Plan Review Details - Permit 05080202
Plan Review Stops For Permit 05080202
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-29 Cont ID  
Sent By shill Date 2005-08-29 Time 18:17 Rev Time 2.00
Received By shill Date 2005-08-29 Time 18:17 Sent To  
Notes
2005-12-14 00:00:00 
  
 ***NOTE*** LETTER SUBMITTED FROM
 ARCHITECT & OWNER REGARDING OCCUPANCY,
 NMK DETERMINED THAT OCCUPANCY IS "F"
  
2005-08-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 2.)THE SHEETS PREPARED BY THE
 LANDSCAPE ARCHITECT ARE TO BE SIGNED,
 SEALED AND DATED FAC61G10-11.010(2).
  
 3.)THE ARCHITECT?S TITLE BLOCK IS TO
 COMPLY WITH FAC61G1-16-003,004.THE
 SEAL IS TO BE DATED.
  
 4.)THE OWNER ON THE APPLICATION
 CONFLICTS WITH OUR RECORDS.
  
 5.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 6.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 7.)DECLARE AN OCCUPANCY FOR THE
 EXISTING BUILDING AND THE ADDITION,
 FBC305, FBC307.THE NOTE ON THE PLAN
 STATING ?NO OPERATIONAL EQUIP IN
 PROPOSED ADDITION? IS ACKNOWLEDGED.THE
 ROOM LABEL CALLS THIS ROOM AN WELDING &
 PIPEFITTING LABORATORY; IF THERE IS NO
 OPERATIONAL EQUIPMENT, WHAT TYPE OF
 LABORATORY IS IT?THERE ARE 220 OUTLETS
 ON THE ELECTRIC PLAN, EXHAUST FANS ON
 THE ROOF FRAMING PLAN, AND SHEET M1
 LABELS THIS ROOM AS A WELDING AND
 PIPEFITTING SHOP.
  
 8.)SHOW OCCUPANCY SEPARATION REQUIRED
 BY FBC TABLE 704.1.
  
 9.)NOTE THAT IF THIS IS F OCCUPANCY,
 TWO EXITS REQUIRED.
  
 10.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING BUILDING; MINIMUM BUILDING
 TYPE, HEIGHT (NUMBER OF STORIES),
 PROTECTED OR UNPROTECTED, SPRINKLED OR
 UNSPRINKLED, OCCUPANCY.
  
 11.)THE PRODUCT APPROVALS SUBMITTED
 FOR THE ROOF WERE FOR A ROOF DECK.THE
 DETAILS SHOW LIGHTWEIGHT CONCRETE.
  
 12.)SUBMIT PRODUCT APPROVALS FOR THE
 OVERHEAD DOORS, EXTERIOR DOOR, ROOF
 VENT.
  
 13.)THE FLOOR PLAN SHOWS AN ADDITION,
 OPEN PRACTICE AREA.THIS DOES NOT
 APPEAR ON THE OTHER SHEETS.NOTE THAT
 IT ALSO DOES NOT SHOW A DOOR.CLARIFY
 THE SCOPE OF WORK.
  
 14.)PROVIDE A DETAIL FOR THE
 MECHANICAL EQUIPMENT ON THE ROOF, FBC
 1511.7.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By dpalmer Date 2005-08-11 Time 20:49 Rev Time 0.80
Received By dpalmer Date 2005-08-11 Time 20:43 Sent To  
Notes
2005-08-11 00:00:00IN ELEC FOR REVIEW
 *********** UNSAT ************
  
 1)NOTE: PLEASE SHOW ALL NEW CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.
 PLEASE ALSO SHOW EXHAUST FANS ON
 ELECTRICAL PLANS.
 215.5
  
 2)NOTE: PLEASE CORRELATE NOTES TO
 ELECTRICLA PLANS, PANEL SCHEDULE AND
 PLANS, NOTES MENTION 250A PANEL MIN AND
 OTHERS 225A?
 215.5
  
 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM
 SHOWING WHERE NEW PANEL IS BEING FED
 FROM, SIZE OF EXISTING PANEL/DISCONNECT/
 SERVICE.
 PLEASE SUBMIT LOAD CALCULATIONS FOR
 ADDITION OF NEW LOADS TOEXISTING
 SERVICE.
 220.3,220.10,220.11,220.13 ETC.
 PLEASE SEE THAT ALL CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS ARE SHOWN AT 125%.
 215.3,230.42 ETC.
  
 4)NOTE: PLEASE SEE ALL EM/EXT LTS ARE TO
 BE CIRCUITED PER 700.12E, WHICH REQUIRES
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 5)NOTE: PLEASE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM PANEL TO EXIST
 ,,
 PLEASE SEE "NOTES" MENTION A 2/0 FOR
 EQUIPMENT GROUNDING? PLEASE VERIFY THIS.
 250.110,250.122,250.24
  
 6)NOTE: PLEASE SEE NOTE TO PANEL
 MENTIONS: ALL WORK PER NEC AND "COUNTY
 CODES", PLEASE SEE THIS JOB IS LOCATED
 IN THE CITY OF WEST PALM BEACH AND PLANS
 SHOULD NOTE CITY OF WEST PALM BEACH
 LOCAL AMENDMENTS.
  
 7)NOTE: PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCK PER FAC
 61G1-16.004.
 PLEASE SEE MISSING THE PRINTED NAME AND
 LICENSE NUMBER FOR ARCHITECT OF RECORD.
 PLEASE SEE THIS INFORMATION IS REQUIRED
 ON ALL SHEETS AND FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
 ********
 PLEASE SEE COMMENTS FROM BLDG REVIEW
 ALSO, PLEASE SEE SURVEY IS REQUIRED TO
 HAVE AN ORIGINAL SIGNATURE BY THE PERSON
 SEALING SURVEY PLANS.
 PLEASE SEE FS 472.025
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE
 REMOVED FROM SETS AND INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE SET OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-02 Cont ID  
Sent By mwennerg Date 2005-09-02 Time 09:46 Rev Time 0.00
Received By mwennerg Date 2005-09-02 Time 09:46 Sent To  
Notes
2005-09-02 00:00:00******DENIED******
  
 1) PLANS SHOW FIRE ALARM EQUIPMENT ON
 ELEC. SHEETS. ARE THERE EXISTING FIRE
 ALARM AND FIRE SPRINKLER SYSTEMS?
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS IF APPLICABLE.
  
 3) PLEASE INDICATE EXISTING AND NEW
 OCCUPANCY CLASSIFICATION FOR ALL SPACES.
  
 4) PLEASE CLARIFY SCOPE OF WORK AS SOME
 SHEETS SHOW INCONSISTENCIES.
  
 5) PLEASE SEE BUILDING COMMENTS
 REGARDING SEPARATION REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-08 Cont ID  
Sent By lmartine Date 2005-09-08 Time 14:42 Rev Time 0.00
Received By lmartine Date 2005-08-04 Time 09:47 Sent To  
Notes
2005-08-05 00:00:00TO "COMM" BD#30
2005-08-04 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-08-30 Cont ID  
Sent By pkrauss Date 2005-08-30 Time 08:48 Rev Time 0.40
Received By pkrauss Date 2005-08-30 Time 08:48 Sent To  
Notes
2005-08-30 00:00:00PLEASE PROVIDE DETAIL ON THE ROOF CURBS
 FOR THE EXHAUST FANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-09-07 Cont ID  
Sent By kstevens Date 2005-09-07 Time 09:24 Rev Time 2.75
Received By kstevens Date 2005-09-07 Time 09:24 Sent To  
Notes
2005-09-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE
 CERTIFICATE OF AUTHORIZATION NUMBER
 REQUIRED IN THE TITLE BLOCK IS INDICATED
 AS NULL AND VOID AS OF 02/28/03 PER DBPR
 WEBSITE. SEE ATTACHED SHEET. - ALSO THE
 PRINTED NAME OF THE PERSON IS REQUIRED
 AS WELL AS THE DATED SEAL. FAC
 61G1-16.004(5)(6) & FS 481.219 FS
 481.2055.
 2. SHT "1" OF 9 MINIMUM FACILITIES SHOWN
 DOES NOT INDICATE A DRINKING FOUNTAIN.
 PER TABLE 403.1, 3 DRINKING FOUNTAINS
 ARE REQUIRED.
 3. SHT "7" OF 9 MINIMUM SCUPPER SIZE
 REQUIRED IS 22 SQ.IN. AND MINIMUM
 OPENING OF SCUPPERS IS 4" PER SECTION
 1107.3. 2"X8" SCUPPER INDICATED IN
 DETAIL 1/5 IS NOT APPROVED.
 4. SHT "7" OF 9 SUBMIT AN ISOMETRIC
 STORM RISER DIAGRAM SHOWING ALL PIPE
 SIZES AND INDICATE THE TERMINATION POINT
 FOR THE STORM FROM THE UPPER ROOF. SHOW
 THE SQUARE FOOTAGE AS IT ACCUMULATES IN
 THE STORM SYSTEM. SECTION 104.3.1.1.
 5. SHT M-1 DRY HORIZONTAL VENTS ARE NOT
 APPROVED PER SECTIONS 905.3 & 905.4.
 6. SUBMIT A FIXTURE SCHEDULE TO INDICATE
 THE NEW FIXTURES SHOWN ON FLOOR PLAN.
 SECTION 104.2.1.
 7. SUBMIT A SANITARY RISER DIAGRAM AND A
 WATER RISER DIAGRAM IN ISOMETRIC FORM.
 SHOW ALL PIPE SIZES, TRAPS, VENTS ECT
 FOR THE SANT. SHOW ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ARRESTORS, (IF
 REQUIRED BY SECTION 604.9), AND POINT OF
 CONNECTION. SECTION 104.3.1.1.
 8. LANDSCAPE SHEETS SHALL BE SEALED BY
 THE LANDSCAPE ARCHITECT PER FAC
 61G1-16.003 & FS 481.321(1) - THE
 CERTIFICATE OF AUTHORIZATION, (LANDSCAPE
 ARCHITECT BUSINESS LICENSE HAS BEEN NULL
 AND VOID SINCE 11/30/95 PER DBPR RECORDS
 AND SHALL BE UPDATED PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW. THE
 CA # IS REQUIRED PER FAC 61G1-16.004(2)
 AND FS 481.319.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-30 Cont ID  
Sent By pkrauss Date 2005-08-30 Time   Rev Time  
Received By pkrauss Date 2005-08-30 Time   Sent To  
Notes
2005-08-30 00:00:00PLANS SIGNED BY SHIRLEY GRAHAM