| Plan Review Stops For Permit 05080350 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-09 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-09 |
Time |
08:14 |
Sent To |
M |
|
| Notes |
| 2005-08-09 00:00:00 | TO "M" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-08-09 |
Time |
16:19 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2005-08-09 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2005-08-09 00:00:00 | PROVISO: | | | 1.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 | | | FBC(M)307.2.3. | | | | | | 2.CONDENSATE SHALL TERMINATE A MINIMUM | | | OF 12" FROM THE BUILDING STRUCTURE PER | | | 2001 FBC 1503.4.4. | | | | | | 3.PER 2001 FBC(M)603.15, BALANCING | | | DAMPERS OR OTHER MEANS OF SUPPLY | | | ADJUSTMENT SHALL BE PROVIDED IN THE | | | BRANCH DUCTS OR INDIVIDUAL DUCT | | | REGISTER, GRILLE OR DIFFUSER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
|