Plan Review Details - Permit 05080400
Plan Review Stops For Permit 05080400
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-23 Cont ID  
Sent By rmcdouga Date 2005-08-23 Time 10:33 Rev Time 0.00
Received By rmcdouga Date 2005-08-23 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-16 Cont ID  
Sent By rmcdouga Date 2005-08-16 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2005-08-16 Time 09:28 Sent To  
Notes
2005-08-16 00:00:00DENIED
  
 1) PLANS ARE NOT CLEAR ON WALL TYPES.
 DETAIL 2 ON A8.0 SPECIFIES WALL TYPE 'B'
 AS A NON RATED FULL HEIGHT PARTITION.
 HOWEVER, BELOW THE DETAIL A NOTE
 SPECIFIES 1-HOUR RATED TENANT SEPARATION
 WALL UL DESIGN U 465.
  
 2) SPECIFY THE THICKNESS AND TYPE OF
 GYPSUM WALL SHEATHING ON THE DETAILS.
  
 3) SPECIFY THE RATING OF THE DOORS AND
 CLOSER TYPE FOR DOORS IN THE FIRE RATED
 PARTITIONS. SEE FBC 705.1.3.1 AND
 705.1.3.5.
  
 4) SPECIFY THE RATING OF DOORS 200A IN
 THE RELOCATED PARTITION (WALL TYPE 'B')
 AT THE TV CONTROL ROOM.
  
 5) SPECIFY THAT SIGNS OR STENCILING WILL
 BE PROVIDED AS REQUIRED BY FBC
 704.2.1.4.
  
 6) ADDRESS COMMENTS FROM OTHER
 REVIEWERS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-19 Cont ID  
Sent By dpalmer Date 2005-08-19 Time 19:48 Rev Time 0.30
Received By dpalmer Date 2005-08-19 Time 19:48 Sent To  
Notes
2005-08-19 00:00:00** REDLINED PLANS ***
  
 NO ELECTRICAL CONDUITS OF ANYKIND
 PERMITTED TO BE INSTALLED BETWEEN BLDGS
 FROM 601 S AUST OR 500 S AUSTCROSSING
 PROPERTY LINES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-15 Cont ID  
Sent By dpalmer Date 2005-08-15 Time 07:39 Rev Time 1.50
Received By dpalmer Date 2005-08-15 Time 06:42 Sent To  
Notes
2005-08-15 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS.
 PLEASE SEE THERE ARE MANY LOCATIONS IN
 THE NEC WHICH PERMITS ELECTRICAL SYSTEMS
 FROM ONE BLDG TO ANOTHER, SERVICES,
 FEEDERS ETC, HOWEVER THESE ARE PERMITTED
 ON THE "SAME PROPERTY". PLEASE SEE THESE
 ARE TWO SEPARATE "LEGAL " PROPERTIES.
 PLEASE SEE ANY COMMENTS FOR LEGAL
 SEPARATTION OR GRANTING OF AN EASEMENT
 ETC SHOULD BE DIRECTED TOTHE BUILDING
 OFFICAL.
 PLEASE SEE ANY
  
 2)NOTE: PLEASE SEE 104.6.5 CITY OF WEST
 PALM BEACH ADMINISTRATIVE CODE,
 VALUATION IS BASED ON ALL LABOR AND
 MATERIALS, THIS INCLUDES ANY EQUIPMENT
 EVEN IF OWNER SUPPLIED.
  
 PLEASE SEE THE ABOVE WILL BE REQUIRED
 BEFORE ANY ELECTRICAL CAN BE PASSED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-22 Cont ID  
Sent By nmccray Date 2005-08-22 Time 10:32 Rev Time 0.00
Received By nmccray Date 2005-08-22 Time 10:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-15 Cont ID  
Sent By mwennerg Date 2005-08-15 Time 10:25 Rev Time 0.00
Received By mwennerg Date 2005-08-15 Time 10:25 Sent To  
Notes
2005-08-15 00:00:00******DENIED******
  
 1) PLEASE SEE ELECTRICAL REVIEW NOTE #1.
  
 2) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, NEW DUCT SMOKE DETCTION
 DEVICES SHALL BE WIRED TO THE FIRE ALARM
 PANEL TO CAUSE A GENERAL FIRE ALARM
 CONDITION UPON ACTIVATION.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 10:53 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 10:53 Sent To  
Notes
2005-08-19 00:00:00TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-17 Cont ID  
Sent By pkrauss Date 2005-08-17 Time 06:58 Rev Time 0.00
Received By pkrauss Date 2005-08-09 Time 11:08 Sent To  
Notes
2005-08-12 00:00:00PUT ON BUILD OUT BOARD #8
2005-08-09 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-24 Cont ID  
Sent By pkrauss Date 2005-08-24 Time 16:39 Rev Time 0.40
Received By pkrauss Date 2005-08-24 Time 16:34 Sent To  
Notes
2005-08-24 00:00:00PROVISO:
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION BY MEANS OF A FLOAT SWITCH OR
 SECONDARY DRAIN TERMINATING AT A
 CONSPICUOUS POINT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-17 Cont ID  
Sent By pkrauss Date 2005-08-17 Time 06:42 Rev Time 0.45
Received By pkrauss Date 2005-08-17 Time 06:42 Sent To  
Notes
2005-08-17 00:00:00DENIED:
 1.PLAN SHEET A4.0 & A8.0 DO NOT
 CORRELLATE.WALL & PARTITION DETAIL 1
 INDICATES TYPE A EXISTING (DOES NOT
 INDICATE A RATING).DETAIL 2 TYPE 'B'
 INDICATES NON-RATED ON THE PICTORIAL &
 UNDER THE WALL TYPE THE PLANS STATE 'A':
 1 HR RATED TENANT SEP WALL UL DESIGN
 U465.PLEASE CLARIFY.
  
 2.PLEASE NOTE FIRE DAMPERS REQUIRED
 FOR PENETRATIONS THROUGH A RATED
 PARTITION/WALL OR SHALL COMPLY WITH THE
 EXCEPTIONS ALLOWED IN 2001
 FBC(M)607.1.3.
  
 3.PER 2001 FBC(M)607.6, FIRE DAMPERS
 ARE TO BE IDENTIFIED ON THE PLANS.
 PLEASE PROVIDE INSTALLATION DETAILS.
  
 4.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM PER
 2001 FBC(M)602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.