Plan Review Details - Permit 05080507
Plan Review Stops For Permit 05080507
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-06 Cont ID  
Sent By rmcdouga Date 2005-09-06 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2005-09-06 Time 15:05 Sent To  
Notes
2005-09-06 00:00:00PROVISO
  
 1) THE POCKET DOOR AND HARDWARE MUST
 COMPLY WITH 2001 FBC 11-4.13 AND
 11-4.13.9.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-12 Cont ID  
Sent By rmcdouga Date 2005-08-12 Time 12:27 Rev Time 0.00
Received By rmcdouga Date 2005-08-12 Time 12:27 Sent To  
Notes
2005-08-12 00:00:00DENIED
  
 1) FBC 707.1 CONCEALED SPACES IN TYPES
 I, II AND IV CONSTRUCTION.COMBUSTIBLES
 SHALL NOT BE PERMITTED IN CONCEALED
 SPACES OF TYPES I, II OR IV
 CONSTRUCTION. BACKING IN WALLS CAN NOT
 BE COMBUSTIBLE MATERIALS.
  
 2) FBC 1012.1.4 DURING ITS SWING, ANY
 DOOR IN A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST ONE HALF OF THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY, OR LANDING, NOR PROJECT MORE
 THAN 7 IN.(17.8 CM)INTO THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY
 OR LANDING, WHEN FULLY OPEN.DOORS
 SHALL NOT OPEN IMMEDIATELY ONTO A STAIR
 WITHOUT A LANDING.THE LANDING SHALL
 HAVE A WIDTH AT LEAST EQUAL TO THE WIDTH
 OF THE DOOR SEE ?1021.3 FOR DOOR SWING
 IN GROUP E OCCUPANCIES. THE OFF SET
 SHOWN AT THE BATHROOM DOOR ON THE FLOOR
 PLAN WILL NOT ALLOW THE DOOR TO OPEN 180
 DEGREES.
  
 3) INDICATE THE CLEAR FLOOR SPACE AT
 LAVATORY AND WATER CLOSET. FBC 11-4.19.3
 AND 11-4.16.2
  
 4) INDICATE THE UNOBSTRUCTED TURNING
 SPACE REQUIRED BY FBC 11-4.22.3.
  
 5) PROVIDE BATHROOM ELEVATIONS ON THE
 PLANS. SHOW THE REQUIRED LOCATIONS
 CLEARANCES AND HEIGHTS OF ALL ACCESSIBLE
 FIXTURES. FBC CHAPTER 11.
  
 7) THE DISTANCE FROM THE WALL TO THE
 CENTER OF THE WATER CLOSET IS 18". SEE
 FBC CHAP.11 FIGURE 28.
  
 8) SIDE GRAB BAR IS REQUIRED TO BE 12"
 OFF THE REAR WALL. SEE FIGURE 29.
  
 9) MIRRORS MUST COMPLY WITH FBC
 11-4.19.6.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2005-09-02 Cont ID  
Sent By dpalmer Date 2005-09-02 Time 11:07 Rev Time 0.10
Received By dpalmer Date 2005-09-02 Time 11:07 Sent To  
Notes
2005-09-02 00:00:00NO ELECTRICAL WORK BEING DONE.
 NO VERIFICATION OF ELECTRICAL DEVICE
 HEIGHTS FOR ADA.
 ELECTRICAL EXSITING MEETS ADA PER
 CONTRACTOR AND JIM WITMER.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-15 Cont ID  
Sent By dpalmer Date 2005-08-15 Time 13:29 Rev Time 0.10
Received By dpalmer Date 2005-08-15 Time 13:28 Sent To  
Notes
2005-08-15 00:00:00****UNSAT ***
  
 1)NOTE: PLEASE SHOW ANY NEW OR EXISTING
 ELECTRICAL DEVICES MEETING THE HEIGHT
 AND LOCATION REQUIREMENTS OF ADA.
  
 PLEASE SEE OTHER COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-08 Cont ID  
Sent By mwennerg Date 2005-09-08 Time 09:29 Rev Time 0.00
Received By mwennerg Date 2005-09-08 Time 09:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-15 Cont ID  
Sent By mwennerg Date 2005-08-15 Time 10:52 Rev Time 0.00
Received By mwennerg Date 2005-08-15 Time 10:52 Sent To  
Notes
2005-08-15 00:00:00******DENIED******
  
 1) PLEASE SEE BUILDING REVIEW NOTE #2 IN
 REGARDS TO DOOR SWING INTO MEANS OF
 EGRESS.
  
 2) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION OF WALLS AND
 CEILING.
  
 3) WILL THIS WORK IMPACT EXISTING FIRE
 PROTECTION EQUIPMENT. IF SO, SEPARATE
 SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM
 REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 11:07 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 11:07 Sent To  
Notes
2005-08-30 00:00:00TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-16 Cont ID  
Sent By pkrauss Date 2005-08-16 Time 07:12 Rev Time 0.00
Received By pkrauss Date 2005-08-09 Time 17:59 Sent To  
Notes
2005-08-09 00:00:00TO "BOB" #5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-16 Cont ID  
Sent By pkrauss Date 2005-08-16 Time 07:10 Rev Time 0.20
Received By pkrauss Date 2005-08-16 Time 07:10 Sent To  
Notes
2005-08-16 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 3 Status N Date 2005-09-09 Cont ID  
Sent By kstevens Date 2005-09-09 Time 08:53 Rev Time 0.33
Received By kstevens Date 2005-09-09 Time 08:53 Sent To  
Notes
2005-09-09 00:00:00NO PLUMBING WORK THIS PERMIT-ALL
 TOILET ROOMS EXISTING - ONLY CHANGING
 OUT DOOR TO TOILET ROOM

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-09-07 Cont ID  
Sent By kstevens Date 2005-09-07 Time 18:52 Rev Time 0.78
Received By kstevens Date 2005-09-07 Time 18:52 Sent To  
Notes
2005-09-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
 1. SEE NOTES DATED 8-9-5 RMCDONALD
 RE: HANDICAP REST ROOM DETAIL "A"
 SHOW THE FOLLOWING:
 FOR W/C'S:
 11-4.16.2 CLEAR FLOOR SPACE
 11-4.16.3 HEIGHT
 11-4.16.4 GRAB BARS
 11-4.16.5 FLUSH CONTROLS
 11-4.16.6 DISPENSERS
 FOR LAV'S:
 11-4.19.2 HEIGHT & CLEARANCES
 11-4.19.3 CLEAR FLOOR SPACE
 11-4.19.4 EXPOSED PIPES & SURFACES
 11-4.19.5 FAUCETS
 11-4.19.6 MIRRORS
 FOR TOILET ROOMS:
 11-4.22.3 UNOBSTRUCTED TURNING AREA
 2. 104.6.5 BUILDING PERMIT VALUATION OF
 $1500.00 APPEARS TO BE UNDER ESTIMATED
 ON THE APPLICATION. THE PERMIT WILL BE
 DENIED UNLESS THE APPLICATION CAN SHOW A
 BONAFIDE SIGNED CONTRACT. - ALTHOUGH THE
 APPLICATION WAS INCREASED TO $2500.00,
 NO CONTRACT SUBMITTED.
 3. SECTION 104.3.1.1 (104.2) DRAWINGS
 AND SPECIFICATIONS:
 SUBMIT DRAIN, WASTE AND VENT ISOMETRIC
 AND A WATER PIPING ISOMETRIC. SHOW ALL
 PIPE SIZES, TYPE OF MATERIAL, VALVES,
 TRAPS AND POINTS OF CONNECTION.
 ***************NEW COMMENT*************
 1B. PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-13 Cont ID  
Sent By pschmitz Date 2005-08-13 Time 07:48 Rev Time 0.00
Received By pschmitz Date 2005-08-13 Time 07:48 Sent To E
Notes
2005-08-13 00:00:00PAUL SCHMITZ, PLUMBING PLANS EXAMINER
 561-805-6692 [email protected]
  
 PLUMBING PLAN REVIEW FBC 2001
  
 (1)SEE NOTES DATED 8-9-05 RMCDOUGAL
 RE: HANDICAP REST ROOM DETAIL "A".
  
 (2) 104.6.5 BUILDING PERMIT VALUALATION
 OF $1500.00APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION.THE
 PERMIT WILL BE DENIED UNLESS THE
 APPLICANT CAN SHOW A BONA FIIED SIGNED
 CONTRACT.
 (3) SEC 104.2
 DRAWINGS AND SPECIFICATIONS:
 DRAIN WASTE AND VENT,INC WATER PIPING
 ISOMETRIC, SHOW TYPE OF MATERIAL AND
 PIPE SIZES.
 END OF COMMENTS