| Plan Review Stops For Permit 05080175 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2006-07-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-07-12 |
Time |
17:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-07-12 |
Time |
17:53 |
Sent To |
|
|
| Notes |
| 2006-07-12 00:00:00 | REVISION ASP1, A1, A2, A4, A5 DATED 6/19 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2006-06-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-06-08 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-06-08 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2006-06-08 00:00:00 | ****CORRECTIONS**** | | | ****REVISION**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)ALL CHANGES TO THE PLAN ARE TO BE | | | CLOUDED.IT APPEARS THAT THE CLOUDS FOR | | | REVISION #6 DID NOT PRINT. | | | | | | 2.)THE AREA CALCULATIONS ON THE | | | REVISION DIFFER FROM THE OLD PLAN.THE | | | OLD PLAN SHOWS 13,504 AS EXISTING; THE | | | REVISION SHOWS 15,272 AS EXISTING.THE | | | EXISTING BUILDING SIZE SHOULD NOT HAVE | | | CHANGED; WAS THERE AN ERROR IN BUILDING | | | SIZE ON THE ORIGINAL PLAN? | | | | | | 3.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.CALL 233-5025 FOR MORE | | | INFORMATION.IMPACT FEES ARE ASSESSED | | | BASED ON HABITABLE SPACE (UNDER AIR). | | | ALTHOUGH YOU ARE ELIMINATING SQUARE | | | FOOTAGE, IT IS LIKELY THAT IMPACT FEES | | | WERE NEVER PAID ON THAT AREA AS IT WAS A | | | COVERED PORCH.IF THE COUNTY DETERMINES | | | THAT IMPACT FEES ARE NOT DUE, THEY WILL | | | STAMP THE PLAN WITH A $0 BALANCE DUE. | | | IF THEY DO THIS, HAVE THEM INDICATE ON | | | THE STAMP THAT THEY ARE AWARE THAT THERE | | | IS AN ADDITION OF 228 FEET. | | | | | | 3.) THE PANTRY DOOR IS TO COMPLY WITH | | | FBC11-4.13 (WIDTH). | | | | | | 4.)PROVIDE INFORMATION IN REGARDS TO | | | DESIGN LOAD, ROOF FRAMING. | | | | | | 5.)IT IS NOT CLEAR HOW DOOR 120B LEADS | | | TO AN EXIT DISCHARGE.IT IS SHOWN AS AN | | | EXIT ON E1.FROM THE PARTIAL FLOOR PLAN | | | THAT DOOR APPEARS TO LEAD TO ANOTHER | | | ROOM, BUT IT IS NOT CLEAR WHERE IT LEADS | | | FROM THERE, AND WHAT THE PATH OF TRAVEL | | | DISTANCE IS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2006-05-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-05-03 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-05-03 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2006-05-03 00:00:00 | DETAIL SK5 DATED 4/10/6 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-04-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-04-18 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-04-18 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2006-04-18 00:00:00 | REVISION DATED 4/3/06, ASP1, SK1 THROUGH | | | SK4 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-02-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-02-16 |
Time |
15:46 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2006-02-16 |
Time |
15:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-12-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-12-25 |
Time |
15:35 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2005-12-23 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2005-12-25 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | | | | 1.)FROM PREVIOUS REVIEW, #4.PROVIDE | | | INFORMATION IN REGARDS TO | | | THE EXISTING BUILDING; MINIMUM BUILDING | | | TYPE, HEIGHT (NUMBER OF STORIES), | | | PROTECTED OR UNPROTECTED, SPRINKLED OR | | | UNSPRINKLED, OCCUPANCY SO THAT FBC TABLE | | | 500 COMPLIANCE CAN BE DETERMINED. | | | | | | PLEASE PROVIDE ALL INFORMATION | | | REQUESTED.SHOW COMPLIANCE WITH FBC | | | TABLE 500 AS REQUESTED ON FIRST REVIEW. | | | THIS IS TYPICALLY DONE IN A CODE SUMMARY | | | SECTION.SOME INFORMATION WAS PROVIDED | | | BUT NOT ENOUGH TO DETERMINE CODE | | | COMPLIANCE.FOR INSTANCE, WHETHER OR | | | NOT THE BUILDING IS SPRINKLED WAS NOT | | | DECLARED ON THE PLAN.THE OCCUPANCY | | | CLASSIFICATION AND SUBCLASSIFICATION WAS | | | NOT DECLARED, PROTECTED OR UNPROTECTED. | | | IT APPEARS TO BE ONE STORY, PLEASE | | | DECLARE SO ON THE PLAN. | | | | | | 2.)SEE FBC503.1.2.YOU SHOW A PORTION | | | OF THE BUILDING AS TYPE V, ANOTHER | | | PORTION AS TYPE III.FOR A BUILDING TO | | | BE DECLARED TWO DIFFERENT BUILDING | | | TYPES, A FIRE WALL BETWEEN THE TWO | | | BUILDING TYPES IS REQUIRED.SHOW | | | EXISTING OR PROPOSED FIRE WALL AND | | | PROVIDE A DETAIL.PROVIDE INFORMATION | | | IN REGARDS TO EXISTING CONSTRUCTION SO | | | THAT THE BUILDING TYPE DECLARED CAN BE | | | CONFIRMED. | | | | | | 3.)IF THIS IS TWO BUILDINGS AS DEFINED | | | BY FBC503.1.2, PROVIDE TOTAL AREA OF | | | EACH BUILDING TYPE SO THAT TABLE 500 | | | COMPLIANCE CAN BE DETERMINED. | | | | | | 4.)IF THIS ENTIRE BUILDING IS ACTUALLY | | | A TYPE V BUILDING, SEE FBC TABLE 500. | | | AN UNSPRINKLED TYPE V A2 BUILDING IS | | | RESTRICTED TO A SIZE OF 8000 SF.THIS | | | BUILDING IS OVER 13,000 AND YOU ARE | | | PROPOSING TO ADD 200 SF.THE ADDITION | | | AS PRESENTED DOES NOT APPEAR CODE | | | COMPLIANT BUT NOT ENOUGH INFORMATION WAS | | | PROVIDED TO MAKE THIS DETERMINATION. | | | | | | 5.)DECLARE GOVERNING CODE.IF YOU ARE | | | DESIGNING UNDER THE FBC2004, PLEASE | | | ADVISE SO THAT I CAN REVISE CODE | | | REFERENCE NUMBERS IF NECESSARY. | | | COMMENTS STILL APPLY. | | | | | | 6.)IF YOU ARE DESIGNING UNDER FBC2004, | | | PRODUCT APPROVALS ARE TO BE REVIEWED BY | | | THE DESIGNER OF RECORD, CITY OF WEST | | | PALM BEACH AMENDMENTS TO THE FBC2004 | | | 106.3.3. | | | | | | 7.)FROM PREVIOUS REVIEW, ITEM #8. | | | FLORIDA STATE OR LOCAL PRODUCT APPROVALS | | | REQUIRED FOR THE ROOF AND THE WINDOW. | | | PROVIDE BOTH THE STATE OR LOCAL PRODUCT | | | APPROVAL AND THE CORRESPONDING | | | EVALUATION OR TEST REPORT AND | | | INSTALLATION INSTRUCTIONS.THE | | | RESPONSE LETTER FROM THE ARCHITECT | | | STATES THAT THE WINDOWS ARE EXISTING AND | | | NOT BEING REPLACED.THERE IS A NEW | | | WINDOW SHOWN AT THE SINK IN THE KITCHEN | | | ADDITION.PRODUCT APPROVAL FOR THE ROOF | | | WERE NOT SUBMITTED. | | | | | | WWW.FLORIDABUILDING.ORG | | | | | | 7.)IMPACT PROTECTION REQUIRED FOR THE | | | WINDOW FBC1606.1.4.IF YOU PROPOSE | | | USING REMOVABLE SHUTTERS, APPROVAL BY | | | THE BUILDING OFFICIAL IS REQUIRED.SEE | | | ATTACHED POLICY, ITEM 13. | | | | | | 8.)SHEETS A1, A4, A7, S1 ARE NOT | | | SEALED.DOCUMENTS PREPARED BY AN | | | ARCHITECT AND SUBMITTED FOR PUBLIC | | | RECORD ARE TO BE SIGNED, SEALED, AND | | | DATED ORIGINALS.FAC61G1-16. | | | | | | 9.)THE NOA SUBMITTED IS EXPIRED, OVER | | | 90 DAYS WITHOUT COMMENCING WORK, | | | FS713.13(2). | | | | | | 10.) SHOW TURNING RADIUS IN BATHROOM, | | | FBC11-4.22.3. | | | | | | 11.) SPECIFY HURRICANE STRAPS AND SHOW | | | DESIGN CRITERIA, SHEET A7. | | | | | | 12.) SEE ATTACHED FS553.80(2)(B).A 4X | | | PLAN REVIEW IS REQUIRED TO BE CHARGED IF | | | THE CORRECTIONS ARE NOT PROPERLY | | | ADDRESSED IN THE THIRD REVIEW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-29 |
Time |
15:29 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2005-08-29 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2005-08-29 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 | | | | | | 2.)THIS IS AN OVER 50% IMPROVEMENT | | | FBC3401.7.2.6 (SEE PROPERTY APPRAISER | | | VALUATION).SOME COMMENTS MAY RELATE TO | | | THIS CODE SECTION. | | | | | | 3.)PROVIDE AREA CALCULATIONS ? | | | EXISTING, PROPOSED, NEW TOTAL. | | | | | | 4.)PROVIDE INFORMATION IN REGARDS TO | | | THE EXISTING BUILDING; MINIMUM BUILDING | | | TYPE, HEIGHT (NUMBER OF STORIES), | | | PROTECTED OR UNPROTECTED, SPRINKLED OR | | | UNSPRINKLED, OCCUPANCY SO THAT FBC TABLE | | | 500 COMPLIANCE CAN BE DETERMINED. | | | | | | 5.)SPECIFY MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR THE DECLARED | | | OCCUPANCY, FBC TABLE 803.3. | | | | | | 6.)MEANS OF EGRESS SHALL BE TO THE | | | EXTERIOR OF THE BUILDING, FBC1001.3. | | | EXIT LIGHTS ARE REQUIRED AT THE GATES | | | LEADING OUTSIDE THE COVERED AREAS. | | | | | | 7.)THE TITLE BLOCK FOR THE ENGINEER IS | | | TO CONTAIN ALL INFORMATION REQUIRED BY | | | FAC61G15-23.002 (PRINTED NAME OF THE | | | PERSON SEALING THE DOCUMENT). | | | | | | 8.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVALS REQUIRED FOR: | | | | | | ROOF | | | WINDOW | | | | | | WWW.FLORIDABUILDING.ORG | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
10 |
Status |
P |
Date |
2006-12-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-09 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-09 |
Time |
16:47 |
Sent To |
PC |
|
| Notes |
| 2006-12-09 17:00:44 | REDLINED E-2 AGAIN FOR THE MINIMUM SIZE FOR THE GEC AS | | | STATED AND REDLINED ON PREVIOUS PLANS. NEEDS TO BE A | | | 2/0 MIN PER 250.66 AND THE SEC'S SHOWN ON RISER. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-17 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-17 |
Time |
14:35 |
Sent To |
PC |
|
| Notes |
| 2006-10-17 14:59:06 | CONTRACTOR CALLED, | | | REMOVED OLD E-2, AS THIS RISER DOES NOT APPLY. | | | | | | RISERGROUNDING ELECTRODE CONDUCTOR NEEDS TO BE SIZED | | | PER 250.66. THIS APPEARS IT SHOULD BE 2/0. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
F |
Date |
2006-10-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-14 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-14 |
Time |
17:27 |
Sent To |
PC |
|
| Notes |
| 2006-10-14 17:41:53 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE TWO COMPLETELY DIFFERENT SETS OF | | | RISER DIAGRAMS ARE BEING SUBMITTED WHICH ARE BOTH DATED | | | THE SAME DAY. PLEASE SEE THE SEC'S, FEEDERS ETC ARE ALL | | | DIFFERENT AND IS INCLEAR WHICH ONE IS WANTING TO BE | | | REVIEWED. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS NOTES FOR SIZING OF THE | | | GEC BASED ON 250.66. THIS WAS REDLINED ON ORIGINAL | | | PLANS AND NOTED ON LAST REVIEW , HOWEVER BASED ON THE | | | SEC'S FROM EITHER RISER, THE SIZE APPEARS TO BE ONE | | | UNDER PER 250.66. (2/0MIN). | | | | | | 3) NOTE: PLEASE SEE 110.9, AND 240.12 FOR SELECTIVE | | | COORDINATION OF EQUIPMENT AND RATINGS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2006-09-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-05 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-05 |
Time |
13:34 |
Sent To |
PC |
|
| Notes |
| 2006-09-05 00:00:00 | ****UNSAT ***** | | | | | | 1) NOTE: PLEASE SEE PLANS NEED TO BE | | | RE-PRINTED AS HAND DRAWN ITEMS ON PLANS | | | ARE NOT PERMITTED. | | | FBC ADMIN SECT 106.1.2 | | | | | | 2) NOTE: PLEASE SEE GROUNDING ELECTRODE | | | CONDUCTOR TO BE SIZED PER 250.66. | | | PLEASE SEE SYSTEM SHALL BE CONTINUOUS. | | | 250.50,250.64.250.66 | | | 1/0 MIN, #4 SHOWN. | | | PLEASE ALSO VERIFY THE ATTCHMENT | | | LOCATION OF THE GEC. SHOWN TO MAIN, IS | | | THIS GOING TO THE GUTTER/, IF SO, PLEASE | | | REVISE. | | | | | | 3) NOTE: PLEASE KNOW, NEW REVISED PLANS | | | DONE BY THE ENGINEER SHALL CONTAIN TITLE | | | BLOCKS AS REQUIRED PER FAC 61G15-23.002, | | | FS 471.023 | | | | | | PLEASE REVISE THE ABOVE AND SUBMIT FOR | | | REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2006-06-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-07 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-07 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2006-06-07 00:00:00 | REDLINED: | | | | | | MCB ON MAIN #1 REQUIRED. | | | | | | | | | PASSED PENDING PALM BEACH COUNTY IMPACT | | | FEE STAMP AND POSSIBLE FEE SFOR | | | ADDITION. | | | SQ FT ADDED. SEE BUILDING REVIEW NOTES. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2006-04-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-24 |
Time |
19:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-24 |
Time |
19:35 |
Sent To |
|
|
| Notes |
| 2006-04-24 00:00:00 | *********UNSAT ******* | | | | | | ** PLEASE SEE A NOTE FROM SAMANTA | | | HILL,MENTIONS FOR ALL REVIEWS TO BE | | | DONE, NOW THAT PLANS ARE BEING SUBMITTED | | | INCLUDING KITCHEN ADDITION. | | | | | | 1) NOTE: PLEASE SEE ORIG PLANS OMITTED | | | THE KITCHEN ADDITION FROM SCOPE OF WORK | | | FOR PERMIT. | | | PLEASE SEE REVSION IS NOW COMING FOR | | | KITCHEN ADDITION, HOWEVER NO ELECTRICAL | | | IS BEING SHOWN. PLEASE SUBMIT AND | | | CORRELATE WITH THE PANEL SCHEDULES TO BE | | | SUBMITTED. | | | PLEASE SEE THIS IS IN CONFLICT WITH NOTE | | | ON PLANS, AS ONE NOTE MENTIONS | | | RENOVATION OF EXISTING KITCHEN OR WORDS | | | TO THAT AFFECT. | | | | | | 2) NOTE: PLEASE ADJUST VALUATION FOR | | | SCOPE OF WORK FOR ADDITION. | | | FBC 104.6.5. | | | PLEASE ALSO SEE BUIDLING REVIEW NOTES | | | FOR THIS.. | | | | | | ** PLEASE KNOW, ANY REVISIONS TO | | | ELECTRICAL SHALL BE DONE BY THE | | | ELECTRICAL ENGINEER OF RECORD. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-03-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-06 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-06 |
Time |
17:20 |
Sent To |
|
|
| Notes |
| 2006-03-06 00:00:00 | KITCHEN ADDITION IS NOT IN SCOPE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-12-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-21 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-20 |
Time |
21:21 |
Sent To |
|
|
| Notes |
| 2005-12-21 00:00:00 | ************* UNSAT *************** | | | | | | PLEASE SEE SOME NOTES FROM FIRST REVIEW | | | STILL NEED TO BE ADDRESSED. | | | PLEASE ALSO SEE CHANGES IN ELECTRICAL | | | RISER ALONG WITH PLANS STILL SHOWING | | | OTHER NEED TO BE ADDRESSED. | | | | | | *** PLEASE KNOW, WHEN PLANS WERE | | | SUBMITTED BACK TO THE CONSTRUCTION | | | SERVICES DEPT. ON OCT 12, 2005, "ONLY" | | | THE OLD/ UN-CORRECTED PLANS WERE | | | SUBMITTED BACK FOR REVIEW AND NO "NEW" | | | OR REVISED PLANS WERE SUBMITTED. THIS IS | | | THE REASON WHY FIRE AND ELECTRICAL | | | REVIEW HAD A 2ND REVIEW WHICH REFERENCED | | | TO THE SAME COMMENTS FROM ORIGINAL | | | REVIEW. | | | ** PLEASE KNOW THAT THE NEW/REVISED | | | PLANS NOT SUBMITTED BACK ON OCT 12, WERE | | | ALLOWED TO BE BROUGHT IN ON NOV 21ST, | | | 2005 TO BE RE-REVIEWED. THESE PLANS WERE | | | BROUGHT IN BY MR. KEVIN BUTLER II. | | | I HOPE THIS CLEARS UP ANY CONFUSION OVER | | | WHY THERE WAS REFERENCE TO OLD/PLANS. | | | | | | PLEASE SEE THE FOLLOWING: | | | | | | ** NOTES TAKEN DIRECTLY FROM FIRST | | | REVIEW. | | | | | | 1)NOTE:NOTE #1, NO. PLEASE SEE FIRST | | | PART OF NOTE MENTIONED TO SHOWALL | | | CIRCUITING NEWAND CORRELATE WITH | | | SUBMITTED PANEL SCHEDULE(S). | | | THIS WAS DONE, HOWEVER PLEASE SEE THIS | | | NOTE AND NOTE #2 REQUESTED ALLEM/EXT | | | LTS TO BE CIRCUITED TO THE LOCAL BRANCH | | | CIRCUIT FEEDING UNIT EQUIPMENT.THIS WAS | | | DONE FOR EM LTS, HOWEVER NOT THE EXT | | | LTS. | | | PLEASE ADJUST CIRCUITING. | | | | | | | | | 2)NOTE: NOTE #2,YES/NO PLEASE SEE THAT | | | BATTERY BACK UP EXIT LTS WERE ADDED FOR | | | LIGHTING THE EGRESS PATH TO EXIT | | | DISCHARGE, HOWEVER COULD NOT LCOATE ANY | | | INFORMATION WITH RESPECT TO NOTES OR MIN | | | FT CANDLES REQUIRED. PLEASE SEE NFPA-101 | | | 7-8, WHICH REQUIRES THE MEANS OF EGRESS | | | LIGHTING TO MEET AMIN OF 10 FT CANDLES | | | DURING NORMAL POWERE AND A MIN OF 1 FT | | | CANDLE DURING EMERGENCY CONDITIONS( LOSS | | | OF NORMAL POWER). | | | PLEASE PROVIDE AT A MININUM, NOTING FOR | | | THESE MIN REQUIREMENTS. | | | PLEASE SEE 2003 NFPA-101 7.8, 7.9 | | | | | | 3)NOTE: NOTE #3 OK. | | | | | | 4)NOTE: NOTE #4 OK. | | | | | | 5)NOTE: NOTE #5 OK. (ONLY NOTED) | | | | | | 6)NOTE: NOTE #6 NO, PLEASE SEE A NOTE | | | WAS ADDED MENTIONING "WHEN REQUIRED" | | | PLEASE SEE FIRE/MECHANCICAL REVIEW | | | NOTES, A "SHUNT TRIP" OF SOME SORT WOULD | | | BE REQUIRED TO SHUT DOWN ALL ELECTRICAL | | | IN A HOOD AREA. | | | PLEASE PROVIDE REFERENCE TO NFPA-96 WITH | | | MEANS OF SHUT DOWN OF ANY | | | ELECTRICAL DEVICES UNDER HOOD. | | | PLEASE SEE CHAPTERS 9 AND 10 | | | | | | 7)NOTE: NOTE #7 OK, A DOOR AND WALL WERE | | | ADDED TO SEPARATE FROM STORAGE AREA OF | | | CLOSET. | | | | | | 8)NOTE: NOTE #8, OK. | | | | | | 9)NOTE: NOTE #9, NO PLEASE SEE | | | 250.6,250.24, "EQUIPMENT GROUNDING " | | | CONDUCTORS ARE ONLY INSTALLED AFTER THE | | | FIRST MEANS OF DISCONNECT. | | | PLEASE SEE THESE "EQIPMENT GROUNDING | | | CONDUCTORS"ARE STILL BEING SHOWN , | | | BOTH ON REFERENCE TO THE EXISTING SEC'S | | | AND TO THE NEW SEC'S. | | | PLEASE SEE NEW COMMENTS WITH RESPECT TO | | | THE SERVICE. | | | PLEASE SEE EQP GRND FROM METER TO | | | MAIN.(NEW)AND EXISTING. | | | | | | 10)NOTE: NOTE #10 OK. | | | | | | 11)NOTE: NOTE #11 NO/YES, PLEASE SEE THE | | | TAPS FOR NEW MAIN IS NOW SHOWN, HOWEVER | | | PLEASE SEE NEW NOTE ADDING A TAP TO | | | EXISTING MAIN WILL NOT BE PERMITTED. | | | PLEASE ALSO KNOW, PREVIOUS COMMENT | | | REQUESTED OF THIS WAS A NEW SERVICE OR | | | COMING FROM THE EXISTING SERVICE RISER? | | | PLEASE SEE RISER NOW INDICATES THIS TAP | | | LOCATED IN "CT" AND DOES NOT SHOW A NEW | | | RISER OR SEC'S UP TO A NEW WEATHER HEAD. | | | THERFORE, PLEASE SHOW EXISTING SEC'S IN | | | RISER AND PLEASE BE SURE TO MAKE SURE | | | THE EXISTING SIZE IS ADEQUATE FOR BOTH | | | NEW AND EXISITNG. PLEASE SEE EXISITNG IS | | | SHOWN AS 600A'S AND NEW MAIN IS 400'S. | | | PLEASE SEE 230.2 FOR NEW | | | SERVICE AS SHOWN ON PLANS. PLEASE | | | CLARIFY IF "NEW SERVICE" IS GOING TO BE | | | FED FROM THE SAME SERVICE DROP AND | | | TRANSFORMER. | | | *** PLEASE SEE PLANS STILL INDICATE | | | THERE BEING A "NEW METER", AN "EXISITNG | | | METER" AND AND "EXISITNG CT" WHICH DOES | | | NOT CORRELATE WITH THE RISER DIAGRAM | | | SHOWN FOR SERVICE. | | | PLEASE CORRELATE THE ABOVE AND CALL TO | | | GO OVER OPTIONS IF NEEDED. | | | 215.5 | | | | | | ** NEW NOTE: | | | | | | 1)NOTE: PLEASE SEE COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO THE DESIGN | | | PROFESSIONAL AND REPEAT COMMENTS FOR | | | CODE COMPLIANCE. | | | PLEASE KNOW THIS IS ONLY A NOTICE GIVEN | | | AT THIS TIME. | | | ONE COPY OF ELECTRICAL PLANS ARE BEING | | | RETAINED. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONE SET OF OLD/VOIDED SHEETS ARE | | | REQUIRED FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2005-12-20 00:00:00 | IN ELEC FOR REVIEW. | | | THIS REVIEW IS BEING DONE ON THE "NEW" | | | PLANS SUBMITTED ON NOV 21ST, 2005. | | | | | | SOME COMMENTS FROM PREVIOUS REVIEW STILL | | | NEED TO BE ADDRESSED, AND COMMENTS DUE | | | TO INFORMATION ADDED TO PLANS. | | | NOTES TO FOLLOW, REVIEW IN PROGRESS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-11-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-11-15 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-11-15 |
Time |
07:02 |
Sent To |
|
|
| Notes |
| 2005-11-15 00:00:00 | ********* UNSAT 2ND REVIEW ********* | | | | | | | | | 1)NOTE: PLEASE SEE THE NOTES FROM | | | PREVIOUS REVIEW. PLEASE SEE NO NOTES | | | SEEMED TO HAVE BEEN ADDRESSED, YET | | | RESPONSE LETTER MENTIONS ITEMS CORRECTED | | | AND CHANGED. | | | | | | 2)NOTE: PLEASE SEE COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO THE DESIGN | | | PROFESSIONAL AND REPEAT COMMENTS. | | | THIS IS ONLY A NOTE AT THIS TIME. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-08-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-15 |
Time |
17:13 |
Rev Time |
2.50 |
| Received By |
dpalmer |
Date |
2005-08-15 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2005-08-15 00:00:00 | ********* UNSAT ********* | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING FOR | | | NEWAND CORRELATE WITH SUBMITTED PANEL | | | SCHEDULE(S). | | | PLEASE SEE EXT/ EM LT PER 700.12E,THE | | | BRANCH | | | CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL | | | BE THE SAME BRANCH CIRCUIT AS THAT | | | SERVING THE NORMAL LIGHTING IN THE AREA | | | AND CONNECTED AHEAD OF ANY LOCAL | | | SWITCHES. | | | | | | | | | 2)NOTE: PLEASE SEE NFPA-101 7-8, WHICH | | | REQUIRES MEANS OF EGRESS LIGHTING TO THE | | | EXIT DISCHARGE/ TO PUBLIC RIGHT OF WAY. | | | PLEASE SEE CORRIDORS IN OPEN COURTYARD | | | AREAS. 101,15.2 | | | PLEASE ALSO SEE 700.12E FOR CIRCUITINGOF | | | EM/LTS.PREVIOUSLY NOTED. | | | | | | 3)NOTE: PLEASE SEE 2002 NEC FOR | | | PROTECTION OF RECEPTS IN KITCHENS IN | | | OTHER THAN DWELLING UNITS, WHICH | | | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT | | | RECEPTACLES IN NONDWELLING-TYPE KITCHENS | | | TO BE GFCI PROTECTED. THIS REQUIREMENT | | | APPLIES TO EACH AND EVERY 15- AND | | | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, | | | WHETHER OR NOT THE RECEPTACLE SERVES | | | COUNTERTOP APPLIANCES. | | | | | | 4)NOTE: PLEASE SEE MISSING THE "PRINTED" | | | LICENSE NUMBER OF THE ENGINEER OF | | | RECORD. PLEASE SEE FAC 61G15-23.002 | | | FS 471 | | | | | | 5)NOTE: PLEASE SEE BLDG, ZOING COMMENTS, | | | NO SURVEY/SITE PLAN SHOWING SETBACKS FOR | | | NEW KITCHAN ADDITION WAS SUBMITTED. | | | PLEASE SEE FS 472.025, FAC 61G17-7.002, | | | PLEASE BE SURE ALL SURVEY'S CONTAIN THE | | | ABOVE. | | | | | | 6)NOTE: PLEASE PROVIDE REFERENCE TO | | | NFPA-96 WITH MEANS OF SHUT DOWN OF ANY | | | ELECTRICAL DEVICES UNDER HOOD. | | | PLEASE SEE CHAPTERS 9 AND 10 | | | | | | 7)NOTE: PLEASE SEE PANEL "B" WHICH IS | | | SHOWN AS EXISTING SHALL NOT BE LOCATED | | | IN "OFFICE CLOSET". PLEASE SEE FIRE | | | REVIEW NOTES, NO STORAGE PERMITTED IN | | | SPACES ABOUT ELECTRICAL EQUIPMENT/RMS. | | | PLEASE SEE 408.7,240.24D, 110.26 ETC | | | PLEASE SEE THIS AREA FOR LOCATION OF | | | PANEL NEEDS TO REFERENCE, ELEC/MECH RM. | | | | | | 8)NOTE:PLEASE CLARIFY/ SHOW EITHER NEW | | | OR EXISTING ROOF-TOP WP GFI RECEPTS FOR | | | RTU'S PER 210.63 | | | | | | 9)NOTE: PLEASE SEE 250.6,250.24, | | | "EQUIPMENT GROUNDING " CONDUCTORS ARE | | | ONLY INSTALLED AFTER THE FIRST MEANS OF | | | DISCONNECT. | | | PLEASE SEE EQP GRND FROM METER TO | | | MAIN.(NEW). | | | | | | 10)NOTE: PLEASE SHOW METHOD OF EQUIPMENT | | | GROUNDING FROM PANELS TO ALL RTU'S. | | | PLEASE KNOW, EMT MAY ONLY BE USED AS AN | | | "EQUIPMENT GROUND PATH" IF USED IN | | | CONNECTION WITH NEW "LISTED" EQUIPMENT | | | GROUNDING CONNECTORS AND COUPLINGS. | | | 110.3 | | | | | | 11)NOTE: PLEASE SEE 230.2 FOR NEW | | | SERVICE AS SHOWN ON PLANS. PLEASE | | | CLARIFY IF "NEW SERVICE" IS GOING TO BE | | | FED FROM THE SAME SERVICE DROP AND | | | TRANSFORMER. | | | 215.3 | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONE SET OF OLD/VOIDED SHEETS ARE | | | REQUIRED FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2006-08-02 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-08-02 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-08-02 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2006-08-02 00:00:00 | REVISION DATED 6/19/06 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2006-06-09 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-06-09 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-06-09 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2006-06-09 00:00:00 | REVISION DATED 3/28/06 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2006-05-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-05-31 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-05-31 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2006-05-31 00:00:00 | REVISION DATED 3/26/06 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2005-12-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-12-07 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-12-07 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2005-12-07 00:00:00 | 1. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR HOOD, DUCT, AND SUPPRESSION SYSTEM | | | PLANNED FOR USE. | | | | | | 2. OTHER WORK SHALL COMPLY WITH NFPA | | | 241. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2005-11-16 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-11-16 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-11-16 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2005-11-16 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE FIRE REVIEW COMMENTS FROM | | | FIRST REVIEW. PLANS ILLUSTRATE EXIT | | | SIGNS AND EMERGENCY LIGHTS IN | | | CLASSROOMS, BUT NOT COMMON AREA | | | CORRIDORS. HOW WOULD PERSONS BE DIRECTED | | | TO AN EXIT DISCHARGE? | | | | | | 2) RESPONSE LETTER INDICATES THAT FIRE | | | EXTINGUISHERS HAVE BEEN ADDED TO THE | | | DRAWINGS. PLEASE INDICATE SHEET NUMBER. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-09-06 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-09-06 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-09-06 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2005-09-06 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE THAT REQUIRED MEANS OF | | | EGRESS MUST BE CLEARLY MARKED. PLEASE | | | SHOW LOCATIONS OF ALL ILLUMINATED EXIT | | | SIGNS AND EMERGENCY LIGHTING FACILITIES | | | IN AREAS DIRECTING PERSONS TO AN EXIT | | | AND EXIT DISCHARGE. | | | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED AND SHALL BE MOUNTED TO SATISFY | | | THE 75' TRAVEL DISTANCE REQUIREMENT. | | | PLEASE SHOW IF EXISTING OR NEW. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND | | | FIRER ALARM REMODEL IF APPLICABLE. | | | | | | 4) NO COOKING OF FOODS THAT PRODUCE | | | GREASE LADEN VAPORS UNLESS PROTECTED BY | | | APPROVED HOOD AND SUPPRESSION SYSTEMS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2006-07-15 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-07-15 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-07-15 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2006-07-15 00:00:00 | GAS NOT INCLUDED IN THIS PERMIT, | | | SEPERATE PLANS AND PERMIT. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-06-24 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-06-24 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-06-24 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2006-06-24 00:00:00 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | | PAUL SCHMITZ | | | FBC 2004 FUEL GAS CODE, PLAN REVIEW | | | | | | DENIED | | | | | | 1) SHT P-1 | | | NATURAL GAS PIPING RISER DENIED. | | | PLAN REVIEW COMMENTS SHALL BE RESPONDED | | | TO BY THE DESIGN PROFESSIONALS. REFERING | | | TO EACH OTHER OR CONTRACTOR, IS NOT | | | HELPFUL IN EXPEDITING YOUR PERMIT. | | | SEPERATE GAS RISER, SIGNED AND SEALED BY | | | ENGINEER OF RECORD | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR THE GAS PERMIT: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | 3. TYPE OF GAS, (LP OR NATURAL) | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304 | | | . | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. | | | | | | 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | 10. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | 12. SEC 409.5 EQUIPMENT SHUT OFF VALVE. | | | EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWNSTREAM OF MANUAL SHUT OFF VALVE. | | | | | | 13. NFPA-96 SEC10.5.1 & | | | NFPA -1 SEC 50.4/7.1GAS EMERGENCY SOV | | | TO BE 42? TO 48? AFF | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2006-12-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-08 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-08 |
Time |
11:11 |
Sent To |
E |
|
| Notes |
| 2006-12-08 11:11:34 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2006-10-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-06 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-06 |
Time |
09:11 |
Sent To |
E |
|
| Notes |
| 2006-10-06 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-08-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-26 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-26 |
Time |
15:41 |
Sent To |
E |
|
| Notes |
| 2006-08-26 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-06-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-27 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-27 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2006-07-12 00:00:00 | TO "COMM" BD#19 | | 2006-06-27 00:00:00 | WAITING FOR "COMM" BD-REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-05-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-11 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-11 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2006-05-25 00:00:00 | TO "COMM" BD#3 | | 2006-05-11 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-04-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-20 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-20 |
Time |
09:49 |
Sent To |
B |
|
| Notes |
| 2006-04-20 00:00:00 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-04-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-06 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-06 |
Time |
15:13 |
Sent To |
B |
|
| Notes |
| 2006-04-20 00:00:00 | TO "COMM" BD#44 | | 2006-04-06 00:00:00 | WAITING FOR "COMM" BD-REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-02-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-02 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-02 |
Time |
18:41 |
Sent To |
|
|
| Notes |
| 2006-03-06 00:00:00 | TO "COMM" BD#62 | | 2006-02-02 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-11-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-14 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-14 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2005-11-14 00:00:00 | TO "COMM" BD#6 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-09-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-09-09 |
Time |
06:54 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-08-04 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2005-08-05 00:00:00 | TO "COMM" BD#19 | | 2005-08-04 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2006-06-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-27 |
Time |
08:08 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-06-27 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2006-06-27 00:00:00 | MECHANICAL PLANS SUBMITTED FOR A/C | | | PACKAGE UNITS ON ROOF. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2006-05-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-05-11 |
Time |
11:56 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-05-11 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2006-05-11 00:00:00 | *** NOTE *** | | | ADDITIONAL PERMITS ARE REQUIRED FOR THE | | | KITCHEN EXHAUST HOOD, AND ONE FOR THE | | | HOOD FIRE SUPPRESSION SYSTEM. PLEASE | | | PROVIDE PLANS AND MANUFACTURERS | | | SUBMITTAL DATA WITH PERMIT APPLICATION. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-01-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-01-23 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-01-23 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2006-01-23 00:00:00 | PROVISO: | | | ADDITIONAL PERMIT REQUIRED FOR HOOD & | | | FIRE SUPPRESSION.PLEASE PROVIDE PLANS | | | & MANUFACTURERS SUBMITTAL DATA WITH | | | PERMIT APPLICATION. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-09-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-09-08 |
Time |
08:41 |
Rev Time |
1.45 |
| Received By |
pkrauss |
Date |
2005-09-08 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2005-09-08 00:00:00 | DENIED: | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS IN | | | ACCORDANCE WITH 2001 FBC(M) TABLE 403.3. | | | | | | 2.PLEASE INDICATE TYPE OF VENT TO THE | | | WATER HEATER. REFERENCE 2001 FBC(F) | | | CHAPTER 5.PROVIDE MANUFACTURER'S | | | INSTALLATION INFORMATION. | | | | | | 3.PLAN SHEET M-2 HVAC GENERAL NOTE #17 | | | INDICATES HOOD FOR THE GAS STOVE. | | | PLEASE NOTE, SEPARATE PERMIT REQUIRED | | | FOR HOOD & SUPPRESSION.PLEASE PROVIDE | | | PLANS AND MANUFACTURER'S SPECIFICATIONS | | | FOR THE HOOD.HOOD & GREASE DUCT SHALL | | | COMPLY WITH 2001 FBC(M) 507 & 506 | | | RESPECTIVELY. | | | | | | 4.CONDENSATE SHALL TERMINATE IN | | | ACCORDANCE WITH 2001 FBC(M)307.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2006-07-15 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-07-15 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-07-15 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2006-07-15 00:00:00 | PROVISO: | | | SEC 606.1(4) SOV ON ALL WATER DROPS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2006-06-24 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-06-24 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-06-24 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2006-06-24 00:00:00 | PLUMBING OK | | | ADDED STOP FOR GAS DENIED SEE NOTES. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2006-06-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-06-03 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-06-03 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2006-06-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | MUNICIPAL CODE | | | | | | 1. SUBMIT A SANITARY RISER DIAGRAM AND | | | PLAN VIEW OF THE PIPING. SHOW ALL PIPE | | | SIZES, VENTS, TRAPS ETC. SECTION | | | 104.3.1.1. | | | | | | 2. SUBMIT A WATER RISER DIAGRAM AND PLAN | | | VIEW OF THE PIPING. SHOW ALL PIPE SIZES, | | | VALVES AND WATER HAMMER ARRESTORS IF | | | REQUIRED BY SECTION 604.9. SECTION | | | 104.3.1.1. | | | | | | 3. A GREASE INTERCEPTOR MAY BE REQUIRED | | | AND IF SO, A GREASE WASTE SYSTEM WILL BE | | | REQUIRED FOR THE KITCHEN. PLEASE CONTACT | | | LYNN MASSON ENVIRONMENTAL COMPLIANCE FOR | | | A DERTIMINATION. HER PHONE NUMBER IS | | | (561) 822-2271, FAX (561 822-2279, AND | | | E-MAIL [email protected]. MUNICIPAL CODE | | | SECTION #3434. | | | | | | 4. THE FOLLOWING INFORMATION IS REQUIRED | | | FOR THE SEPARATE GAS PERMIT: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. (LENGTHS FOR EACH CUT | | | SECTION NOT SHOWN). | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | (NO RESPONSE, NOT ADDRESSED). | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). (NO RESPONSE, | | | NOT ADDRESSED) | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (NO | | | RESPONSE, NOT ADDRESSED). | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. (NO | | | RESPONSE, NOT ADDRESSED). | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. (NEEDS TO | | | BE SHOWN ON THE GAS RISER ISOMETRIC). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2006-03-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-03-06 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-03-06 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2006-03-06 00:00:00 | | | | | | | | | | | | | KITCHEN EXPANSION NOT INCLUDED IN THIS | | | PERMIT. THIS INCLUDES THE SANT, WATER, | | | AND GAS PIPING FOR THE KITCHE.SEE | | | SHEET P-1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-01-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-01-31 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-01-31 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2006-01-31 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | A. PREVIOUS COMMENTS FROM FIRST REVIEW | | | NOT ADDRESSED. COMMENT NUMBERS TO REMAIN | | | THE SAME AS FIRST REVIEW: | | | | | | 1. INDICATE AGE OF STUDENTS TO DETERMINE | | | THE OCCUPANCY. SECTION 104.2.1. (NOT | | | ADDRESSED, NO RESPONSE). PLEASE INDICATE | | | OCCUPANCY AND INDICATE AGE OF STUDENTS. | | | 2. ROUTE PLANS TO THE PALM BEACH HEALTH | | | UNIT DIVISION OF ENVIRONMENTAL HEALTH | | | FOR REVIEW PRIOR TO RESUBMITTING FOR | | | PLAN REVIEW AT THE CITY WPB. SECTION | | | 101.4.7. (NO RESPONSE, NOT ADDRESSED). | | | 4. SHT A-6 SHOW THE FOLLOWING TO SHOW | | | COMPLIANCE OF THE ACCESSIBILITY CODE: | | | FOR LAVS... | | | 11-4.19.5 FAUCETS | | | TOILET ROOM: | | | 11-4.22.3 TURNING AREA IN TOILET ROOM, | | | NOT IN THE STALL. | | | 5. SHT P-1 IF THE DESIGN PROFESSIONAL IS | | | AN ARCHITECT OR ENGINEER LEGALLY | | | REGISTERED UNDER THE LAWS OF THIS STATE | | | REGULATING THE PRACTICE OF ARCHITECTURE | | | OR ENGINEERING, THEN HE/SHE SHALL AFFIX | | | HIS/HER OFFICIAL SEAL TO SAID DRAWINGS, | | | AS REQUIRED FY FLORIDA STATUTES. SECTION | | | 104.2.2. (SHEETS A-1, A-4,A-7, & S-1 NOT | | | SIGNED, SEALED, DATED) | | | 8. THE FOLLOWING INFORMATION IS REQUIRED | | | FOR THE SEPARATE GAS PERMIT: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. (LENGTHS FOR EACH CUT | | | SECTION NOT SHOWN). | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | (NO RESPONSE, NOT ADDRESSED). | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). (NO RESPONSE, | | | NOT ADDRESSED) | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (NO | | | RESPONSE, NOT ADDRESSED). | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. (NO | | | RESPONSE, NOT ADDRESSED). | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. (NEEDS TO | | | BE SHOWN ON THE GAS RISER ISOMETRIC). | | | | | | **************NEW COMMENT*************** | | | 1B. SEE ATTACHED SHEET CONCERNING FS | | | 553.80(2)(B) AND THE DESIGN | | | PROFESSIONAL. (ATTACHED TO ELECTRICAL | | | COMMENTS). THIS IS GIVEN AS A NOTICE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-09-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-09-07 |
Time |
14:50 |
Rev Time |
1.96 |
| Received By |
kstevens |
Date |
2005-09-07 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2005-09-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | | | | 1. INDICATE AGE OF STUDENTS TO DETERMINE | | | THE OCCUPANCY. SECTION 104.2.1. | | | 2. ROUTE PLANS TO THE PALM BEACH HEALTH | | | UNIT DIVISION OF ENVIRONMENTAL HEALTH | | | FOR REVIEW PRIOR TO RESUBMITTING FOR | | | PLAN REVIEW AT THE CITY WPB. SECTION | | | 101.4.7. | | | 3. MINIMUM FACILITIES REQUIRE A DRINKING | | | FOUNTAIN AND A SERVICE SINK PER TABLE | | | 403.1. | | | 4. SHT A-6 SHOW THE FOLLOWING TO SHOW | | | COMPLIANCE OF THE ACCESSIBILITY CODE: | | | FOR W/C'S.. | | | 11-4.16.2 CLEAR FLOOR SPACE | | | 11-4.16.3 HEIGHT | | | 11-4.16.5 FLUSH CONTROLS | | | FOR UNINAL.. | | | 11.4.18.2 HEIGHT | | | 11-4.18.3 CLEAR FLOOR SPACE | | | 11-4.18.4 FLUSH CONTROLS | | | FOR LAVS... | | | 11-4.19.2 HEIGHT & CLEARANCES - | | | INCLUDING LAV OUTSIDE ACCESSIBLE STALL. | | | 11-4.19.3 CLEAR FLOOR SPACE | | | 11-4.19.4 EXPOSED PIPES & SURFACES | | | 11-4.19.5 FAUCETS | | | TOILET ROOM: | | | 11-4.22.3 TURNING AREA IN TOILET ROOM, | | | NOT IN THE STALL. | | | 5. SHT P-1 IF THE DESIGN PROFESSIONAL IS | | | AN ARCHITECT OR ENGINEER LEGALLY | | | REGISTERED UNDER THE LAWS OF THIS STATE | | | REGULATING THE PRACTICE OF ARCHITECTURE | | | OR ENGINEERING, THEN HE/SHE SHALL AFFIX | | | HIS/HER OFFICIAL SEAL TO SAID DRAWINGS, | | | AS REQUIRED FY FLORIDA STATUTES. SECTION | | | 104.2.2. | | | 6. SHT P-1 SANT RISER DIAGRAM, SHOW ALL | | | PIPE SIZES, CLEANOUTS REQUIRED BY | | | SECTION 708.3.3, (AT CHANGE OF | | | DIRECTION), VENTS ECT. SECTIONS 104.2.1 | | | & SECTION 901.2.1. - IF SINKS ARE IN THE | | | FOOD PREPARATION AREA THEN THE SINKS | | | SHALL DRAIN INDIRECTLY INTO A FLOOR SINK | | | PER SECTION 802.3. | | | 7. SHT P-1 WATER RISER DIAGRAM, SHOW ALL | | | PIPE SIZES, VALVES AND WATER HAMMER | | | ARRESTORS IF REQUIRED BY SECTION 604.9, | | | (QUICK CLOSING VALVES). | | | 8. THE FOLLOWING INFORMATION IS REQUIRED | | | FOR THE SEPARATE GAS PERMIT: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | C. TYPE OF GAS, (LP OR NATURAL) | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | I. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-07-27 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-07-27 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-05-19 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-05-19 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-05-19 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2006-05-19 00:00:00 | 5/19/06 ***FAILED*** | | | | | | PER THE FINAL ORDER FOR ZBA CASE NO. | | | 3136, A UNITY OF TITLE SHALL BE FILED | | | WITH THE PALM BEACH COUNTY CLERK OF THE | | | CIRCUIT COURT, AND A CERTIFIED COPY | | | PROVIDED TO THE PLANNING AND ZONING | | | DEPARTMENT, PRIOR TO THE ISSUANCE OF A | | | BUILDING PERMIT. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, | | | SENIOR PLANNER, AT (561) 822-1435. |
|
|