Plan Review Details - Permit 05080355
Plan Review Stops For Permit 05080355
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-08-30 Cont ID  
Sent By jhiggins Date 2005-08-30 Time 09:54 Rev Time 0.00
Received By jhiggins Date 2005-08-30 Time 09:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-12-05 Cont ID  
Sent By rmcdouga Date 2005-12-05 Time 14:37 Rev Time 0.00
Received By rmcdouga Date 2005-12-05 Time 12:30 Sent To  
Notes
2005-12-05 00:00:00PROVISO
  
 THE SOIL REPORT INDICATES THAT MUCK IS
 LOCATED ON THE SITE. THE PROPERTY MUST
 BE DEMUCKED AND A CERTIFICATION OF SOIL
 BEARING CAPACITY SUBMITTED BEFORE THE
 FOUNDATION IS POURED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-04 Cont ID  
Sent By rmcdouga Date 2005-10-04 Time 15:52 Rev Time 0.00
Received By rmcdouga Date 2005-10-04 Time 15:52 Sent To  
Notes
2005-10-04 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR
 THE COUNTY IMPACT FEES.
  
 2) THE SOIL REPORT INDICATES THAT MUCK
 IS LOCATED ON THE SITE. THE PROPERTY
 MUST BE DEMUCKED AND A CERTIFICATION OF
 SOIL BEARING CAPACITY SUBMITTED BEFORE
 THE FOUNDATION IS POURED.
  
 3) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 4) SUBMIT PRODUCT APPROVALS FOR THE
 16' X 8' OVERHEAD GARAGE DOOR. THE ONE
 SUBMITTED IS LIMITED TO A MAXIMUM WIDTH
 OF 9'.
  
 5) SUBMIT THE COVER SHEET FROM THE
 FLORIDA PRODUCT APPROVAL WEBSITE THAT
 CORRESPONDS WITH THE NOA FOR THE TRACO
 MULLIONS (FL #450).
  
 6) SUBMIT THE FL COVER SHEET AND THE
 CORRESPONDING NOA LISTED ON THE FLORIDA
 PROD. APP. WEBSITE FOR THE PGT FIXED
 WINDOWS. (FL #243.2 AND NOA #03.1105.01)
  
 7) ADDRESS COMMENTS FROM OTHER PLANS
 EXAMINERS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-26 Cont ID  
Sent By rmcdouga Date 2005-08-26 Time 12:37 Rev Time 0.00
Received By rmcdouga Date 2005-08-26 Time 12:37 Sent To  
Notes
2005-08-26 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) DETAIL 16 ON S4 SPECIFIES A USP
 KST237 STRAP WITH ONE NED FASTENED TO
 MASONRY WITH TAP CONS. THE 2005 CATALOG
 LISTS THIS AS A WOOD TO WOOD CONNECTOR.
 SUBMIT A LETTER OR BULLETIN FROM USP
 THAT WILL ALLOW THIS APPLICATION.
  
 3) CONNECTION DETAIL 11 ON S4 LISTS
 DIFFERENT NUMBERS OF FASTENERS FOR THE
 HUC HANGERS THAN ARE SPECIFIED IN THE
 2005 USP CATALOG. SEE PAGE 128.
  
 4) THE CONCRETE NOTES ON G1 LISTS THE
 WRONG EDITIONS OF ACI 318 AND 530. FBC
 CHAPTER 35 REFERENCES THE 2002 EDITIONS.
  
 5) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT THE
 FL COVER SHEET FOR THE FIXED WINDOWS.
  
 6) THE WINDOWS AT THE TUB IN THE MASTER
 BATH ARE REQUIRED TO HAVE SAFETY
 GLAZING. SEE FBC 2405.2.
  
 7) SUBMIT PRODUCT APPROVALS INCLUDING
 THE FLORIDA COVER SHEETS FOR THE
 STRUCTURAL MULLIONS, THE TRUSS
 CONNECTORS AND ENTRY PANEL DOORS.
  
 8) SPECIFY ON THE PLANS HOW THE ROOF
 TILES WILL BE FASTENED TO RESIST THE
 REQUIRED UPLIFT MOMENT REQUIRED BY THE
 TABLES LISTED ON PAGES 8 AND 9 IN THE
 PRODUCT APPROVAL BASED ON EXPOSURE
 CATEGORY.
  
 9) THE EXPOSURE CATEGORY LISTED ON G1 IS
 INCORRECT. SHORELINES IN HURRICANE
 REGIONS ARE EXCLUDED. SEE ASCE7-98.
  
 10) THE OVERHEAD GARAGE DOOR
 INSTALLATION DRAWINGS ARE ILLEGIBLE.
 SUBMIT CLEAR LEGIBLE DRAWINGS.
  
 11) THE FLORIDA COVERSHEET THAT WAS
 SUBMITTED FOR THE SH-701 SINGLE HUNG
 WINDOWS IS NOT THE CORRECT ONE. IT IS
 FOR ANOTHER MODEL OF WINDOW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-02-07 Cont ID  
Sent By btrobaug Date 2007-02-07 Time 09:42 Rev Time 0.50
Received By btrobaug Date 2007-02-07 Time 09:42 Sent To PC
Notes
2007-02-07 09:50:51 
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-04-26 Cont ID  
Sent By dpalmer Date 2006-04-26 Time 17:41 Rev Time 0.00
Received By dpalmer Date 2006-04-25 Time 15:55 Sent To PC
Notes
2006-04-26 00:00:00PLANS REVISED AFTER ROUGH ELECTRICAL
 INSPECTION, NOTICE SENT TO ELEC INSPEC.
2006-04-25 00:00:00PROJECT ON HOLD, NEEDS ROUGH ELECTRICAL

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-03-30 Cont ID  
Sent By dpalmer Date 2006-03-30 Time 07:10 Rev Time 0.00
Received By dpalmer Date 2006-03-30 Time 06:44 Sent To M
Notes
2006-03-30 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE MININUM FEEDER SIZES
 AND MAX OCP FOR FEEDERS TO SUB PANEL.
 PLEASE SEE310.15B6, WHICH PERMITS
 FEEDERS TO BE DERATED FOR A 120/240
 RESIDENTIAL SERVICE, HOWEVER #3'S ARE
 SHOWN WHICH ARE ONLY RATED FOR 110A'S.
 THE NEC DOES PERMIT TO GO TO THE NEXT
 HIGHER SIZE OCP WHEN A DEVICE DOES NOT
 CORRELATE WITH THE AMERAGE. PLEASE SEE
 240.6, 110A'S IS A COMMON OCP SIZE.
 PLEASE EITHER INCREASE FEEDER OR ADJUST
 MAX OCP.
 215.5
  
 2) NOTE: PLEASE SEE PLANS INDICATE A
 PANEL IN GARAGE BUT DOES NOT INDICATE
 WHICH ONE. IT IS UNCLEAR WHICH PANEL
 THIS IS. PLEASE SEE THREE PANELS ARE
 SHOWN ON RISER AND ONLY TWO ON PLANS?
 (POOL PANEL IS LABELED).
 215.5
  
 3) NOTE: PLEASE SEE 240.24,310.16.
 PLEASE SEE WHIRL-POOL TUB SHOWS 40A OCP
 ON #10 AWG.
  
 4) NOTE: PLEASE VERIFY HP RATINGS FOR
 GDO'S. PLANS SHOW TWO , HOWEVER ONLY ONE
 CIRCUIT IS SHOWN IN PANEL.
 PLEASE SEE 430.24, 430.148
 IF HP RATINGS ARE 1/3 HP AND ABOVE, THEN
 A DEDICATED CIRCUIT WOULD BE REQUIRED
 FOR EACH.
  
 ** PLEASE SUBMIT THEABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-10-13 Cont ID  
Sent By dpalmer Date 2005-10-13 Time 12:33 Rev Time 1.00
Received By dpalmer Date 2005-10-13 Time 11:33 Sent To B
Notes
2005-10-13 00:00:00******* PROVISO/REVISION REQUIRED *****
  
  
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BEWTEEN MAIN
 DISCONNECT AND SUB PANEL "A".
 250.24,250.110,250.122
  
 2)NOTE: PLEASE SEE TABLE 9 NEC FOR MIN
 CONDUIT SIZE PER CONDUCTOR SIZES AND
 NUMBER OF CONDUCTORS WITH RESPECT TO
 TYPE OF CONDUIT.
 PLEASE SEE CONDUIT FOR POOL SUB PANEL
 SHALL BE INCREASED TO 1 1/4 MIN.
  
 3)NOTE: PLEASE SEE CONTINUOUS LOADS FOR
 POOL HEATER AND POOL PUMP NOT CLEAR.
 215.3,230.42 ETC.
  
 PLEASE REVISE THE ABOVE INFORMATION FOR
 REVIEW ALONG WITH ANY OTHER
 CHANGES/REVSIONS ON PLANS. PLEASE BE
 SURE PLANS ARE SUBMITTED FOR REVIEW AND
 STAMPING TO BE ON SITE BEFORE "ROUGH"
 ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-20 Cont ID  
Sent By dpalmer Date 2005-09-20 Time 08:28 Rev Time 0.75
Received By dpalmer Date 2005-09-20 Time 08:12 Sent To P
Notes
2005-09-20 00:00:00********* UNSAT *********
  
 PLEASE SEE NEW NOTES DUE TO CHANGE IN
 PLANS AND RISER DIAGRAM.
  
  
 1)NOTE: PLEASE SEE NEW RISER NOW SHOWS A
 NEW POOL PANEL, PLEASE CORRELATE FEEDERS
 SHOWN ON RISER (#3) AND PANEL SCHEDULE
 "A" (#2).
 PLEASE SEE FOLLOWING COMMENT
  
 2)NOTE: PLEASE SHOW LOCATION OF NEW POOL
 PANEL ON PLANS. THIS COULD NOT BE
 LOCATED.?
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 @125%, (HEAT PUMP AND POOL PUMP) THESE
 LOADS ARE 3 OR MORE HRS.
 PLEASE ADJUST LOAD CALCUALTIONS ON PANEL
 AND SERVICE.
 215.3,230.42 ETC.
  
 4)NOTE: PLEASE SEE NOTE WAS ADDED FOR
 ARC-FAULT PROTECTION PER 210.12, HOWEVER
 PLEASE SEE THE NEC REFERENCED IS 2004?
 PLEASE SEE THIS SHOULD READ 2002.
  
 5)NOTE: PLEASE SEE POOL PANEL SCHEDULE,
 WHICH INDICATES AHU AS HEAT? PLEASE SEE
 MECH PLANS INDICATE THIS UNIT AS COOL
 ONLY. PLEASE CORRELATE.
 PLEASE ALSO SEE KW HEAT LOADS ON
 MECHANICAL PLANS AND ELECTRICAL PLANS.
 PLEASE CORRELATE AND ADJUST LOAD
 CALCULATIONS.
 220,215.5
  
 6)NOTE: PLEASE SEE LOAD CALCULATIONS AS
 SHOWN WITH OUT INCREASE FOR CONTINUOUS
 LOADS OR LOAD FOR AHU'SAND LOADS
 ALREADY AT 194A'S WITH ALLPERMITTED
 DE-RATINGS.
 PLEASE SEE SERVICE SIZE WILL BE REQUIRED
 TO BE INCREASED TO A MIN 225A'S
 DEPENDING ON OUTCOME OF ADJUSTED LOAD
 CALCUALTIONS.
 PLEASE SEE PANELS, SERVICES ETC ALL
 SHALL BE SIZED FOR "FUTURE EXPANSION" OF
 LOADS , SPACES.
 90.8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-17 Cont ID  
Sent By dpalmer Date 2005-08-17 Time 07:20 Rev Time 0.55
Received By dpalmer Date 2005-08-17 Time 07:02 Sent To M
Notes
2005-08-17 00:00:00 
 ******** UNSAT ***********
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO
 SUB-PANEL.
 250.110,250.24 SIZED PER 250.122
  
 3)NOTE: PLEASE SEEMISSING RECEPTSON
 PLANS PER 210.52. PLEASE SEE SOME OF
 THESE AREAS ARE REDLIEND ON ONE SET OF
 PLANS.
  
 4)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PLEASE SEE 2002 NEC 210.12
  
 5)NOTE: PLEASE PLACE THE ROOM AND AREA
 DESIGNATIONS ON PLANS.
  
 6)NOTE: PLEASE SEE BLDG COMMENTS IN REF
 TO SURVEY REQUIRING THE ORIGINAL
 SIGNATURE AND RAISED SEAL FOR SURVEYOR.
 FS 472.025, FAC 61G17-17.002
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 09:18 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 09:18 Sent To E
Notes
2007-01-31 09:19:45TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 09:50 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 09:49 Sent To E
Notes
2006-04-21 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-27 Cont ID  
Sent By adarroug Date 2006-03-27 Time 15:26 Rev Time 0.00
Received By adarroug Date 2006-03-27 Time 15:26 Sent To E
Notes
2006-03-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 18:57 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 18:57 Sent To E
Notes
2005-10-11 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-15 Cont ID  
Sent By adarroug Date 2005-09-15 Time 16:12 Rev Time 0.00
Received By adarroug Date 2005-09-15 Time 16:12 Sent To E
Notes
2005-09-15 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 15:37 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 15:37 Sent To E
Notes
2005-08-16 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-26 Cont ID  
Sent By rmcdouga Date 2005-08-26 Time 13:42 Rev Time 0.00
Received By rmcdouga Date 2005-08-09 Time 08:24 Sent To  
Notes
2005-08-09 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-29 Cont ID  
Sent By btrobaug Date 2007-02-07 Time 09:41 Rev Time 0.20
Received By tgordon Date 2005-09-29 Time 11:45 Sent To B
Notes
2005-09-29 00:00:00NOTE: MECH. PLAN IS REVERSED FLOOR PLAN,
 FROM BUILDING PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By prafter Date 2005-08-23 Time 08:50 Rev Time 1.00
Received By prafter Date 2005-08-23 Time 08:50 Sent To B
Notes
2005-08-23 00:00:00MECH. PLAN REVIEW:
  
 1. BEDROOMS #2 #3 #5 REQUIRE R/A OUT
 OF ROOMS. FBC/M 601.4
  
 2. A/C SYSTEM #3 NOT REFLECTED ON A/C
 PLANE BUT SHOWN ON A-1 SHEET.
  
 3. A/C ENERGY SEER RATING NOT
 REFLECTED WITH A/C EQUIPMENT.
  
 4. A/C #3 NOT REFLECTED ON ELECTRICAL
 PANEL OR A/C EQUIPMENT INFORMATION.
  
  
 5. BATHROOM EXHAUST FANS NOT SIZEDON
 A/C OR ELECTRICAL PLANS PLEASE CORRECT.
  
 6. CLOTH DRYER VENT NOT SIZED OR
 REFLECTED ON A/C PLANS.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-02-15 Cont ID  
Sent By jleech Date 2007-02-15 Time 14:48 Rev Time 0.00
Received By jleech Date 2007-02-15 Time 14:48 Sent To  
Notes
2007-02-15 14:49:08REVISED SANITARY RISER DIAGRAM OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-29 Cont ID  
Sent By jleech Date 2005-09-29 Time 10:23 Rev Time 0.50
Received By jleech Date 2005-09-29 Time 10:23 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-20 Cont ID  
Sent By jleech Date 2005-08-20 Time 07:24 Rev Time 0.50
Received By jleech Date 2005-08-20 Time 07:24 Sent To M
Notes
2005-08-20 00:00:00DENIED;
 SANITARY RISER DIAGRAM DOES NOT MATCH
 FLOOR PLAN. PLEASE POSITION FIXTURES TO
 REFLECT PLUMBING AS IT WILL BE
 INSTALLED. KITCHEN SINK SHOULD HAVE A
 MACHANICAL VENT NOT A LOOP VENT. (NOT
 USED ANYMORE) WASHER AND L/T WILL BE
 INSTALL OFF OF ONE STACK. SHOW L/T
 DISCHARGING ABOVE WASHER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-12 Cont ID  
Sent By mmclean Date 2005-08-12 Time 14:02 Rev Time 0.00
Received By mmclean Date 2005-08-12 Time 14:02 Sent To I
Notes
***NONE***