| Plan Review Stops For Permit 05080487 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-08-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-11 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-08-11 |
Time |
11:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-09 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-08-09 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2005-08-09 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)TYPE I UNDERLAYMENT NOA WAS | | | SUBMITTED; METAL PANEL NOA REQUIRES A | | | TYPE II. | | | | | | 2.)THE POLYGLASS APPROVED ASSEMBLY YOU | | | HAVE SELECTED HAS A MAXIMUM DESIGN | | | PRESSURE OF -45 WITH GENERAL LIMITATION | | | #9 WHICH DOES NOT ALLOW ENHANCED | | | FASTENING.MUST COMPLY WITH DESIGN | | | PRESSURE OF -89 OR INCLUDE LIMITATION | | | #7, SEE NOA. |
|
|
|