Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-11 Cont ID  
Sent By shill Date 2005-08-11 Time 11:32 Rev Time 0.00
Received By shill Date 2005-08-11 Time 11:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-09 Cont ID  
Sent By shill Date 2005-08-09 Time 16:10 Rev Time 0.00
Received By shill Date 2005-08-09 Time 16:10 Sent To  
Notes
2005-08-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)TYPE I UNDERLAYMENT NOA WAS
 SUBMITTED; METAL PANEL NOA REQUIRES A
 TYPE II.
  
 2.)THE POLYGLASS APPROVED ASSEMBLY YOU
 HAVE SELECTED HAS A MAXIMUM DESIGN
 PRESSURE OF -45 WITH GENERAL LIMITATION
 #9 WHICH DOES NOT ALLOW ENHANCED
 FASTENING.MUST COMPLY WITH DESIGN
 PRESSURE OF -89 OR INCLUDE LIMITATION
 #7, SEE NOA.