| Plan Review Stops For Permit 05080400 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-08-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-08-23 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-08-23 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-08-16 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-08-16 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2005-08-16 00:00:00 | DENIED | | | | | | 1) PLANS ARE NOT CLEAR ON WALL TYPES. | | | DETAIL 2 ON A8.0 SPECIFIES WALL TYPE 'B' | | | AS A NON RATED FULL HEIGHT PARTITION. | | | HOWEVER, BELOW THE DETAIL A NOTE | | | SPECIFIES 1-HOUR RATED TENANT SEPARATION | | | WALL UL DESIGN U 465. | | | | | | 2) SPECIFY THE THICKNESS AND TYPE OF | | | GYPSUM WALL SHEATHING ON THE DETAILS. | | | | | | 3) SPECIFY THE RATING OF THE DOORS AND | | | CLOSER TYPE FOR DOORS IN THE FIRE RATED | | | PARTITIONS. SEE FBC 705.1.3.1 AND | | | 705.1.3.5. | | | | | | 4) SPECIFY THE RATING OF DOORS 200A IN | | | THE RELOCATED PARTITION (WALL TYPE 'B') | | | AT THE TV CONTROL ROOM. | | | | | | 5) SPECIFY THAT SIGNS OR STENCILING WILL | | | BE PROVIDED AS REQUIRED BY FBC | | | 704.2.1.4. | | | | | | 6) ADDRESS COMMENTS FROM OTHER | | | REVIEWERS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-08-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-19 |
Time |
19:48 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-08-19 |
Time |
19:48 |
Sent To |
|
|
| Notes |
| 2005-08-19 00:00:00 | ** REDLINED PLANS *** | | | | | | NO ELECTRICAL CONDUITS OF ANYKIND | | | PERMITTED TO BE INSTALLED BETWEEN BLDGS | | | FROM 601 S AUST OR 500 S AUSTCROSSING | | | PROPERTY LINES. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-08-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-15 |
Time |
07:39 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2005-08-15 |
Time |
06:42 |
Sent To |
|
|
| Notes |
| 2005-08-15 00:00:00 | ********* UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS. | | | PLEASE SEE THERE ARE MANY LOCATIONS IN | | | THE NEC WHICH PERMITS ELECTRICAL SYSTEMS | | | FROM ONE BLDG TO ANOTHER, SERVICES, | | | FEEDERS ETC, HOWEVER THESE ARE PERMITTED | | | ON THE "SAME PROPERTY". PLEASE SEE THESE | | | ARE TWO SEPARATE "LEGAL " PROPERTIES. | | | PLEASE SEE ANY COMMENTS FOR LEGAL | | | SEPARATTION OR GRANTING OF AN EASEMENT | | | ETC SHOULD BE DIRECTED TOTHE BUILDING | | | OFFICAL. | | | PLEASE SEE ANY | | | | | | 2)NOTE: PLEASE SEE 104.6.5 CITY OF WEST | | | PALM BEACH ADMINISTRATIVE CODE, | | | VALUATION IS BASED ON ALL LABOR AND | | | MATERIALS, THIS INCLUDES ANY EQUIPMENT | | | EVEN IF OWNER SUPPLIED. | | | | | | PLEASE SEE THE ABOVE WILL BE REQUIRED | | | BEFORE ANY ELECTRICAL CAN BE PASSED. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-08-22 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2005-08-22 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-08-22 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-08-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-08-15 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-08-15 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2005-08-15 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE ELECTRICAL REVIEW NOTE #1. | | | | | | 2) IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS, NEW DUCT SMOKE DETCTION | | | DEVICES SHALL BE WIRED TO THE FIRE ALARM | | | PANEL TO CAUSE A GENERAL FIRE ALARM | | | CONDITION UPON ACTIVATION. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-08-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-19 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-19 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2005-08-19 00:00:00 | TO "BOB"#9 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-08-17 |
Time |
06:58 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-08-09 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2005-08-12 00:00:00 | PUT ON BUILD OUT BOARD #8 | | 2005-08-09 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-08-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-08-24 |
Time |
16:39 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-08-24 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2005-08-24 00:00:00 | PROVISO: | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION BY MEANS OF A FLOAT SWITCH OR | | | SECONDARY DRAIN TERMINATING AT A | | | CONSPICUOUS POINT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-08-17 |
Time |
06:42 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2005-08-17 |
Time |
06:42 |
Sent To |
|
|
| Notes |
| 2005-08-17 00:00:00 | DENIED: | | | 1.PLAN SHEET A4.0 & A8.0 DO NOT | | | CORRELLATE.WALL & PARTITION DETAIL 1 | | | INDICATES TYPE A EXISTING (DOES NOT | | | INDICATE A RATING).DETAIL 2 TYPE 'B' | | | INDICATES NON-RATED ON THE PICTORIAL & | | | UNDER THE WALL TYPE THE PLANS STATE 'A': | | | 1 HR RATED TENANT SEP WALL UL DESIGN | | | U465.PLEASE CLARIFY. | | | | | | 2.PLEASE NOTE FIRE DAMPERS REQUIRED | | | FOR PENETRATIONS THROUGH A RATED | | | PARTITION/WALL OR SHALL COMPLY WITH THE | | | EXCEPTIONS ALLOWED IN 2001 | | | FBC(M)607.1.3. | | | | | | 3.PER 2001 FBC(M)607.6, FIRE DAMPERS | | | ARE TO BE IDENTIFIED ON THE PLANS. | | | PLEASE PROVIDE INSTALLATION DETAILS. | | | | | | 4.NO COMBUSTIBLES ALLOWED ABOVE THE | | | CEILING IN THE RETURN AIR PLENUM PER | | | 2001 FBC(M)602.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|