| 2005-08-09 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)SEE ATTACHED POLICY.PLEASE |
| | INCLUDE MEAN ROOF HEIGHT AND DECK TYPE |
| | SO THAT CODE COMPLIANCE CAN BE |
| | DETERMINED. |
| | |
| | 2.)THE APPLICATION STATES "TEAR OFF", |
| | THE SHEET SUBMITTED IS FOR RECOVER.A |
| | RECOVER IS GOING OVER AN EXISTING ROOF. |
| | |
| | 3.)SUBMIT THE FIRST SHEETS OF THE NOA |
| | WHICH DESCRIBE THE COMPONENTS OF THE |
| | APPROVED ASSEMBLIES, THE ONE OR TWO |
| | SHEETS FOR THE APPROVED ASSEMBLY YOU ARE |
| | USING, AND THE LAST SHEET OR TWO OF THE |
| | NOA WHICH HAVE THE PRODUCT LIMITATIONS. |
| | |
| | 4.)THE MAX DESIGN PRESSURE IS -52.5; |
| | NON COMPLIANT (NEEDS -89 OR HAVE PRODUCT |
| | LIMITATION #7 REFERRED TO IN THE |
| | APPROVED ASSEMBLY WHICH ALLOWS ENHANCED |
| | FASTENING). |
| | |
| | 5.)THE STATE PRODUCT APPROVAL STATES |
| | "VALIDATED".PLEASE CHECK THE 2001 |
| | FLORIDA BUILDING CODE DATABASE ON THE |
| | WEBSITE TO SEE IF THERE IS A CURRENT |
| | (APPROVED) STATE PRODUCT APPROVAL.CALL |
| | ME IF YOU NEED ASSISTANCE. |