Plan Review Details - Permit 05080402
Plan Review Stops For Permit 05080402
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-05-24 Cont ID  
Sent By pschmitz Date 2006-05-24 Time 09:53 Rev Time 0.00
Received By pschmitz Date 2006-05-24 Time 09:53 Sent To  
Notes
2006-05-24 00:00:00REVISIONDELETE POOL HEATER

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-09-26 Cont ID  
Sent By jleech Date 2005-09-26 Time 09:32 Rev Time 0.50
Received By jleech Date 2005-09-26 Time 09:32 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-08-16 Cont ID  
Sent By jleech Date 2005-08-16 Time 09:25 Rev Time 0.50
Received By jleech Date 2005-08-16 Time 09:25 Sent To  
Notes
2005-08-16 00:00:00DENIED;
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2 (FIRE
 PLACE, ONLY 5000 BTU'S?)
 9. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 10.PERSON WHO DREW THE DRAWING IS
 REQUIRED TO PRINT AND SIGN HIS OR HER
 NAME TO SAME.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-09 Cont ID  
Sent By adarroug Date 2005-09-09 Time 08:45 Rev Time 0.00
Received By adarroug Date 2005-09-09 Time 08:45 Sent To G
Notes
2005-09-09 00:00:00TO "G" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 11:05 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 11:05 Sent To G
Notes
2005-08-09 00:00:00TO "G" BOX


Account Summary | Usage Policy | Privacy Policy