| 2005-08-19 00:00:00 | DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) THE DISTANCE FROM THE ADDITION TO THE |
| | PROPERTY LINE IS ILLEGIBLE ON THE SITE |
| | PLAN. THIS IS REQUIRED TO DETERMINE THE |
| | PERCENTAGE OF WALL AREA ALLOWED AS |
| | OPENINGS. IF THE DISTANCE IS OVER 10' TO |
| | 20' THE AMOUNT OF WALL AREA ALLOWED AS |
| | OPENINGS IS 40 PERCENT. |
| | |
| | 4) PROVIDE ELEVATIONS OF THE STRUCTURE. |
| | SPECIFY THE ROOF PITCH AND THE MEAN ROOF |
| | HEIGHT. |
| | |
| | 5) SPECIFY THE SIZE OF THE THREE REBARS |
| | IN THE STEM WALL FOOTING. |
| | |
| | 6) FL. BLD CODE 1606.1.7 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 7) SPECIFY THE WINDLOAD PRESSURES AT THE |
| | EXTERIOR OPENINGS. |
| | |
| | 8) PROVIDE A ROOF FRAMING PLAN AND A |
| | TRUSS ANCHOR SCHEDULE. |
| | |
| | 9) SPECIFY THE CEILING AND INTERIOR WALL |
| | FINISHES. SPECIFY THE EXTERIOR WALL AND |
| | SOFFIT MATERIALS. |
| | |
| | 10) SPECIFY THE ATTIC AND WALL |
| | INSULATION. |
| | |
| | 11) SUBMIT ENERGY CALCULATIONS. |
| | |
| | 12) SPECIFY ATTIC VENTILATION PER FBC |
| | 2309.7. |
| | |
| | 13) SPECIFY THE ROOF SHEATHING MATERIAL |
| | AND FASTENER TYPE AND SPACING. SEE CITY |
| | OF WPB AMENDMENTS TO FBC TABLES 2306.1 |
| | AND 2307.6B. |
| | |
| | 14) PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | SUBMIT STATE OR LOCAL PRODUCT APPROVALS |
| | (COVER SHEET AND NOA OR OTHER |
| | EVAUALUATION WITH INSTALLATION |
| | INSTRUCTIONS) FOR WINDOWS, MULLIONS, |
| | STORM PANELS, ROOFING MATERIALS AND |
| | TRUSS CONNECTORS. |
| | |
| | 15) ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN PER |
| | CITY AMENDMENTS TO FBC 104.2.1. |
| | |
| | 16)FBC 1606.1.4 REQUIRES IMPACT |
| | PROTECTION FOR GLAZED OPENINGS. SUBMIT |
| | TWO SETS OF KEY PLANS AND INSTALLATION |
| | SCHEDULES FOR THE STORM PANELS. SPECIFY |
| | THE MOUNT TYPE, FASTENER TYPE AND |
| | FASTENER SPACING. |
| | |
| | 17) IN ORDER TO REUSE THE EXISTING |
| | WINDOWS, STATE OR LOCAL PRODUCT |
| | APPROVALS FOR THEM IS REQUIRED TO BE |
| | SUBMITTED. |
| | |
| | 18) ADDITIONAL COMMENTS MAY RESULT WHEN |
| | THE ADDITIONAL INFORMATION REQUESTED |
| | ABOVE IS SUBMITTED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |