| 2005-09-01 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SUBMIT MANUFACTURE |
| | SPEC/CUT SHEETS FOR GENERATOR, AUTOMATIC |
| | TRANSFER SWITCH, AND ANY SUB-BASE FUEL |
| | TANK. |
| | PLEASE BE SURE ALL INDICATE LISTINGS |
| | FROM A NRTL. |
| | PLEASE BE SURE DISCONNECTING MEANS IS |
| | RATED AS "SERVICE EQUIPMENT" 225.36. |
| | |
| | 2)NOTE: PLEASE SEE BUILDING REVIEW |
| | COMMENTS PERTAING TO CHAPTER 34 OF THE |
| | FBC. PLEASE SEE ANY REQUIREMENTS WHICH |
| | MAY AFFECT ELECTRICLA PLANS. |
| | |
| | 3)NOTE: PLEASE SUBMITWIND LOADING |
| | CALCULATIONS FOR NEW SITE LIGHTING |
| | POLES. |
| | MUST MEET FBC 140 MPH. |
| | |
| | 4)NOTE: PLEASE SEE THAT ARCHITECTS TITLE |
| | BLOCK CONTAINS THE "PRINTED NAME AND |
| | LICENSE NUMBER" FOR THE ARCHITECT. FAC |
| | 61G1-16.004 |
| | PLEASE KNOW, THIS IS REQUIRED ON ALL |
| | SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 5)NOTE: PLEASE SUBMIT SETS OF PLANS |
| | ATTACHED TOGETHER INTO SETS. PLEASE SEE |
| | PLANS WERE SUBMITTED AS INDIVIDUAL |
| | SHEETS. |
| | PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE |
| | REMOVED AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | 6)NOTE: PLEASE SEE LOADS INDICATED FOR |
| | RTU'S ON EDP, MUST BE FIGURED AS ALL |
| | LOADS ON AND UNDER HEAT UNLESS AN |
| | AUTOMATIC MEANS OF LOAD SHEDDING IS |
| | PROVIDED. |
| | IF LOAD SHEDDING WILL BE USED, PLEASE |
| | PROVIDE A WIRING DETAIL (ETC) FOR |
| | METHOD, WIRING TO BE USED. |
| | 702.5 |
| | |
| | 7)NOTE: PLEASE SEE LOADS ON OPTIONAL |
| | BACK -UP POWER. PLEASE SEE GENERAL |
| | LTS.RECEPTS LOADS ARE PERMITTED TO BE |
| | DE-RATED, HOWEVER ANY CONNECT MOTOR |
| | LOADS, APPLIANCE LOADS, MUST BE FIGURED |
| | AT 100%. |
| | |
| | 8)NOTE: PLEASE SEE 210.8B3 IN KITCHENS |
| | OTHER THAN IN DWELLING UNITS WHICH |
| | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT |
| | RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| | TO BE GFCI PROTECTED. THIS REQUIREMENT |
| | APPLIES TO EACH AND EVERY 15- AND |
| | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| | WHETHER OR NOT THE RECEPTACLE SERVES |
| | COUNTERTOP APPLIANCES. |
| | |
| | 9)NOTE: PLEASE SEE THAT PLANS SHOULD |
| | ALSO INDICATE SIGNAGE REQUIRED AT |
| | DISCONNECTING MEANS AT ELECTRICAL ROOM |
| | FOR GENERATOR FEED. |
| | PLEASE VERIFY HOW NEW GENERATOR WILL GET |
| | TO EXISTING ELECTRICAL RM? |
| | PLEASE SEE A DISCONNECTING MEANS AT BLDG |
| | MAY ALSO BE REQUIRED IF FED OVERHEAD |
| | INTO BLDG.. IF GEN IS FED FROM OUTSIDE |
| | BLDG (AROUND) OR UNDER GROUND, THIS DISC |
| | AT ELECTRICAL ROOM WILL BE OK. |
| | 225.31,225.34,110.27 |
| | |
| | 10)NOTE: PLEASE SEE NOTES ON ELECTRICAL |
| | RISER DIAGRAM PAGE WHICH NOTES PANEL |
| | "MPD", THIS SEEMS TO BE A MISPRINT? |
| | PLEASE CORRECT. |
| | |
| | 11)NOTE: PLEASE SEE FIRE REVIEW NOTES: |
| | PLEASE SEE A "KNOX BOX" MAY BE REQUIRED |
| | AND LOCATION DETERMINED BY FIRE MARSHALS |
| | OFFICE. |
| | PLEASE SEE FIRE ALARM CONTROL PANEL AND |
| | GENERATOR ANNUNCIATOR PANEL SHALL BE |
| | GROUPED. THIS LOCATION WILL ALSO BE |
| | NOTED BY TH FMO. |
| | PLEASE SHOW GAP ON PLANS. |
| | |
| | 12)NOTE: PLEASE VERIFY OCP AT GENERATOR, |
| | AS 70KW 3/0 120/208V DOES NOT SEEM TO |
| | PROVIDE 250A'S??? |
| | 215.5 |
| | |
| | 13)NOTE: PLEASE CORRELATE ELECTRICAL RM |
| | LAYOUT WITH ELECTRICAL POWER PLANS FOR |
| | LOCATIONS OF EQUIPMENT. |
| | 215.5 |
| | |
| | 14)NOTE: PLEASE CORRELATE WATER HEATERS |
| | AND LOADS SHOWN. |
| | PLEASE SEE LOAD CALCS SHOWS 24KW, YET |
| | PANEL "C" ALSO SHOWS AN 11KW WH? |
| | PLEASE ALSO SEE CIRCUITING SHOWS PUMP |
| | AND WH? |
| | PLEASE SEE 422.11F FOR UNITS OVER 48A'S. |
| | SHOWS A SINGLE OCP FOR UNIT?? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |