Plan Review Details - Permit 05080175
Plan Review Stops For Permit 05080175
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-07-12 Cont ID  
Sent By shill Date 2006-07-12 Time 17:53 Rev Time 0.00
Received By shill Date 2006-07-12 Time 17:53 Sent To  
Notes
2006-07-12 00:00:00REVISION ASP1, A1, A2, A4, A5 DATED 6/19

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-06-08 Cont ID  
Sent By shill Date 2006-06-08 Time 11:33 Rev Time 0.00
Received By shill Date 2006-06-08 Time 09:56 Sent To  
Notes
2006-06-08 00:00:00****CORRECTIONS****
 ****REVISION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)ALL CHANGES TO THE PLAN ARE TO BE
 CLOUDED.IT APPEARS THAT THE CLOUDS FOR
 REVISION #6 DID NOT PRINT.
  
 2.)THE AREA CALCULATIONS ON THE
 REVISION DIFFER FROM THE OLD PLAN.THE
 OLD PLAN SHOWS 13,504 AS EXISTING; THE
 REVISION SHOWS 15,272 AS EXISTING.THE
 EXISTING BUILDING SIZE SHOULD NOT HAVE
 CHANGED; WAS THERE AN ERROR IN BUILDING
 SIZE ON THE ORIGINAL PLAN?
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.CALL 233-5025 FOR MORE
 INFORMATION.IMPACT FEES ARE ASSESSED
 BASED ON HABITABLE SPACE (UNDER AIR).
 ALTHOUGH YOU ARE ELIMINATING SQUARE
 FOOTAGE, IT IS LIKELY THAT IMPACT FEES
 WERE NEVER PAID ON THAT AREA AS IT WAS A
 COVERED PORCH.IF THE COUNTY DETERMINES
 THAT IMPACT FEES ARE NOT DUE, THEY WILL
 STAMP THE PLAN WITH A $0 BALANCE DUE.
 IF THEY DO THIS, HAVE THEM INDICATE ON
 THE STAMP THAT THEY ARE AWARE THAT THERE
 IS AN ADDITION OF 228 FEET.
  
 3.) THE PANTRY DOOR IS TO COMPLY WITH
 FBC11-4.13 (WIDTH).
  
 4.)PROVIDE INFORMATION IN REGARDS TO
 DESIGN LOAD, ROOF FRAMING.
  
 5.)IT IS NOT CLEAR HOW DOOR 120B LEADS
 TO AN EXIT DISCHARGE.IT IS SHOWN AS AN
 EXIT ON E1.FROM THE PARTIAL FLOOR PLAN
 THAT DOOR APPEARS TO LEAD TO ANOTHER
 ROOM, BUT IT IS NOT CLEAR WHERE IT LEADS
 FROM THERE, AND WHAT THE PATH OF TRAVEL
 DISTANCE IS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-05-03 Cont ID  
Sent By shill Date 2006-05-03 Time 10:10 Rev Time 0.00
Received By shill Date 2006-05-03 Time 10:10 Sent To  
Notes
2006-05-03 00:00:00DETAIL SK5 DATED 4/10/6

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-18 Cont ID  
Sent By shill Date 2006-04-18 Time 16:48 Rev Time 0.00
Received By shill Date 2006-04-18 Time 16:48 Sent To  
Notes
2006-04-18 00:00:00REVISION DATED 4/3/06, ASP1, SK1 THROUGH
 SK4

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-02-16 Cont ID  
Sent By shill Date 2006-02-16 Time 15:46 Rev Time 1.00
Received By shill Date 2006-02-16 Time 15:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-25 Cont ID  
Sent By shill Date 2005-12-25 Time 15:35 Rev Time 3.00
Received By shill Date 2005-12-23 Time 16:56 Sent To  
Notes
2005-12-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
  
 1.)FROM PREVIOUS REVIEW, #4.PROVIDE
 INFORMATION IN REGARDS TO
 THE EXISTING BUILDING; MINIMUM BUILDING
 TYPE, HEIGHT (NUMBER OF STORIES),
 PROTECTED OR UNPROTECTED, SPRINKLED OR
 UNSPRINKLED, OCCUPANCY SO THAT FBC TABLE
 500 COMPLIANCE CAN BE DETERMINED.
  
 PLEASE PROVIDE ALL INFORMATION
 REQUESTED.SHOW COMPLIANCE WITH FBC
 TABLE 500 AS REQUESTED ON FIRST REVIEW.
 THIS IS TYPICALLY DONE IN A CODE SUMMARY
 SECTION.SOME INFORMATION WAS PROVIDED
 BUT NOT ENOUGH TO DETERMINE CODE
 COMPLIANCE.FOR INSTANCE, WHETHER OR
 NOT THE BUILDING IS SPRINKLED WAS NOT
 DECLARED ON THE PLAN.THE OCCUPANCY
 CLASSIFICATION AND SUBCLASSIFICATION WAS
 NOT DECLARED, PROTECTED OR UNPROTECTED.
 IT APPEARS TO BE ONE STORY, PLEASE
 DECLARE SO ON THE PLAN.
  
 2.)SEE FBC503.1.2.YOU SHOW A PORTION
 OF THE BUILDING AS TYPE V, ANOTHER
 PORTION AS TYPE III.FOR A BUILDING TO
 BE DECLARED TWO DIFFERENT BUILDING
 TYPES, A FIRE WALL BETWEEN THE TWO
 BUILDING TYPES IS REQUIRED.SHOW
 EXISTING OR PROPOSED FIRE WALL AND
 PROVIDE A DETAIL.PROVIDE INFORMATION
 IN REGARDS TO EXISTING CONSTRUCTION SO
 THAT THE BUILDING TYPE DECLARED CAN BE
 CONFIRMED.
  
 3.)IF THIS IS TWO BUILDINGS AS DEFINED
 BY FBC503.1.2, PROVIDE TOTAL AREA OF
 EACH BUILDING TYPE SO THAT TABLE 500
 COMPLIANCE CAN BE DETERMINED.
  
 4.)IF THIS ENTIRE BUILDING IS ACTUALLY
 A TYPE V BUILDING, SEE FBC TABLE 500.
 AN UNSPRINKLED TYPE V A2 BUILDING IS
 RESTRICTED TO A SIZE OF 8000 SF.THIS
 BUILDING IS OVER 13,000 AND YOU ARE
 PROPOSING TO ADD 200 SF.THE ADDITION
 AS PRESENTED DOES NOT APPEAR CODE
 COMPLIANT BUT NOT ENOUGH INFORMATION WAS
 PROVIDED TO MAKE THIS DETERMINATION.
  
 5.)DECLARE GOVERNING CODE.IF YOU ARE
 DESIGNING UNDER THE FBC2004, PLEASE
 ADVISE SO THAT I CAN REVISE CODE
 REFERENCE NUMBERS IF NECESSARY.
 COMMENTS STILL APPLY.
  
 6.)IF YOU ARE DESIGNING UNDER FBC2004,
 PRODUCT APPROVALS ARE TO BE REVIEWED BY
 THE DESIGNER OF RECORD, CITY OF WEST
 PALM BEACH AMENDMENTS TO THE FBC2004
 106.3.3.
  
 7.)FROM PREVIOUS REVIEW, ITEM #8.
 FLORIDA STATE OR LOCAL PRODUCT APPROVALS
 REQUIRED FOR THE ROOF AND THE WINDOW.
 PROVIDE BOTH THE STATE OR LOCAL PRODUCT
 APPROVAL AND THE CORRESPONDING
 EVALUATION OR TEST REPORT AND
 INSTALLATION INSTRUCTIONS.THE
 RESPONSE LETTER FROM THE ARCHITECT
 STATES THAT THE WINDOWS ARE EXISTING AND
 NOT BEING REPLACED.THERE IS A NEW
 WINDOW SHOWN AT THE SINK IN THE KITCHEN
 ADDITION.PRODUCT APPROVAL FOR THE ROOF
 WERE NOT SUBMITTED.
  
 WWW.FLORIDABUILDING.ORG
  
 7.)IMPACT PROTECTION REQUIRED FOR THE
 WINDOW FBC1606.1.4.IF YOU PROPOSE
 USING REMOVABLE SHUTTERS, APPROVAL BY
 THE BUILDING OFFICIAL IS REQUIRED.SEE
 ATTACHED POLICY, ITEM 13.
  
 8.)SHEETS A1, A4, A7, S1 ARE NOT
 SEALED.DOCUMENTS PREPARED BY AN
 ARCHITECT AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED, SEALED, AND
 DATED ORIGINALS.FAC61G1-16.
  
 9.)THE NOA SUBMITTED IS EXPIRED, OVER
 90 DAYS WITHOUT COMMENCING WORK,
 FS713.13(2).
  
 10.) SHOW TURNING RADIUS IN BATHROOM,
 FBC11-4.22.3.
  
 11.) SPECIFY HURRICANE STRAPS AND SHOW
 DESIGN CRITERIA, SHEET A7.
  
 12.) SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW IS REQUIRED TO BE CHARGED IF
 THE CORRECTIONS ARE NOT PROPERLY
 ADDRESSED IN THE THIRD REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-29 Cont ID  
Sent By shill Date 2005-08-29 Time 15:29 Rev Time 2.00
Received By shill Date 2005-08-29 Time 15:29 Sent To  
Notes
2005-08-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 2.)THIS IS AN OVER 50% IMPROVEMENT
 FBC3401.7.2.6 (SEE PROPERTY APPRAISER
 VALUATION).SOME COMMENTS MAY RELATE TO
 THIS CODE SECTION.
  
 3.)PROVIDE AREA CALCULATIONS ?
 EXISTING, PROPOSED, NEW TOTAL.
  
 4.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING BUILDING; MINIMUM BUILDING
 TYPE, HEIGHT (NUMBER OF STORIES),
 PROTECTED OR UNPROTECTED, SPRINKLED OR
 UNSPRINKLED, OCCUPANCY SO THAT FBC TABLE
 500 COMPLIANCE CAN BE DETERMINED.
  
 5.)SPECIFY MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR THE DECLARED
 OCCUPANCY, FBC TABLE 803.3.
  
 6.)MEANS OF EGRESS SHALL BE TO THE
 EXTERIOR OF THE BUILDING, FBC1001.3.
 EXIT LIGHTS ARE REQUIRED AT THE GATES
 LEADING OUTSIDE THE COVERED AREAS.
  
 7.)THE TITLE BLOCK FOR THE ENGINEER IS
 TO CONTAIN ALL INFORMATION REQUIRED BY
 FAC61G15-23.002 (PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT).
  
 8.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FOR:
  
 ROOF
 WINDOW
  
 WWW.FLORIDABUILDING.ORG
  

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2006-12-09 Cont ID  
Sent By dpalmer Date 2006-12-09 Time 16:59 Rev Time 0.00
Received By dpalmer Date 2006-12-09 Time 16:47 Sent To PC
Notes
2006-12-09 17:00:44REDLINED E-2 AGAIN FOR THE MINIMUM SIZE FOR THE GEC AS
 STATED AND REDLINED ON PREVIOUS PLANS. NEEDS TO BE A
 2/0 MIN PER 250.66 AND THE SEC'S SHOWN ON RISER.

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2006-10-17 Cont ID  
Sent By dpalmer Date 2006-10-17 Time 14:57 Rev Time 0.00
Received By dpalmer Date 2006-10-17 Time 14:35 Sent To PC
Notes
2006-10-17 14:59:06CONTRACTOR CALLED,
 REMOVED OLD E-2, AS THIS RISER DOES NOT APPLY.
  
 RISERGROUNDING ELECTRODE CONDUCTOR NEEDS TO BE SIZED
 PER 250.66. THIS APPEARS IT SHOULD BE 2/0.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2006-10-14 Cont ID  
Sent By dpalmer Date 2006-10-14 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2006-10-14 Time 17:27 Sent To PC
Notes
2006-10-14 17:41:53*** UNSAT ***
  
 1) NOTE: PLEASE SEE TWO COMPLETELY DIFFERENT SETS OF
 RISER DIAGRAMS ARE BEING SUBMITTED WHICH ARE BOTH DATED
 THE SAME DAY. PLEASE SEE THE SEC'S, FEEDERS ETC ARE ALL
 DIFFERENT AND IS INCLEAR WHICH ONE IS WANTING TO BE
 REVIEWED.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTES FOR SIZING OF THE
 GEC BASED ON 250.66. THIS WAS REDLINED ON ORIGINAL
 PLANS AND NOTED ON LAST REVIEW , HOWEVER BASED ON THE
 SEC'S FROM EITHER RISER, THE SIZE APPEARS TO BE ONE
 UNDER PER 250.66. (2/0MIN).
  
 3) NOTE: PLEASE SEE 110.9, AND 240.12 FOR SELECTIVE
 COORDINATION OF EQUIPMENT AND RATINGS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-09-05 Cont ID  
Sent By dpalmer Date 2006-09-05 Time 14:17 Rev Time 0.00
Received By dpalmer Date 2006-09-05 Time 13:34 Sent To PC
Notes
2006-09-05 00:00:00****UNSAT *****
  
 1) NOTE: PLEASE SEE PLANS NEED TO BE
 RE-PRINTED AS HAND DRAWN ITEMS ON PLANS
 ARE NOT PERMITTED.
 FBC ADMIN SECT 106.1.2
  
 2) NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR TO BE SIZED PER 250.66.
 PLEASE SEE SYSTEM SHALL BE CONTINUOUS.
 250.50,250.64.250.66
 1/0 MIN, #4 SHOWN.
 PLEASE ALSO VERIFY THE ATTCHMENT
 LOCATION OF THE GEC. SHOWN TO MAIN, IS
 THIS GOING TO THE GUTTER/, IF SO, PLEASE
 REVISE.
  
 3) NOTE: PLEASE KNOW, NEW REVISED PLANS
 DONE BY THE ENGINEER SHALL CONTAIN TITLE
 BLOCKS AS REQUIRED PER FAC 61G15-23.002,
 FS 471.023
  
 PLEASE REVISE THE ABOVE AND SUBMIT FOR
 REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-06-07 Cont ID  
Sent By dpalmer Date 2006-06-07 Time 16:51 Rev Time 0.00
Received By dpalmer Date 2006-06-07 Time 16:20 Sent To  
Notes
2006-06-07 00:00:00REDLINED:
  
 MCB ON MAIN #1 REQUIRED.
  
  
 PASSED PENDING PALM BEACH COUNTY IMPACT
 FEE STAMP AND POSSIBLE FEE SFOR
 ADDITION.
 SQ FT ADDED. SEE BUILDING REVIEW NOTES.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-04-24 Cont ID  
Sent By dpalmer Date 2006-04-24 Time 19:35 Rev Time 0.00
Received By dpalmer Date 2006-04-24 Time 19:35 Sent To  
Notes
2006-04-24 00:00:00*********UNSAT *******
  
 ** PLEASE SEE A NOTE FROM SAMANTA
 HILL,MENTIONS FOR ALL REVIEWS TO BE
 DONE, NOW THAT PLANS ARE BEING SUBMITTED
 INCLUDING KITCHEN ADDITION.
  
 1) NOTE: PLEASE SEE ORIG PLANS OMITTED
 THE KITCHEN ADDITION FROM SCOPE OF WORK
 FOR PERMIT.
 PLEASE SEE REVSION IS NOW COMING FOR
 KITCHEN ADDITION, HOWEVER NO ELECTRICAL
 IS BEING SHOWN. PLEASE SUBMIT AND
 CORRELATE WITH THE PANEL SCHEDULES TO BE
 SUBMITTED.
 PLEASE SEE THIS IS IN CONFLICT WITH NOTE
 ON PLANS, AS ONE NOTE MENTIONS
 RENOVATION OF EXISTING KITCHEN OR WORDS
 TO THAT AFFECT.
  
 2) NOTE: PLEASE ADJUST VALUATION FOR
 SCOPE OF WORK FOR ADDITION.
 FBC 104.6.5.
 PLEASE ALSO SEE BUIDLING REVIEW NOTES
 FOR THIS..
  
 ** PLEASE KNOW, ANY REVISIONS TO
 ELECTRICAL SHALL BE DONE BY THE
 ELECTRICAL ENGINEER OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-06 Cont ID  
Sent By dpalmer Date 2006-03-06 Time 17:31 Rev Time 0.00
Received By dpalmer Date 2006-03-06 Time 17:20 Sent To  
Notes
2006-03-06 00:00:00KITCHEN ADDITION IS NOT IN SCOPE.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-12-21 Cont ID  
Sent By dpalmer Date 2005-12-21 Time 07:19 Rev Time 0.00
Received By dpalmer Date 2005-12-20 Time 21:21 Sent To  
Notes
2005-12-21 00:00:00************* UNSAT ***************
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE CHANGES IN ELECTRICAL
 RISER ALONG WITH PLANS STILL SHOWING
 OTHER NEED TO BE ADDRESSED.
  
 *** PLEASE KNOW, WHEN PLANS WERE
 SUBMITTED BACK TO THE CONSTRUCTION
 SERVICES DEPT. ON OCT 12, 2005, "ONLY"
 THE OLD/ UN-CORRECTED PLANS WERE
 SUBMITTED BACK FOR REVIEW AND NO "NEW"
 OR REVISED PLANS WERE SUBMITTED. THIS IS
 THE REASON WHY FIRE AND ELECTRICAL
 REVIEW HAD A 2ND REVIEW WHICH REFERENCED
 TO THE SAME COMMENTS FROM ORIGINAL
 REVIEW.
 ** PLEASE KNOW THAT THE NEW/REVISED
 PLANS NOT SUBMITTED BACK ON OCT 12, WERE
 ALLOWED TO BE BROUGHT IN ON NOV 21ST,
 2005 TO BE RE-REVIEWED. THESE PLANS WERE
 BROUGHT IN BY MR. KEVIN BUTLER II.
 I HOPE THIS CLEARS UP ANY CONFUSION OVER
 WHY THERE WAS REFERENCE TO OLD/PLANS.
  
 PLEASE SEE THE FOLLOWING:
  
 ** NOTES TAKEN DIRECTLY FROM FIRST
 REVIEW.
  
 1)NOTE:NOTE #1, NO. PLEASE SEE FIRST
 PART OF NOTE MENTIONED TO SHOWALL
 CIRCUITING NEWAND CORRELATE WITH
 SUBMITTED PANEL SCHEDULE(S).
 THIS WAS DONE, HOWEVER PLEASE SEE THIS
 NOTE AND NOTE #2 REQUESTED ALLEM/EXT
 LTS TO BE CIRCUITED TO THE LOCAL BRANCH
 CIRCUIT FEEDING UNIT EQUIPMENT.THIS WAS
 DONE FOR EM LTS, HOWEVER NOT THE EXT
 LTS.
 PLEASE ADJUST CIRCUITING.
  
  
 2)NOTE: NOTE #2,YES/NO PLEASE SEE THAT
 BATTERY BACK UP EXIT LTS WERE ADDED FOR
 LIGHTING THE EGRESS PATH TO EXIT
 DISCHARGE, HOWEVER COULD NOT LCOATE ANY
 INFORMATION WITH RESPECT TO NOTES OR MIN
 FT CANDLES REQUIRED. PLEASE SEE NFPA-101
 7-8, WHICH REQUIRES THE MEANS OF EGRESS
 LIGHTING TO MEET AMIN OF 10 FT CANDLES
 DURING NORMAL POWERE AND A MIN OF 1 FT
 CANDLE DURING EMERGENCY CONDITIONS( LOSS
 OF NORMAL POWER).
 PLEASE PROVIDE AT A MININUM, NOTING FOR
 THESE MIN REQUIREMENTS.
 PLEASE SEE 2003 NFPA-101 7.8, 7.9
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 OK. (ONLY NOTED)
  
 6)NOTE: NOTE #6 NO, PLEASE SEE A NOTE
 WAS ADDED MENTIONING "WHEN REQUIRED"
 PLEASE SEE FIRE/MECHANCICAL REVIEW
 NOTES, A "SHUNT TRIP" OF SOME SORT WOULD
 BE REQUIRED TO SHUT DOWN ALL ELECTRICAL
 IN A HOOD AREA.
 PLEASE PROVIDE REFERENCE TO NFPA-96 WITH
 MEANS OF SHUT DOWN OF ANY
 ELECTRICAL DEVICES UNDER HOOD.
 PLEASE SEE CHAPTERS 9 AND 10
  
 7)NOTE: NOTE #7 OK, A DOOR AND WALL WERE
 ADDED TO SEPARATE FROM STORAGE AREA OF
 CLOSET.
  
 8)NOTE: NOTE #8, OK.
  
 9)NOTE: NOTE #9, NO PLEASE SEE
 250.6,250.24, "EQUIPMENT GROUNDING "
 CONDUCTORS ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
 PLEASE SEE THESE "EQIPMENT GROUNDING
 CONDUCTORS"ARE STILL BEING SHOWN ,
 BOTH ON REFERENCE TO THE EXISTING SEC'S
 AND TO THE NEW SEC'S.
 PLEASE SEE NEW COMMENTS WITH RESPECT TO
 THE SERVICE.
 PLEASE SEE EQP GRND FROM METER TO
 MAIN.(NEW)AND EXISTING.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 NO/YES, PLEASE SEE THE
 TAPS FOR NEW MAIN IS NOW SHOWN, HOWEVER
 PLEASE SEE NEW NOTE ADDING A TAP TO
 EXISTING MAIN WILL NOT BE PERMITTED.
 PLEASE ALSO KNOW, PREVIOUS COMMENT
 REQUESTED OF THIS WAS A NEW SERVICE OR
 COMING FROM THE EXISTING SERVICE RISER?
 PLEASE SEE RISER NOW INDICATES THIS TAP
 LOCATED IN "CT" AND DOES NOT SHOW A NEW
 RISER OR SEC'S UP TO A NEW WEATHER HEAD.
 THERFORE, PLEASE SHOW EXISTING SEC'S IN
 RISER AND PLEASE BE SURE TO MAKE SURE
 THE EXISTING SIZE IS ADEQUATE FOR BOTH
 NEW AND EXISITNG. PLEASE SEE EXISITNG IS
 SHOWN AS 600A'S AND NEW MAIN IS 400'S.
 PLEASE SEE 230.2 FOR NEW
 SERVICE AS SHOWN ON PLANS. PLEASE
 CLARIFY IF "NEW SERVICE" IS GOING TO BE
 FED FROM THE SAME SERVICE DROP AND
 TRANSFORMER.
 *** PLEASE SEE PLANS STILL INDICATE
 THERE BEING A "NEW METER", AN "EXISITNG
 METER" AND AND "EXISITNG CT" WHICH DOES
 NOT CORRELATE WITH THE RISER DIAGRAM
 SHOWN FOR SERVICE.
 PLEASE CORRELATE THE ABOVE AND CALL TO
 GO OVER OPTIONS IF NEEDED.
 215.5
  
 ** NEW NOTE:
  
 1)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO THE DESIGN
 PROFESSIONAL AND REPEAT COMMENTS FOR
 CODE COMPLIANCE.
 PLEASE KNOW THIS IS ONLY A NOTICE GIVEN
 AT THIS TIME.
 ONE COPY OF ELECTRICAL PLANS ARE BEING
 RETAINED.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS ARE
 REQUIRED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-12-20 00:00:00IN ELEC FOR REVIEW.
 THIS REVIEW IS BEING DONE ON THE "NEW"
 PLANS SUBMITTED ON NOV 21ST, 2005.
  
 SOME COMMENTS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED, AND COMMENTS DUE
 TO INFORMATION ADDED TO PLANS.
 NOTES TO FOLLOW, REVIEW IN PROGRESS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-11-15 Cont ID  
Sent By dpalmer Date 2005-11-15 Time 07:18 Rev Time 0.00
Received By dpalmer Date 2005-11-15 Time 07:02 Sent To  
Notes
2005-11-15 00:00:00********* UNSAT 2ND REVIEW *********
  
  
 1)NOTE: PLEASE SEE THE NOTES FROM
 PREVIOUS REVIEW. PLEASE SEE NO NOTES
 SEEMED TO HAVE BEEN ADDRESSED, YET
 RESPONSE LETTER MENTIONS ITEMS CORRECTED
 AND CHANGED.
  
 2)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO THE DESIGN
 PROFESSIONAL AND REPEAT COMMENTS.
 THIS IS ONLY A NOTE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-15 Cont ID  
Sent By dpalmer Date 2005-08-15 Time 17:13 Rev Time 2.50
Received By dpalmer Date 2005-08-15 Time 13:41 Sent To  
Notes
2005-08-15 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING FOR
 NEWAND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE(S).
 PLEASE SEE EXT/ EM LT PER 700.12E,THE
 BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
  
 2)NOTE: PLEASE SEE NFPA-101 7-8, WHICH
 REQUIRES MEANS OF EGRESS LIGHTING TO THE
 EXIT DISCHARGE/ TO PUBLIC RIGHT OF WAY.
 PLEASE SEE CORRIDORS IN OPEN COURTYARD
 AREAS. 101,15.2
 PLEASE ALSO SEE 700.12E FOR CIRCUITINGOF
 EM/LTS.PREVIOUSLY NOTED.
  
 3)NOTE: PLEASE SEE 2002 NEC FOR
 PROTECTION OF RECEPTS IN KITCHENS IN
 OTHER THAN DWELLING UNITS, WHICH
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 4)NOTE: PLEASE SEE MISSING THE "PRINTED"
 LICENSE NUMBER OF THE ENGINEER OF
 RECORD. PLEASE SEE FAC 61G15-23.002
 FS 471
  
 5)NOTE: PLEASE SEE BLDG, ZOING COMMENTS,
 NO SURVEY/SITE PLAN SHOWING SETBACKS FOR
 NEW KITCHAN ADDITION WAS SUBMITTED.
 PLEASE SEE FS 472.025, FAC 61G17-7.002,
 PLEASE BE SURE ALL SURVEY'S CONTAIN THE
 ABOVE.
  
 6)NOTE: PLEASE PROVIDE REFERENCE TO
 NFPA-96 WITH MEANS OF SHUT DOWN OF ANY
 ELECTRICAL DEVICES UNDER HOOD.
 PLEASE SEE CHAPTERS 9 AND 10
  
 7)NOTE: PLEASE SEE PANEL "B" WHICH IS
 SHOWN AS EXISTING SHALL NOT BE LOCATED
 IN "OFFICE CLOSET". PLEASE SEE FIRE
 REVIEW NOTES, NO STORAGE PERMITTED IN
 SPACES ABOUT ELECTRICAL EQUIPMENT/RMS.
 PLEASE SEE 408.7,240.24D, 110.26 ETC
 PLEASE SEE THIS AREA FOR LOCATION OF
 PANEL NEEDS TO REFERENCE, ELEC/MECH RM.
  
 8)NOTE:PLEASE CLARIFY/ SHOW EITHER NEW
 OR EXISTING ROOF-TOP WP GFI RECEPTS FOR
 RTU'S PER 210.63
  
 9)NOTE: PLEASE SEE 250.6,250.24,
 "EQUIPMENT GROUNDING " CONDUCTORS ARE
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
 PLEASE SEE EQP GRND FROM METER TO
 MAIN.(NEW).
  
 10)NOTE: PLEASE SHOW METHOD OF EQUIPMENT
 GROUNDING FROM PANELS TO ALL RTU'S.
 PLEASE KNOW, EMT MAY ONLY BE USED AS AN
 "EQUIPMENT GROUND PATH" IF USED IN
 CONNECTION WITH NEW "LISTED" EQUIPMENT
 GROUNDING CONNECTORS AND COUPLINGS.
 110.3
  
 11)NOTE: PLEASE SEE 230.2 FOR NEW
 SERVICE AS SHOWN ON PLANS. PLEASE
 CLARIFY IF "NEW SERVICE" IS GOING TO BE
 FED FROM THE SAME SERVICE DROP AND
 TRANSFORMER.
 215.3
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS ARE
 REQUIRED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2006-08-02 Cont ID  
Sent By mwennerg Date 2006-08-02 Time 09:07 Rev Time 0.00
Received By mwennerg Date 2006-08-02 Time 09:07 Sent To  
Notes
2006-08-02 00:00:00REVISION DATED 6/19/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2006-06-09 Cont ID  
Sent By mwennerg Date 2006-06-09 Time 10:40 Rev Time 0.00
Received By mwennerg Date 2006-06-09 Time 10:40 Sent To  
Notes
2006-06-09 00:00:00REVISION DATED 3/28/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-05-31 Cont ID  
Sent By mwennerg Date 2006-05-31 Time 14:20 Rev Time 0.00
Received By mwennerg Date 2006-05-31 Time 14:20 Sent To  
Notes
2006-05-31 00:00:00REVISION DATED 3/26/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-12-07 Cont ID  
Sent By mcarsill Date 2005-12-07 Time 11:11 Rev Time 0.00
Received By mcarsill Date 2005-12-07 Time 11:11 Sent To  
Notes
2005-12-07 00:00:001. SEPERATE PLANS AND PERMITS REQUIRED
 FOR HOOD, DUCT, AND SUPPRESSION SYSTEM
 PLANNED FOR USE.
  
 2. OTHER WORK SHALL COMPLY WITH NFPA
 241.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-11-16 Cont ID  
Sent By mwennerg Date 2005-11-16 Time 15:07 Rev Time 0.00
Received By mwennerg Date 2005-11-16 Time 15:07 Sent To  
Notes
2005-11-16 00:00:00******DENIED******
  
 1) PLEASE SEE FIRE REVIEW COMMENTS FROM
 FIRST REVIEW. PLANS ILLUSTRATE EXIT
 SIGNS AND EMERGENCY LIGHTS IN
 CLASSROOMS, BUT NOT COMMON AREA
 CORRIDORS. HOW WOULD PERSONS BE DIRECTED
 TO AN EXIT DISCHARGE?
  
 2) RESPONSE LETTER INDICATES THAT FIRE
 EXTINGUISHERS HAVE BEEN ADDED TO THE
 DRAWINGS. PLEASE INDICATE SHEET NUMBER.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-06 Cont ID  
Sent By mwennerg Date 2005-09-06 Time 14:06 Rev Time 0.00
Received By mwennerg Date 2005-09-06 Time 14:06 Sent To  
Notes
2005-09-06 00:00:00******DENIED******
  
 1) PLEASE SEE THAT REQUIRED MEANS OF
 EGRESS MUST BE CLEARLY MARKED. PLEASE
 SHOW LOCATIONS OF ALL ILLUMINATED EXIT
 SIGNS AND EMERGENCY LIGHTING FACILITIES
 IN AREAS DIRECTING PERSONS TO AN EXIT
 AND EXIT DISCHARGE.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND SHALL BE MOUNTED TO SATISFY
 THE 75' TRAVEL DISTANCE REQUIREMENT.
 PLEASE SHOW IF EXISTING OR NEW.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND
 FIRER ALARM REMODEL IF APPLICABLE.
  
 4) NO COOKING OF FOODS THAT PRODUCE
 GREASE LADEN VAPORS UNLESS PROTECTED BY
 APPROVED HOOD AND SUPPRESSION SYSTEMS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-07-15 Cont ID  
Sent By pschmitz Date 2006-07-15 Time 08:52 Rev Time 0.00
Received By pschmitz Date 2006-07-15 Time 08:52 Sent To  
Notes
2006-07-15 00:00:00GAS NOT INCLUDED IN THIS PERMIT,
 SEPERATE PLANS AND PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-06-24 Cont ID  
Sent By pschmitz Date 2006-06-24 Time 12:16 Rev Time 0.00
Received By pschmitz Date 2006-06-24 Time 12:15 Sent To  
Notes
2006-06-24 00:00:00 
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 END OF COMMENTS, QUESTIONS 561-805-6692
 PAUL SCHMITZ
 FBC 2004 FUEL GAS CODE, PLAN REVIEW
  
 DENIED
  
 1) SHT P-1
 NATURAL GAS PIPING RISER DENIED.
 PLAN REVIEW COMMENTS SHALL BE RESPONDED
 TO BY THE DESIGN PROFESSIONALS. REFERING
 TO EACH OTHER OR CONTRACTOR, IS NOT
 HELPFUL IN EXPEDITING YOUR PERMIT.
 SEPERATE GAS RISER, SIGNED AND SEALED BY
 ENGINEER OF RECORD
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304
 .
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 12. SEC 409.5 EQUIPMENT SHUT OFF VALVE.
 EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWNSTREAM OF MANUAL SHUT OFF VALVE.
  
 13. NFPA-96 SEC10.5.1 &
 NFPA -1 SEC 50.4/7.1GAS EMERGENCY SOV
 TO BE 42? TO 48? AFF
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-12-08 Cont ID  
Sent By adarroug Date 2006-12-08 Time 11:11 Rev Time 0.00
Received By adarroug Date 2006-12-08 Time 11:11 Sent To E
Notes
2006-12-08 11:11:34TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-10-06 Cont ID  
Sent By adarroug Date 2006-10-06 Time 09:11 Rev Time 0.00
Received By adarroug Date 2006-10-06 Time 09:11 Sent To E
Notes
2006-10-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-08-26 Cont ID  
Sent By adarroug Date 2006-08-26 Time 15:41 Rev Time 0.00
Received By adarroug Date 2006-08-26 Time 15:41 Sent To E
Notes
2006-08-26 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-27 Cont ID  
Sent By adarroug Date 2006-06-27 Time 16:45 Rev Time 0.00
Received By adarroug Date 2006-06-27 Time 16:45 Sent To  
Notes
2006-07-12 00:00:00TO "COMM" BD#19
2006-06-27 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 10:05 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 10:05 Sent To  
Notes
2006-05-25 00:00:00TO "COMM" BD#3
2006-05-11 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-20 Cont ID  
Sent By adarroug Date 2006-04-20 Time 09:49 Rev Time 0.00
Received By adarroug Date 2006-04-20 Time 09:49 Sent To B
Notes
2006-04-20 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-06 Cont ID  
Sent By adarroug Date 2006-04-06 Time 15:13 Rev Time 0.00
Received By adarroug Date 2006-04-06 Time 15:13 Sent To B
Notes
2006-04-20 00:00:00TO "COMM" BD#44
2006-04-06 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-02 Cont ID  
Sent By adarroug Date 2006-02-02 Time 18:41 Rev Time 0.00
Received By adarroug Date 2006-02-02 Time 18:41 Sent To  
Notes
2006-03-06 00:00:00TO "COMM" BD#62
2006-02-02 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 08:55 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 08:55 Sent To  
Notes
2005-11-14 00:00:00TO "COMM" BD#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-09 Cont ID  
Sent By pkrauss Date 2005-09-09 Time 06:54 Rev Time 0.00
Received By pkrauss Date 2005-08-04 Time 09:53 Sent To  
Notes
2005-08-05 00:00:00TO "COMM" BD#19
2005-08-04 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-06-27 Cont ID  
Sent By tgordon Date 2006-06-27 Time 08:08 Rev Time 0.30
Received By tgordon Date 2006-06-27 Time 08:08 Sent To  
Notes
2006-06-27 00:00:00MECHANICAL PLANS SUBMITTED FOR A/C
 PACKAGE UNITS ON ROOF.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2006-05-11 Cont ID  
Sent By tgordon Date 2006-05-11 Time 11:56 Rev Time 0.30
Received By tgordon Date 2006-05-11 Time 11:56 Sent To  
Notes
2006-05-11 00:00:00*** NOTE ***
 ADDITIONAL PERMITS ARE REQUIRED FOR THE
 KITCHEN EXHAUST HOOD, AND ONE FOR THE
 HOOD FIRE SUPPRESSION SYSTEM. PLEASE
 PROVIDE PLANS AND MANUFACTURERS
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-23 Cont ID  
Sent By pkrauss Date 2006-01-23 Time 09:27 Rev Time 0.00
Received By pkrauss Date 2006-01-23 Time 08:42 Sent To  
Notes
2006-01-23 00:00:00PROVISO:
 ADDITIONAL PERMIT REQUIRED FOR HOOD &
 FIRE SUPPRESSION.PLEASE PROVIDE PLANS
 & MANUFACTURERS SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-08 Cont ID  
Sent By pkrauss Date 2005-09-08 Time 08:41 Rev Time 1.45
Received By pkrauss Date 2005-09-08 Time 08:37 Sent To  
Notes
2005-09-08 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC(M) TABLE 403.3.
  
 2.PLEASE INDICATE TYPE OF VENT TO THE
 WATER HEATER. REFERENCE 2001 FBC(F)
 CHAPTER 5.PROVIDE MANUFACTURER'S
 INSTALLATION INFORMATION.
  
 3.PLAN SHEET M-2 HVAC GENERAL NOTE #17
 INDICATES HOOD FOR THE GAS STOVE.
 PLEASE NOTE, SEPARATE PERMIT REQUIRED
 FOR HOOD & SUPPRESSION.PLEASE PROVIDE
 PLANS AND MANUFACTURER'S SPECIFICATIONS
 FOR THE HOOD.HOOD & GREASE DUCT SHALL
 COMPLY WITH 2001 FBC(M) 507 & 506
 RESPECTIVELY.
  
 4.CONDENSATE SHALL TERMINATE IN
 ACCORDANCE WITH 2001 FBC(M)307.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-07-15 Cont ID  
Sent By pschmitz Date 2006-07-15 Time 08:54 Rev Time 0.00
Received By pschmitz Date 2006-07-15 Time 08:54 Sent To  
Notes
2006-07-15 00:00:00PROVISO:
 SEC 606.1(4) SOV ON ALL WATER DROPS.

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-06-24 Cont ID  
Sent By pschmitz Date 2006-06-24 Time 13:09 Rev Time 0.00
Received By pschmitz Date 2006-06-24 Time 13:09 Sent To  
Notes
2006-06-24 00:00:00PLUMBING OK
 ADDED STOP FOR GAS DENIED SEE NOTES.

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-06-03 Cont ID  
Sent By kstevens Date 2006-06-03 Time 11:26 Rev Time 0.00
Received By kstevens Date 2006-06-03 Time 11:26 Sent To  
Notes
2006-06-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 MUNICIPAL CODE
  
 1. SUBMIT A SANITARY RISER DIAGRAM AND
 PLAN VIEW OF THE PIPING. SHOW ALL PIPE
 SIZES, VENTS, TRAPS ETC. SECTION
 104.3.1.1.
  
 2. SUBMIT A WATER RISER DIAGRAM AND PLAN
 VIEW OF THE PIPING. SHOW ALL PIPE SIZES,
 VALVES AND WATER HAMMER ARRESTORS IF
 REQUIRED BY SECTION 604.9. SECTION
 104.3.1.1.
  
 3. A GREASE INTERCEPTOR MAY BE REQUIRED
 AND IF SO, A GREASE WASTE SYSTEM WILL BE
 REQUIRED FOR THE KITCHEN. PLEASE CONTACT
 LYNN MASSON ENVIRONMENTAL COMPLIANCE FOR
 A DERTIMINATION. HER PHONE NUMBER IS
 (561) 822-2271, FAX (561 822-2279, AND
 E-MAIL [email protected]. MUNICIPAL CODE
 SECTION #3434.
  
 4. THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE SEPARATE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. (LENGTHS FOR EACH CUT
 SECTION NOT SHOWN).
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 (NO RESPONSE, NOT ADDRESSED).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). (NO RESPONSE,
 NOT ADDRESSED)
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (NO
 RESPONSE, NOT ADDRESSED).
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. (NO
 RESPONSE, NOT ADDRESSED).
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. (NEEDS TO
 BE SHOWN ON THE GAS RISER ISOMETRIC).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-03-06 Cont ID  
Sent By kstevens Date 2006-03-06 Time 16:49 Rev Time 0.00
Received By kstevens Date 2006-03-06 Time 16:49 Sent To  
Notes
2006-03-06 00:00:00 
  
  
  
 KITCHEN EXPANSION NOT INCLUDED IN THIS
 PERMIT. THIS INCLUDES THE SANT, WATER,
 AND GAS PIPING FOR THE KITCHE.SEE
 SHEET P-1

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-31 Cont ID  
Sent By kstevens Date 2006-01-31 Time 09:15 Rev Time 0.00
Received By kstevens Date 2006-01-31 Time 09:15 Sent To  
Notes
2006-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 A. PREVIOUS COMMENTS FROM FIRST REVIEW
 NOT ADDRESSED. COMMENT NUMBERS TO REMAIN
 THE SAME AS FIRST REVIEW:
  
 1. INDICATE AGE OF STUDENTS TO DETERMINE
 THE OCCUPANCY. SECTION 104.2.1. (NOT
 ADDRESSED, NO RESPONSE). PLEASE INDICATE
 OCCUPANCY AND INDICATE AGE OF STUDENTS.
 2. ROUTE PLANS TO THE PALM BEACH HEALTH
 UNIT DIVISION OF ENVIRONMENTAL HEALTH
 FOR REVIEW PRIOR TO RESUBMITTING FOR
 PLAN REVIEW AT THE CITY WPB. SECTION
 101.4.7. (NO RESPONSE, NOT ADDRESSED).
 4. SHT A-6 SHOW THE FOLLOWING TO SHOW
 COMPLIANCE OF THE ACCESSIBILITY CODE:
 FOR LAVS...
 11-4.19.5 FAUCETS
 TOILET ROOM:
 11-4.22.3 TURNING AREA IN TOILET ROOM,
 NOT IN THE STALL.
 5. SHT P-1 IF THE DESIGN PROFESSIONAL IS
 AN ARCHITECT OR ENGINEER LEGALLY
 REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE
 OR ENGINEERING, THEN HE/SHE SHALL AFFIX
 HIS/HER OFFICIAL SEAL TO SAID DRAWINGS,
 AS REQUIRED FY FLORIDA STATUTES. SECTION
 104.2.2. (SHEETS A-1, A-4,A-7, & S-1 NOT
 SIGNED, SEALED, DATED)
 8. THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE SEPARATE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. (LENGTHS FOR EACH CUT
 SECTION NOT SHOWN).
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 (NO RESPONSE, NOT ADDRESSED).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). (NO RESPONSE,
 NOT ADDRESSED)
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (NO
 RESPONSE, NOT ADDRESSED).
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. (NO
 RESPONSE, NOT ADDRESSED).
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. (NEEDS TO
 BE SHOWN ON THE GAS RISER ISOMETRIC).
  
 **************NEW COMMENT***************
 1B. SEE ATTACHED SHEET CONCERNING FS
 553.80(2)(B) AND THE DESIGN
 PROFESSIONAL. (ATTACHED TO ELECTRICAL
 COMMENTS). THIS IS GIVEN AS A NOTICE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-09-07 Cont ID  
Sent By kstevens Date 2005-09-07 Time 14:50 Rev Time 1.96
Received By kstevens Date 2005-09-07 Time 14:50 Sent To  
Notes
2005-09-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
 1. INDICATE AGE OF STUDENTS TO DETERMINE
 THE OCCUPANCY. SECTION 104.2.1.
 2. ROUTE PLANS TO THE PALM BEACH HEALTH
 UNIT DIVISION OF ENVIRONMENTAL HEALTH
 FOR REVIEW PRIOR TO RESUBMITTING FOR
 PLAN REVIEW AT THE CITY WPB. SECTION
 101.4.7.
 3. MINIMUM FACILITIES REQUIRE A DRINKING
 FOUNTAIN AND A SERVICE SINK PER TABLE
 403.1.
 4. SHT A-6 SHOW THE FOLLOWING TO SHOW
 COMPLIANCE OF THE ACCESSIBILITY CODE:
 FOR W/C'S..
 11-4.16.2 CLEAR FLOOR SPACE
 11-4.16.3 HEIGHT
 11-4.16.5 FLUSH CONTROLS
 FOR UNINAL..
 11.4.18.2 HEIGHT
 11-4.18.3 CLEAR FLOOR SPACE
 11-4.18.4 FLUSH CONTROLS
 FOR LAVS...
 11-4.19.2 HEIGHT & CLEARANCES -
 INCLUDING LAV OUTSIDE ACCESSIBLE STALL.
 11-4.19.3 CLEAR FLOOR SPACE
 11-4.19.4 EXPOSED PIPES & SURFACES
 11-4.19.5 FAUCETS
 TOILET ROOM:
 11-4.22.3 TURNING AREA IN TOILET ROOM,
 NOT IN THE STALL.
 5. SHT P-1 IF THE DESIGN PROFESSIONAL IS
 AN ARCHITECT OR ENGINEER LEGALLY
 REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE
 OR ENGINEERING, THEN HE/SHE SHALL AFFIX
 HIS/HER OFFICIAL SEAL TO SAID DRAWINGS,
 AS REQUIRED FY FLORIDA STATUTES. SECTION
 104.2.2.
 6. SHT P-1 SANT RISER DIAGRAM, SHOW ALL
 PIPE SIZES, CLEANOUTS REQUIRED BY
 SECTION 708.3.3, (AT CHANGE OF
 DIRECTION), VENTS ECT. SECTIONS 104.2.1
 & SECTION 901.2.1. - IF SINKS ARE IN THE
 FOOD PREPARATION AREA THEN THE SINKS
 SHALL DRAIN INDIRECTLY INTO A FLOOR SINK
 PER SECTION 802.3.
 7. SHT P-1 WATER RISER DIAGRAM, SHOW ALL
 PIPE SIZES, VALVES AND WATER HAMMER
 ARRESTORS IF REQUIRED BY SECTION 604.9,
 (QUICK CLOSING VALVES).
 8. THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE SEPARATE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-27 Cont ID  
Sent By jroach Date 2006-07-27 Time 12:00 Rev Time 0.00
Received By jroach Date 2006-07-27 Time 12:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-19 Cont ID  
Sent By jroach Date 2006-05-19 Time 14:34 Rev Time 0.00
Received By jroach Date 2006-05-19 Time 14:34 Sent To  
Notes
2006-05-19 00:00:005/19/06 ***FAILED***
  
 PER THE FINAL ORDER FOR ZBA CASE NO.
 3136, A UNITY OF TITLE SHALL BE FILED
 WITH THE PALM BEACH COUNTY CLERK OF THE
 CIRCUIT COURT, AND A CERTIFIED COPY
 PROVIDED TO THE PLANNING AND ZONING
 DEPARTMENT, PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.