Plan Review Details - Permit 05080244
Plan Review Stops For Permit 05080244
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-28 Cont ID  
Sent By alange Date 2005-09-28 Time 10:28 Rev Time 0.50
Received By alange Date 2005-09-28 Time 10:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-08 Cont ID  
Sent By jwitmer Date 2005-08-08 Time 12:45 Rev Time 0.55
Received By jwitmer Date 2005-08-08 Time 12:31 Sent To  
Notes
2005-08-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080244
 ADD: 2505 METROCENTRE BLVD
 CONT: MICHAEL R. FITZMAURICE INC.
 TEL: (561)844-9535
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) DOORS 1 & 2 ARE INDICATED AS 3/4 HR
 RATED DOORS, BUT NO MENTION OF THE SIDE
 LIGHT ALSO REQUIRING 3/4 HR RATING.SEE
 705.1.2.
  
 4)705.1.3.2.3 ALL DOORS IN SMOKE
 BARRIERS, HORIZONTAL EXITS, STAIRWAY
 ENCLOSURES AND OTHER DOORS OPENING
 BETWEEN ROOMS AND FIRE-RATED EXIT
 ACCESS CORRIDORS SHALL BE SELF-CLOSING
 AND SHALL BE MAINTAINED CLOSED OR, IN
 BUILDINGS OF LOW OR ORDINARY HAZARD
 CONTENTS WHEN APPROVED BY THE BUILDING
 OFFICIAL, SHALL BE PERMITTED TO BE
 AUTOMATIC-CLOSING DOORS PROVIDED WITH
 APPROVED DOOR HOLDING DEVICES OF THE
 FAIL-SAFE TYPE WHICH WILL RELEASE THE
 DOOR CAUSING IT TO BECOME AUTOMATIC
 CLOSING AND TO CLOSE WHEN ACTIVATED BY
 APPROVED LISTED SMOKE DETECTORS
  
 5) KITCHEN SINK:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER THAN
 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-10-20 Cont ID  
Sent By dpalmer Date 2005-10-20 Time 14:49 Rev Time 0.33
Received By dpalmer Date 2005-10-20 Time 14:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-10-06 Cont ID  
Sent By dpalmer Date 2005-10-06 Time 19:43 Rev Time 0.33
Received By dpalmer Date 2005-10-06 Time 19:43 Sent To  
Notes
2005-10-06 00:00:00******* UNSAT *********
  
 PLEASE SEE ITMES LISTED BELOW WHICH WERE
 REQUESTED ON PREVIOUS REVIEW AND
 ORIGINAL REVIEW.
  
 1)NOTE: PLEASE SEE A/C -2 SHEET IS STILL
 A PHOTO-COPY OF SIGNED AND SEALED PLANS.
 PLEASE ALSO SEE P-SHEET IS ALSO STILL A
 PHOTOCOPY OF SIGNED, DATED AND SEALED,
 PLANS.
 PREVIOUS REVIEW STATED THE SAME, PLUMB
 SHEETS WERE PASSSED AND STAMPED IN ERROR
 AND NOW HAVE BEEN VOIDED.
 PLEASE SEE NO NEW A/C-2 SHEET WAS
 SUBMITTED.
 PLEASE SEE FS 471.025, AND FAC
 61G15-23.002
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WETHER OR NOT COMMENTS ARE
 MADE BY OTHER TRADES AS STATED ON
 PREVIOUS REVIEW.
  
 2)NOTE: PLEASE SEE AS STATED IN THE TWO
 PREVIOUS REVIEWS, PLEASE REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND "INSERT"
 ONLY THE NEW REVISED CORRECTED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE SET OF ALL OLD/VOIDED
 SHEETS ARE REQUIRED TO BE SUBMITTED
 SEPARATELY FOR REFERENCE.
  
 3)NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS 3 OR MORE
 TIMES. THIS IS ONLY A NOTICE.
  
 4)NOTE: PLEASE SEE ITEM NOT NOTED ON
 PREVIOUS REVIEW. PERMIT APPLICATION AND
 PLANS ARE REQUIRED TO CONTAIN THE SUITE/
 UNIT NUMBER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND ONCE AGAIN IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-15 Cont ID  
Sent By dpalmer Date 2005-09-15 Time 08:47 Rev Time 0.00
Received By dpalmer Date 2005-09-15 Time 08:29 Sent To  
Notes
2005-09-15 00:00:00************ UNSAT 2ND REVIEW*******
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE PLANS ARE GOING TO BE
 COMING ABCK FOR MECH AND PLUMB COMMENTS.
 PLEASE SEE MECH AND PLUMB ARE NOT
 SIGNED, DATED OR SEALED, BY DESIGNER OF
 RECORD.
 PLEASE SEE PHOTO COPIES OF ORIGINALS.
 FS 471.025
  
  
 1)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS
 IN OTHER THAN DWELLINGS,WHICH REQUIRES
 ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 2)NOTE: PLEASE BE SURE EXISTING RISER
 INDICATES WHICH BRKR/METER FEEDS NEW
 TENANT AND INDICATE OCP.
 215.5
 PLEASE KNOW, CONDUCTORS SHOWN CAN NOT BE
 VERIFIED AT THIS TIME.
 MORE THAN ONE BRKR IS BEING SHOWN IN
 METER CENTER, SOME 200A, 300A AND 400A.
  
  
 PLEASE BE SURE TO SEE ANY POSSILBE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF ALL REMOVED OLD/VOIDED SHEETS
 ARE REQUIRED TO BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-09 Cont ID  
Sent By dpalmer Date 2005-08-09 Time 12:38 Rev Time 0.75
Received By dpalmer Date 2005-08-09 Time 12:38 Sent To  
Notes
2005-08-09 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE AS SHOWN.
 PLEASE SEE EM/EXT LTS, SEE 700.12E,THE
 BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 2)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS
 IN OTHER THAN DWELLINGS,WHICH REQUIRES
 ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 3)NOTE: PLEASE SEE RISER INDICATES PANEL
 AS 225 2-P (MCB)? AND ALSO MLO. PLEASE
 CORRELATE. PLEASE SEE TEANT IS REQUIRED
 TO HAVE ACCESS TO ALL MEANS OF OCP.
 240.24
 215.5
  
 4)NOTE: PLEASE BE SURE EXISTING RISER
 INDICATES WHICH BRKR/METER FEEDS NEW
 TENANT AND INDICATE OCP.
 215.5
  
 PLEASE BE SURE TO SEE ANY POSSIBE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STMAPING.
 ONE SET OF ALL REMOVED OLD/VOIDED SHEETS
 ARE REQUIRED TO BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-21 Cont ID  
Sent By mwennerg Date 2005-09-21 Time 09:48 Rev Time 0.00
Received By mwennerg Date 2005-09-21 Time 09:48 Sent To  
Notes
2005-09-21 00:00:00******APPROVED******
  
 SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By mwennerg Date 2005-08-11 Time 10:01 Rev Time 0.00
Received By mwennerg Date 2005-08-11 Time 10:01 Sent To  
Notes
2005-08-11 00:00:00******DENIED******
  
 1) IN ADDITION TO THE FBC, LIFE SAFETY
 TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) PLEASE SEE EXIT DOOR FROM EXECUTIVE
 OFFICE SHALL NOT OBSTRUCT MORE THAN 1/2
 THE TOTAL CORRIDOR WIDTH DURING IT'S
 SWING. PLEASE VERIFY.
  
 3) PLEASE SHOW LOCATION OF 2A-10B,C
 RATED FIRE EXTINGUISHER(S). IF EXISTING
 IN COMMON AREAS, PLEASE ADVISE.
  
 4) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-18 Cont ID  
Sent By adarroug Date 2005-10-18 Time 16:12 Rev Time 0.00
Received By adarroug Date 2005-10-18 Time 16:12 Sent To  
Notes
2005-10-18 00:00:00TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-05 Cont ID  
Sent By adarroug Date 2005-10-05 Time 09:32 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 09:32 Sent To  
Notes
2005-10-05 00:00:00TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 14:58 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 14:58 Sent To  
Notes
2005-09-12 00:00:00TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-11 Cont ID  
Sent By mwennerg Date 2005-08-11 Time 10:08 Rev Time 0.00
Received By mwennerg Date 2005-08-05 Time 08:54 Sent To  
Notes
2005-08-05 00:00:00TO "BOB"#8

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-10-19 Cont ID  
Sent By hmoser Date 2005-10-19 Time 14:00 Rev Time 0.00
Received By hmoser Date 2005-10-19 Time 13:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-10-07 Cont ID  
Sent By prafter Date 2005-10-07 Time 08:32 Rev Time 0.00
Received By hmoser Date 2005-10-19 Time 13:40 Sent To  
Notes
2005-10-07 00:00:00MECH. PLAN REVIEW, RESUB 10/4/05:
  
 1. MECH. PLAN REVIEW 08/10/05 PATTY
 KRAUSS. 1. AND 2.ITEMS O/K.
  
 3. SMOKE DETECTORS REFLECTED ON A/C-1
 FOR AUTO. FAN SHUT DOWN, ITEM O/K
  
 4. ITEM 4. NOT COMPLETE, A/C-1 PLAN
 CALLS FOR LETTER FROM ENG. SIGN SEALED,
 IN REGARD TO EXISTING A/C EQUIPMENT
 STAND CONFORMING TO CODE REQUIRED WIND
 LOAD/WEIGHT RATING.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.
  
  
 .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-09-26 Cont ID  
Sent By prafter Date 2005-09-26 Time 11:21 Rev Time 1.50
Received By prafter Date 2005-09-26 Time 11:21 Sent To B
Notes
2005-09-26 00:00:00MECH. RESUB PLAN REVIEW:
  
 MECH. PLAN REVIEW 08/10/05 PATTY
 KRAUSS.
 1. AND 2. ITEMS O/K .
  
 3. MUST BE ADHEARED TO.A/C SYSTEMS
 COMBINED WITH OVER 2000 CFM REQUIR AUTO
 FAN SHUT DOWN AND CONNECTED TO EXISTING
 FIRE ALARM SYSTEM. 2001 FBC/M 606.2.1.
  
 4. COND. UNIT SUPPORT STAND
 INFORMATION, REQUIRED SIZE OF UNITS
 AND WEIGHT CASAPITY OF STAND. 2003 FBC/M
 301.13 WIND RESISTANCE .
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-10 Cont ID  
Sent By pkrauss Date 2005-08-10 Time 16:30 Rev Time 0.55
Received By pkrauss Date 2005-08-10 Time 16:30 Sent To  
Notes
2005-08-10 00:00:00DENIED:
 1.PLAN SHEET AC-1, VERIFY & INDICATE
 FIRE DAMPER FORTHE O.A. DUCT
 PENETRATION PER 2001 FBC(M)607.1.2 7.
 PROVIDE INSTALLATION DETAILS FOR FIRE
 DAMPERS AS REQUIRED PER 2001 FBC(M)
 607.6.PLEASE NOTE, FIRE DAMPERS NOT
 REQUIRED FOR DUCTS THAT COMPLY WITH 2001
 FBC(M)607.1.3 #3 ITEMS 1 THROUGH 4.
  
 2.PLAN SHEET AC-1, DRYER EXHAUST DUCT
 PENETRATING FLOOR INTO THE GARAGE AREA.
 PLEASE PROVIDE INFORMATION AS TO THE
 FIRE RATING FOR THE SEPARATION BETWEEN
 OCCUPANCIES.PROVIDE FIRE PENETRATION
 DETAIL.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE
 REQUIRED FOR AHU-2.2001 FBC(M)606.2.1.
  
 4.PROVIDE LOCATION OF THE CONDENSING
 UNIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-06-29 Cont ID  
Sent By pschmitz Date 2006-06-29 Time 13:43 Rev Time 0.00
Received By pschmitz Date 2006-06-29 Time 13:43 Sent To  
Notes
2006-06-29 00:00:00REVISION: AS BUILT DWV

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-10-21 Cont ID  
Sent By jleech Date 2005-10-21 Time 08:55 Rev Time 1.00
Received By jleech Date 2005-10-21 Time 08:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-10-07 Cont ID  
Sent By jleech Date 2005-10-07 Time 10:07 Rev Time 0.50
Received By jleech Date 2005-10-07 Time 10:06 Sent To  
Notes
2005-10-06 00:00:00SEE "P" SHEETS HAVE BEEN VOIDED.
 THESE ARE NOT SIGNED , DATED OR SEALED.
 FS 471.025

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-17 Cont ID  
Sent By pschmitz Date 2005-09-17 Time 23:35 Rev Time 0.00
Received By pschmitz Date 2005-09-17 Time 23:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-06 Cont ID  
Sent By pschmitz Date 2005-08-06 Time 12:41 Rev Time 0.00
Received By pschmitz Date 2005-08-06 Time 11:15 Sent To  
Notes
2005-08-06 00:00:00PAUL SCHMITZ, PLUMBING & GASPLANS
 EXAMINER.FBC 2001 DENIED
 561-805-6692 [email protected]
  
 (1)SHT A-3 GRAB BAR MOUNTING DETAIL:
 GRAB BAR BEHIND WATER CLOSET 24".
 CONFLICTS WITH NOTES FOR BATH ROOM
 PLANS,SHT A-1, NOTE #4REQ. TO BE 36".
 (2) SHT A-1 BREAK ROOM SINK:
 ?11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
  
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
  
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
  
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
  
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
  
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
  
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
 (3)SHT A-1 BREAK ROOM, WATER HEATER.
 ?P501.4 LOCATION. WATER HEATERS AND
 STORAGE TANKS SHALL BE LOCATED AND
 CONNECTED SO AS TO PROVIDE ACCESS FOR
 OBSERVATION, MAINTENANCE, SERVICING
 AND REPLACEMENT.
 END OF COMMENTS
  
  
  
  
  
  
 REVIEW
  
 DENIED