SINK, THE DRINKING
 FOUNTAIN, AND THE BREAKROOM SINK SHALL
 CONNECT DOWNSTREAM OF THE BATHROOM
 FIXTURES, NOT ON THE STACK WITH THE LAVS
 ON THE SANITARY RISER DIAGRAMS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-08-19 Cont ID  
Sent By kstevens Date 2005-08-19 Time 16:37 Rev Time 1.50
Received By kstevens Date 2005-08-19 Time 16:37 Sent To  
Notes
2005-08-19 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
 4. THE BREAK ROOM SINK SHALL BE
 ACCESSIBLE. NEW SINK NOTED. PLEASE
 SUBMIT A DETAIL SHOWING THE FOLLOWING:
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
 5. FOR DRINKING FOUNTAINS:
 C. 11-4.15.4 CONTROLS
 6. FOR W/C'S
 D. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 8. SUBMIT A SANITARY RISER DIAGRAM
 SHOWING ALL PIPE SIZES, VENTS, TRAPS,
 AND POINTS OF CONNECTION. SECTION
 106.3.5.1.3.
 9. SUBMIT A WATER ISOMETRIC RISER
 DIAGRAM SHOWING ALL PIPE SIZES, VALVES,
 WATER HAMMER ARRESTORS IF REQUIRED BY
 SECTION 604.9, AND POINTS OF CONNTECTION
 .
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By kstevens Date 2005-08-11 Time 18:54 Rev Time 3.00
Received By kstevens Date 2005-08-11 Time 18:54 Sent To  
Notes
2005-08-11 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. (SEE SHEET A-1)
 2. SHT A-1 GENERAL BLDG CODE ANALSYS
 READS FBC-2001, BUT PLANS WERE TO BE
 DESIGNED TO FBC-2004. PLEASE CLARIFY.
 3. SHT A-1 KITCHEN SPACE INDICATED IN
 MEANS OF EGRESS AND OCCUPANT LOAD
 SECTIONS OF CODE ANALSYS, BUT KITCHEN
 SPACE NOT FOUND ON PLANS. PLEASE
 INDICATE IF THE BREAKROOM IS THE SAME
 ROOM. SECTION 106.1.1.
 4. SHT A-1 BREAKROOM SINK BE ACCESSIBLE
 AND SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. PLEASE SUBMIT A
 DETAIL SHOWING THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD
 APPROACH IS REQUIRED AND SHALL EXTEND A
 MAX. 19" UNDERNEATH THE SINK. CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR
 FLOOR SPACE.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
 5. SHT A-1 PER TABLE 403.1 2 DRINKING
 FOUNTAINS ARE REQUIRED. - INDICATE
 LOCATION OF FIXTURES AND SUBMIT A DETAIL
 SHOWING THE FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCTION
 C. 11-4.15.4 CONTROLS
 D. 11-4.15.5 CLEARANCES/CLEAR FLOOR
 SPACE.
 E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 6. SHT A-1 ACCESSIBLE TOILET ROOM.
 SUBMIT A DETAIL SHOWING THE FOLLOWING:
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 FOR LAVS
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
 FOR TOILET ROOMS - SECTION 11-4.22 AND
 ALL SUBSECTIONS.
 7. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE, AND SHALL BE THE SAME
 SIZE AS THE WATER SERVICE. TABLE
 603.1(D) AND SECTION 606.8.13.2
 8. SUBMIT A SANITARY RISER DIAGRAM
 SHOWING ALL PIPE SIZES, VENTS, TRAPS AND
 POINT OF CONNECTION. SECTION 106.3.5.1.3
 9. SUBMIT A WATER ISOMETRIC RISER
 DIAGRAM SHOWING ALL PIPE SIZES, VALVES,
 WATER HAMMER ARRESTORS IF REQUIRED BY
 SECTION 604.9, AND POINT OF CONNECTION.
 10. PER TABLE 403.1 A SERVICE SINK IS
 REQUIRED.
 11. PLEASE INDICATE THE AGES OF THE
 STUDENTS IN THE SCHOOL. REQUIREMENTS FOR
 DIFFERENT AGE GROUPS SHALL BE PER THE
 ACCESS BOARD RECOMMENDATIONS. (SEE
 BUILDING ELEMENTS FOR CHILDREN: ADAAG
 AMENDMENTS)
 WWW.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX.
 HTM
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]